First Co UC-HW User Manual

UC(S)-HW SERIES FAN COIL UNIT
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
**WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER**
Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty
and may result in adverse operational performance and/or a possible hazardous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning. Current Maintenance Program is available at www. rstco.com under "Product Information".
GENERAL
The manufacturer assumes no respon­sibility for equipment installed in violation of any code requirement. These instructions give information rela­tive to the installation of UC-HW fan coil units only. For other related equipment refer to the proper instructions. Material in this shipment has been inspected at the factory and released to the transportation agency in good condi­tion. When received, a visual inspection of all cartons should be made immedi­ately. Any evidence of rough handling or apparent damage should be noted on the delivery receipt and the material inspected in the presence of the carrier's representative. If damage is found, a claim should be fi led against the carrier
immediately.
FAN COIL UNIT
The installer must adhere strictly to all local and national code requirements pertaining to the installation of this equip­ment. These units are designed to be installed vertically in the upfl ow position by the following mounting means:
Hung on closet wall
Using mounting kit 90PK3, air handler may be wall mounted. Brackets and screws are provided for both the closet wall and the air handler. It is recommended that sound isolat­ing material be installed to prevent any undesired transfer of sound.
Recessed in a wall
Installation of the fan coil recessed into a partition wall with it's recommended framing is shown in fi gure 1. Note: the
front face of the unit must be installed
ush with the dry wall. This application requires the optional louvered wall panel which must be ordered separately. Wall panel with frame is secured to the studs
by screws or nails after the dry wall has been installed. Refer to fi gure 2 and 3.
Closet Platform Front Return
Fan coil is to be set on a platform and secured by screws or nails. Suffi cient space for drain piping is required under the platform. All fan coil units are U.L. Listed for in­stallation with zero inches clearance to combustible materials. This includes the
****** WARNING ******
Extreme caution must be taken that no internal damage will result if screws or holes are drilled into the cabinet.
fan coil cabinet, discharge plenum and connecting ducts. Suffi cient clearance must be provided at the front of the fan coil to allow access to electrical controls and removal of the motor /blower assem­bly for servicing. This clearance distance should be approximately the same as the depth dimension of the fan coil unit.
****** WARNING ******
Unit must not be operated during building construction due to excessive airborne dust and debris. The unit must not be operated under any circumstances without an air fi lter in place.
AIR DISTRIBUTION DUCTS
All duct work must be installed in ac-
cordance with National Fire Protection Association Codes 90A and 90B. Ducts should be adequately insulated to pre­vent condensation during the cooling cycle and to minimize heat loss during the heating cycle. All return air must be ltered to prevent dirt buildup on the coil surface. If there is no ducted return, ap­plicable installation codes may limit the unit to installation only in a single story residence. In many cases it is acceptable to use ducting of the same size as the fan coil connections. However, unique arrangements or long duct runs must be confi rmed by a local professional. The manufacturer will not be responsible for misapplied equipment.
L2465 4/08
ELECTRICAL
All wiring must comply with local and national code requirements. Units are
provided with wiring diagrams and plate data to provide information required for necessary fi eld wiring. Refer to fi gure 2 for points of entry of the wiring into the cabinet.
name-
****** WARNING ******
Any devices such as fan switches or thermostats that have been furnished by the factory for fi eld installation must be wired in strict accor­dance with the wiring diagram that is supplied with the unit. Failure to do so could result in damage to components and will void all warranties.
These units may be provided with a Class 2 transformer for 24-volt control circuits. Should any add-on equip­ment also have a Class 2 transformer furnished, care must be taken to pre­vent interconnecting outputs of the two transformers by using a thermostat with isolating contacts.
INSTALLATION PRECAUTIONS
Installation of this fan coil should only be performed by a licensed contractor to ensure proper installation and the safety of the installer. The following are some precautions to be followed for typical installations.
Always use proper tools and equip-
ment.
No wiring or other work should be at-
tempted without fi rst ensuring that the fan coil is completely disconnected from the power source and locked out. Always verify that a good ground connection exists prior to energizing any power sources.
Always review the nameplate on each
unit for proper voltage and control confi g- urations. This information is determined from the components and wiring of the
unit and may vary from unit to unit.
