Fisher IM Supplement: Safety manual for FIELDVUE DVC6200 SIS Digital Valve Controller, Position Monitor, and LCP200 Local Control Panel Manuals & Guides
This safety manual provides information necessary to design, install, verify and maintain a Safety
Instrumented Function (SIF) utilizing the Fisher DVC6200 SIS digital valve controller. The DVC6200
SIS can be installed with a local control panel (LCP200). This document must be thoroughly
reviewed and implemented as part of the safety lifecycle. This information is necessary for
meeting the IEC 61508 or IEC 61511 functional safety standards.
WARNING
This instruction manual supplement is not intended to be used as a stand-alone document. It must be used in conjunction
with the following documents:
Fisher DVC6200 Series Quick Start Guide (D103556X012
Fisher DVC6200 SIS Instruction Manual (D103557X012
Fisher LCP200 Instruction Manual (D104296X012
Failure to use this instruction manual supplement in conjunction with the above referenced documents could result in
personal injury or property damage. If you have any questions regarding these instructions or need assistance in obtaining
any of these documents, contact your Emerson sales office
)
)
)
.
www.Fisher.com
DVC6200 SIS Digital Valve Controller
February 2022
Instruction Manual Supplement
D103601X012
2.Description of the Device
The Fisher DVC6200 SIS digital valve controller is an instrument which delivers controlled
pneumatic pressure to modulate a valve actuator in response to an electrical signal. An optional
valve position monitor will either transmit a 420 mA signal in response to the actual valve travel or
open and close a discrete limit switch based on a configurable trip point. An LCP200 can be used in
conjunction with the DVC6200 SIS to locally open and close a safety shutdown valve as well as
initiating a partial stroke test.
This safety manual applies to the DVC6200 SIS instrument with electronics hardware revision 2
(HW2) and firmware revision 4, 5, 6, and 7 with the following product options.
OPTION
MODELCONSTRUCTION
DVC6200 SISIntegral, Aluminumnnnnnnnn
DVC6200S SIS
DVC6205 SIS
DVC6215
Integral,
Stainless Steel
Remote Mount
Aluminum
DETTETT4-20 mA24 VDC
nnnnnnnn
(1)
,
nnnnnnnn
Double-
Acting
Direct
Single-
Acting
Reverse
Single-
Acting
Direct
Position
Monitor
APPLICATION
DETTnnnnnnn
ETTnnnnnn
4-20 mAnnnnnnn
24 VDCnnnnnn
1. The Remote Mount construction is not available with the DVC6200 SIS High Cv option.
Accessories
LCP100/LCP200Local Control Panel, HART Only
LC340Line Conditioner, 24 VDC
2
Instruction Manual Supplement
D103601X012
DVC6200 SIS Digital Valve Controller
February 2022
3.Terms, Abbreviations, and Acronyms
βBeta factor for common cause effects of failure
DD
DETTDeenergize to Trip
DTM
DVC6200 SISDigital Valve Controller, product model designation for Safety Instrumented System applications
ESDEmergency Shut Down
ETTEnergize to Trip
FITFailure In Time (1x109 failures per hour)
FMEDAFailure Mode Effect and Diagnostic Analysis
HART
HCv1
HCv2
HCv3Pneumatic booster with an exhaust Cv of 6.2 and a fill Cv of 3.2 for single direct acting.
HFTHardware Fault Tolerance
λ
LC340
LCP100
LCP200
Low Demand
Mode
Multidrop
PFD
AVG
PointtoPointOperating mode of the DVC6200 SIS whereby the instrument is powered with 420 mA.
PVSTPartial Valve Stroke Test
Relay A
Relay B
Relay C
SafetyFreedom from unacceptable risk of harm.
Safety
Function
SFFSafe Failure Fraction
SIFSafety Instrumented Function
SILSafety Integrity Level
SISSafety Instrumented System
SOVSolenoid Operated Valve
Type A
Element
Type B
Element
Device Description, an electronic data file that describes specific features and functions of a
device to be used by host applications.
