Fluke 289 Service Guide

Multimeter measurements
on variable frequency
drives using the new
Fluke 289 DMM
Editor’s note: For similar instructions using the
Fluke 87V DMM, reference Fluke article 12345.
In the past, motor repair meant dealing with traditional three-phase motor failures that were largely the result of water, dust, grease, failed bearings, misaligned motor shafts, or just plain old age. But, motor repair has changed in a big way with the introduction of electronically controlled motors, more commonly referred to as variable frequency drives (VFD). Drives present technicians with a unique set of measurement problems that can vex the most seasoned pro.
This application note describes the elec­trical measurements you can make dur­ing the installation and commissioning of a drive, as well as other measurements to aid in diagnosing bad components, and other conditions that may lead to prema­ture motor failure in VFDs.
Application Note
Troubleshooting philosophy
There are many different ways to go about troubleshooting an electrical circuit, and a good troubleshooter will always find the problem—eventually. The trick is to track down the problem as quickly as possible, keeping downtime to a minimum.
The most efficient procedure for troubleshooting is to begin at the motor, and then systemati­cally work back toward the elec­trical source, looking for the most obvious problems first. A lot of time and money can be wasted replacing perfectly good parts when the problem is nothing more than a simple loose con­nection.
From the Fluke Digital Library @ www.fluke.com/library
Next, take care to make accurate measurements. Nobody makes inaccu rate measurements on purpose of course, but it’s easier to do than you may think, especially when working in a high energy, noisy environment like that of an VFD. Choosing the right test tools for troubleshoot­ing, the drive, the motor, and the connections is of the utmost importance. This is especially true when making voltage, frequency and current measurements on the output side of the motor drive. Until now the only meter on the market able to make these measurements accurately was the Fluke 87V Digital Multimeter. Fluke has just introduced the next generation of high performance Multimeter, the new Fluke 289,
incorporating the same selectable low pass filter found in the successful 87V DMM. The filter allows the meter to make accurate drive output measure­ments that will now agree with the motor drive controller display indica- tions. No longer does the technician have to guess whether the drive is operating correctly and deliv- ering the correct voltage, current, or frequency for a given control setting.
Drive measurements
Input side measurements
You can use any good quality true rms multimeter to verify proper input power to the drive. The input voltage readings should be within 2 % of one another when measured phase to phase with no load. A sig­nificant unbalance may lead to erratic drive operation and should be corrected when dis­covered.
Output side measurements
Measurements on the output side of a pulse width modulated (pwm) motor drive have been difficult or impossible to make, especially accurate measure­ments, that would agree with the drive controller displayed values. The traditional true rms multimeter will not provide accu­rate answers. This is because the voltage applied to the motor terminals by the VFD is a pulse width modulated non-sinusoidal voltage.
A true-rms DMM will give an accurate reading of the heat­ing effect of the non-sinusoidal voltage applied to the motor, but will not agree with the motor controller’s output voltage read­ing which is displaying the rms value of the fundamental component only (typically from 30 Hz to 60 Hz). The issues are bandwidth and shielding. Many of today’s true rms digital multi­meters have a wide bandwidth, sometimes out as far as 20 kHz or more, which allows the meter to respond not only to the fun­damental component that the motor really responds to, but also to all of the high frequency com­ponents generated by the pwm drive.
In addition, if the dmm is not shielded for high frequency noise, this can also lead to poor measurement performance due to the high noise levels generated by the drive controller. Because of their higher bandwidth and shielding issues, many true rms meters will display readings as much as 20 to 30 % higher than the drive controller is indicating.
289 dual display showing frequency and voltage
Fluke’s new 289 multimeter, with it’s ¼ VGA dot matrix dis­play, has the ability to display multiple parameters at the same time and utilize the selectable low pass filter, giving the trou­bleshooter or engineer the ability make accurate voltage, current and frequency measurements on the output side of the drive either at the drive itself or at the motor terminals and also display the filtered output voltage and frequency (motor speed) simulta­neously. With the filter selected, the 289 readings for both volt­age and frequency (motor speed) should now agree with the associated drive control display indications if they are available. When measuring output current with a clamp accessory, the low pass filter allows for accurate current measurements and fre­quency measurements simultane­ously when using the Hall-effect type clamps. All of these mea­surements are especially helpful when making measurements at the motor location when the drives displays are not in view.
