First Co HBQB -3, HBQB -2.5, HBQB -4 User Manual

NOW EQUIPPED WITH MULTI-FUNCTION MICRO-PROCESSOR
HBQB Series
Vertical / Horizontal / Counterflow (Except 60HBQB) Combo Air Handler
Cooling or Heat Pump / Hot Water Heating 1-1/2 through 5 tons, up to 143,000 BTUH Heating
Description :
The "Combo" air handler converts a properly sized gas or oil-fired water heater into a highly efficient space heating appliance that can heat your home as well as provide hot water. Compared to other heating systems, combo heaters offer high efficiency, greater installation flexibility, cost less to install, and are much easier to service. The HBQB Series incorporates a Multi-function Micro-processor that not only reduces the number of components but adds a number of standard system funstions that would not normally be available, such as an automatic pump timer, and blower delay, just to name a few. The HBQB air handler in th eonly product avail­able with these high quality features! Cooling efficiencies up to 15 SEER.
First Co's customer is ultimately responsible for confirming which fan coil models are compatible with selected outdoor unit(s) and which expansion valves (if any) are required. To determine certified indoor/outdoor matches, go to:www.firstco.com or contact the factory
Proper water heater sizing is required to ensure adequate hot water supply for both domestic use and space heating. Contact the factory for sizing information.
NOW WITH 2-SPEED FAN OPERATION
(High Speed-Cool, Medium Speed-Heat)
FEATURES: Heating Cycle
1. Automatic pump timer: The pump operatesfor sixty seconds every six hours in order to purge the water
from the hot water coil and piping (the pump timer cycle is skipped while the compressor is operating). Note: State of MA, .248 CMR code of the state of MA requires a pump timer. (60 seconds every 6 hours)
2. Blower-on delay: On a call for heat, the hot water coil is preheated for 45 seconds before the blower energizes.
3. Blower-off delay: Blower continues to operate for 20 seconds after thermostat is satisfied, extracting more heat from the heating coil and increasing heating performance.
Cooling Cycle
1. Blower-off delay: Blower continues to operate for 45 seconds after thermostat
is satisfied, extracting more cooling from the cooling coil and maximizing cooling efficiency.
Optional features
board but each option requires an optional field installed switch. (Contact factory)
1. Freeze protection: circuit board has terminals for optional freeze protector switch. Freeze protector energizes the circulating pump if water coil temperature falls below 40 degrees.
2. Factory or field installed R22 or R410A TXV's (non-bleed type).
(logic for the following options is built into the micro-processor circuit
Additional features
1. 4-way airflow
2. Built-in circulating pump, air purge valve, and easy access hot water check valve.
3. Blower door safety switch (excep
4. Compatible with all major brands of split condensing units and heat pumps
5. Slide out hot water coil assembly for easier service
6. Fully insulated galvanized steel cabinet
7. High efficiency copper tube/aluminum fin heating and cooling coils
8. Primary and secondary drain connections on cooling coil
9. Factory installed filter
FIRST CO. - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.firstco.com
(kit required for counterflow - 60HBQB not approved for counterflow installation)
t 60HBQB)
HBQB Series
COOLING or HEAT PUMP HOT WATER HEATING
Efficiency:
The HBQB series air handler is the latest state-of-the-art air handler for hot water heating. Depending on the water heater efficiency and the condensing unit used, heating efficiency can exceed 90% and cooling effi­ciency can exceed 14 SEER (depending on the selected outdoor unit). Cooling coils have either piston type metering devices or R22 or R410A TXV’s and are circuited for cooling or heat pump operation.
First Co's customer is ultimately responsible for confirming which fan coil models are compatible with selected outdoor unit(s) and which expansion valves (if any) are required. To determine certified indoor/outdoor matches, go to: www.firstco.com or contact the factory.
Components:
Each air handler includes a high efficiency cooling coil, a separate hot water coil, circulating pump, air purge valve, anti-thermosyphon check valve, blower door safety switch (except 60HBQB), 120V blower motor, throw away filter, and 24V transformer.
Cabinets:
Cabinets are fully insulated and painted with an attractive, baked-on powder coating (light gray).
