Fisher IM Supplement: Safety manual for FIELDVUE DVC6200 SIS Digital Valve Controller, Position Monitor, and LCP200 Local Control Panel Manuals & Guides

Instruction Manual Supplement
D103601X012
DVC6200 SIS Digital Valve Controller
February 2022
Safety manual for Fisher™ FIELDVUE™ DVC6200 SIS Digital Valve Controller, Position Monitor, and LCP200 Local Control Panel
This supplement applies to
1. Purpose
This safety manual provides information necessary to design, install, verify and maintain a Safety Instrumented Function (SIF) utilizing the Fisher DVC6200 SIS digital valve controller. The DVC6200 SIS can be installed with a local control panel (LCP200). This document must be thoroughly reviewed and implemented as part of the safety lifecycle. This information is necessary for meeting the IEC 61508 or IEC 61511 functional safety standards.
WARNING
This instruction manual supplement is not intended to be used as a stand-alone document. It must be used in conjunction with the following documents: Fisher DVC6200 Series Quick Start Guide (D103556X012 Fisher DVC6200 SIS Instruction Manual (D103557X012 Fisher LCP200 Instruction Manual (D104296X012
Failure to use this instruction manual supplement in conjunction with the above referenced documents could result in personal injury or property damage. If you have any questions regarding these instructions or need assistance in obtaining any of these documents, contact your Emerson sales office
)
)
)
.
www.Fisher.com
DVC6200 SIS Digital Valve Controller
February 2022
Instruction Manual Supplement
D103601X012
2. Description of the Device
The Fisher DVC6200 SIS digital valve controller is an instrument which delivers controlled pneumatic pressure to modulate a valve actuator in response to an electrical signal. An optional valve position monitor will either transmit a 420 mA signal in response to the actual valve travel or open and close a discrete limit switch based on a configurable trip point. An LCP200 can be used in conjunction with the DVC6200 SIS to locally open and close a safety shutdown valve as well as initiating a partial stroke test.
This safety manual applies to the DVC6200 SIS instrument with electronics hardware revision 2 (HW2) and firmware revision 4, 5, 6, and 7 with the following product options.
OPTION
MODEL CONSTRUCTION
DVC6200 SIS Integral, Aluminum n n n n n n n n
DVC6200S SIS
DVC6205 SIS DVC6215
Integral, Stainless Steel
Remote Mount Aluminum
DETT ETT 4-20 mA 24 VDC
n n n n n n n n
(1)
,
n n n n n n n n
Double-
Acting
Direct
Single-
Acting
Reverse
Single-
Acting
Direct
Position Monitor
APPLICATION
DETT n n n n n n n ETT n n n n n n 4-20 mA n n n n n n n 24 VDC n n n n n n
1. The Remote Mount construction is not available with the DVC6200 SIS High Cv option.
Accessories
LCP100/LCP200Local Control Panel, HART Only LC340Line Conditioner, 24 VDC
2
Instruction Manual Supplement
D103601X012
DVC6200 SIS Digital Valve Controller
February 2022
3. Terms, Abbreviations, and Acronyms
β Beta factor for common cause effects of failure
DD
DETT Deenergize to Trip
DTM
DVC6200 SIS Digital Valve Controller, product model designation for Safety Instrumented System applications ESD Emergency Shut Down ETT Energize to Trip FIT Failure In Time (1x109 failures per hour) FMEDA Failure Mode Effect and Diagnostic Analysis
HART
HCv1
HCv2
HCv3 Pneumatic booster with an exhaust Cv of 6.2 and a fill Cv of 3.2 for single direct acting. HFT Hardware Fault Tolerance
λ
LC340
LCP100 LCP200 Low Demand Mode
Multidrop
PFD
AVG
PointtoPoint Operating mode of the DVC6200 SIS whereby the instrument is powered with 420 mA. PVST Partial Valve Stroke Test
Relay A
Relay B
Relay C
Safety Freedom from unacceptable risk of harm. Safety Function SFF Safe Failure Fraction SIF Safety Instrumented Function SIL Safety Integrity Level SIS Safety Instrumented System SOV Solenoid Operated Valve Type A Element Type B Element
Device Description, an electronic data file that describes specific features and functions of a device to be used by host applications.