Making safe measurements
Before making any electri­cal measure ments, be sure you understand how to make them safely. No test instrument is com­pletely safe if used improperly, and you should be aware that many test instruments on the market are not appropriate for testing variable frequency drives. Also insure that the appropriate personal protective equipment (PPE) is used in accordance with the specific working environ­ment and the measurements to be made. If at all possible, never work alone.
Safety ratings for electrical test equipment
ANSI and the International Electro technical Commission (IEC) are the primary independent organizations that define safety standards for test equipment manufacturers. The IEC 61010 second edition standard for test equipment safety states two basic parameters, a voltage rat­ing and a measurement category rating. The voltage rating is the maximum continuous working voltage the instrument is capable of measuring. The category rat­ings depict the measurement environment expected for a given category. Most three-phase VFD installations would be considered a CAT III measurement environ­ment with power supplied from either 480V or 600V distribution systems. When using a digital multimeter for measurements on these high energy systems, insure that the multimeter is rated at a mini­mum for CAT III 600V and pref­erably for CAT IV 600V/CAT III 1000V. The category rating and voltage limit are typically found on the front panel of the multimeter right at the input terminals.
The new Fluke 289 DMM is dual rated CAT IV 600V and CAT III 1000V.
Refer to the ABC’s of DMM Safety from Fluke for additional information on category ratings and making safe measurements.
2 Fluke Corporation Multimeter measurements on variable frequency drives using the new Fluke 289 DMM
Making the measurements
Measurements for this procedure will be made on a 480 V three phase drive control at the control panel terminal strips using the new Fluke 289 digital multimeter. These procedures would also be valid for lower voltage 3 phase drives powered by either single or 3 phase supply voltages. For these tests the motor is running at 30 Hz.
Input Voltage
To measure the ac voltage supply to the input side of the drive at the drive:
1. Select the 289’s ac voltage
function.
2. Connect the black probe to
one of the three phase input terminals. This will be the reference phase.
3. Connect the red probe to one
of the other two phase input terminals and record the reading or save it to the 289’s internal memory.
4. Leaving the black probe on
the reference phase now move the red probe to the third phase input and record or save this reading to the 289’s internal memory.
5. Check to make sure that
there is no more than a 2 % difference between these two readings.
The new Fluke 289 also contains internal memory for saving specific individual measurements that can be recalled on screen or downloaded to reports generated by Fluke View Forms
®
software.
Input Current
Measuring the input current requires using a current clamp accessory. This is because it is not practical to “break the circuit” to make an in-line series current measurement. Regardless of the type of clamp used, check to insure that all readings are within 5 % of each other for proper balance.
Transformer type clamp (Fluke models i200, i400, 80i-400, 80i-600A, i800)
1. Connect the clamp to the 289’s common and
400 mA input jacks.
2. Select the mA/A ac function.
3. Place the clamp around each of the input supply
phase cables in succession, recording or saving to internal memory each of the readings as they are taken. Since these clamps output 1 milliamp per amp, the milliamp readings shown on the 289 display are the actual phase current read­ing in amps.
Hall Effect type (AC/DC) clamp (i410, i-1010)
1. Connect the clamp to the 289’s common and
V/Ω input jacks.
2. Select the 289’s mVac voltage function for cur-
rent measurements up to 500 amps.
3. Since the lowest range on the 289 is
50.000 mVac push the range button once to place the meter in the 500.00 mVac range if the drive current will exceed 50 amps for the measurement.
4. Place the clamp around each of the input supply
phase cables in succession, recording each of the readings as they are taken or again save to the 289’s internal memory. Since these clamps output 1 millivolt per amp, the millivolt readings shown on the 289 display are the actual phase current reading in amps.
3 Fluke Corporation Multimeter measurements on variable frequency drives using the new Fluke 289 DMM
289 with i1010 AC/DC Clamp accessory
Output voltage and motor speed using the low pass filter
Output voltage reading with low pass filter enabled
Output voltage and motor speed (Output frequency using voltage as a reference)
An important new feature on the 289 multimeter is its ability to simultaneously display both the filtered output voltage and frequency (motor speed) at the same time without having to push additional buttons or change functions.