Installation:
No modification is required for vertical or horizontal (right-to-left) airflow. A horizontal drain pan is factory installed for right-to-left airflow and can be re-positioned within the cabinet to offer left-to-right airflow. An optional counterflow conversion kit is available for downflow installations.
Operation:
When space heating is needed, the wall thermostat energizes the circulating pump which circulates hot water from the water heater to the hot water coil in the air handler. As the blower motor forces cool return air from the home over the hot water coil, the air absorbs heat from the hot water. This warm air (105 to 110 degrees) is then circulated throughout the duct system and into the home. The water loses only about 15 degrees of temperature while it circulates through the coil and is then returned to the water heater to be reheated.
Accessories:
Accessories include counterflow conversion kits, TXV expansion valve kits, and freeze protector.
4-WAY AIRFLOW
-2-
(60 HBQB NOT CONVERTIBLE TO
DOWNFLOW)
(SEE NOTE NEXT TO BLOWER
DATA TABLE)
HBQB Series
(1-1/8 O.D. on 60HBQB)
COOLING or HEAT PUMP HOT WATER HEATING
COIL
CONNECTIONS
18/24 30/36 48/60
LIQUID
3/8 3/8 1/2
SUCTION
5/8 3/4 7/8
(See P.4 for Model Numbers)
PERFORMANCE DATA
UNIT
MODEL
18HBQB
24HBQB
30HBQB
36HBQB
48HBQB
60HBQB
NOMINAL COOLING
BTUH
18,000 USM318AP 3-1/2 4.3 24.2 29.1 33.9 53.3
24,000 USM424AP 3-1/2 4.3 25.2 30.3 35.3 55.5
30,000 USM330AP 3-1/2 5.0 31.1 37.4 43.6 68.5
36,000 USM436A 3-1/2 5.0 35.4 42.4 49.5 77.8
42,000/
48,000
60,000 USM460BP 7 8.8 65.0 78.0 91.0 143.0
COIL #
USM348AP 3-1/2 3.4
GPM
(2)
(HTG.)
P.D.
(FT. WTR.)
(1) Use 48HBQB for 3.5 ton applications and field-convert fan motor to low speed. (2) See “USM” data sheet for additional coil information.
NOTES:
1. Heating output of fan coil will not exceed net output of water heater.
2. Approved for installation with 0” clearance to combustible materials.
3. Heat BTUH is at 70°F entering air temperature.
ELECTRICAL DATA
UNIT
MODEL
18HBQB
24HBQB
30HBQB
36HBQB
48HBQB
60HBQB
MOTOR
HP
(120V)
1/5 2.8 0.57 5 15
1/5 5.1 0.57 7 15
1/5 5.1 0.57 7 15
1/2 8.5 0.57 12 15
3/4 10.7 0.57 14 15
1 11.5 0.75 16 20
MOTOR
AMPS
PUMP
MIN. CIR.
AMPACITY
BTUH (1000) AT ENT.
WATER TEMP.
120oF 130oF 140oF 180oF
45.9
55.0
64.2
49.1
HACR
BREAKER
59.0
MAX.
68.8
100.8
108.1
PHYSICAL DIMENSIONS
UNIT
MODEL
18HBQB 24HBQB
30HBQB 36HBQB
48HBQB
60HBQB
A B C D E F G H
40 20 20 18-1/2 16 2 18 16 18 X 20 X 1
42 23 20 21-1/2 16 2 18 19 20 X 22 X 1
48 28 21-1/4 26-1/4 17-1/4 2 18 24 20 X 25 X 1
52 28 25-1/4 26-1/2 21-1/4 2 22 24
FILTER
SIZE
14 X 24 X 1 (2 required)
BLOWER DATA UPFLOW / HORIZONTAL ONLY DOWNFLOW ONLY
UNIT
MODEL
18HBQB
24HBQB
30HBQB
36HBQB
48HBQB
60HBQB
MOTOR
HP-AMP
(120V)
1/5-2.8
1/5-5.1
1/5-5.1
1/2-8.5
3/4-10.7
1-11.5
MOTOR
SPEED CONN.
