Fluke Victoreen 943-227-15, Victoreen 943-27 Operator's Manual

®
Victoreen
Digital Preamplifier, Model 943-227-15,for use with
Model 943-27 Current Mode Beta Detector
February 2008 Manual No. 943-227-15-1, Rev. 3 ©2007, 2008 Fluke Corporation, All rights reserved. Printed in U.S.A. All product names are trademarks of their respective companies
Operator Manual
Fluke Biomedical
6045 Cochran Road Cleveland, Ohio 44139
440.498.2564
www.flukebiomedical.com
Table of Contents
Section 1: General Information............................................................................................................. 1-1
1.1 General Description ............................................................................................................... 1-1
1.2 Application.............................................................................................................................. 1-1
1.3 Specifications ......................................................................................................................... 1-2
1.4 Auxiliary Equipment ............................................................................................................... 1-6
1.5 Recommend Spare Parts.......................................................................................................1-6
1.6 Receiving Inspection .............................................................................................................. 1-6
1.7 Storage................................................................................................................................... 1-7
Section 2: Theory of Operation............................................................................................................. 2-1
2.1 Functional Description............................................................................................................ 2-1
2.2 Main Circuit Boards................................................................................................................ 2-1
2.3 977-200-15M Electrometer Board.......................................................................................... 2-1
2.4 977-210-10M Interface Board ................................................................................................ 2-4
2.5 Preamplifier Switch & Jumper Settings.................................................................................. 2-5
Section 3: Operation .............................................................................................................................. 3-1
3.1 Installation .............................................................................................................................. 3-1
3.2 Set-Up .................................................................................................................................... 3-2
3.3 Operation ............................................................................................................................... 3-3
3.4 Configuration Functions ......................................................................................................... 3-4
3.5 Set point Error Codes............................................................................................................. 3-5
3.6 Software Calculations ............................................................................................................ 3-5
Section 4: Maintenance, Calibration and Troubleshooting ............................................................... 4-1
4.1 Maintenance........................................................................................................................... 4-1
4.2 Calibration .............................................................................................................................. 4-1
4.3 Troubleshooting ..................................................................................................................... 4-2
Appendix A: Connector Designations .....................................................................................................A-1
A.1 Connector Designations......................................................................................................... A-1
Appendix B: Applicable Drawings............................................................................................................ B-1
B.1 Applicable Drawings............................................................................................................... B-1
Appendix C: Bill of Materials.....................................................................................................................C-1
C.1 Bill of Materials.......................................................................................................................C-1
Appendix D: Cable Termination Instructions..........................................................................................D-1
D.1 Cable Termination Instructions ..............................................................................................D-1
Appendix E: Modification Sheets/Engineering Instructions............................ .....................................E-1
E.1 Modification Sheets/Engineering Instructions........................................................................ E-1
(Blank page)
General Information
General Description
1
Section 1
General Information
1.1 General Description
The Victoreen® Model 943-227-15 Digital Preamplifier, is designed to operate with the Model 943-27, Current Mode Beta Scintillation detector and the Model 942A-200C Series Digital Ratemeter (UDR) or the Model 960 Series Digital Process Control system. When connected to the beta sensitive scintillation detector, it comprises a monitoring system which operates in the range of 10 Pico amperes). The UDR provides display, control, and annunciator functions for the monitoring system.
The preamplifier contains a microprocessor controlled, auto-zeroing, integrating electrometer, a programmable gain amplifier, an analog-to-digital converter and an asynchronous serial communications interface. Communications with the UDR is accomplished via the optically isolated Victoreen Serial Communication Loop driver/receiver circuitry.
Interconnection of the detector and preamplifier is accomplished utilizing two, six (6) foot coaxial cables. One cable supplies the high voltage for the detector (negative polarity). The other cable is used for the detector output signal. Interconnection between the preamplifier and the UDR or 960 system is accomplished via a six-conductor cable and a high voltage coaxial cable.
The detector operates at a potential of approximately (-) 500 VDC, and produces a nominal DC output current of 1 x 10 this corresponds to a range of 1 x 10
The preamplifier is a self-contained electronics unit that processes the DC input signal from the detector, digitizes the signal, and transmits the digitized value to the readout via a modified RS232C compatible serial data communication port. It contains two printed circuit boards (mounted on the rear of the enclosure cover, a terminal block for terminating the field cable from its associated controller and two connectors for terminating the detector Signal and HV coaxial cables. The larger of the two printed circuit boards is the 977-210-10M Serial Interface board. This board controls the communications with the controller. The smaller board is the 977-200-15M Electrometer. It contains the microprocessor and associated circuitry for converting the detector output current into a digital value.
For additional information on the detector or readout device, refer to the instruction manual for the Model 943-27-31 detector, the Model 942A-200C UDR, or the applicable Model 960 System manual.
-12
amperes to 1 x 10
-4
amperes. Depending on sampling geometry and detector set up,
-3
to 1 x 10
+5
uCi/cc.
-3
to 105 uCi/cc (or 1E0 to 1E8
1.2 Application
The Model 943-227-15 Digital Preamplifier is used with the Victoreen 942A-200C or Model 960 microprocessor based radiation monitors. The Model 942A-200C or 960 system provides the +15 VDC preamplifier electronics power, (-) 500 VDC detector power and the RS232C serial communications support. The digital preamplifier is available in two serial port configurations. For applications less than 50 feet, the Model 943-227-15, configured for RS232C communications, is used. For applications requiring signal transmission distances of up to 1 mile, the Model 943-227-15VL, configured for Victoreen Loop communications is used. Table 1-1 is a list of available configurations and compatible 9XX series equipment. Please contact Fluke Biomedical Radiation Management Services for additional information.