To measure the ac output voltage and motor speed, either at the drive or at the motor disconnect:
1. Plug the black test lead into the common jack and the red test lead into the V/ jack.
2. Select the 289’s ac voltage function.
3. Select MENU then (LPF+Hz) to enable the low pass filter and the Hz function.
4. Connect the black probe to one of the three phase output voltage or motor terminals. This will be the reference phase.
5. Connect the red probe to one of the other two phase output voltage or motor terminals and record the reading or save to the 289’s internal memory.
6. Leaving the black probe on the reference phase now move the red probe to the third phase output voltage or motor terminal and record or save this reading.
7. Check to make sure that there is no more than a 2 % difference between these two readings. These readings should also agree within these limits with the controller display panel if available.
8. If the low pass filter is not enabled the output voltage readings may be between 10-30 % higher than what is expected and the frequency readings will be inaccurate and unstable.
Output voltage and frequency (motor speed) without the low pass filter (incorrect readings)
Output voltage and frequency (motor speed) using the low pass filter (correct readings)
4 Fluke Corporation Multimeter measurements on variable frequency drives using the new Fluke 289 DMM
Output current and frequency (motor speed)
With the large dot matrix display on the 289 multimeter, it is possible to display both the ac current reading and its’ associated frequency simultaneously, allowing the technician or installer to see both the load current and motor speed at the same time, in the same display.
Transformer type clamp (i200, i400, 80i-400, 80i-600A, i800)
1. Regardless of the type of clamp used, check to insure that all phase current readings are within 5% of each other for proper balance
2. Connect the clamp to the 289’s common and 400 mA input jacks.
3. Select the mA/A ac function. If you want to take advantage of the 289’s dual display, then select MENU then Hz.
4. Place the clamp around each of the output phase cables in succession, recording each of the readings as they are taken or save them to internal memory for later use. Since these clamps output 1 milliamp per amp, the milliamp readings shown on the 289 display are the actual phase current reading in amps as well as the frequency of the ac current signal.
Hall Effect type (AC/DC) clamp (i410, i-1010)
1. Connect the clamp to the 289’s common and V/Ω input jacks.
2. Select the 289’s mVac voltage function for current measurements up to 500 amps.
3. Select MENU then (LPF+Hz) to enable the low pass filter and the Hz function. This will allow the meter to reject all of the high frequency noise generated by the drive controller. Once the low pass filter has been enabled the meter is now in manual range mode.
4. Since the lowest range on the 289 is 50.000 mVac push the range button once to place the meter in the 500.00 mVac range if the drive current will exceed 50 amps for the measurement.
5. Place the clamp around each of the output supply phase cables in succession, recording each of the readings as they are taken or again save to the 289’s internal memory. Since these clamps output 1 millivolt per amp, the millivolt readings shown on the 289 display are the actual phase current reading in amps.
Caption?
Phase current reading + motor speed using i1010 clamp
DC Bus measurements
A healthy dc bus is a must for a properly operating motor drive. If the bus voltage is not correct or unstable it may be an indication that the converter diodes or capacitors may be starting to fail. The dc bus voltage should be approximately 1.414 times the phase to phase input voltage. For a 480 volt input, the dc bus should be approximately 679 V dc. The DC Bus is typically labeled as DC+, DC- or B+, B- on
To measure the dc bus voltage:
1. Select the 289’s dc voltage function.
2. Connect the black probe to either the DC- or B- terminal.
3. Connect the red probe to the DC+ or B+ terminal.
The bus voltage should agree with the example mentioned above and be relatively stable. You can also check the amount of ac ripple on the bus by simply switching the 289’s function switch to the vac function.
the drive terminal strip.
5 Fluke Corporation Multimeter measurements on variable frequency drives using the new Fluke 289 DMM
Fluke. Keeping your world up and running.
Fluke Corporation PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V. PO Box 1186, 5602 BD Eindhoven, The Netherlands
For more information call: In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa +31 (0) 40 2675 200 or Fax +31 (0) 40 2675 222 In Canada (800)-36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com
©2008 Fluke Corporation. Specifications subject to change without notice. Printed in U.S.A. 7/2008 3291974 A-EN-N Rev A
®
Loading...