First Co SPXA User Manual

4.5 (2)
SPX SERIES
****** WARNING ******
Unit must not be operated during building construction due to excessive airborne dust and debris. The units must not be operated under any circumstances without an air filter in place.
P ACKAGED AIR CONDITIONING/HEA T PUMP UNITS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
**WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER**
Altering the product or replacing part s with non authorized factory parts voids all warranty or implied warranty
and may result in adverse operational performance and/or a possible hazardous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning. Current Maintenance Program is available at www.firstco.com under "Product Information".
GENERAL
These instructions give information relative to the SPX unit only . Refer to Wall Sleeve and Grille installation instructions for those components. The manufacturer assumes no responsibility for equipment installed in violation of any code requirements. For other related equipment refer to the proper instructions.
The SPX is shipped in one package, completely assembled. Material in this shipment has been inspected at the factory and released to the transportation agency in good condition. When received, a visual inspection of all cartons should be made immediately. Any evidence of rough handling or apparent damage should be noted on the delivery receipt and the material inspected in the presence of the carrier’s representative. If damage is found a claim should be filed against the carrier immediately .
HW Units - Note: State of MA.-248 CMR code of the state of MA. requires a pump timer (60 seconds on every 6 hours). See diagram.
Figure 1 - Typical Suite Installation
P ACKING LIST
Items packed inside the unit: (1 ) Filter Bracket
(1 ) Filter Clip
LOCA TION
The SPX is designed for through­the-wall installation. The interior portion of the unit is surrounded by a closet with a rear access (Fig. 1). The vertical discharge allows for ducting to the top of the room for best air circulation and elimination of cold drafts on occupants. The exterior (grille side) of the unit must have no obstructions (trees, landscape materials, etc.) within 18 inches. Do not locate two units adjacent to each
1
other on an inside corner or where they may exhaust into each other.
Provisions should be made to allow access to the indoor side of the unit for installation and inspection. The closet or access panel opening must be centered with the exterior wall opening and be at least 24” wide by 84” tall. Three (3) inches of unobstructed space is required on all sides of the SPX to allow for adequate air flow. At least 27 inches of unobstructed space should be provided in front of the access door to permit
L268 2/09
Electrical
****** W ARNING ******
Make sure a high grade non­hardening sealant approved for exterior use has been applied between edge of the sleeve and the structure, on the inside and outside walls, to prevent air and water from migrating inside (Fig. 4).
****** WARNING ******
There must be a minimum 3" clearance maintained around the SPX chassis on all sides for adequate airflow to achieve optimum performance. These guidelines give minimum spac­ing requirements only. It is acceptable to go beyond these limits at any time.
****** WARNING ******
After sleeve installation ensure that the sleeve seal is in contact with the sleeve sides. Any air gaps must be sealed or outdoor air and/or water leakage will occur.
****** W ARNING ******
Architectural Grille must be installed prior to the installation of the SPX unit into the sleeve.
Disconnect
Rear Access
Panel
Approximate
Fastener
Locations
Architectural Grille
Wall Sleeve
Drain
Outside
Electrical Service Knock-out
removal of the unit should repair and inspection be required.
For installations requiring access panels refer to unit brochure for panel dimensions.
W ALL SLEEVE INST ALLATION
Refer to installation instructions packed with wall sleeve to assemble and mount it in the wall. Before unit installation, make sure sleeve components are not damaged, drain line is unobstructed and leak free. Check all seals to ensure that they are in position and un-damaged. Ensure that the bottom of the wall sleeve is pitched 1/2 bubble toward the outside of the building so that rain water will drain to the outside (Fig. 4). Securely fasten the Architectural grille to the front of the sleeve using the supplied hardware.
Figure 2 - General Assembly
The unit comes with a factory supplied disconnect, however, the contractor is responsible for providing over current protection on the branch circuit. Refer to the unit wiring diagram for single point electrical connection.
These units are provided with a Class 2 transformer for 24 volt control circuits. Should any add-on equipment also have a Class 2 transformer furnished, care must be taken to prevent interconnecting outputs of the two transformers by using a thermostat with isolating
contacts.
ELECTRICAL
All wiring must comply with local and national code requirements. Any alteration of the internal wiring will void UL certification and manufacturer’s warranty.
Nameplate data indicates the operating voltage, phase, ampacity, maximum over current protection and minimum voltage. Units must never be installed or operated where voltage exceeds the nameplate voltage by more than 10%. Failure of the compressor as a result of operation with improper voltage voids the compressor replacement warranty.
2
Loading...
+ 4 hidden pages