Device driver that provides a unified structure for accessing device parameters, configuring and
operating the devices, and diagnosing problems.
Highway Addressable Remote Transducer, open protocol for digital communication
superimposed over a direct current.
Pneumatic booster with a Cv of 1.2 for double acting and both single direct and reverse acting.
(Note: single-acting reverse certified for ETT applications only.)
Pneumatic booster with a Cv of 3.2 for double acting and both single direct and reverse acting.
(Note: single-acting reverse certified for ETT applications only.)
Failure rate. λDD: dangerous detected; λDU: dangerous undetected; λSD: safe detected; λSU: safe
undetected.
Line Conditioner; product model designation for a device that is inserted in the loop when the
instrument (in Multidrop Mode) is powered with a lowimpedance 24 V source, to enable HARTr
communications.
Local Control Panel; product model designation for a device that can be connected to a DVC6200
SIS instrument to enable manuallyinitiated functions.
Mode of operation of a safety instrumented function where the demand interval is greater than
twice the proof test interval.
Operating mode of the DVC6200 SIS where the instrument controls the current drawn to enable
it to be powered with 24 VDC.
Average Probability of Failure on Demand
Pneumatic booster relay for double or single acting applications. Typical construction for double
acting DETT applications.
Pneumatic booster relay for single acting reverse applications. Typical construction for single
acting ETT applications.
Pneumatic booster relay for single acting direct applications. Typical construction for single
acting DETT applications.
Function of a device or combination of devices intended to be used within a Safety Instrumented
System to reduce the probability of a specific hazardous event to an acceptable level.
“NonComplex” element (using discrete components); for details see 7.4.4.1.2 of IEC 615082.
“Complex” element (using complex components such as micro controllers or programmable
logic); for details see 7.4.4.1.3 of IEC 615082.
3
DVC6200 SIS Digital Valve Controller
February 2022
4.Related Literature
D Fisher DVC6200 Series Quick Start Guide (D103556X012)
Instruction Manual Supplement
D103601X012
D Fisher DVC6200 SIS Instruction Manual (D103557X012
D 62.1:DVC6200 SIS, Fisher DVC6200 SIS Product Bulletin (D103555X012
D HART Field Device Specification for Fisher DVC6200 SIS (D103638X012
D Fisher LCP200 Local Control Panel Instruction Manual (D104296X012
D 62.1:LCP200, Fisher LCP200 Local Control Panel Product Bulletin (D104313X012
)
)
)
)
)
D IEC 61508: 2010 Functional safety of electrical/electronic/programmable electronic
safetyrelated systems
D ANSI/ISA 84.00.012004 (IEC 61511 Mod.) Functional Safety – Safety Instrumented Systems for
the Process Industry Sector
D Exida FMEDA Report for Fisher DVC6200 SIS, Position Monitor Applications
Report No. EFC 12/02027 R001
D Exida FMEDA Report for Fisher DVC6200 SIS, DETT and ETT Applications
Report No. EFC 12-02-027 R004 V3 R0
D Exida FMEDA Report for Fisher DVC6200 SIS Digital Valve Controller with High Cv Option, ESD
D Exida FMEDA Report for Fisher DVC6200 SIS Digital Valve Controller with High Cv Option, ESD
ETT applications - Report No. EFC 14/03-045 R001 V1 R5
4
Instruction Manual Supplement
D103601X012
DVC6200 SIS Digital Valve Controller
5.General Requirements
WARNING
To ensure safe and proper functioning of equipment, users of this document must carefully read all
instructions, warnings, and cautions in this safety manual and the Quick Start Guide.
D Refer to the Fisher DVC6200 SIS Quick Start Guide (D103556X012) for mounting and
configuration.
February 2022
D If a LCP200 is used, refer to the Fisher LCP200 instruction manual (D104296X012
configurations and mounting.