Device driver that provides a unified structure for accessing device parameters, configuring and operating the devices, and diagnosing problems.
Highway Addressable Remote Transducer, open protocol for digital communication superimposed over a direct current. Pneumatic booster with a Cv of 1.2 for double acting and both single direct and reverse acting. (Note: single-acting reverse certified for ETT applications only.) Pneumatic booster with a Cv of 3.2 for double acting and both single direct and reverse acting. (Note: single-acting reverse certified for ETT applications only.)
Failure rate. λDD: dangerous detected; λDU: dangerous undetected; λSD: safe detected; λSU: safe undetected. Line Conditioner; product model designation for a device that is inserted in the loop when the instrument (in Multidrop Mode) is powered with a lowimpedance 24 V source, to enable HARTr communications. Local Control Panel; product model designation for a device that can be connected to a DVC6200 SIS instrument to enable manuallyinitiated functions. Mode of operation of a safety instrumented function where the demand interval is greater than twice the proof test interval. Operating mode of the DVC6200 SIS where the instrument controls the current drawn to enable it to be powered with 24 VDC. Average Probability of Failure on Demand
Pneumatic booster relay for double or single acting applications. Typical construction for double acting DETT applications. Pneumatic booster relay for single acting reverse applications. Typical construction for single acting ETT applications. Pneumatic booster relay for single acting direct applications. Typical construction for single acting DETT applications.
Function of a device or combination of devices intended to be used within a Safety Instrumented System to reduce the probability of a specific hazardous event to an acceptable level.
“NonComplex” element (using discrete components); for details see 7.4.4.1.2 of IEC 615082.
“Complex” element (using complex components such as micro controllers or programmable logic); for details see 7.4.4.1.3 of IEC 615082.
3
DVC6200 SIS Digital Valve Controller
February 2022
4. Related Literature
D Fisher DVC6200 Series Quick Start Guide (D103556X012)
Instruction Manual Supplement
D103601X012
D Fisher DVC6200 SIS Instruction Manual (D103557X012
D 62.1:DVC6200 SIS, Fisher DVC6200 SIS Product Bulletin (D103555X012
D HART Field Device Specification for Fisher DVC6200 SIS (D103638X012
D Fisher LCP200 Local Control Panel Instruction Manual (D104296X012
D 62.1:LCP200, Fisher LCP200 Local Control Panel Product Bulletin (D104313X012
)
)
)
)
)
D IEC 61508: 2010 Functional safety of electrical/electronic/programmable electronic
safetyrelated systems
D ANSI/ISA 84.00.012004 (IEC 61511 Mod.) Functional Safety – Safety Instrumented Systems for
the Process Industry Sector
D Exida FMEDA Report for Fisher DVC6200 SIS, Position Monitor Applications 
Report No. EFC 12/02027 R001
D Exida FMEDA Report for Fisher DVC6200 SIS, DETT and ETT Applications 
Report No. EFC 12-02-027 R004 V3 R0
D Exida FMEDA Report for Fisher DVC6200 SIS Digital Valve Controller with High Cv Option, ESD
DETT applications - Report No. EFC 12/02-037 R002 V2 R3
D Exida FMEDA Report for Fisher DVC6200 SIS Digital Valve Controller with High Cv Option, ESD
ETT applications - Report No. EFC 14/03-045 R001 V1 R5
4
Instruction Manual Supplement
D103601X012
DVC6200 SIS Digital Valve Controller
5. General Requirements
WARNING
To ensure safe and proper functioning of equipment, users of this document must carefully read all instructions, warnings, and cautions in this safety manual and the Quick Start Guide.
D Refer to the Fisher DVC6200 SIS Quick Start Guide (D103556X012) for mounting and
configuration.
February 2022
D If a LCP200 is used, refer to the Fisher LCP200 instruction manual (D104296X012
configurations and mounting.
