Fluke T5-600, T5-1000 Installation Instructions

Voltage Indicator
®
Continuity & Resistance
Display HOLD
T5-600/T5-1000
Electrical Tester
Instruction Card
Lisez la fiche de sécurité T5-600/T5-1000 avant d'utiliser cet appareil.
Prima di usare questo tester leggere le istruzioni per la sicurezza allegate al T5­600/T5-1000.
Vor Verwendung des Prüfgeräts das Sicherheitsblatt T5-600/T5-1000 lesen.
Lea la hoja de instrucciones de seguridad T5-600/T5-1000 antes de utilizar este probador.
Antes de usar este instrumento de teste, leia a Folha de Segurança T5-600/T5-1000.
Lees vóór gebruik veiligheidsblad bij de T5-600/T5-1000.
Les sikkerhetsdataene for T5-600/T5-1000 før testinstrumentet tas i bruk.
Man bør læse sikkerhedsanvisning T5-600/T5­1000 inden man benytter instrumentet.
Lue T5-600/T5-1000 –turvaohjeet ennen tämän mittarin käyttöä.
Läs säkerhetsdatabladet för T5-600/T5-1000
innan du använder denna testare.
Warning
van deze tester het
V
T5-600 max: 600 V CAT III T5-1000 max: 1000 V CAT III, 600 V CAT IV
HOLD
AC/DC
V
Automatic
Selection
V
45 Hz - 66 Hz T5-600 max: 600 V rms CAT III T5-1000 max: 1000 V rms CAT III, 600 V rms CAT IV
Open
A
0.5"(12.9 mm) maximum
Short
1000 Range
Less than 25
Greater than 400
AC
A
AC
HOLD
Tactile Barrier
HOLD
1
HOLD
2
HOLD
PN 1631780 December 2001, Rev. 3, 1/13
2001 - 2013 Fluke Corporation. All rights reserved. Printed in China.
©
AC/DC
V
Automatic
Selection
HOLD
AC
HOLD
OK
Sensor
OK
Zone
OK
1 Wire
only
3
Auto Off
LO
45 min
OFF
Warning
Disconnect test leads from power source before opening battery door.
Débranchez les cordons d'essai avant d'ouvrir le couvercle de la pile.
Prima di aprire lo sportello del vano della pila, scollegare i cavetti dal circuito di alimentazione.
Die Prüfleiter vor dem Öffnen des Batteriefachs von der Stromquelle trennen.
Desconecte los conductores de prueba de la fuente de alimentación antes de abrir la cubierta de la batería.
Antes de abrir a tampa do compartimento das pilhas,
desconecte os terminais de teste da
fonte de alimentação.
Maak de meetkabels los van de stroombron voordat u de batterijklep opent.
Koble prøveledningene fra strømkilden før batteridekselet åpnes.
Søgeledningerne skal tages evt. emne, inden batteridækslet åbnes.
Irrota koestusjohtimet virtalähteestä ennen paristolokeron avaamista.
Koppla bort mätsladdarna från strömkällan
innan du öppnar batteriluckan.
Do not
+
overtighten screw
+
2 AA
+
+
Specifications
Specifications subject to change without notice.
Calibration 1-year calibration cycle Temperature
Operating: Storage:
Altitude Operating: Storage:
Relative Humidity
Battery Type and Life
RF Field Specification
Enclosure Rating
Temperature coefficient
Accuracy
Safety ......................... IEC 61010-1: Pollution Degree 2
Electromagnetic
Environment ................ IEC 61326-1: Portable
-10 °C to +50 °C (14 °F to 122 °F)
-30 °C to +60 °C (-22 °F to +140 °F)
2000 m (6562 ft) 10,000 m (32808 ft)
0 % to 95 %, 5 °C to 30 °C (41
°F to 86 °F); 0 % to 75 %,
°C to 40 °C
30 (86
°F to 104 °F); 0 % to 45 %,
40
°C to 50 °C
(104
°F to 122 °F)
AA (2); 360 hours continuous with alkaline; 125 hours continuous with zinc chloride
0.5 % full scale + (specified accuracy) at 3 V / m
IP 52 per IEC 60529, no vacuum applied
0.1 x (specified accuracy) / °C for <18
°C or >28 °C (< 64.4 °F or > 82.4 °F) ± ( [ % of reading] + [number of least
significant digits] ) Accuracy is specified for 1 year after calibration, at 18 (64
°F to 82 °F) with relative humidity
to 90 %. AC conversions are ac­coupled, average responding, and calibrated to the rms value of a sine wave input.
°C to 28 °C
Function
T5-600 Range
(600 V
CAT III)
600 V
600 V 1000 V 1 V ±(1 % + 1 digit)
100.0 A 100.0 A
1000 1000 1 ±(1 % + 2 digits)
rms
T5-1000
Range (1000 V CAT III)
1000 V
rms
Reso­lution
1 V ±(1.5 % + 2 digits)
0.1 A
Replacement Parts
Test Lead Assembly. Replace only with Fluke double-insulated
See "Accessories" for available
leads (
)
probes.
rooD yrettaB
wercS rooD yrettaB
Use only specified replacement parts.
Accessories
H
5 Belt Holster
TP1 Probe Set, Flat-Blade AC285 SureGrip Alligator Clips AC220 SureGrip Alligator Clips Service Information Sheet, PN 686953
To contact Fluke, call:
USA: 1-800-44-FLUKE (1-800-443-5853) Canada: 1-800-36-FLUKE (1-800-363-5853) Europe: +31 402-675-200
Japan: +81-67143114 Singapore: +65-738-5655 Anywhere in the world: +1-425-446-5500
Visit Fluke's Web site at www.fluke.com.
Accuracy
45 Hz - 66 Hz
±(3 % + 3 digits)
45 Hz - 66 Hz
PN 648029
PN 2091779
PN 8758161