D Tools needed:
DVC6200 SIS
D Flat Head Screwdriver, 3 mm Thin Blade (wiring terminations)
D Phillips Screwdriver
D 3/8” Hex Key (terminal box conduit plug)
D 6 mm Hex Key (module base screws)
D 5 mm Hex Key (terminal box screw)
D 2.5 mm Hex Key (I/P converter screws)
D 1.5 mm Hex Key (terminal box cover screw)
D 9/64” Hex Key (spool valve screws, HCv1)
D 3 mm Hex Key (spool valve screws, HCv2 and HCv3)
LCP200
) for wiring
D Phillips Screwdriver (ground screw)
D Flat Head Screwdriver, 3 mm Thin Blade (wiring terminations)
D 10 mm Hex Key (cable entry plug)
D 4 mm Hex Key (terminal cover screw)
D 2.5 mm Hex Key (LED module screw, front panel screw)
D Torque wrench capable of 2 - 2.5 N•m (18 - 22 lb•in) (terminal cover screw)
D Personnel performing maintenance and testing on the DVC6200 SIS and LCP200 shall be
competent to do so.
5
DVC6200 SIS Digital Valve Controller
February 2022
Instruction Manual Supplement
D103601X012
6.Safety Instrumented System Design
When using the DVC6200 SIS digital valve controller or DVC6200 SIS with the LCP200 in a safety
instrumented system, the following items must be reviewed and considered.
6.1 SIL Capability
6.2 Safety Function
6.3 Failure Rates
6.4 Application Limits
6.5 Environmental Limits
6.6 Application of the Switch Output for Diagnostic Annunciation
6.1. SIL Capability
D Systematic Integrity
SIL 3 Capable— the digital valve controller has met manufacturer design process
requirements of IEC 61508 Safety Integrity Level 3.
D Random Integrity
D The digital valve controller is classified as a Type A device according to IEC 61508. The
complete final element subsystem will need to be evaluated to determine the SFF. If the
SFF of the subsystem is >90%, and the PFD
< 103, the design can meet SIL 3 @ HFT=0.
avg
D The position monitor is classified as a Type B device according to IEC 61508. The
complete final element subsystem will need to be evaluated to determine the SFF. If the
SFF of the subsystem is >90%, and the PFD
If the SFF of the subsystem is between 60% and 90%, and the PFD
< 102, the design can meet SIL 2 @ HFT=0.
avg
< 101, the design
avg
can meet SIL 1 @ HFT=0.
D The LCP200 is classified as a Type B device per IEC61508. If the SFF of the relay output
state change subsystem is >90% and the PFD
avg
0. If the SFF of the subsystem is between 60% and 90%, and the PFD
< 10
2,
the design can meet SIL2 @ HFT =
< 101, the design
avg
can meet SIL 1 @ HFT=0.
6
Instruction Manual Supplement
D103601X012
DVC6200 SIS Digital Valve Controller
February 2022
6.2. Safety Function
DDeenergize to Trip Application: The application of the digital valve controller is limited for SIS
to low demand mode. Table 1 describes the normal and safe states of DVC6200 SIS for a DETT
configuration. The digital valve controller may be operated with one of the following control
signals:
D024 VDC: Normal operation is with a 24 VDC signal applied to the digital valve
controller. A shutdown command is issued by interrupting the loop or taking the
voltage signal to 1 VDC or less.
D420 mA: Normal operation is with a 20 mA current loop signal to the digital valve
controller. A shutdown command is issued by taking the current signal to 4 mA
(nominal). If a looppowered LCP100/LCP200 is attached, the shutdown command is
issued by taking the current signal to 8 mA (nominal).