When soldering or brazing to the
unit, it is recommended to have a fi re extinguisher readily available. When soldering close to valve packages or other components, heat shields or wet rags are required to prevent damage.
When the fan coil unit is in opera-
tion components are rotating at high speeds.
Units must be installed level to ensure
proper drainage and operation.
Check unit prior to operation to ensure
that the condensate water will drain to­ward the drain connection. An overfl ow drain or an auxiliary drain pan under the fan coil may be required as a back up to a clogged primary drain.
On units with plastic drain pans DO
NOT tighten more than hand tight.
Be sure that the drain pan is free from
foreign material prior to start up.
Check fi lter media installation to en-
sure that it is installed correctly. Use the directional arrows or other information on the fi lter to determine the proper fl ow direction.
NOISE
These fan coil units are designed for quiet operation, however, all air condition­ing equipment will transfer some amount of noise to the conditioned space. This should be taken into consideration when planning the location of the equipment.
UC-HW RECESSED WALL MOUNTING
CROSS MEMBER - TOP & BOTTOM
(PLACE UPPER CROSS MEMBER
3" ABOVE UC UNIT)
ATTACH UNIT TO FRAME USING
6 SCREWS / NAILS IN CABINET AT
LOCATIONS SHOWN
COOLING COIL PIPING
These fan coil units are supplied with a direct expansion refrigerant coil. The suction and liquid lines must be sized in accordance with the outdoor unit manu­facturer's recommendations.
****** WARNING ******
When connecting piping to fan coil units, do not bend or reposition the coil header tub­ing for alignment purposes. This could cause a tubing fracture resulting in a water leak when water pressure is applied to the system.
For front drain applications a tab must be removed from the inner front edge of the unit as shown in Fig 5. This opera­tion must be performed after the unit is installed to prevent damage to the front of the unit. For installation of a thermostatic expan­sion valve see Fig. 6.
****** WARNING ******
Failure to perform modifi ca- tions for front drain installa­tion may result in structural and equipment damage.
VERTICAL 2 X 4
BRACKET PLACEMENT FOR HANGING IN A CLOSET
MOUNT UNIT FLUSH WITH DRY WALL (1/2" MIN. IN FRONT OF WALL STUD)
****** WARNING ******
Do not touch any rotating component with any object. Damage to the equipment and personal injury can occur.
LEAVE SUFFICIENT SPACE FOR DRAIN PIPING 10" TO 12" MINIMUM RECOMMENDED
SUPPORT FRAMING
Figure 1
Condensate drain lines must be installed with adequate slope away from the unit to assure positive drainage. Since the drain pan is located on the suction side of the blower, a negative pressure exists at the drain pan and a minimum trap of 1-1/2 inches must be provided in the drain line
to assure proper drainage.
****** WARNING ******
On units with plastic drain pans the drain connections must be made hand tight only.
NOTE: If a Condensate Overfl ow Shut-
off Switch, that is designed to be installed in the drain line, is used in
secondary drain line, then the cut-off switch should be located in the primary drain line between the fan coil unit and the P-trap.
HOT WATER COIL PIPING PRECAUTIONS
• Flush all fi eld piping prior to connection to remove all debris.
• Use wet cotton rags to cool valve bod­ies when soldering.
• Open all valves (midway for hand valves, manually open on motorized valves) prior to soldering.
•When soldering to bronze or brass, heat the piping while in the socket/cup and begin introducing the solder when the ux boils rapidly. Avoid direct fl ame into the solder joint.
• Heat can only be applied to the cup of the valve body for a minimal time before damage occurs (even with the use of wet rags.
place of a
• Avoid rapid quenching of solder joints as this will produce joints of inferior quality.
• Connect all piping per accepted industry standards and observe all regulations governing installation of piping systems. When all connections are complete the system must be pressure tested. Repair any solder joint leaks and gently tighten any leaking valve packing nuts and pip­ing accessories as required. Hydronic systems are not designed to hold pres­surized air and should only be tested with water.
HOT WATER COIL PIPING
Refer to Flow Control Module instal-
lation instructions for proper pump instal­lation, if used. The hot water coil connections are 3/4 inch nominal (7/8” OD) copper. The hot water supply to the fan coil should be on the right when facing the fan coil upright and from the front.
