Fluke 718, 753, 754, 707, 87V Service Guide

HART® Transmitter
Calibration
Application Note
Introduction
In today’s process plants, most new field instruments are smart digital instruments. Smart implies a microprocessor-based instrument with extra function­ality and digital compensation, supporting multiple sensor types or multiple variables. These instruments generally offer better accuracy, long-term sta­bility, and reliability than con­ventional analog instruments.
The most common class of smart instruments incorpo­rates the HART protocol, with more than five million HART instruments in use in 100,000 plants worldwide. HART, an acronym for Highway Address­able Remote Transducer, is an industry standard that defines the communications protocol between smart field devices and a control system that employs traditional 4-20 mA wiring.
Two capabilities are required to properly service HART instru­ments: precision analog source and measure capability and digital communication capabil­ity. Until recently, this required two separate tools, a calibrator and a communicator. Today, the capabilities of those two tools are available in a single HART Documenting Process Calibra­tor that can help you quickly and effectively service HART instruments.
From the Fluke Digital Library @ www.fluke.com/library
HART calibration
Sensor
Sensor Trim LRV/URV Adjust Output Trim
PV PVAO 4-20 mA
Input
Section
Conversion
Section
Output
Section
Analog
Input
(digital
input)
(digital
4-20 mA)
Analog
mA Output
is required!
A common misconception is that the accuracy and stability of HART instruments eliminate the need for calibration. Another misconception is that calibra­tion can be accomplished by re­ranging field instruments using only a HART communicator. Still another misconception is that the control system can remotely calibrate smart instruments. These are not true. All instru­ments drift. Re-ranging with just a communicator is not cali­bration. A precision calibrator or standard is required. Regular performance verification with a calibrator traceable to national standards is necessary due to:
1. Shifts in performance of electronic instruments over time, due to exposure of the electronics and the primary sensing element to tempera­ture, humidity, pollutants, vibration, and other field environmental factors.
2. Regulations governing occu­pational safety, consumer safety, and environmental protection.
3. Quality programs such as ISO 9000 standards for all instru­ments that impact product quality.
4. Commercial requirements such as weights, measures, and custody transfer.
Regular calibration is also prudent since performance checks will often uncover problems not directly caused by the instrumentation, such as solidified or congealed pressure lines, installation of an incor­rect thermocouple type, or other errors and faults.
A calibration procedure con­sists of a verification (As Found) test, adjustment to within acceptable tolerance if neces­sary, and a final verification (As Left) test if an adjustment has been made. Data from the cali­bration are collected and used to complete a report of calibra­tion, documenting instrument performance over time.
All instruments, even HART instruments, must be cali­brated on a regular, preventive maintenance schedule. The calibration interval should be set short enough to insure that
an instrument never drifts out of tolerance, yet long enough to avoid unnecessary calibra­tions. Alternatively, the interval may be determined by critical process requirements, e.g., cali­bration before each batch.
How are HART instruments properly calibrated?
To calibrate a HART instrument consistent with its application, it is very helpful to understand the functional structure of a typical HART transmitter.
HART instruments consist of three distinct sections (see Figure 1). Proper HART calibra­tion may involve either or both sensor trim and output trim. Adjusting range values (LRV and URV) without a calibrator is not calibration. Performing an output trim while ignoring the input section is not proper calibration. Adjusting range
values with a calibrator may be a practical calibration alterna­tive for instruments operated in 4-20 mA analog mode, provided that the PV and PVAO are not used for process control.
Figure 1.
2 Fluke Corporation Abridged HART Transmitter Calibration
Model Number
PV
(Primary Variable)
PVAO
(Digital representation
of the Primary Variable
Analog Output)
Analog Measure Value Analog Source Value
Tag ID
PV LRV (Primary Variable Lower Range Value)
PV URV (Primary Variable Upper Range Value)
Figure 2.
New tool speeds calibration
Today, instrument maintenance is moving out of the shop and into the field. This reduces process interruptions and avoids the time and expense of returning instruments to the shop. Portable communicators and calibrators are often used
3 Fluke Corporation Abridged HART Transmitter Calibration
together to complete field cali­brations. However, the desire to carry less equipment and to per­form maintenance in the field has created a need for a new class of calibration tool.
The new 754 Documenting Process Calibrator from Fluke is a powerful yet easy-to-use tool for field calibration of HART instrumentation. Pressing a
single key enters the HART mode and displays the essential HART information in the Active Device Screen, shown in Figure
2. Additional HART functional­ity is accessed with only a few more keystrokes, per the menu tree in Figure 3.
Loading...
+ 5 hidden pages