1-
1
943-227-15 Digital Preamplifier
Operator Manual
Table 1-1. 943-227-15 Variations and Compatible Equipment
Preamplifier Variations
943-227-15 Digital Preamplifier
943-227-15VL Digital Preamplifier
943-227-15VL-M1 Digital Preamplifier
Application Detector Readout
Transmission Distances Less than 50 feet
Transmission Distances up to 1 mile
Transmission Distances up to 1 mile; 2.0 inch conduit field cable interface
943-27-31 Beta Detector, Current Mode Operation
943-27-31 Beta Detector, Current Mode Operation
943-27-31 Beta Detector, Current Mode Operation
942A-200C Digital Ratemeter or Model 960 Digital Process Control System
942A-200C Digital Ratemeter or Model 960 Digital Process Control System
942A-200C Digital Ratemeter or Model 960 Digital Process Control System
1.3 Specifications
General specifications for the Model 943-227-15 Digital Preamplifier are listed below. The 943-227-15 series products are designed for nuclear applications, and any repairs to it by personnel not qualified to ANSI 45.2.6 1978, Skill Level II may void the nuclear rating.
If a problem develops, the preamplifier may either be returned to the factory for service, or repaired by a qualified technician.
1-2
Table 1-2. General Specifications for the 943-227-15 Digital Preamplifier
Feature: Specification:
Preamplifier Power
Preamplifier Input
Preamplifier Output
Electronic Accuracy
Response Time
Dimensions (H x W x D)
Weight
Housing
Operating Temperature
Relative Humidity
Compatible Detectors
Detector Interface
Cable Requirements
Modification Information
+ 15 v @ 20 mA DC current, 1E-12 to 1E-3 amperes from 943-27 Current Mode Beta
Scintillation detector 943-227-15, RS232C; 943-227-15VL, Modified RS232C serial data for transmission distances up to 5,280 feet.
± 10% of the input current Decade / Time:
1 / 80 sec 2 / 32 sec 3 / 16 sec 4 / 4 sec 5 / 2 sec 6 / 0.9 sec 7 / 0.2 sec 8 / 0.2 sec
943-227-15 or 943-227-15VL:
8.0 in. x10.0 in. x 4.0 in. (20.3 cm x 25.4 cm x 10.2 cm)
943-227-15-M1 or 943-227-15VL-M1:
8.0 in. x10.0 in. x 6.0 in. (20.3 cm x 25.4 cm x 15.2 cm)
Approximately 8 lbs. (3.6 kg)
Gasketed, NEMA 4, Steel enclosure with hinged cover 32 °F to 122 °F
0 °C to + 50 °C 0 to 99 % non-condensing
Victoreen 943-27 Current Mode Beta scintillation detector only Detector cables enter thru “Seal Grip” fittings; Mating SHV receptacle
provided for HV; Mating BNC receptacle provided for Signal Victoreen Loop Communications: 6 conductors, 18 AWG (2, TwPr, 2 Single conductor) with overall shield. For max transmission distance, 16 AWG is recommended; RS232C communications: 8 Conductors, 18 AWG (4 TwPr) with overall shield. For the Model 943-227-15VL-M1, refer to Modification description provided in Appendix E
General Information
Application
1
1-3
943-227-15 Digital Preamplifier
Operator Manual
Table 1-3. Preamplifier Serial Interface Board 977-210-10M Switch Settings
Switch Normal
Op.
SW1 Open Microprocessor Reset switch, momentary contact SW2 N/A Not supplied SW3-1 ON OFF Selects 300 baud • 1/ON Selects 4800 baud (normal setting)
SW3-2 OFF OFF • (No function is implemented in the 977-210-10M) SW3-3 OFF OFF Selects Rate Mode (normal) • (Selects Maintenance Mode for
SW3-4 OFF OFF • (No function is implemented in the 977-210-10M)
Switch Function
factory PGA and Auto Zero set-up only)
NOTE
SW3 is a 4-position DIP switch on the 977-210-10M serial interface board.
Table 1-4. Jumper Positions for Preamplifier Serial Interface Board 977-210-10M
Jumper Normal Setting Function Alternate Setting Function
JMP1 A to B JMP2 N/A Deleted, Not Used N/A Deleted, Not Used
Table 1-5. Jumper Positions for Preamplifier Electrometer Board 977-200-15M
Jumper Normal Setting Function Cal. Position Function
JMP1 A to B Normal Operation B to C PGA Offset Adjust *
* Programmable Gain Amplifier requires a special test PROM and is a factory adjustment
Enables Victoreen Loop (normal)
B to C Enables RS232C
1-4
Table 1-6. Field Electrical Connections, 943-227-15 and 943-227-15VL
General Information
Specifications
1
943-227-15
TB1- Description
1 XMIT
2 DTR
3 GND
4 REC
5
6
7 + 15 VDC J3-7 Not Used
8 Ground
9 - 15 VDC J3-4 Not Used Not Used
10 Not Used Not Used Not Used J3-11
HV Detector MHV
SIG Detector BNC
Table 1-7. 977-210-10M LEDs
LED # Indicates
LED1 +15 VDC is being supplied to the circuit board LED2 Communications – Receive;
Table 1-8. 977-210-10M Test points
Test Point Function
TP2 RS232 Transmit
Not Used
Not Used
Detector
Connections
from the UDR when ON ON (bright): both + 15 and -15 volt loops
present ON (dim): Only one loop supply present OFF: no loop voltage from either supply
Connects To
977-210-10M
J4-1
J4-2 J4-3 J4-4
Not Used Not Used
J3-8
From Field
coaxial cable
Factory
Terminated,
To 977-200-
15M, R41
943-27-15VL
Description
+ VL, 15
VDC + TX
- TX
- VL
+ RX
- RX
Ground
Detector
Connections
Detector
MHV
Detector
BNC
Connects To
977-210-10M
J3-1
J3-2
J3-3
J3-4
J3-5 J3-6
Not Used
J3-8
From Field
coaxial cable
Factory
Terminated,
To 977-200-
15M, R41
1-
5
943-227-15 Digital Preamplifier
Operator Manual
1.4 Auxiliary Equipment
Model Description
None
1.5 Recommended Spare Parts
Table 1-9. Recommended Spare Parts List for the Model 943-227-15 Digital Preamplifier
Part Number Description Used On
977-200-15M Electrometer Circuit Board -
977-210-10M Serial Interface Circuit Board -
92-7072 Fuse, F1, F2, 1Amp, Communication Fuse
450-1-0531 Dryer, Air (5 Grams)
977-210-10M
977-200-15
1.6 Receiving Inspection
Upon receipt of the unit:
1. Inspect the carton(s) and contents for damage. If damage is evident, file a claim with the carrier and notify the Fluke Biomedical Radiation Management Services Customer Service Department.
