First Co SHW User Manual

24/36/48/60 SHW / SVW
BLOWER COIL UNITS
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
***** WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER *****
Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty and may result in adverse operational performance and/or a possible hazard­ous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning.
GENERAL
The manufacturer assumes no re­sponsibility for equipment installed in violation of any code requirement. These instructions give informa­tion relative to the installation of these blower coil units only. For other related equipment refer to the proper instructions. Material in this shipment has been inspected at the factory and re­leased to the transportation agency in good condition. When received, a visual inspection of all cartons should be made immediately. Any evidence of rough handling or ap­parent damage should be noted on the delivery receipt and the material inspected in the presence of the carrier's representative. If damage is found, a claim should be filed against the carrier immediately.
****** WARNING ******
Unit must not be operated during building construction due to excessive airborne dust and debris. The units must not be operated under any circumstances without an air filter in place.
BLOWER COIL UNIT
The installer must adhere strictly to all local and national code re­quirements pertaining to the instal­lation of this equipment.
The SHW blower coil units are designed to be installed in a horizon­tal position with discharge air in a horizontal direction. The SVW blower coil units are designed for installation in a vertical position with discharge air in a vertical direction. Both unit models incorporate a posi­tive slope drain pan with a 3/4" NPT nipple that exits the unit on the side of the coil header connections. All units need to be leveled in such a way to insure positive slope toward the condensate drain nipple.
NOTICE: Before mounting unit remove red headed shipping bolts and metal bushing at blower base and blower outlet. In addition remove, if present, the wire tie securing motor to blower rail before operating.
Sufficient clearance must be pro­vided on the side of the blower coil to allow access to electrical controls and to service the motor blower as­sembly. Standard unit configuration is right hand looking with the direction of airflow. The unit can be field con­verted to left hand by repositioning the coil, drain pan and remounting the motor and pulleys. NOTE: Motor rotation must be re­versed. See motor nameplate for details.
AIR DISTRIBUTION DUCTS
All duct work must be installed in accordance with National Fire Pro-
tection Association Codes 90A and 90B. Ducts should be adequately insulated to prevent condensation during the cooling cycle and to mini­mize heat loss during the heating cycle. All return air must be filtered to prevent dirt buildup on the coil surface. In many cases it is accept­able to use ducting of the same size as the blower coil return air connec­tion. However, unique arrange­ments or long duct runs must be confirmed by a local professional. The manufacturer will not be re­sponsible for misapplied equip­ment.
ELECTRICAL
All wiring must comply with local and national code requirements. Units are provided with wiring dia­grams and nameplate data to pro­vide information required for neces­sary field wiring. A 4 x 4 electrical box is provided on the cabinet for connection of power supply.
****** WARNING ******
Any devices such as fan switches or thermostats that have been furnished by the factory for field installation must be wired in strict accor­dance with the wiring dia­gram that is supplied with the unit. Failure to do so could result in damage to compo­nents and will void all warran­ties.
L45321 3/02
These blower coil units can be provided with a optional Class 2 relay/transformer for 24-volt control circuits (3/4 HP maximum load rat­ing). Should any add-on equipment also have a Class 2 transformer furnished, care must be taken to prevent interconnecting outputs of the two transformers by using a th­ermostat with isolating contacts.
PIPING
These units employ a hydronic coil designed for use with either hot or chilled water. Each coil has a 1/4 inch bleed line. All piping must be adequately sized to meet the design water flow requirements as specified for the specific installation. Piping must be installed in accordance with all ap­plicable codes. All chilled water piping must be insulated to prevent condensation.
****** WARNING ******
When connecting piping or valve kits to blower coil units, do not bend or reposition the coil header tubing for align­ment purposes. This could cause a tubing fracture re­sulting in a water leak when water pressure is applied to the system.
The piping connections on the equipment are not necessarily in­dicative of the proper supply and return line sizes. To minimize re­strictions, piping design should be kept as simple as possible.
Caution: Prior to connecting to the blower coil all external piping must be purged of debris. Condensate drain lines must be installed with adequate slope away from the unit to assure positive drainage. Since the drain pan is located on the suction side of the blower, a negative pressure exists at the drain pan and a minimum trap of 1-1/2 inches must be provided in the drain line to assure proper drainage. NOTE: Drain pan has positive slope to the nipple which is located on the coil connection side of the unit.
GENERAL PIPING PRECAUTIONS
1. Flush all field piping prior to connection to remove all debris.
2. Use wet cotton rags to cool valve bodies, if present, when soldering.
3. Open all valves (mid-way for hand valves, manually open on motorized valves) prior to soldering.
4. When soldering to bronze or brass, heat the piping while in the socket/cup and begin introducing the solder when the flux boils rap­idly. Avoid direct flame into the solder joint.
