First Co SHW User Manual

24/36/48/60 SHW / SVW
BLOWER COIL UNITS
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
***** WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER *****
Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty and may result in adverse operational performance and/or a possible hazard­ous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning.
GENERAL
The manufacturer assumes no re­sponsibility for equipment installed in violation of any code requirement. These instructions give informa­tion relative to the installation of these blower coil units only. For other related equipment refer to the proper instructions. Material in this shipment has been inspected at the factory and re­leased to the transportation agency in good condition. When received, a visual inspection of all cartons should be made immediately. Any evidence of rough handling or ap­parent damage should be noted on the delivery receipt and the material inspected in the presence of the carrier's representative. If damage is found, a claim should be filed against the carrier immediately.
****** WARNING ******
Unit must not be operated during building construction due to excessive airborne dust and debris. The units must not be operated under any circumstances without an air filter in place.
BLOWER COIL UNIT
The installer must adhere strictly to all local and national code re­quirements pertaining to the instal­lation of this equipment.
The SHW blower coil units are designed to be installed in a horizon­tal position with discharge air in a horizontal direction. The SVW blower coil units are designed for installation in a vertical position with discharge air in a vertical direction. Both unit models incorporate a posi­tive slope drain pan with a 3/4" NPT nipple that exits the unit on the side of the coil header connections. All units need to be leveled in such a way to insure positive slope toward the condensate drain nipple.
NOTICE: Before mounting unit remove red headed shipping bolts and metal bushing at blower base and blower outlet. In addition remove, if present, the wire tie securing motor to blower rail before operating.
Sufficient clearance must be pro­vided on the side of the blower coil to allow access to electrical controls and to service the motor blower as­sembly. Standard unit configuration is right hand looking with the direction of airflow. The unit can be field con­verted to left hand by repositioning the coil, drain pan and remounting the motor and pulleys. NOTE: Motor rotation must be re­versed. See motor nameplate for details.
AIR DISTRIBUTION DUCTS
All duct work must be installed in accordance with National Fire Pro-
tection Association Codes 90A and 90B. Ducts should be adequately insulated to prevent condensation during the cooling cycle and to mini­mize heat loss during the heating cycle. All return air must be filtered to prevent dirt buildup on the coil surface. In many cases it is accept­able to use ducting of the same size as the blower coil return air connec­tion. However, unique arrange­ments or long duct runs must be confirmed by a local professional. The manufacturer will not be re­sponsible for misapplied equip­ment.
ELECTRICAL
All wiring must comply with local and national code requirements. Units are provided with wiring dia­grams and nameplate data to pro­vide information required for neces­sary field wiring. A 4 x 4 electrical box is provided on the cabinet for connection of power supply.
****** WARNING ******
Any devices such as fan switches or thermostats that have been furnished by the factory for field installation must be wired in strict accor­dance with the wiring dia­gram that is supplied with the unit. Failure to do so could result in damage to compo­nents and will void all warran­ties.
L45321 3/02
These blower coil units can be provided with a optional Class 2 relay/transformer for 24-volt control circuits (3/4 HP maximum load rat­ing). Should any add-on equipment also have a Class 2 transformer furnished, care must be taken to prevent interconnecting outputs of the two transformers by using a th­ermostat with isolating contacts.
PIPING
These units employ a hydronic coil designed for use with either hot or chilled water. Each coil has a 1/4 inch bleed line. All piping must be adequately sized to meet the design water flow requirements as specified for the specific installation. Piping must be installed in accordance with all ap­plicable codes. All chilled water piping must be insulated to prevent condensation.
****** WARNING ******
When connecting piping or valve kits to blower coil units, do not bend or reposition the coil header tubing for align­ment purposes. This could cause a tubing fracture re­sulting in a water leak when water pressure is applied to the system.
The piping connections on the equipment are not necessarily in­dicative of the proper supply and return line sizes. To minimize re­strictions, piping design should be kept as simple as possible.
Caution: Prior to connecting to the blower coil all external piping must be purged of debris. Condensate drain lines must be installed with adequate slope away from the unit to assure positive drainage. Since the drain pan is located on the suction side of the blower, a negative pressure exists at the drain pan and a minimum trap of 1-1/2 inches must be provided in the drain line to assure proper drainage. NOTE: Drain pan has positive slope to the nipple which is located on the coil connection side of the unit.
GENERAL PIPING PRECAUTIONS
1. Flush all field piping prior to connection to remove all debris.
2. Use wet cotton rags to cool valve bodies, if present, when soldering.
3. Open all valves (mid-way for hand valves, manually open on motorized valves) prior to soldering.
4. When soldering to bronze or brass, heat the piping while in the socket/cup and begin introducing the solder when the flux boils rap­idly. Avoid direct flame into the solder joint.
5. Heat can only be applied to the cup of the valve body for a minimal time before damage occurs (even with the use of wet rags.
6. Avoid rapid quenching of solder joints as this will produce joints of inferior quality.
7. The coil header or valve package will not support the weight of the connecting pipes. All pipes which are connected to the unit must be completely supported prior to con­nection to the unit.
8. Provisions must be made for expansion and contraction of piping systems. All horizontal and vertical risers, including runouts, must be able to withstand significant move­ment with temperature changes. Failure to do so will result in damage and failure of piping, fittings and valves throughout the building.
9. Never insulate the heads or mo­torized portion of control valves. Damage can occur in the form of excessive heat build up and interfer­ence to the operation and moving parts may result.
10. All piping fabricated in the field should be installed with consider­ation of additional space for any electrical routing that may be re­quired.
11. Connect all piping per accepted industry standards and observe all regulations governing installation of piping systems. When all connec­tions are complete the system must be pressure tested. Repair any sol­der joint leaks and gently tighten any leaking valve packing nuts and pip­ing accessories as required. Hy­dronic systems are not designed to hold pressurized air and should only be tested with water.
STANDARD UNIT
L
N
GRD
BLK
BLK
120V-1PH-60HZ
FAN
MOTOR
SUPPLY
JUNCTION
FIELD WIRING
FACTORY WIRING
BOX
WIRING DIAGRAMS
OPTIONAL RELAY / TRANSFORMER
N
GRD
BLK
(FIELD INSTALLED)
L
BLK
120V-1PH-60HZ
SUPPLY
BLK
120V 24V
WHT
BLK
RED
RELAY / TRANSFORMER
3/4 HP Max. Load Rating
BLOWER
MOTOR
JUNCTION
BOX
FIELD WIRING
FACTORY WIRING
R
W
Y
C
G
Loading...
+ 2 hidden pages