Fluke Biomedical
Radiation Management Service
6045 Cochran Road
Cleveland, Ohio 44139
Phone: 440.248.9300
Fax: 440.542.3682
2. Remove the contents from the packing material.
3. Verify that all items listed on the packing list have been received and are in good condition.
NOTE
If any of the listed items are missing or damaged, notify the Fluke Biomedical Radiation Management Service Customer Service Department.
1-6
General Information
Spare Parts/Receiving Inspection
1
1.7 Storage
Storage of Fluke Biomedical instruments must comply with Level B storage requirements as outlined in ANSI N45.2.2 (1972) Section 6.1.2(.2). The storage area shall comply with ANSI N45.2.2 (1972) Section
6.2 Storage Area, Paragraphs 6.2.1 through 6.2.5. Housekeeping shall conform to ANSI N45.2.3 (1972).
Level B components shall be stored within a fire resistant, tear resistant, weather tight enclosure, in a well-ventilated building or equivalent.
Storage of Fluke Biomedical instruments must comply with the following:
1. Inspection and examination of items in storage must be in accordance with ANSI N45.2.2 (1972) Section 6.4.1.
2. Requirements for proper storage must be documented and written procedures or instructions must be established.
3. In the event of fire, post-fire evaluation must be in accordance with ANSI N45.2.2 (1972), Section
6.4.3.
4. Removal of items from storage must be in accordance with ANSI N45.2.2 (1972), Sections 6.5 and
6.6.
1-
7
(Blank Page)
Theory of Operation
Functional Description
2
Section 2
Theory of Operation
2.1 Functional Description
The Model 943-227-15 Digital Preamplifier is an eight-decade, linear reading radiation. The preamplifier is sensitive to moisture and is mounted in a NEMA 4 sealed enclosure. The preamplifier box contains a desiccant package to remove moisture from the interior of the preamplifier. The desiccant has a color indicator to show when it should be replaced when the color changes to blue.
The detector electrometer converts the current from the detector to a voltage which is measured by the analog to digital converter of the preamplifier. Under program control, this measurement is made every 50 milliseconds on the first five decades and every 100 milliseconds on the upper three decades.
The electrometer is auto-ranging and auto-zeroing. An internal coarse zero control (factory adjusted) is provided. The microprocessor in the preamplifier performs data collection, integration and multiplication by a stored calibration factor, range changing and communication with the Model 942A-200C Digital Ratemeter or Model 960 Digital Process Radiation monitoring system.
2.2 Main Circuit Boards
The wide range ion chamber detector block diagram is shown in figure 2-1. Detector electronics are contained within two circuit board assemblies located in the preamplifier enclosure: the 977-210-10 High Voltage/Communications Interface circuit board assembly and the 977-200-15 Electrometer circuit board assembly. Schematic diagrams are located in Appendix B.
The 977-200-15M Electrometer circuit board contains the microprocessor, the EPROM, the integrating electrometer, the programmable gain amplifier, the analog to digital (A/D) converter, and the auto zero DAC circuit.
The 977-210-10M Communications Interface circuit board contains the dc voltage regulator, the BDC/DC converter, the asynchronous communication interface adapter (ACIA), the Victoreen communication loop driver/receiver, the RS232 communications driver/receiver, and the communication loop fuses.
2.3 977-200-15M Electrometer
Refer to the electrometer schematic 977-200-18M located in Appendix B. Z7 is a Texas Instruments TMS 70C00 microprocessor, which is utilized to control detector operation. Z8 latches port C of the microprocessor to form the lower order bits of memory address. Z10 is a 27C64 EPROM containing the operational firmware for the detector. Z18 is an optional RAM socket which is not utilized for this model detector. Z9 is a decoder for the upper order address bits. Z11 is a latch used to store control bits to select the gain of the programmable gain amplifier formed by the combination of Z5, Z4, and RN2. Available gains are 1 through 128 in binary increments 1, 2, 4, . . . 128. Z3 is an eight-bit analog to digital converter used to digitize the output of the programmable gain amplifier. Analog switch Z17 pin 11 selects either the integrating electrometer or the high voltage sense line as the input to the programmable gain amplifier is not active in this application. Refer to Table 2-1 for preamplifier register addresses and Table 2-2 for electrometer control bit assignments.
2-1
943-227-15 Digital Preamplifier
Operator Manual
0/-12 Vdc
0 - 10 Vdc
INTEGRATING ELECTROMETER
SIGNAL
DETECTOR ASSEMBLY
PGA
ANALOG SWITCH
HIGH VOLTAGE
MICROPROCESSOR CONTROL
SIGNAL
ALARM OUTPUT
Resistor
Resistor
DAC EPROM
ADC
HIGH VOLTAGE POWER SUPPLY
RS232
Figure 2-1. Typical Detector Electronics Block Diagram
Table 2-1. Preamplifier Register Addresses
Function Hex Address
Electrometer Control 2000 ADC Convert CMD 4000 ADC Read Data 6000 ACIA T/R Data A000 ACIA Status Register A001 ACIA Command Register A002 ACIA Control Register A003 Input SW3 A008 RAM (not used) C000-DFFF EPROM E000-FFFF
CONTROL
MICROPROCESSOR
+VL
VICO LOOP
+TX
-TX
+RX
-RX
-VL
ACIA
2-2
Theory of Operation
Main Circuit Boards
2
Table 2-2. Electrometer Control Bit Assignments
Bit Position 7 6 5 4 3 2 1 0 Description
X X X X X 0 0 0 Gain = 1 X X X X X 0 0 1 Gain = 2 X X X X X 0 1 0 Gain = 4 X X X X X 0 1 1 Gain = 8 X X X X X 1 0 0 Gain = 16 X X X X X 1 0 1 Gain = 32 X X X X X 1 1 0 Gain = 64 X X X X X 1 1 1 Gain = 128 X X X X 0 X X X Unshort capacitor X X X X 1 X X X Short capacitor X X X 0 X X X X Digitize electrometer X X X 1 X X X X Digitize high voltage
X = Bit position does not matter (1 or 0)
The integrating electrometer is formed by the combination of current source Z6, dual MOSFET Q4, operational amplifier Z12, transistor Q3, and analog switch Z17, pin 15.
