Flir AX8 Data Sheet

FLIR AX8
Automated, multi-spectral temperature sensor for condition monitoring and hot spot detection
FLIR AX8
Combining thermal and visual cameras in a small, affordable package,
the AX8 provides continuous temperature monitoring and alarming
for uninterrupted condition monitoring of critical electrical and
mechanical equipment.
The AX8 helps you guard against unplanned outages, service
interruptions, and equipment failure by providing uninterrupted
temperature monitoring, so you’ll get the benets of continuous
condition monitoring and hot spot detection without the need for
periodic manual scans.
Compact and easy to install, AX8 provides continuous monitoring of:
• Process and manufacturing industries
• Data centers
• Energy generation and distribution
• Transportation and mass transit
• Storage facilities
IP67 Rated Housing
FLIR’s Revolutionary Lepton
Micro Thermal Camera Core
640 x 480 Built-In
Visual Camera
54 × 25 × 95 mm
®
• Refrigeration warehouses
AUTOMATIC ANALYSIS AND ALARMS
With its streaming video output, the AX8 not only gives you live video
of every installation, but it also provides automated alarming when
pre-set temperature thresholds are exceeded. More advanced alarms
like temperature trending can be done by using PLC’s.
AX8 provides:
Industry-standard interfaces
• Ethernet/IP
• Modbus TCP
Multiple streaming video formats
• MPEG
• MJPEG
• H.26 4
IDENTIFY PROBLEMS EARLY
Loose Connection
Overloaded Fuse
The images displayed may not be representative of the actual resolution of the camera shown. Images for illustrative purposes only. Specifications are subject to change without notice.
ww w.flir.com
COMPACT & EASY TO INSTALL
Combining thermal and visual cameras in a small, affordable package,
the AX8 measures only 54 x 25 x 95 mm, making it easy to install in
space-constrained areas for uninterrupted condition monitoring of
critical electrical and mechanical equipment.
Constantly Monitor Critical Equipment
Peace of Mind in Manufacturing
MULTIPLE VIDEO OPTIONS
With A X8, you can view its thermal imagery, visible light imagery, or
the two combined into FLIR’s proprietary, patent pending MSX multi-
spectral dynamic imaging.
MSX provides image detail from the visible camera embossed on the thermal image, giving you:
• Sharper edge detail
• The abilit y to read labels
• Better contextual awareness
With MSX
Spot Heat Variance Quickly
AX8 KEY FEATURES
• Extremely affordable
• Ultra-compact
• Intelligent temperature sensor
• Built in analysis
• Power over Ethernet (PoE)
• MSX
Without MSX
Innovative, small and affordable the FLIR AX8 is an industry game changer for continuous thermal monitoring of critical installations and facilities.
Technical specifications FLIR AX8
Imaging & Optical Data
IR resolution 80 × 60 pixels
Thermal sensitivity/NETD < 0.10°C @ +30 °C (+8 6°F) / 100 mK
Field of view ( FOV ) 48° × 37°
Focus Fixed
Detector data
Detector t ype Focal Plane Array (FPA), uncooled microbolometer
Spectral range 7.5 –13 μ m
Visual camera
Built-in digital camera 640 × 480
Digital camera, FOV Max 66°, Adapts to the IR lens
Sensitivity Minimum 10 Lux without illuminator
Measurement
Object temperature range –10°C to +150°C (14°F to 302° F)
Accuracy
±2°C (±3.6 °F) or ±2% of reading (+10 to +100C@+10 to +35 amb)
Measurement analysis
Spotmeter 6
Area 6 boxes with max./min./average/position
Automatic hot/ cold detection
Isotherm 1 with above/below/interval
Measurement presets Ye s
Measurement option Schedule response: File sending (ftp), email (SM TP)
Difference temperature
Reference temperature
Atmospheric transmission correction
Optics transmission correction
Emissivity correction Variable from 0.01 to 1.0
Reected apparent temperature correction
External optics/ windows correction
Measurement corrections Global and individual object parameters
Max/Min temp. value and position shown within box
Delta temperature between measurement
functions or reference temperature
Manually set or captured
from any measurement function
Automatic, based on inputs for distance,
atmospheric temperature and relative humidity
Automatic, based on signals from internal sensors
Automatic, based on input of reected temperature
Automatic, based on input of optics/window
transmission and temperature
Alarm
Alarm functions
Alarm output
6 automatic alarms on any selected measurement
function, Digital In, Camera temperature
Digital Out, log, store image, le sending
(ftp), email (SMTP), notication
Set-up
Color palettes Color palettes (BW, BW inv, Iron, Rain)
Set-up commands Date/time, Temperature °C/ °F
Web interface Yes
Storage of images
Storage media Built-in memor y for image storage
Image storage mode
Periodic image storage Yes
File formats JPEG, JPEG+FFF, PNG+JPEG, FFF, FFF+PNG
IR/ visual images, simultaneous storage of IR
and visual images. Visual and IR image
automatically grouped together.
