Fluke proudly introduces an entry level thermal imager for quick,
easy, and accurate problem identification and troubleshooting
designed specifically for the building inspection professional.
cian, energy auditor, HVAC, insulator, or windows installer the
Fluke Thermal Imaging Scanner is the perfect tool to help you
identify hidden building construction issues, find moisture intrusion, detect energy loss/missing insulation, and many basic
electrical connection and load problems.
in a thermal imager engineered for the value-conscious building
professional.
imager in its price class and the most affordable thermal camera
to meet the proposed RESNET infrared inspection standards.
Technical Data
Whether you are a building inspector, home inspector, electri-
Now Fluke quality, durability, and performance are available
The Fluke TiS Thermal Imaging Scanner is the top-performing
Building problems,
defects and general
maintenance
Energy audit,
building inspection,
weatherization
Restoration,
water damage,
roofing
United States and Canada
Key features:
• The most affordable thermal imager on the market that meets
the proposed RESNET infrared inspection standard
• Highest resolution (120x120) in price class
• Only imager in price class with versatile, one-handed,
manual focus
• Largest display size (3.7 in) in price class. 30 % larger than
comparable imagers!
• Long battery life lasts ~4 hours
• Rugged body engineered to withstand 2 m (6.5 ft) drop test
• Award winning ergonomic design
• Easy to use—the TiS Thermal Imaging Scanner provides you
with a basic, reliable solution for the building professional
• Trusted quality of Fluke brand

Detailed specifications
Temperature
Temperature measurement range
(not calibrated below -10 °C)
Temperature measurement accuracy ± 5 °C or 5 % (at 25 °C nominal, whichever is greater)
Imaging performance
Image capture frequency 9 Hz refresh rate
Detector type 120 X 120 Focal Plane Array, uncooled microbolometer
Thermal sensitivity (NETD) ≤ 0.1 °C at 30 °C target temp. (100 mK)
Infrared spectral band 7.5 µm to 14 µm (long wave)
Standard infrared lens type
Focus mechanism Versatile, one-handed manual focus
Image presentation
Palettes Ironbow, Blue-Red, Grayscale
Level and span Smooth auto-scaling and lock of level and span
Minimum span (in auto mode) 5 °C (9 °F)
Image capture, review, save mechanism One-handed image capture, review, and save capability
Storage medium SD Memory Card (2 GB memory card will store at least 1200 fully radiometric (.is2)
File formats Non-radiometric (.bmp) or fully-radiometric (.is2)
Export file formats w/SmartView
Memory review Sequential image navigation and review
®
software BMP, DIB, GI F, JPE, JFIF, JPEG, JPG, PNG, TIF, and TI FF
TiS
-20 °C to +100 °C (-4 °F to +212 °F)
Field of view: 17° x 17°
Spatial resolution: (IFOV) 2.50 mRad
Minimum focus distance: 15 cm (approx. 6 in)
IR images annotations, or 3000 basic bitmap (.bmp) images, transferrable to PC via included
multi-format USB card reader
No analysis software required for non-radiometic bitmap (.bmp) files
General specifications
Operating temperature -10 °C to +50 °C (14 °F to 122 °F)
Storage temperature -20 °C to +50 °C (-4 °F to 122 °F) without batteries
Relative humidity 10 % to 95 % non-condensing
Display 9.1 cm (3.7 in) diagonal landscape color VGA (640 x 480) LCD with backlight and clear
Controls and adjustments User selectable temperature scale (°C/°F)
Software SmartView
Batteries Internal rechargeable battery pack (included)
Battery life Three to four hours continuous use (assumes 50 % brightness of LCD)
Battery charge time 2.5 hours to full charge
AC battery charging AC adapter/charger (110 V ac to 220 V ac, 50/60 Hz) (included), charges battery while imager
AC operation AC operation with included power supply (110 V ac to 220 V ac, 50/60 Hz), ac mains
Power saving Sleep mode activated after five minutes of inactivity, automatic power off after 30 minutes of
Safety standards CSA (US and CAN): C22.2 No. 61010-1-04, UL: UL STD 61010-1 (2nd Edition), ISA: 82.02.01
Electromagnetic compatibility Meets all applicable requirements in EN61326-1:2006
C Tick IEC/EN 61326-1
US FCC CFR 47, Part 15 Class B
Vibration 0.03 g2/Hz (3.8 grms), IEC 68-2-6
Shock 25 g, IEC 68-2-29
Drop 2 meter (6.5 feet)
Size (H x W x L) 26.7 cm x 12.7 cm x 15.2 cm (10.5 in x 5.0 in x 6.0 in)
Weight (battery included) 1.2 kg (2.6 lb)
Enclosure rating IP54 (protected against dust, limited ingress; protection against water spray from
Warranty Two-years (standard)
Recommended calibration cycle Two-years (assumes normal operation and normal aging)
Supported Languages Czech, English, Finnish, French, German, Italian, Japanese, Korean, Polish, Portuguese,
protective cover
Language selection
Time/Date set
User selectable backlight: “Full Bright” or “Auto”
® full analysis and reporting software included
is operating or turned off, ac mains adapters included
adapters included
inactivity
all directions)
Russian, Simplified Chinese, Spanish, Swedish, Traditional Chinese, Turkish, and
(Dutch and Hungarian in manual only)
2 Fluke Corporation Fluke TiS Building Diagnostic Thermal Imaging Scanner - United States and Canada