Fluke 922 Catalog Page

Fluke 922
922 Airflow Meter
Measures pressure, air flow and velocity for maintaining balanced and comfortable ventilation
The Fluke 922 makes air ow measurements easy by combining pressure, air  ow, and velocity into a single, rugged meter. Compatible with most Pitot tubes, the Fluke 922 allows technicians to conveniently enter their duct shape and dimensions for maximum measurement accuracy.
Use the Fluke 922 to: Ensure proper air  ow balance and maintain a comfortable environment; measure pressure drops across  lters and coils; match ventilation to occupant loads; monitor indoor vs. outdoor pressure relationships and manage the building envelope; and perform duct traversals for accurate air ow readings.
Feature Range Resolution Accuracy
Operating Specifications
Air Pressure ± 4000 Pascals
Air Velocity 250 to 16,000 fpm
Air Flow (Volume) 0 to 99,999 cfm
Temperature 0 °C to 50 °C 0.1°C ± 1 % + 2 °C
± 16 in H2O ± 400 mm H2O ± 40 mbar ± 0.6 PSI
1 to 80 m/s
0 to 99,999 m 0 to 99,999 l/s
• Provides differential and static pressure, air velocity and  ow readings
• Convenient colored hoses help you properly diagnose pressure readings
• Bright, backlit display for clear viewing in all environments
• Min/Max/Average/Hold functions for easy data analysis
• Auto power off saves battery life
Specifications
(Check the Fluke web for detailed specifications)
3
/hr
1 Pascal
0.001 in H2O
0.1 mm H2O
0.01 mbar
0.0001 PSI 1 fpm
0.001 m/s 1 cfm
1 m3/hr
1 l/s
± 1% +1 Pascal ± 1% + 0.01 in H2O ± 1% + 0.1 mm H2O ± 1% +0.01 mbar ± 1% + 0.0001 PSI
± 2.5 % of reading at 10 m/s (2000 p/min)
Accuracy is a function of velocity and duct size
Included Accessories
Fluke 922: Two Rubber Hoses, Wrist Strap, Four AA Batteries 1.5 V Alkaline, Users Manual and Soft Carrying Case Fluke 922 Kit Includes: Fluke 922 Airflow Meter,
30.48 cm Pitot tube, ToolPak, Two Rubber Hoses, Wrist Strap, Four AA Batteries 1.5 V Alkaline, Users Manual and Hard Carrying Case
Ordering Information
Fluke 922 Air Flow Meter Fluke 922/Kit Airflow Meter with
30.48 cm Pitot Tube
General Specifications
General specifications
Operating Temperature 0 ºC to +50 ºC Storage Temperature -40 ºC to +60 ºC Operating Relative Humidity Non condensing (<10 ºC)
IP Rating IP40 Operating Altitude 2000 m Storage Altitude 12000 m EMI, RFI, EMC Meets requirements for EN61326-1 Vibration MIL-PREF-28800F, Class 3 Max Pressure at Each Port 10 PSI
Data Storage: 99 readings Size (HxWxD): 175 mm x 77.5 mm x 41.9 mm Weig ht : 0.64 kg Battery: Four AA batteries Battery Life: 375 hours without backlight,
80 hours with backlight
Two Year Warranty
90% RH (10 ºC to 30 ºC) 75% RH (30 ºC to 40 ºC) 45% RH (40 ºC to 50 ºC) Without Condensation
Fluke 922/Kit
Recommended Accessories
94
PT12
Pitot Tube, 30.48 cm
TPAK
Toolpak
See page 155