Counter Z15 and ladder network RN3 form the auto-zero portion of the integrating electrometer. Refer to section 4 for auto-zero adjustment instructions (note this is a factory only adjustment).
Dual MOSFET Q4 acts as a low leakage input buffer to the electrometer. C17 is an integrating capacitor, while Z17, pin 15 and Q3 are the shorting elements of the integrator.
There is a hysteresis built into the range changing function of the electrometer. The range change-up occurs at the decade points whereas the range change-down occurs at 80% of the decade points. This hysteresis results in the display of only two significant digits when in the upper 20% of a decade. Whether or not this occurs depends on which direction the radiation level is trending. An increasing trend will result in three significant digits while a decreasing trend will result in two significant digits.
The response times for a change in reading within the same decade are listed in Table 2-1. If a change of 100 to 1000 times the current reading occurs, the instrument will range change within a single 50­millisecond clock cycle.
Table 2-3. Response Time
DECADE RANGE RESPONSE TIME
1 0.1 to 1.0 mR/h 80 sec. 2 1.0 to 10 mR/h 32 sec. 3 10 to 100 mR/h 16 sec. 4 100 to 1000 mR/h 4 sec. 5 1.0 to 10 R/h 2 sec. 6 10 to 100 R/h 0.9 sec. 7 100 to 1000 R/h 0.2 sec. 8 1.0 k to 10 kR/h 0.2 sec.
2-3
943-227-15 Digital Preamplifier
Operator Manual
The following Test are provided on the 977-200-15M board:
Table 2-4. 977-200-15M Test Points
Test Point Function
TP1 Electrometer Output TP2 Analog +5 VDC supply TP3 - 5 VDC supply TP4 Digital +5 VDC supply (From 977-210-10M) TP5 High Voltage Sense (Not Used) TP6 + 12 VDC supply (From 977-210-10M) TP7 DC Ground TP8 Programmable Gain Amplifier Output TP9 Microprocessor Clock Signal
TP10 Chip Enable - EPROM
2.4 977-210-10M Interface Board
Refer to the Communications Interface, P/N 977-210-13M, schematic diagram in Appendix B. U12 is an asynchronous communications interface adapter (ACIA) which communicates with the UDR or 960 system. U1 is an analog switch used to select either the Victoreen loop or the RS232 driver/receiver for external communications. Optical isolation U10 isolates data transmitted on the Victoreen loop while the circuitry comprised of Q6, Q7, Q14, and Q18 are the actual loop drivers. Optical isolator U8 isolates the receive data from the Victoreen loop.
U2 and U3 are, respectively, the receiver and driver circuits for the RS232 port. U14 decodes address block A000 to provide chip enables to the ACIA switch input register U6.
Regulated power for the electronics (+/- 12 VDC) is derived from three terminal regulators VR3 and VR4. The ±5 Vdc logic power is derived from the three terminal regulators VR1 and VR2.
Power for the detector is normally provided by the electronic high voltage power supply in the asso ciated Model 942A-200C UDR or Model 960 System.
The following LEDs are provided to indicate operation of certain functions of the 977-210-10M board:
Table 2-5. 977-210-10M LEDs
LED # Indicates
LED1 +15 VDC is being supplied to the circuit board
from the UDR when ON
LED2 Communications – Receive;
ON (bright): both + 15 and -15 volt loops present ON (dim): Only one loop supply present OFF: no loop voltage from either supply
The following Test are provided on the 977-210-10M board:
Table 2-6. 977-210-10M Test points
Test Point Function
TP2 RS232 Transmit
2-4
Theory of Operation
Communications
2
Victoreen Communications Loop – 943-227-15VL
Communication between the detector preamplifier and the UDR or 960 controller may be perfo rmed via Victoreen loop, a serial asynchronous communications interface. The communication utili zes Victoreen protocol and is intended for use in electrically hostile environments where high noise immunity is required. Noise immunity is achieved using differential line driving, and electrically isolating the end of each transmit/receive pair with opto-isolators. Using a ±15 Vdc communications power supply, each 0 to 1 transition is equivalent to a 30-volt swing in loop voltage. Refer to the Model 942-200-80-1 Communications Board instruction manual for further information.
Jumper JP1 controls the communication communications method employed. JP1, A-B selects Victoreen loop communications.
RS232C Communications – 943-227-15
Communication between the detector preamplifier and the UDR or 960 controller may be perfo rmed via RS232C serial asynchronous communications interface. Jumper JP1 controls the communication communications method employed.
JP1, B-C selects RS232C communications.
2.5 Preamplifier Switch & Jumper Settings
Switch and jumper settings for the preamplifier are summarized in Table 2-7, 2-8, and 2-9. Table 2-7. Preamplifier Serial Interface Board 977-210-10M Switch Settings
Switch Normal
Op.
SW1 Open Microprocessor Reset switch, momentary contact SW2 N/A Not supplied SW3-1 ON OFF Selects 300 baud • 1/ON Selects 4800 baud (normal setting)
SW3-2 OFF OFF • (No function is implemented in the 977-210-10M) SW3-3 OFF OFF Selects Rate Mode (normal) • (Selects Maintenance Mode for
SW3-4 OFF OFF • (No function is implemented in the 977-210-10M)
Switch Function
factory PGA and Auto Zero set-up only)
NOTE
SW3 is a 4-position DIP switch on the 977-210-10M serial interface board.