5. Heat can only be applied to the cup of the valve body for a minimal time before damage occurs (even with the use of wet rags.
6. Avoid rapid quenching of solder joints as this will produce joints of inferior quality.
7. The coil header or valve package will not support the weight of the connecting pipes. All pipes which are connected to the unit must be completely supported prior to con­nection to the unit.
8. Provisions must be made for expansion and contraction of piping systems. All horizontal and vertical risers, including runouts, must be able to withstand significant move­ment with temperature changes. Failure to do so will result in damage and failure of piping, fittings and valves throughout the building.
9. Never insulate the heads or mo­torized portion of control valves. Damage can occur in the form of excessive heat build up and interfer­ence to the operation and moving parts may result.
10. All piping fabricated in the field should be installed with consider­ation of additional space for any electrical routing that may be re­quired.
11. Connect all piping per accepted industry standards and observe all regulations governing installation of piping systems. When all connec­tions are complete the system must be pressure tested. Repair any sol­der joint leaks and gently tighten any leaking valve packing nuts and pip­ing accessories as required. Hy­dronic systems are not designed to hold pressurized air and should only be tested with water.
STANDARD UNIT
L
N
GRD
BLK
BLK
120V-1PH-60HZ
FAN
MOTOR
SUPPLY
JUNCTION
FIELD WIRING
FACTORY WIRING
BOX
WIRING DIAGRAMS
OPTIONAL RELAY / TRANSFORMER
N
GRD
BLK
(FIELD INSTALLED)
L
BLK
120V-1PH-60HZ
SUPPLY
BLK
120V 24V
WHT
BLK
RED
RELAY / TRANSFORMER
3/4 HP Max. Load Rating
BLOWER
MOTOR
JUNCTION
BOX
FIELD WIRING
FACTORY WIRING
R
W
Y
C
G
PIPING INSULATION
After the system has been proven leak free, all lines and valve control packages must be insulated to pre­vent condensate drippage or insu­lated as specified on the building plans.
Note: Many valve packages will not physically allow all components to fit over an auxiliary drain pan. It is the installers responsibility to capture all condensation or insulate the piping to ensure adequate condensation prevention.
DUCT WORK
All duct work must be installed in accordance with industry accepted practices, and all applicable national and local code requirements.
NOISE
These blower coil units are de­signed for quiet operation, however, all air handling equipment will trans­fer some amount of noise to the conditioned space. This should be taken into consideration when plan­ning the location of the equipment.
MOUNTING
It is important to ensure that the blower coil unit is securely mounted and the structure is sufficient to sup­port the weight of the equipment. Two (2) mounting rails are supplied on the blower coil unit. All anchors for mounting the equipment must be placed and sized to ensure a safe and durable installation. When nec­essary use shims to obtain the proper level. This will ensure that the condensate will drain from the unit.
INSTALLATION PRECAUTIONS
Installation of this equipment should only be performed by prop­erly trained personnel to ensure proper installation and the safety of the installer. The following are some precautions to be followed for typical installations.
1. Always use proper tools and equipment.
2. No wiring or other work should be attempted without first ensuring that the blower coil is completely discon­nected from the power source and locked out. Always verify that a good ground connection exists prior to energizing any power sources.
3. Always review the nameplate on each unit for proper voltage and control configurations. This infor­mation is determined from the com­ponents and wiring of the unit and may vary from unit to unit.
4. When soldering or brazing to the unit it is recommended to have a fire extinguisher readily available. When soldering close to valve pack­ages or other components heat shields or wet rags are required to prevent damage.
5. When the blower coil unit is in operation components are rotating at high speeds.
6. Units must be installed level to ensure proper drainage and opera­tion.
7. Check unit prior to operation to ensure that the condensate water will drain toward the drain connec­tion. An auxiliary overflow pan may be required as a back up to a clogged primary drain.
8. Be sure that the drain pan is free from foreign material prior to start up.
9. Check filter media installation to ensure that it is installed correctly. Use the directional arrows or other information on the filter to determine the proper flow direction.
10. Ensure that the air distribution system does not exceed the exter­nal static rating of the unit. This could cause the motor to activate its internal motor temperature protec­tor and shut off on safety.
****** WARNING ******
The manufacturer does NOT WARRANT equipment sub­jected to abuse. Metal chips, dust, drywall tape, paint over spray, etc. can void warran­ties and liability for equip­ment failure, personal injury and property damage.