Table 1. Normal and Safe States for De-Energize to Trip (DETT) Application
ActionOutput Type
Direct
Single
Reverse
DoubleDirect
1. DVC6200 SIS High Cv option is not certified for single-acting reverse DETT application.
(1)
Input Voltage or
Current
0 VDC or 4 mAPort A < 1 psi
24 VDC or 20 mA
0 VDC or 4 mA
24 VDC or 20 mAPort B < 1 psi
0 VDC or 4 mA
24 VDC or 20 mA
Normal StateSafe State
Port A
≥ 95% of Supply
Output B ≥ Supply
Pressure less 5 psi
Port A pressure
≤ Port B pressure
Port A ≥ 95% of Supply
Port B < 1 psi
DEnergize to Trip Application (a less common application): The application of the digital valve
controller is limited for SIS to low demand mode. Normal operation is with a 4 mA current
loop signal to the digital valve controller. If a looppowered LCP100/LCP200 is attached,
normal operation is with an 8 mA (nominal) current loop signal to the digital valve controller.
Table 2 describes the normal and safe states of DVC6200 SIS for an ETT configuration. A
shutdown command is issued by taking the current signal to 20 mA (nominal).
Table 2. Normal and Safe States for Energize to Trip (ETT) Application
ActionOutput TypeInput CurrentNormal StateSafe State
SingleReverse
DoubleDirect
4 mAPort B ≥ 95% of Supply
20 mAPort B < 1 psi
4 mA
20 mA
Port A < 1 psi
Port B ≥ 95% of Supply
Port A ≥ Port B
pressure
DPosition Monitor Application: The safety function of the position transmitter output is to
transmit a 420 mA analog signal that represents valve position. The safety function of the
limit switch output is to transmit a discrete signal that represents a user configurable
7
DVC6200 SIS Digital Valve Controller
February 2022
Instruction Manual Supplement
threshold of valve position. Table 3 describes the normal and alarm states of the Position
Monitor function of the DVC6200 SIS.
Table 3. Normal and Alarm States for the Position Monitor Application
Output FunctionNormal StateAccuracyAlarm State
420 mA
Position Transmitter
0/1A
Limit Switch
1. Configurable high or low. Values are per NAMUR NE43. Fail high when the instrument is powered.
2. On loss of loop circuit power, the limit switch will go to the open state.
Actual Valve Position5%
CLOSED5%OPEN
>22.5 mA or
<3.6 mA
(1)
(2)
D LCP200
D The LCP200 will respond to a local TRIP button press with a change of state of the Trip
relay output.
D The LCP200 will respond to a local RESET button press with a change of state of the reset
relay output.
6.3. Failure Rates
D103601X012
The failure rate data listed in tables 4, 5, 6, 8, 7, 9, and 10 is only valid for the 15year useful
lifetime of the DVC6200 SIS digital valve controller and the LCP200, when used. The failure rates
will increase after this time period. Reliability calculations based on the data listed in the FMEDA
report for mission times beyond the useful lifetime may yield results that are too optimistic, i.e.
the calculated Safety Integrity Level will not be achieved. When used, the LCP100/LCP200 failure
rates and the LC340 failure rates are to be added to the failure rates of the DVC6200 SIS. These
failure rates assume that the self test shutdowns in the DVC6200 SIS are disabled. Consult the
FMEDA report for a detailed list of the assumptions used in the analysis.
Table 4. Failure Rates for DVC6200 SIS with 024 VDC or 420 mA Control Signal, DETT
Failure Rate (in FIT)
DVC6200 SIS
Failure
Category
Fail Safe
Detected
Fail Safe
Undetected
Fail Dangerous
Detected
Fail Dangerous
Undetected
No Effect1,0601,6368841,46027--Annunciation
Failure Detected
Annunciation
Failure
Undetected
1. This number can be subtracted from the annunciated failure undetected number when the DVC6200 SIS is configured to perform a SOV test.
Double Acting, Single
Acting, Direct Acting
w/PVST
Diagnostics
1820182----62
1433251323142934190
720103-----
441175215512--
3980398-----
1770177----62
Normal
Single Acting,
Reverse Acting
w/PVST
Diagnostics
NormalLCP100LCP200
Adders for LCP Loop or
24V External Power
Non-Interfering
LC340
SOV
Test
Config.
(1)
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.