2-5
943-227-15 Digital Preamplifier
Operator Manual
Table 2-8. Jumper Positions for Preamplifier Serial Interface Board 977-210-10M
Jumper Normal
Setting
JMP1 A to B JMP2 N/A Deleted, Not Used N/A Deleted, Not Used
Table 2-9. Jumper Positions for Preamplifier Electrometer Board 977-200-15M
Jumper Normal
Setting
JMP1 A to B Normal Operation B to C PGA Offset Adjust *
* Programmable Gain Amplifier requires a special test PROM and is a factory adjustment
Function Alternate
Setting Enables Victoreen Loop (normal)
Function Cal.
B to C Enables RS232C
Position
Function
Function
2-6
Operation
Installation
3
Section 3
Operation
3.1 Installation
Installation consists of mounting the equipment, making the required electrical connections, and entering the desired set points.
CAUTION
Remove all power prior to installing the Preamplifier.
Preamplifier Mounting
The preamplifier is a self-contained unit that is designed for mounting on a wall, or structurally sound surface, within 6 feet of the detector. The preamplifier must be located in an area that is accessible for future maintenance.
CAUTION
Remove all power prior to connecting field wiring.
Electrical Interface
Electrical connections at the preamplifier include connecting the detector high voltage and sign al coaxial cables and the field cable from the associated controller.
The detector high voltage and signal cables enter the preamplifier through “Se al Grip” type penetrations on the enclosure body. The “Seal Grips” contain a rubber gland that is intended to grip the coaxial cables to prevent moisture entry into the enclosure. The “Seal Grips” are an integral part of the detector cables. The “Seal Grip” enclosure nut is removed from the fitting. The insulating washer stay with the fitting. The detector signal and high voltage cables, with connectors and “Seal Grip” fitting nuts are then inserted into the holes preamplifier enclosure. The “Seal Grip: end fittings are then re-installed securely again st the wall of the enclosure.
The detector Signal (BNC) and High Voltage (SHV) cables are then terminated on the bulkhead connectors located on the enclosure inner panel.
On the 943-227-15 or 943-227-15VL, the field cable is terminated on a “MS” type connector. A mating “MS” style connector supplied with the detector. It is not necessary to open the preamplifier enclosure to complete the interconnection to the associated controller.
On the 943-227-15VL-M1, a 2.0-inch conduit hub is provided to interface with the field conduit system and cable. The field conduit is connected to the preamplifier conduit hub and the field cable is routed through the conduit and into the preamplifier enclosure. The field signal cable is then terminated on the terminal block in the enclosure. Refer to the applicable wiring diagram or Table 3-1. The high voltage coax cable is then terminated on the mating SHV connector. Refer to Appendix D for further information.
A desiccant bag is provided in the enclosure to absorb moisture. The desiccant bags should be checked for moisture absorption prior to placing into service. Each bag contains a color indicator stripe that turns red when it should be replaced.
3-1
943-227-15 Digital Preamplifier
Operator Manual
NOTE
The electrometer circuitry in the preamplifier is highly sensitive to moisture and physical damage. Use extreme care when the preamplifier case is opened as the high impedance electrometer circuitry is easily damaged. Do not leave the preamplifier enclosure in the open position for any extended period of time.
The preamplifier terminations are listed below.
Table 3-1. 943-227-15 Preamplifier Electrical Connections
943-227-15
943-27-15VL
TB1- Description
1 XMIT
2 DTR
3 GND
4 REC
5
6
7 + 15 VDC J3-7 Not Used
8 Ground
9 - 15 VDC J3-4 Not Used Not Used
10 Not Used Not Used Not Used J3-11
HV Detector MHV
SIG Detector BNC
Not Used
Not Used
Detector
Connections
Connects To
977-210-10M
J4-1
J4-2 J4-3 J4-4
Not Used Not Used
J3-8
From Field
coaxial cable
Factory
Terminated,
To 977-200-
15M, R41
Description
+ VL, 15
VDC + TX
- TX
- VL
+ RX
- RX
Ground
Detector
Connections
Detector
MHV
Detector
BNC
Connects To
977-210-10M
J3-1
J3-2
J3-3
J3-4
J3-5 J3-6
Not Used
J3-8
From Field
coaxial cable
Factory
Terminated,
To 977-200-
15M, R41
3.2 Set-up
To place the system in operation, the following steps should be performed:
Ensure you have read and fully understand Section 1, 2 and 3 prior to continuing.
1. Verify that jumpers and DIP switches and jumpers on the preamplifier, are set for the operational features desired. Refer to Section 1, Table 1-4.
2. Refer to the applicable controller manual prior to powering up the controller.
3-2
NOTE
943-227-15 Digital Preamplifier
Operator Manual
3-3
Operation
Configuration
3
3.3 Operation
Operation of the 943-227-15 Digital Preamplifier is automatic and is controlled by the Model 942A-200C Digital Ratemeter or Model 960 Digital Process Radiation monitoring system. Once the power to the controlling device is turned on, the preamplifier begins operation. No operator interaction is required.
Refer to the instruction manual for the applicable controller, detector and the Model 942-200-80 Communications Option Board for further information.
Normal Operation
If the measured radiation field is within the range of the detector during power-up, the uCi/cc value will be displayed on the controller. The digital display will update once per second.
Alarms
The radiation alarms are initiated by the applicable controller. Refer to the applicable controller manual.
Fail Alarm
There are two equipment failure conditions that can produce a FAIL output or an error display on the associated controller. The fail condition is true whenever any equipment failure is detected and false when no equipment failures are detected.
The following are the fail alarms provided by the 943-227-15 Preamplifier:
1. POWER Failure
2. Loop Test Failure
To return the channel to normal operation after a FAIL alarm, the condition, which caused the alarm, must be located and corrected.