START-UP OPERATION
Pre-start Check
1. Check that supply voltage matches nameplate data.
2. Ensure that the unit is properly grounded.
3. With power off, ensure that the blower wheel(s) rotate freely and quietly.
4. Check that coil(s), valves and pip­ing have been leak checked and insulated as required.
5. Ensure that all air has been vented from the system.
6. Install all panels.
7. Install any filters which may have been removed during the installa­tion process.
HANGING ROD MOUNTING DIMENSIONS
MODEL A B
(TOP VIEW)
AIR FLOW
24SH 35 29
36SH 35 38-1/2
48SH 37 40
60SH 40 47
****** WARNING ******
Always wear eye protection.When blower coil is operating,
some components are operating at high speeds. Personal injury can result from touching these items with any object All electrical and service access panels must be returned and secured in their proper place. Clear surrounding area of all tools, equipment and debris. Check the entire unit to ensure it's cleanliness.
Blower Speed Adjustment
Adjustment of blower speed is made by loosening the set screw in the outer (movable) pulley face and turning this face half or full turns only, so that the adjusting set screw will be positioned precisely over the flat on the pulley hub. Speed is reduced by adjusting the pulley faces so that they are further apart; speed is increased with faces closer together. Check all of the pulleys' set screws for tightness.
Inspection and Cleaning
Before start-up all of the compo­nents should be given a thorough check. Optimal operation of this equipment requires cleanliness. Often after installation of this equip­ment additional construction activi­ties occur. Care must be taken to protect the equipment from debris during these construction phases.
MAINTENANCE
To achieve maximum perfor­mance and service life of each piece of equipment a formal sched­ule of regular maintenance should be established and maintained by a certified contractor. The following is provided as a rec-
ommended maintenance schedule. Specific instructions for mainte­nance proce
check list.
dures are given after the
****** WARNING ******
Disconnect electrical power and allow all rotating equipment to stop before servicing the unit. Failure to do so may result in personal injury or death from electrical shock or entangle­ment in moving parts.
Monthly Check List
- Inspect the unit air filters. Clean or replace as required.
- Inspect the drainpan to be sure it is clean to permit the flow of conden­sate through the drain lines.
- Inspect the fan belt for wear and alignment. Replace or adjust as required.
Yearly Check List
- Clean the blower motor and oil if required.
- Inspect the blower coil unit casing for corrosion and loose fasteners.
- Inspect the blower wheel and housing. Clean if necessary.
- Check the motor pulley and blower pulley for alignment and tighten their set screws. Adjust belt tension if necessary.
- Inspect all coil connections for leaks. Inspect the coil fins for excessive dirt or damage. Clean or repair if required.
Pulley Alignment and Belt Tension
Belt tension and pulley alignment should be checked. Belt tension is adjusted by means of the motor tail­piece adjusting bolt or the position of the motor on the base style motor mount. A deflection of about 3/4" to 1" per foot of span should be ob­tained by pressing the belt firmly. The adjusting bolt should be locked in position after the adjustment is made. Alignment of pulley grooves is made by locating the motor pulley on the motor shaft or by moving the entire motor along the motor mount­ing bracket. For blower speed ad­justment refer to that section.
3/4" to 1" PER
FOOT OF SPAN
Blower
Inspect the bearings for wear. They are ball bearing, self-aligning and grease packed. Replace if required. Inspect the thrust collars for end play and alignment of wheel. Check the blades for accumu­lations of dirt and clean
imbalance and vibration.
mounting brackets, base bolts and isola­tion material.
in order to avoid
Check
Motor
Check motor connections to en­sure that they are secure and made in accordance with the wiring dia­gram.
The blower motor should be cleaned annually and if it has oiling ports, it should be oiled with a good grade of SAE 20 oil. Normally a few drops of oil in each bearing is suffi­cient.
Coil
Any dust or other contaminants which accumulate on the heat trans­fer surfaces interferes with the air flow and impairs heat transfer. The coil must be kept clean by any of the following methods.
1. Cleaning with low pressure
compressed air.
2. Flushing or rinsing with water (a detergent is advisable for greasy surfaces).
3. If strainers are installed in the valve packages, clean the strainers once a year per manufactures direc­tions.
Filter
The air filter should be cleaned or replaced as often as necessary to prevent restriction of air flow. Al­ways replace the filter with the same type as originally furnished. To clean permanent filters, remove the filter and wash in water to re­move the old filter oil. Rinse in clean, hot water and allow to dry. Recoat both sides of the filter with RP filter coat, or an equivalent. Al­low to drain and dry thoroughly be­fore reinstalling the filter.
Drain Piping
The drain should always be con­nected or piped to an acceptable disposal point sloped away from the unit. Check the drain line for restric­tions or blockage before summer operation and monthly during the cooling season.
Drain Pan
The drain pan should be clean to allow proper condensate flow. Re­move any accumulation of residue from the drain pan and inspect for rust and leaks.
Loading...