D Tools needed:
DVC6200 SIS
D Flat Head Screwdriver, 3 mm Thin Blade (wiring terminations)
D Phillips Screwdriver
D 3/8” Hex Key (terminal box conduit plug)
D 6 mm Hex Key (module base screws)
D 5 mm Hex Key (terminal box screw)
D 2.5 mm Hex Key (I/P converter screws)
D 1.5 mm Hex Key (terminal box cover screw)
D 9/64” Hex Key (spool valve screws, HCv1)
D 3 mm Hex Key (spool valve screws, HCv2 and HCv3)
LCP200
) for wiring
D Phillips Screwdriver (ground screw)
D Flat Head Screwdriver, 3 mm Thin Blade (wiring terminations)
D 10 mm Hex Key (cable entry plug)
D 4 mm Hex Key (terminal cover screw)
D 2.5 mm Hex Key (LED module screw, front panel screw)
D Torque wrench capable of 2 - 2.5 N•m (18 - 22 lb•in) (terminal cover screw)
D Personnel performing maintenance and testing on the DVC6200 SIS and LCP200 shall be
competent to do so.
5
DVC6200 SIS Digital Valve Controller
February 2022
Instruction Manual Supplement
D103601X012
6. Safety Instrumented System Design
When using the DVC6200 SIS digital valve controller or DVC6200 SIS with the LCP200 in a safety instrumented system, the following items must be reviewed and considered.
6.1 SIL Capability
6.2 Safety Function
6.3 Failure Rates
6.4 Application Limits
6.5 Environmental Limits
6.6 Application of the Switch Output for Diagnostic Annunciation
6.1. SIL Capability
D Systematic Integrity
SIL 3 Capable— the digital valve controller has met manufacturer design process requirements of IEC 61508 Safety Integrity Level 3.
D Random Integrity
D The digital valve controller is classified as a Type A device according to IEC 61508. The
complete final element subsystem will need to be evaluated to determine the SFF. If the SFF of the subsystem is >90%, and the PFD
< 103, the design can meet SIL 3 @ HFT=0.
avg
D The position monitor is classified as a Type B device according to IEC 61508. The
complete final element subsystem will need to be evaluated to determine the SFF. If the SFF of the subsystem is >90%, and the PFD If the SFF of the subsystem is between 60% and 90%, and the PFD
< 102, the design can meet SIL 2 @ HFT=0.
avg
< 101, the design
avg
can meet SIL 1 @ HFT=0.
D The LCP200 is classified as a Type B device per IEC61508. If the SFF of the relay output
state change subsystem is >90% and the PFD
avg
0. If the SFF of the subsystem is between 60% and 90%, and the PFD
< 10
2,
the design can meet SIL2 @ HFT =
< 101, the design
avg
can meet SIL 1 @ HFT=0.
6
Instruction Manual Supplement
D103601X012
DVC6200 SIS Digital Valve Controller
February 2022
6.2. Safety Function
DDeenergize to Trip Application: The application of the digital valve controller is limited for SIS
to low demand mode. Table 1 describes the normal and safe states of DVC6200 SIS for a DETT configuration. The digital valve controller may be operated with one of the following control signals:
D024 VDC: Normal operation is with a 24 VDC signal applied to the digital valve
controller. A shutdown command is issued by interrupting the loop or taking the voltage signal to 1 VDC or less.
D420 mA: Normal operation is with a 20 mA current loop signal to the digital valve
controller. A shutdown command is issued by taking the current signal to 4 mA (nominal). If a looppowered LCP100/LCP200 is attached, the shutdown command is issued by taking the current signal to 8 mA (nominal).