Power Failure
If the power to the controller is lost, the bar graph, alarm indicators, and the display are blanked (turned off). The HIGH, WARN, and FAIL relay coils will de-energize. If power to the preamplifier only is lost, or if there is a break in the power cable, operation of the microprocessor will stop. The display on the controller will then cease to update. If power to the controller is not lost, a break in the interconnecting wiring or the internal communication power fuses on the 977-210-10M Interface board should be checked. Loss of power to the preamplifier will also result in a loop communication failure.
Loop Failure
If the UDR or 960 controller does not receive a valid message from the preamplifier in ten seconds, a loop failure is detected and an E0009 code will normally be displayed. Note the error code displayed is defined by the controlling device, and not by the preamplifier.
The loop failure can originate from bad seating of the serial communications board in the UDR or 960CD, bad connections in the preamplifier, bad connections at the P2 connector of the UDR, a baud rate mismatch between the setting on the serial board and that in the preamplifier, an invalid address setting on the serial board, or blown communication loop fuses.
The baud rate of the preamplifier may be set to either 300 or 4800 baud. SW3-1 on the 977-interface board must be in the ON position to select a baud rate of 4800 baud, the normal setting.
3-4
943-227-15 Digital Preamplifier
Operator Manual
For UDR systems, the address of the 942-200-80 Communications board in the UDR must be set 4040 and the baud rate must be set to 4800 baud. If the wiring of the Communications option board to the P2 connector is suspected, a loop test can be performed as described in "Loop Test Mode". The instruction manual for the Communications option board (P/N 942-200-80-1) contains information on how to set up the serial board in the UDR.
Firmware Version
This system requires a PROM for operation. For the part number and the latest revision of the PROM, see the Factory Test Data Sheet. This Manual has been prepared for use with the P/N 227LNK, Rev. 2, PROM.
3.4 Configuration Functions
The preamplifier configuration jumpers and required settings for this application are listed below:
Table 3-2. Preamplifier Serial Interface Board 977-210-10M Switch Settings
Switch Normal
Op.
SW1 Open Microprocessor Reset switch, momentary contact SW2 N/A Not supplied
SW3-1 ON
SW3-2 SW3-3
SW3-4
OFF OFF
OFF
Switch Function
OFF Selects 300 baud • 1/ON Selects 4800 baud (normal setting)
OFF • (No function is implemented in the 977-210-10M)
OFF Selects Rate Mode (normal) • (Selects Maintenance Mode for
factory PGA and Auto Zero set-up only)
OFF • (No function is implemented in the 977-210-10M)
NOTE
SW3 is a 4-position DIP switch on the 977-210-10M serial interface board.
Table 3-3. Jumper Positions for Preamplifier Serial Interface Board 977-210-10M
Jumper Normal
Setting
JMP1 JMP2 N/A Deleted, Not Used N/A Deleted, Not Used
Table 3-4. Jumper Positions for Preamplifier Electrometer Board 977-200-15M
Jumper Normal
JMP1
* Programmable Gain Amplifier requires a special test PROM and is a factory adjustment
A to B
Setting A to B
Function Alternate
Setting Enables Victoreen Loop (normal)
Function Cal.
Normal Operation B to C PGA Offset Adjust *
B to C Enables RS232C
Position
Function
Function
3-5
Operation
Configuration
3
3.5 Set Point Error Codes
Failure of the 943-227-17 preamplifier may result in the following error codes being displayed on the controlling device:
Code E0009 is normally used to identify a Loop communication failure. The error code may be due to a baud rate mismatch between the preamplifier and the UDR or 960 system communication board, a failure on either the preamplifier or UDR communication board. To clear the error code, the source of the error must be corrected.
3.6 Software Calculations
The 943-227-17 continuously converts the current output of the detector to a digital value, controls the gain of the internal amplifier, performs periodic self checks, communicates with the UDR or Model 960 controller and provides a radiation value to the UDR of Model 960. An asynchronous, serial communication interface, processed through optically isolated drivers/receivers is utilized. The digital value is transmitted to the associated UDR or 960 System controller for further processing. Refer to the associated controller manual for further information. .
3-6
(Blank page)
Maintenance, Calibration and Troubleshooting
Maintenance
4
Section 4
Maintenance, Calibration and Troubleshooting
4.1 Maintenance
The 943-227-15 Digital Preamplifier is designed to operate for extended periods of time with no scheduled maintenance required. Operation may be verified by periodically actuating the check source (provided with the detector and sampling assembly) and observing the response of the unit. If the response varies by more than 50% of the normal value, further troubleshooting may be required. If a problem develops, troubleshoot the unit per Section 4.3 and the drawings in Appendix B.
Whenever the preamplifier enclosure is opened, the condition of the internal desiccant package should be
checked. The desiccant bag is provided in the enclosure to absorb moisture. The desiccant bags should
be checked for moisture absorption prior to placing into service, or whenever the electronics enclosure cover is opened. Each bag contains a color indicator stripe that turns red when it should b e replaced.
4.2 Electronic Calibration
Electronic Adjustments
There are no user adjustments available on the 943-227-15 Digital Preamplifier. The Programmable Gain Amplifier and Auto Zero are factory adjustments, requiring the use of a factory test PROM and test fixture. We strongly recommend the unit be returned to the factory for repair or adjustment.
Table 4-2 lists the electronic adjustments for the 943-227-15 digital preamplifier. The procedures for making these adjustments are contained in the factory Calibration Procedure listed below. Note that special test firmware is required to perform the electrical adjustments.
Table 4-1. Electronic Adjustments
Potentiometer Adjustment (943-227-15) Tolerance R11 Programmable Gain Amplifier Offset Adjustment ± 2 mV R12 Auto Zero Set-Up Adjustment ± 10 mV
Refer to the drawings in Appendix B to locate adjustment and/or test points, if required.
