AQUECOIL
The AQUECOIL is ideal for providing heated air in applications such as residential or commercial
warm air heating, or reheat for humidity control. The
engineered to improve upon duct mounted hot water coils that have been used in the industry for
years. Higher efficiency coils provide greater heat output, lower static pressure on the air stream, and
ure drops in the water line. The galvanized steel frame and unit dimensions are
consistent with products already in use to allow for easy replacement of existing coils. That also
HWC
DUCT MOUNTED
WARM AIR SPACE HEATING USING HOT WATER
DESCRIPTION
AQUECOIL Hot Water Coil A-
lower press
means that there is no learning curve on new installs.
• High-Performance 2-row and 3-row coils
• Low static pressure
• High BTUH output
• High efficiency .0045” aluminum fins
A Series
SPECIFICATION SHEET
FEATURED HIGHLIGHTS
APPLICATION
The AQUECOIL Hot Water Coil A-Series works
in conjunction with any source of hot water
(which can supply enough BTU's to meet your
heating load), such as a Conventional Water
Heater, a Tankless Water Heater, or Boiler, and
an air distribution system. AQUECOIL Hot
Water Coils may be mounted in either the
supply or the return side of the duct system, in
either vertical or horizontal orientation. The
addition of an external air vent is recommended
to assure complete air purging.
• 1/2” OD, .017” wall copper waterways for
improved heat transfer and durability
• Mechanical tube expansion for permanent
bond to fins
• Sweat connections for quick attachment to
water lines
• Up to 500 PSI opera
PSI maximum pressure
• 1" flange on galvanized steel frame
• 3-Year parts warranty
The use of field installed swing check and
isolation valves is strongly recommended.
Heat output can be adjusted to system
requirements by modifying the water flow, air
flow and water temperature. If the hot water
source does not have its own system circulator,
the AQUECOIL Hot Water Coil can be
connected to an AQUECOIL Pump Module,
Models PM-1 or PM-2, to provide the necessary
control functions and specified water flow rates
though the coil.
PO Box 155, Mooresville, North Carolina 28115 ♦ Phone: (704) 662-9232 Fax: (704) 662-9484 ♦ Website: www.AQUECOIL.com
SPECIFICATIONS AND PERFORMANCE INFORMATION
Performance calculations at different
Due to continuous product improvement, these specifications may change without notice.
DIMENSIONS
PERFORMANCE
Model A B C D
HWC-1215-A-2
HWC-1215-A-3 7/8”
HWC-1520-A-2
HWC-1520-A-3
HWC-2020-A-2
HWC-2020-A-3
HWC-2025-A-2
HWC-2025-A-3 1 1/8”
HWC-2030-A-2
HWC-2030-A-3
12 1/2" 15” 14 1/2" 17” 3 3/4"
15” 20” 17” 22” 3 3/4" 7/8”
20” 20” 22” 22” 3 3/4" 7/8”
20” 25” 22” 27” 3 3/4"
20” 30” 22” 32” 3 3/4" 1 1/8”
Width
Model HWC
A Series
(O.D.)
5/8”
7/8”
HWC-1215-A-2
HWC-1215-A-3
HWC-1520-A-2
HWC-1520-A-3
HWC-2020-A-2
HWC-2020-A-3
HWC-2025-A-2
HWC-2025-A-3
HWC-2030-A-2
HWC-2030-A-3
7 700 46,589 .162
7 800 50,565 .205
9 900 55,610 .253 8.7
7 500 46,136 .132
7 600 50,453 .182
10 700 60,146 .239 5.1
7 1200 73,779 .183
7 1400 80,458 .241
10 1500 87,950 .272 4.9
7 800 71,316 .132
7 1100 87,999 .231
12 1200 99,190 .270 4.6
7 1600 93,851 .183
7 1800 99,935 .226
15 2000 118,906 .272 6.0
7 1200 100,645 .162
7 1400 110,877 .213
15 1600 132,953 .270 9.2
10 1900 116,650 .167
10 2200 126,548 .217
20 2500 149,680 .272 6.3
10 1600 132,391 .182
10 1800 142,567 .224
20 2000 166,032 .270 5.8
10 2400 139,494 .183
10 2800 151,220 .241
25 3000 180,381 .272 6.5
10 1800 149,875 .162
10 2200 169,592 .231
25 2400 201,268 .270 9.9
5.5
2.7
2.6
1.8
1.6
2.4
1.9
1.7
1.3
2.0
Galvanized steel frame with 1" flange
using 18 gauge brackets and 20 gauge
sides. Copper waterways using 1/2" O.D.
seamless tubes with .017" walls. 500 PSI
maximum operating pressure, 2500 PSI
ultimate pressure. Aluminum fins are
.0045" thick and tubes are expanded into
fins for permanent surface bond and
maximum heat transfer.
operating parameters are available
upon request.
NOTES:
1) All BTUH calculations use 60°F entering air temperature
and 180°F water temperature.
2) Water circulation is handled either by the existing boiler
system or by installing one of the optional pump
modules, depending on application.
3) The last digit of the model number indicates the number
of rows of copper in the coil.
WARRANTY: All Aquecoil Duct Coils offer a limited 3-year parts warranty.
PO Box 155, Mooresville, North Carolina 28115 ♦ Phone: (704) 662-9232 Fax: (704) 662-9484 ♦ Website: www.AQUECOIL.com
OPTIONAL ACCESSORIES
AK-PM-115 Pump Module, 115 Volt, 3-Speed,3/4” Sweat
AK-PM-230 Pump Module, 230 Volt, 3-Speed,3/4” Sweat
AK-VK-1 Standard Hydronic Valve Kit
REV 10