First Co HWC -24 User Manual

AQUECOIL
MODEL
HOT WATER COILS
The AQUECOIL is ideal for providing heated air in applications such as residential or commercial
warm air heating, or reheat for humidity control. The
Series has been
engineered to improve upon duct mounted hot water coils that have been used in the industry for
years. Higher efficiency coils provide greater heat output, lower static pressure on the air stream, and
ure drops in the water line. The galvanized steel frame and unit dimensions are
consistent with products already in use to allow for easy replacement of existing coils. That also
ting pressure and 2500
HWC
DUCT MOUNTED
WARM AIR SPACE HEATING USING HOT WATER DESCRIPTION
AQUECOIL Hot Water Coil A-
lower press means that there is no learning curve on new installs.
High-Performance 2-row and 3-row coils
Low static pressure
High BTUH output
High efficiency .0045” aluminum fins
A Series
SPECIFICATION SHEET
FEATURED HIGHLIGHTS
APPLICATION
The AQUECOIL Hot Water Coil A-Series works in conjunction with any source of hot water (which can supply enough BTU's to meet your heating load), such as a Conventional Water Heater, a Tankless Water Heater, or Boiler, and an air distribution system. AQUECOIL Hot Water Coils may be mounted in either the supply or the return side of the duct system, in either vertical or horizontal orientation. The addition of an external air vent is recommended to assure complete air purging.
1/2” OD, .017” wall copper waterways for improved heat transfer and durability
Mechanical tube expansion for permanent bond to fins
Sweat connections for quick attachment to water lines
Up to 500 PSI opera PSI maximum pressure
1" flange on galvanized steel frame
3-Year parts warranty
The use of field installed swing check and isolation valves is strongly recommended. Heat output can be adjusted to system requirements by modifying the water flow, air flow and water temperature. If the hot water source does not have its own system circulator, the AQUECOIL Hot Water Coil can be connected to an AQUECOIL Pump Module, Models PM-1 or PM-2, to provide the necessary control functions and specified water flow rates though the coil.
PO Box 155, Mooresville, North Carolina 28115 ♦ Phone: (704) 662-9232 Fax: (704) 662-9484 ♦ Website: www.AQUECOIL.com
SPECIFICATIONS AND PERFORMANCE INFORMATION
/2013
Frame
Header
Model
GPM
CFM
BTUH
APD
WPD
Performance calculations at different
Due to continuous product improvement, these specifications may change without notice.
DIMENSIONS
PERFORMANCE
Model A B C D
HWC-1215-A-2 HWC-1215-A-3 7/8” HWC-1520-A-2 HWC-1520-A-3 HWC-2020-A-2 HWC-2020-A-3 HWC-2025-A-2 HWC-2025-A-3 1 1/8” HWC-2030-A-2 HWC-2030-A-3
12 1/2" 15” 14 1/2" 17” 3 3/4"
15” 20” 17” 22” 3 3/4" 7/8” 20” 20” 22” 22” 3 3/4" 7/8”
20” 25” 22” 27” 3 3/4" 20” 30” 22” 32” 3 3/4" 1 1/8”
Width
Model HWC
A Series
(O.D.)
5/8”
7/8”
HWC-1215-A-2
HWC-1215-A-3
HWC-1520-A-2
HWC-1520-A-3
HWC-2020-A-2
HWC-2020-A-3
HWC-2025-A-2
HWC-2025-A-3
HWC-2030-A-2
HWC-2030-A-3
7 700 46,589 .162 7 800 50,565 .205 9 900 55,610 .253 8.7 7 500 46,136 .132 7 600 50,453 .182
10 700 60,146 .239 5.1
7 1200 73,779 .183 7 1400 80,458 .241
10 1500 87,950 .272 4.9
7 800 71,316 .132 7 1100 87,999 .231
12 1200 99,190 .270 4.6
7 1600 93,851 .183 7 1800 99,935 .226
15 2000 118,906 .272 6.0
7 1200 100,645 .162
7 1400 110,877 .213 15 1600 132,953 .270 9.2 10 1900 116,650 .167 10 2200 126,548 .217 20 2500 149,680 .272 6.3 10 1600 132,391 .182 10 1800 142,567 .224 20 2000 166,032 .270 5.8 10 2400 139,494 .183 10 2800 151,220 .241 25 3000 180,381 .272 6.5
10 1800 149,875 .162 10 2200 169,592 .231 25 2400 201,268 .270 9.9
5.5
2.7
2.6
1.8
1.6
2.4
1.9
1.7
1.3
2.0
Galvanized steel frame with 1" flange using 18 gauge brackets and 20 gauge sides. Copper waterways using 1/2" O.D. seamless tubes with .017" walls. 500 PSI maximum operating pressure, 2500 PSI ultimate pressure. Aluminum fins are .0045" thick and tubes are expanded into fins for permanent surface bond and maximum heat transfer.
operating parameters are available
upon request.
NOTES:
1) All BTUH calculations use 60°F entering air temperature and 180°F water temperature.
2) Water circulation is handled either by the existing boiler system or by installing one of the optional pump modules, depending on application.
3) The last digit of the model number indicates the number of rows of copper in the coil.
WARRANTY: All Aquecoil Duct Coils offer a limited 3-year parts warranty.
PO Box 155, Mooresville, North Carolina 28115 ♦ Phone: (704) 662-9232 Fax: (704) 662-9484 ♦ Website: www.AQUECOIL.com
OPTIONAL ACCESSORIES
AK-PM-115 Pump Module, 115 Volt, 3-Speed,3/4” Sweat AK-PM-230 Pump Module, 230 Volt, 3-Speed,3/4” Sweat
AK-VK-1 Standard Hydronic Valve Kit
REV 10