****** WARNING ******
An expansion tank may be re­quired if a back-fl ow preven- ter is installed in the system.
All piping between the water heater and fan coil unit should be copper and should not exceed 200 feet of total pip­ing. It is recommended that 3/4” nominal (7/8” OD) piping should be used on all UC-HW units to prevent excessive head pressure losses. (Consult the factory for other piping applications.)
It is also recommended that all pip-
ing be adequately insulated to prevent freezing when piping is run in an uncon­ditioned space.
Solder Connections - All copper
joints in the water lines must be made with
low temperature - non lead
solder.
"T" Connections (at the water
heater)-
Water lines to and from the fan coil unit must be taken from the horizontal con­nection of the "T" fi ttings in the vertical hot and cold water supply lines at the water heater. This ensures that any air in the system will be purged each time water is used in the dwelling. See fi gure 4.
Isolation Valves - Two valves are
recommended to be installed within the circulating loop to permit servicing of the system if required and to assist in purging the system.
NOTE: Hot water coil freeze protection
is available for applications where the fan coil is located in ambient air locations (attics, crawl spaces, etc.) or within struc­tures that may be unoccupied during freezing conditions. Consult the factory for additional information.
OPERA TION AND MAINTENANCE
Pre-start Check
• Check that supply voltage matches nameplate data.
• Ensure that the unit is properly grounded.
• With power off, check blower wheel set screw for tightness and ensure that the blower wheels rotates freely and quietly.
• Check that the refrigerant coil connec­tions and piping have been leak checked and insulated as required.
• Check that the water coil, valves and piping have been leak checked and in­sulated as required.
• Ensure that all air has been vented from the hot water coil.
THERMOSTAT WIRING
UC WALL PANEL FRAME (PANEL ASSEMBLY IS ORDERED SEPARATELY)
CROSS MEMBER (ON EDGE)
INSTALLED UNIT
TOP VIEW
WATER OUTLET
Figure 2
2 X 4 POWER SUPPLY WIRING
LIQUID LINE
SUCTION LINE 2 x 4 WALL STUD
WALL STUD
DRY WALL
WATER INLET
DRY WALL
SCREW
WALL PANEL
FRAME
DETAIL OF WALL PANEL FRAME
Note: Front edge of unit to be fl ush with dry wall.
INSTALLATION
Figure 3
****** WARNING ******
Always wear eye protection.
When fan coil is operating,
some components are operating at high speeds. Personal injury can result from touching these items with any object
All electrical and service access panels must be returned and secured in their proper place.
Clear surrounding area of all tools, equipment and debris.
Check the entire unit to ensure it's cleanliness.
NOTE: It may require purging sever­al gallons of water so have a means of discarding the water.
Install all panels.
Install any lters which may have
been removed during the installation process.
Start-up and Maintenance
Before start-up, all of the components
should be given a thorough check. Opti­mal operation of this equipment requires cleanliness. Often after installlation of this equipment additional construction activities occur. Care must be taken to protect the equipment from debris during these construction phases.
Fan
The fan should be inspected and
cleaned, in conjunction with mainte­nance of the motor and bearings. It is important to keep the wheel clean in order to avoid imbalance and vibration.
Motor
Check motor connections to ensure
that they are secure and made in accor­dance with the wiring diagram. The blower motor should be cleaned annually.
Coil
Any dust or other contaminants which
accumulate on the heat transfer surfaces interferes with the air fl ow and impairs heat transfer. The coil must be kept clean by any of the following methods.
Cleaning with low pressure com­pressed air.
Flushing or rinsing with water (a deter­gent is advisable for greasy surfaces).
Filter
The air fi lter should be cleaned or re-
placed every 30 days or more frequently if severe conditions exist. Always replace the fi lter with the same type as originally furnished.
****** WARNING ******
The manufacturer does NOT WARRANT equipment sub­jected to abuse. Metal chips, dust, drywall tape, paint over spray, etc. can void warran­ties and liability for equip­ment failure, personal injury and property damage.