The follow factory calibration and test procedures are listed for reference only. Document Description TP943-227-15VL Test Procedure, Victoreen Loop Communications
TP943-227-15 Test Procedure, RS232 communications TP977-200-15M Electrometer PCB Test Procedure
NOTE
4-1
943-227-15 Digital Preamplifier
Operator Manual
4.3 Troubleshooting
WARNING
Extreme care must be used when troubleshooting a system that has power applied. All standard troubleshooting precautions apply.
WARNING
Once a problem has been located, remove all power before continuing with the repair.
CAUTION
Personnel performing the troubleshooting/repair must be qualified to ANSI 45.2.6, 1978, Skill Level II.
Personnel performing the following procedure must be familiar with the operation of the monitoring system and the location of each piece of equipment used in the system.
If a problem develops, verify that the voltages at connection point inputs and outputs are present and that all wiring is secure. Refer to Appendix B and C for drawings and parts lists. If a PROM requires replacement, specify the board revision level when ordering the part.
Troubleshooting / Adjustments
Troubleshooting includes a verification of the LED operation status, the DC voltage levels and the loop communication loop fuses (Victoreen Loop Communications only).
Specialized test equipment and firmware are required to adjust the auto-zero and PGA subsystems in the electrometer. If the test equipment and firmware is not available, the unit should be returned to Fluke Biomedical RMS for re-alignment.
4-2
Connector Designations
A.1 CONNECTOR DESIGNATIONS, 943-227-15 and 943-227-15VL
Table A-1. Field Electrical Connections, 943-227-15 and 943-227-15VL
943-227-15
943-27-15VL
Appendix
Connector Designations
Appendix A
A
TB1- Description
1 XMIT
2 DTR
3 GND
4 REC
5
6
7 + 15 VDC J3-7 Not Used
8 Ground
9 - 15 VDC J3-4 Not Used Not Used
10 Not Used Not Used Not Used J3-11
HV Detector MHV
SIG Detector BNC
Not Used
Not Used
Detector
Connections
Connects To
977-210-10M
J4-1
J4-2 J4-3 J4-4
Not Used Not Used
J3-8
From Field
coaxial cable
Factory
Terminated,
To 977-200-
15M, R41
Description
+ VL, 15
VDC + TX
- TX
- VL
+ RX
- RX
Ground
Detector
Connections
Detector
MHV
Detector
BNC
Connects To
977-210-10M
J3-1
J3-2
J3-3
J3-4
J3-5 J3-6
Not Used
J3-8
From Field
coaxial cable
Factory
Terminated,
To 977-200-
15M, R41
A-1
943-227-15 Digital Preamplifier
Operator Manual
A.2 SWITCH AND JUMPER POSITIONS,
943-227-15 and 943-227-15VL
Table A-2. Preamplifier Serial Interface Board 977-210-10M Switch Settings
Switch Normal
Op.
SW1 Open Microprocessor Reset switch, momentary contact SW2 N/A Not supplied SW3-1 ON OFF Selects 300 baud • 1/ON Selects 4800 baud (normal setting)
SW3-2 OFF OFF • (No function is implemented in the 977-210-10M) SW3-3 OFF OFF Selects Rate Mode (normal) • (Selects Maintenance Mode for
SW3-4 OFF OFF • (No function is implemented in the 977-210-10M)
Switch Function
factory PGA and Auto Zero set-up only)
NOTE
SW3 is a 4-position DIP switch on the 977-210-10M serial interface board.
Table A-3. Jumper Positions for Preamplifier Serial Interface Board 977-210-10M
Jumper Normal
Setting
JMP1 A to B JMP2 N/A Deleted, Not Used N/A Deleted, Not Used
Table A-4. Jumper Positions for Preamplifier Electrometer Board 977-200 -15 M
Jumper Normal
Setting
JMP1 A to B Normal Operation B to C PGA Offset Adjust *
* Programmable Gain Amplifier requires a special test PROM and is a factory adjustment
Function Alternate
Setting Enables Victoreen Loop (normal)
Function Cal.
B to C Enables RS232C
Position
Function
Function
A-2
Applicable Drawings
Appendix B
Applicable Drawings
B.1 Applicable Drawings 943-227-15 and 943-227-15VL
Drawing No. Description
943-227-15 Preamplifier Assembly, RS232 943-227-15VL Preamplifier Assembly, Victoreen Loop 943-227-15VL-M1 Preamplifier Assembly, Victoreen Loop, w/Conduit Hubs 977-210-10M Preamplifier HV/Interface Printed Circuit Board Assembly 977-210-13M Preamplifier Printed Circuit Board Schematic 977-200-15M Preamplifier Electrometer Board Assembly 977-200-18M Preamplifier Schematic
Appendix
B
B.2 Related Manuals (Not Supplied with this document)
SXXXXXX-1 Applicable 960 Series system Manual
942A-200C-M1 Digital Ratemeter
943-27-31-1 Current Mode Beta Detector
B-1
(Blank page)
Bill of Materials
Appendix C
Bill of Materials
C.1 Bill of Materials- 943-227-15 and 943-227-15VL
Part Number Description
943-227-15 Preamplifier Assembly, RS232 943-227-15VL Preamplifier Assembly, Victoreen Loop 943-227-15VL-M1 Preamplifier Assembly, Victoreen Loop, w/Conduit Hubs 977-210-10M Preamplifier HV/Interface Printed Circuit Board Assembly 977-200-15M Preamplifier Electrometer Board Assembly
Appendix
C
C-1
(Blank page)
Appendix
Cable Termination Instructions
D
Appendix D
Cable Termination Instructions
D.1 Cable Termination Instructions
The procedures and instructions provided in Appendix D are provided for reference in terminating the field cables to the Digital Preamplifier. A mating SHV connector is provided with the preamplifier. Ring lug terminals are to be provided by the user. The instructions provided below are based on the use of P/N 50-100 multi-conductor cable. For other customer-supplied cables, the same basic procedures, modified for the specific cable used, may be utilized.