Table 1. Normal and Safe States for De-Energize to Trip (DETT) Application
Action Output Type
Direct
Single
Reverse
Double Direct
1. DVC6200 SIS High Cv option is not certified for single-acting reverse DETT application.
(1)
Input Voltage or
Current
0 VDC or 4 mA Port A < 1 psi
24 VDC or 20 mA
0 VDC or 4 mA
24 VDC or 20 mA Port B < 1 psi
0 VDC or 4 mA
24 VDC or 20 mA
Normal State Safe State
Port A
≥ 95% of Supply
Output B ≥ Supply
Pressure less 5 psi
Port A pressure
≤ Port B pressure
Port A ≥ 95% of Supply
Port B < 1 psi
DEnergize to Trip Application (a less common application): The application of the digital valve
controller is limited for SIS to low demand mode. Normal operation is with a 4 mA current loop signal to the digital valve controller. If a looppowered LCP100/LCP200 is attached, normal operation is with an 8 mA (nominal) current loop signal to the digital valve controller. Table 2 describes the normal and safe states of DVC6200 SIS for an ETT configuration. A shutdown command is issued by taking the current signal to 20 mA (nominal).
Table 2. Normal and Safe States for Energize to Trip (ETT) Application
Action Output Type Input Current Normal State Safe State
Single Reverse
Double Direct
4 mA Port B ≥ 95% of Supply
20 mA Port B < 1 psi
4 mA
20 mA
Port A < 1 psi
Port B ≥ 95% of Supply
Port A ≥ Port B
pressure
DPosition Monitor Application: The safety function of the position transmitter output is to
transmit a 420 mA analog signal that represents valve position. The safety function of the limit switch output is to transmit a discrete signal that represents a user configurable
7
DVC6200 SIS Digital Valve Controller
February 2022
Instruction Manual Supplement
threshold of valve position. Table 3 describes the normal and alarm states of the Position Monitor function of the DVC6200 SIS.
Table 3. Normal and Alarm States for the Position Monitor Application
Output Function Normal State Accuracy Alarm State
420 mA
Position Transmitter
0/1A
Limit Switch
1. Configurable high or low. Values are per NAMUR NE43. Fail high when the instrument is powered.
2. On loss of loop circuit power, the limit switch will go to the open state.
Actual Valve Position 5%
CLOSED 5% OPEN
>22.5 mA or
<3.6 mA
(1)
(2)
D LCP200
D The LCP200 will respond to a local TRIP button press with a change of state of the Trip
relay output.
D The LCP200 will respond to a local RESET button press with a change of state of the reset
relay output.
6.3. Failure Rates
D103601X012
The failure rate data listed in tables 4, 5, 6, 8, 7, 9, and 10 is only valid for the 15year useful lifetime of the DVC6200 SIS digital valve controller and the LCP200, when used. The failure rates will increase after this time period. Reliability calculations based on the data listed in the FMEDA report for mission times beyond the useful lifetime may yield results that are too optimistic, i.e. the calculated Safety Integrity Level will not be achieved. When used, the LCP100/LCP200 failure rates and the LC340 failure rates are to be added to the failure rates of the DVC6200 SIS. These failure rates assume that the self test shutdowns in the DVC6200 SIS are disabled. Consult the FMEDA report for a detailed list of the assumptions used in the analysis.
Table 4. Failure Rates for DVC6200 SIS with 024 VDC or 420 mA Control Signal, DETT
Failure Rate (in FIT)
DVC6200 SIS
Failure
Category
Fail Safe Detected
Fail Safe Undetected
Fail Dangerous Detected
Fail Dangerous Undetected
No Effect 1,060 1,636 884 1,460 27 - - ­Annunciation
Failure Detected Annunciation
Failure Undetected
1. This number can be subtracted from the annunciated failure undetected number when the DVC6200 SIS is configured to perform a SOV test.
Double Acting, Single
Acting, Direct Acting
w/PVST
Diagnostics
182 0 182 - - - - 62
143 325 132 314 29 34 19 0
72 0 103 - - - - -
44 117 52 155 1 2 - -
398 0 398 - - - - -
177 0 177 - - - - 62
Normal
Single Acting,
Reverse Acting
w/PVST
Diagnostics
Normal LCP100 LCP200
Adders for LCP Loop or
24V External Power
Non-Interfering
LC340
SOV Test
Config.
(1)
8
Loading...
+ 16 hidden pages