Ethernet
Ethernet Control, result and image
Ethernet, type 100 M bps
Ethernet, standard IEEE 802.3
Ethernet, connector type M12 8-pin X-coded
Ethernet, video streaming Yes
Ethernet, power Power over Ethernet, PoE IEEE 802.3af class 0.
Ethernet, protocols
Et he r n e t /I P, M o d b u s T C P, T C P, U D P, SN T P, RT S P,
RTP, HTT P, ICMP, IGMP, ftp, SMTP, SMB (CIFS),
DHCP, MDNS (Bonjour), uPnP
Image streaming
Image streaming formats
Image streaming resolution
Image modes
Automatic image adjustment
Manual image adjustment Level/span/max /min
Motion JPEG, MPEG stream, H.26 4,
Stream format MPEG - 4 ISO/ IEC 14496-2
640 × 480
Thermal, Visual,
MSX (IR -image with enhanced detail presentation)
Continuous/manual; linear or histogram based; possible to lock max, min or span temperature
Power system
External power operation 12/24V DC, 2 W continuously/ 3.1 W absolute max
External power, connector M12 8-pin A-coded (Shared with digital I/O)
Voltage Allowed range 10–3 0V DC
Environmental data
Operating temp. range 0°C to +5 0°C (32°F to +122°F)
Storage temp. range
Humidity (operating and storage)
EMC
Encapsulation IP67 (IEC 60 529 )
Bump 25 g (IEC 600 68 -2-2 9)
Vibration 2 g (IEC 60068 -2- 6)
–4 0°C to +70°C (– 40°F to +158°F)
IAW IEC 6 8-2-1 and IEC 68-2-2
IEC 60 06 8-2-30/ 24 h 95% relative humidity +25°C to +4 0°C (+77°F to +104°F)/ 2 cycles
EN 61000-6-2:2001 (Immunity) EN 61000-6-3:2001 (Emission)
FCC 47 CFR Part 15 Class B (Emission)
Physical data
Camera size (L × W × H)
54 × 25 × 79 mm w/o connectors
54 × 25 × 95 mm w/ connectors
Shipping information
Packaging
Infrared camera with lens, Printed documentation,
User documentation CD-ROM
BELGIUM
FLIR S yst ems Trading Belgium BVBA Luxemburgstraat 2 B-2321 Meer Belgium PH: +32 (0) 3 665 51 00
PORTL AND
Corporate Headquarters
FLIR S yst ems, Inc. 27700 SW Parkway Ave. Wilsonville, OR 970 70 USA PH: +1 866.47 7.3687
www.flir.com flir@flir.com NASDAQ: FLIR
Equipment described herein may require US Government authorization for expo rt purpos es. Diver sion contr ary to US law is p rohibited . Imagery f or illust ration pur poses only. S pecifica tions are sub ject to chan ge without notic e. ©2014 F LIR Syste ms, Inc. All r ights rese rved. (Cre ated 09/ 14)
NASHUA
FLIR S yst ems, Inc. 9 Townsend West Nashua, NH 06063 USA PH: +1 603.324.7 611
SANTA BARBARA
FLIR S yst ems, Inc. 70 Castilian Drive Goleta, CA 93117 USA PH: +1 805.690.5097
ww w.flir.com
Loading...