Detector Cable Termination:
The detector high voltage and signal cables enter the preamplifier through “Seal Grip” type penetrations on the enclosure body. The “Seal Grips” contain a rubber gland that is intended to grip the coaxial cables to prevent moisture entry into the enclosure. The “Seal Grips” are an integral part of the detector cables. The “Seal Grip” enclosure nut is removed from the fitting. The insulating washer stays with the fitting. The detector signal and high voltage cables, with connectors and “Seal Grip” fitting nuts are then inserted into the holes preamplifier enclosure. The “Seal Grip: end fittings are then re-installed securely against the wall of the enclosure.
Detector Field Cable Preparation, “MS” Connector:
Prior to stripping the outer cable jacket, a 4-inch length of 0.75 I.D. shrinkable tubing (provided by the user) should be slid over the 0.675 in cable jacket. The shrink tubing will be used to seal and protect the end of the cable after the termination process is completed. To prepare the cable for termination, a minimum of 7 inches of the cable outer jacket must be stripped off the cable. This will allow for the stripping of approximately one inch from the various conductors, and provide 6 inches of actual service loop cable. In addition, for EMI/RFI protection, the drain wire must be terminated to an earth ground within the enclosure. The length of the drain wire will be based on the distance between the cable entry and the ground location. The length of cable jacket to be stripped will then be based on the distance to the drain wire grounding point.
Once the cable outer jacket is stripped to the proper length, the aluminum tape shield and Mylar binder may be removed, taking care not to damage the No. 20 AWG drain wire. The drain wire may then be separated from the remaining conductors, for routing and termination at the grounding point.
Next, the HV coaxial cable may be separated from the bundle, followed by the single conductors wires that are required for the specific application, and the polyester filler cord. Refer to the project specific detector loop drawing, or the generic detector loop drawing provided in Appendix B for actual conductors to be used.
The polyester filler cord may now be removed. Cut the cord as close to the outer jacket as possible.
The single conductors may now be stripped and soldered to the appropriate connector pin.
D-1
943-227-15 Digital Preamplifier
Operator Manual
Detector Field Cable Preparation, 943-227-15VL-M1, Conduit Hub:
Prior to terminating the cable, the field conduit must be run to the junction box, and the field cable pulled into the junction box.
To prepare the cable for termination, a minimum of 7 inches of the cable outer jacket must be stripped off the cable. This will allow for the stripping of approximately one inch from the various conductors, and provide 6 inches of actual service loop cable. In addition, for EMI/RFI protection, the drain wire must be terminated to an earth ground within the enclosure. The length of the drain wire will be based on the distance between the UDR rear panel and the ground location. The length of cable jacket to be stripped will then be based on the distance to the drain wire grounding point.
Once the cable outer jacket is stripped to the proper length, the aluminum tape shield and Mylar binder may be removed, taking care not to damage the No. 20 AWG drain wire. The drain wire may then be separated from the remaining conductors, for routing and termination at the grounding point.
Next, the HV coaxial cable may be separated from the bundle, followed by the single conductors wires that are required for the specific application, and the polyester filler cord. Refer to the project specific detector loop drawing, or the generic detector loop drawing provided in Appendix B for actual conductors to be used. The ring lug connectors may now be applied to the single conductor cables, and installed in accordance with the project electrical loop diagram.
Trim each conductor as required to reach its assigned terminal poi nt. Allow a minimum of 1 in. spare conductor for future re-termination. Because of the unique requirements of each installation, terminal lugs for the detector single conductor terminations are not included, and are supplied by the user. Ring terminal, Crimp type lugs, Burndy YAE type, sized for the 18 AWG wire, or equivalent, are recommended.
The terminal block is designed to accept a maximum 14 AWG conductor, and is provided with 6-32 mounting screws. Strip the conductor as required by the lug manufacturer, install the lug, and terminate the conductor to the appropriate terminal. The screw terminals may now be torqued to 12 in-lbs.
The mating HV connector, P/N 30-92-1 (Kings 1705-14), may now be terminated per the applicable Kings data sheet attached.
The polyester filler cord may now be removed. Cut the cord as close to the outer jacket as possible
D-2
Appendix
Cable Termination Instructions
D
HV CONNECTOR NOTES (HV)
The mating HV connector, P/N 30-92-1 (Kings 1705-14), may now be terminated per the applicable Kings
data sheet attached
LOCATION P/N DOCUMENT DESCRIPTION SHV 92-9105-A CP-400, Kings High Voltage Connector,
SHV (1705-1) Cabling SHV, male crimp contact Procedure, Trim Code pin (Use Tool KTH-100 with 441, 442 KTH-2062)
SHV Alternate AMP Instruction High Voltage Connector, Connector Sheet SHV, male crimp contact 92-9105-A 408-2187 pin (Use Tool 69710-1 with (51426-5) 220028-2 Die or Integral Die Tool 220022-2)
SHV 32-92-1 CP-1001, Kings Cabling High Voltage Connector, SHV, (1705-14) Procedure, CP-1000, Female solder contact pin
D-3
943-227-15 Digital Preamplifier
Operator Manual
D-4
Appendix
Cable Termination Instructions
D
D-5
943-227-15 Digital Preamplifier
Operator Manual
D-6
Appendix
Cable Termination Instructions
D
D-7
943-227-15 Digital Preamplifier
Operator Manual
D-8
Appendix
Modifications
E
Appendix E
Modification Sheets, Engineering Instructions
E.1 Modification Sheets, Engineering Instructions
P/N Description
943-227-15VL-M1 Modification consists of replacing the standard 8in
H x 10in W x 4in D Enclosure with a 8in H x 10in W x 6in D Enclosure and replacing the field cable “Seal Grip” type entry fitting with a 2.0 in diameter sealed conduit fitting.
E-1
(Blank page)
(Blank page)
Fluke Biomedical
6045 Cochran Road Cleveland, Ohio 44139
440.498.2564
www.flukebiomedical.com
Loading...