Fluke 902 Service Guide

Why true-rms matters for HVAC technicians
Non-linear loads need a true-rms test tool for accurate readings
For today’s HVAC technician, troubleshooting electrical problems is becoming more difficult without the use of true rms test tools. This is due in part to the proliferation of new solid state adjustable speed motor drives and heating controls containing power semiconductors or rectifiers. These loads are referred to as “non linear.” Non linear loads draw current in short pulses rather than the smooth sine wave drawn by a linear load such as an induction motor. The current wave shape can have a drastic effect on a test tool reading.
There are two types of electrical test tools commonly available: “Average responding-rms indicating” and “true-rms.” The average responding units give correct readings for linear loads such as induction motors, resistive heaters, and incandescent lights.
But when loads are non-linear, average responding meters may read anywhere from 5 % to as much as 40 % low when measuring line side currents.
Application Note
True-rms implications for HVAC
Consider all the problems found in complex HVAC and refrigera­tion systems. There’s a full range of electrical and mechanical issues, of course, but also control system problems, air supply bal­ance, compressor performance and the delicate balance of cool­ant temperature and pressure,
F r o m t h e F l u k e D i g i t a l L i b r a r y @ w w w . f l u k e . c o m / l i b r a r y
Checking current on a compressor controller with a true-rms Fluke 902 HVAC Clamp Meter.
superheat, subcooling and air flow that is fundamental to air conditioning and refrigeration performance.
Now consider how many of those involve non-linear loads. Essentially, any control or system containing semiconductors in the power supply would be consid­ered a non linear load.
Normally when troubleshoot­ing an HVAC equipment failure
or nuisance trips due to an elec­trical problem, your first instinct would be to check the panel for tripped circuit breakers or over­loading.
However, if a non-linear load is on that circuit, you’ll need a true-rms test tool to accurately measure the true load current to determine where the problem is—is the circuit faulty, is it over­loaded, or is the problem with the load itself?
One current—two readings. Which do you trust? The branch circuit above feeds a non-linear load with distorted current. The true-rms clamp on the right reads correctly but the average responding clamp reads low by 32 percent.
HVAC electrical measure­ments affected by rms
Here’s a birds-eye view of the HVAC electrical measurements that require a true-rms test tool.
Measuring supply side current
and voltage as well as load side current and voltage
Measuring current and volt-
age phase balance on 3 phase systems
Troubleshooting compressor
electrical motor faults
Troubleshooting compressor motor faults
Compressor failures are often caused by electrical faults. The best tool for this measurement sequence is a true-rms clamp meter like the Fluke 902 or a true rms digital multimeter with a current clamp accessory.
1. Allow the compressor to cool down prior to the electrical test. This allows the device to reset to its normal position. Then, remove the electrical terminal cover.
2. Check line voltage at the load center with the compressor off. Low line voltage causes the motor to draw more current than normal and may result in overheating and premature failure. Line voltage that is too high will cause excessive inrush current at motor start, again leading to premature failure.
3. Check line voltage at the motor terminals with the com­pressor running. The true-rms voltage should be within 10 % of the motor rating.
4. Check running current. The readings should not exceed manufacturers’ full load rated amps during heavy load peri­ods. Low amps are normal during low load conditions. Excessive current may be due to shorted or grounded wind­ings, a bad capacitor, a faulty relay, or bearing fatigue.
Troubleshooting compressor motor failures caused by refrigeration system problems
Compressor electrical problems are often caused by mechani­cal system failure or installation and service errors. Compressor bearings can fail or lock up due to improper lubrication or insuffi­cient oil return to the compressor (largely due to poor piping). To diagnose this problem, measure the compressor current with a true-rms test tool. The current readings should not exceed man­ufacturers full load ratings. Worn bearings will cause higher than normal current readings.
Checking for voltage imbalance in a three-phase compressor motor
Voltage imbalance in three­phase motors causes high cur­rents in the motor windings.
These higher currents generate additional heat that degrades and destroys winding insula­tion. A 10 °C rise in motor tem­perature can reduce motor life by half.
Voltage unbalance is usually caused by adding single phase loads on the same circuit used by the compressor, although sometimes component failure is the culprit. Voltage unbalance for three phase motors shouldn’t exceed one percent, otherwise the motor load capacity should be derated. To calculate voltage unbalance, use this formula:
% Voltage Unbalance = 100 x (maximum deviation from average) / Average voltage
For example, given true-rms voltages of 449, 470, and 462, the average voltage is 460. The maximum deviation from the average is 11 volts. The percent unbalance is 100 x 11 / 460 =
2.39 %. That result indicates a voltage unbalance problem. The closer the motor is matched to the load, the less reserve power it has and the more important it becomes to periodically check motor supply voltages.
Checking for current unbalance in a three-phase compressor motor
For accurate results, measure current with a true-rms clamp meter or true rms DMM with a clamp attachment. The goal behind measuring current on a three-phase compressor motor is to ensure that the full load rat­ing on the motor nameplate isn’t exceeded and to verify that all three phases are balanced.
Unbalanced current can be caused by voltage imbalance between the phases, a shorted motor winding, or a high resis­tance connection. To calculate current unbalance, use the same formula as above but substitute current in amps. Maximum cur­rent unbalance for three-phase motors is typically 8 % to10 %. A 1 % voltage unbalance will cause an 8 % current unbalance.
2 Fluke Corporation Why true-rms matters for HVAC technicians
Loading...
+ 1 hidden pages