HIGH
MED. HIGH
MED. LOW
LOW
HIGH
MED LOW
HIGH
MED LOW
HIGH
MED LOW
HIGH
MED LOW
HIGH
MED LOW
CFM vs. EXTERNAL STATIC PRESSURE
0.05 0.10 0.20 0.30 0.40 0.50 0.05 0.10 0.20 0.30 0.35
810
780
715
650
580
500 680 530 350
950 860 780
1120
850 680
1340 1290 1200
1810 1570 1280
2160 1865 1560
655 505 325
920 835 755
1095
840 670
1310 1260 1170
1780 1550 1260
2125 1840 1540
600 460 325
855 785 705
1045
810 655
1250 1200 1120
1720 1510 1220
2055 1785 1490
545 415 220
790 720 650
995 780 625
1190 1140 1070
1660 1460 1180
1980 1710 1435
490 360 160
720 650 590
940 740 585
1120 1080 1010
1590 1400 1130
1895 1620 1365
420
295
- - -
645
580
510
880
590
510
1050 1000
940
1530 1340 1050
1810 1525 1260
710 640 480 330
760 720 680
1080
885 730
1090 1060 1020
1510 1270 1005
60HBQB is not approved for
-3-
690
630 575 420 260
680 640 600
1010
830 690
1010
980 940
1430 1190
930
570 520 380 220
620 590 550
950 800 660
950 920 890
1380 1150
890
620 460 310
730 690 655
1060
860 720
1070 1030
990
1480 1240
980
downflow conversion
540 490 350 200
590 550 525
920 770 640
925 890 860
1350
NOTE:
1120
860
For downflow applications, select air handler 1/2 ton larger than the outdoor unit in order to achieve nominal airflow.
Model Numbers:
FACTORY INSTALLED TXV’S
MODEL SIZE
(BTU)
18,000 18HBQB 18HBQB w/R22 TXV 18HBQB w/R410A TXV
24,000 24HBQB 24HBQB w/R22 TXV 24HBQB w/R410A TXV
30,000 30HBQB 30HBQB w/R22 TXV 30HBQB w/R410A TXV
36,000 36HBQB 36HBQB w/R22 TXV 36HBQB w/R410A TXV
42,000/48,000 48HBQB 48HBQB w/R22 TXV 48HBQB w/R410A TXV
60,000 60HBQB 60HBQB w/R22 TXV 60HBQB w/R410A TXV
All TXV's are approved for cooling only or heat pump operation (non-bleed type).
NOTE: Expansion valve requirement depends on the selected outdoor unit. Go to www.firstco.com or contact the factory for
assistance.
MODEL
(PISTON)
MODEL
(R22 TXV)
MODEL
(R410A TXV)
ACCESSORIES - (all field installed)
EXPANSION VALVE KITS (Field installed) (cooling only or heat pump)
PART NUMBER
R22 FITS
9EVR22-4 18/24HBQB
9EVR22-5 30/36HBQB
9EVR22-6 42-60HBQB
R410A
9EVR410-3 18/24HBQB
9EVR410-4 30/36HBQB
9EVR410-5 42-60HBQB
NOTES:
1. Above expansion valve kits are approved for both cooling only (non heat pump) and heat pump applications.
2. Valves are non-bleed type. Field added. Hard start kit may be required.
3. Valves have screw-on connections.
In keeping with its policy of continuous progress and product
improvement, First Co. reserves the right to make changes
without notice. Maintenance for all First Co. products is
available under “Product Maintenance” at www.firstco.com.
COUNTERFLOW CONVERSION KITS
FITS KIT NUMBER
18, 24HBQB 30, 36HBQB
48HBQB
919-11 919-12 919-13
Notes:
1. Counterflow conversion not recommended where the air handler is installed above the finished ceiling.
2. No kit is available for the 60HBQB. This model is
not approved for counterflow installation
MISCELLANEOUS
COMPONENT DESCRIPTION PART NUMBER
Freeze Protector
Thermostat
Energizes pump
when coil temperature
falls below 38
24V Heat/Cool T334
o
F
941-1
Notes:
1. Freeze protector attaches to hot water coil and wires to low voltage (24V) circuit.
Catalog No. HBQB613 (Replaces HBQB513)
-4-