Drain Piping
The drain should always be:
Connected or piped to an acceptable disposal point sloped away from the unit at least 1/8" per foot
Checked before summer operation
Periodically checked during summer
operation
Preventative Maintenance
T o achieve maximum performance and
service life of each piece of equipment a formal schedule of regular maintenance should be established and maintained by a licensed contractor.
HEATING CYCLE START - UP
1) Fill the water heater. Open a hot
water faucet while fi lling the water heater to vent the air. When the tank is full and all the air is purged, close the faucet.
2) Ignite the water heater and set the thermostat to 140 degrees.
3) Purge the air handler's hot water coil and lines.
NOTE: It may require purging sev­eral gallons of water so either have a bucket available or a means of discarding the water.
Close valve number 2 and open valve number 3. (See fi gure 4 ) Next, open the air bleed valve. When all of the air is purged from the lines close valve number 3 and open valve number 2. After all the air is purged from the coil and lines, open both valve number 1 and 2 and close the air bleed valve.
4) Switch the room thermostat to the "Heat" position and raise the tem-
perature setting to a position ap­proximately ten degrees above room temperature.
****** WARNING ******
To prevent pump damage, the fan coil unit should not be energized for heating un­til the hot water coil and all water lines have been purged of air.
The pump should energize and begin circulating the hot water through the coil. If the pump is operating properly and the water temperature in the wa­ter heater has reached the set point, then the hot water inlet at the fan coil unit will be hot. If the pump is running but hot water is not circulating, open the air bleed valve long enough to purge any remaining air from the hot water lines and coil. This will allow the pump to begin circulating hot water.
****** WARNING ******
Hot water can cause scald­ing. A hot water mixing valve can be applied to the system to temper domestic water draw.
5) The water heater thermostat should be adjusted so that the water temper­ature entering the hot water coil is as close to 140 degrees as possible with the system energized and operating long enough for all temperatures to stabilize.
PUMP REPLACEMENT (If Flow Control Module is in­stalled)
Disconnect electrical power before
servicing the unit.
T o replace the circulator pump, close
the isolation valves and relieve the water pressure within the heating loop. Dis­connect the pump's 1 15 volt power lines within the control box and remove the four hex head screws securing the pump motor to the pump's volute.
Reverse the above steps for reas-
sembling the pump, however make sure that the pump or volute has the rubber o-ring in place before assembling.
CHECK VALVE
HOT WATER COIL
2
3
HOT WATER
SUPPLY TO
HOUSE
HOT
WATER
HEATER
FLOW
FLOW
WATER SUPPLY
TO HEATER
FLOW CONTROL MODULE CONSIST OF: PUMP, CHECK VALVE AND BLEED VALVE
BLEED VALVE
1)
ISOLATION VALVE: SUPPLY LINE2)
ISOLATION VALVE: RETURN LINE3)
FLOW
1
FLOW CONTROL
MODULE
REPLACEMENT
Disconnect electrical power before
servicing the unit.
To replace the internal check valve,
close the isolation valves and relieve the water pressure within the heating
Remove the four hex head screws secur­ing the pump motor to the pump's volute and remove. The check valve is located in the volute.
Rotate the check valve to release and
remove from the volute.
loop.
Reverse the above steps for reinstall­ing a check valve, however make sure that the pump or volute has the rubber o-ring in place before assembling.
TYPICAL PIPING SCHEMATIC
w / Flow Control Module
**MAINTENANCE UPDATES**
For a current copy of the Maintenance Program log on to www. rstco.com and look under "Product Informa­tion"
Figure 4
FRONT DRAIN APPLICATIONS
Cut along dashed lines to slot and remove
For front drain applications cut as shown and remove metal tab to allow drain piping to slope away from the drain pan properly. Ensure that the drain piping has proper slope and is able to drain.
****** WARNING ******
If secondary drain is not being used it must be plugged to prevent leakage which will cause structrual and equipment damage.
Figure 5
THERMOSTATIC EXPANSION VALVE INSTALLATION
Install expansion valves as shown with directional arrow toward the coil. Attach the TXV bulb to the vertical suc­tion line as shown with the tubing on top. External equal­izer is to be attached to the 1/4" fl are connector. Ensure that a service valve core is not installed before attaching the equalizer line. Wrap the bulb with insulation tape to completly seal the bulb from ambient air.
Figure 6
Loading...