First Co HBC User Manual

HBC, PHBC, RHBC and CHBC
HORIZONTAL HYDRONIC FAN COIL UNITS
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
***** WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER *****
Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty and may result in adverse operational performance and/or a possible hazard­ous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning.
GENERAL
The manufacturer assumes no re­sponsibility for equipment installed in violation of any code requirement. These instructions give information relative to the installation of these fan coil units only. For other related equipment refer to the proper instruc­tions. Material in this shipment has been inspected at the factory and released to the transportation agency in good condition. When received, a visual inspection of all cartons should be made immediately. Any evidence of rough handling or apparent damage should be noted on the delivery re­ceipt and the material inspected in the presence of the carrier's representa­tive. If damage is found, a claim should be filed against the carrier im­mediately.
****** WARNING ******
Unit must not be operated dur­ing building construction due to excessive airborne dust and debris. The units must not be operated under any circum­stances without an air filter in place.
FAN COIL UNIT
The installer must adhere strictly to all local and national code require­ments pertaining to the installation of this equipment. The HBC, PHBC, and RHBC units are designed for installa-
tion in a horizontal position above a dropped ceiling. The CHBC is a cabi­net unit intended for horizontal ex­posed surface mounting. In a HBC free return installation (non-ducted return air), the furred down area must be completely sealed (except return air grille) to ensure that all return air is pulled from the condi­tioned space and not from other areas of the building structure. Access must be provided for servic­ing the unit. If this access is provided by a removable ceiling panel, ample space must be allowed for removal of the blower panel and to provide ac­cess to electrical and plumbing con­trols. While most fan coil units are U.L. Listed for installations with zero clear­ance to combustible materials, refer­ence should be made to the marking on the particular unit being installed where specific information regarding clearances is provided.
AIR DISTRIBUTION DUCTS
All duct work must be installed in accordance with National Fire Protec­tion Association Codes 90A and 90B. Ducts should be adequately insulated to prevent condensation during the cooling cycle and to minimize heat loss during the heating cycle. All return air must be filtered to prevent dirt buildup on the coil surface. If there is no ducted return, applicable instal­lation codes may limit the unit to in­stallation only in a single story resi­dence. In many cases it is acceptable
to use ducting of the same size as the fan coil connections. However, unique arrangements or long duct runs must be confirmed by a local professional. The manufacturer will not be responsible for misapplied equipment.
ELECTRICAL
All wiring must comply with local and national code requirements. Units are provided with wiring dia­grams and nameplate data to provide information required for necessary field wiring. These units may be provided with a optional Class 2 transformer for 24­volt control circuits. Should any add­on equipment also have a Class 2 transformer furnished, care must be taken to prevent interconnecting out­puts of the two transformers by using a thermostat with isolating contacts.
****** WARNING ******
Any devices such as fan switches or thermostats that have been furnished by the factory for field installation must be wired in strict accor­dance with the wiring diagram that is supplied with the unit. Failure to do so could result in damage to components and will void all warranties.
L2395 9/99
Supply Connection
Return Connection
A
Left Hand Arrangement
A
Figure 1 - Determination of Right-hand/Left-hand References
PIPING
These units employ a hydronic coil designed for use with either hot or chilled water. All piping must be adequately sized to meet the design water flow require­ments as specified for the specific installation. Piping must be installed in accordance with all applicable codes. The piping connections on the equipment are not necessarily indica­tive of the proper supply and return line sizes. To minimize restrictions piping design should be kept as simple as possible.
Caution: Prior to connecting to the fan coil all external piping must be purged of debris.
****** WARNING ******
When connecting piping or valve kits to fan coil units, do not bend or reposition the coil header tubing for alignment purposes. This could cause a tubing fracture resulting in a water leak when water pres­sure is applied to the system.
Plenum
(Optional)
All chilled water piping must be in­sulated to prevent condensation. Condensate drain lines must be in­stalled with adequate slope away from the unit to assure positive drain­age. Since the drain pan is located on the suction side of the blower, a nega­tive pressure exists at the drain pan. RHBC and CHBC fan coil units re­quire a minimum trap of 1-1/2 inches be provided in the drain line to assure proper drainage. HBC and PHBC fan coil units may be located where the return air space is large enough that a negative pressure is not present, however, a trapped condensate line is recommended in case a negative condition should occur, the unit would drain properly.
PIPING PRECAUTIONS
1. Flush all field piping prior to con­nection to remove all debris.
2. Use wet cotton rags to cool valve bodies when soldering.
3. Open all valves (mid-way for hand valves, manually open on motorized valves) prior to soldering.
4. When soldering to bronze or brass, heat the piping while in the socket/cup and begin introducing the solder when the flux boils rapidly. Avoid direct flame into the solder joint.
5. Heat can only be applied to the cup
B
A
Right Hand Arrangement
of the valve body for a minimal time before damage occurs (even with the use of wet rags.
6. Avoid rapid quenching of solder joints as this will produce joints of inferior quality.
7. The valve package will not support the weight of the connecting pipes. All pipes which are connected to the units must be completely supported prior to connection to the unit.
8. Provisions must be made for ex­pansion and contraction of piping sys­tems. All horizontal and vertical ris­ers, including runouts, must be able to withstand significant movement with temperature changes. Failure to do so will result in damage and failure of piping, fittings and valves throughout the building.
9. Never insulate the heads or motor­ized portion of control valves. Dam­age can occur in the form of exces­sive heat build up and interference to the operation and moving parts will result.
10. All piping made in the field should be installed with consideration of ad­ditional space for any electrical rout­ing that may be required.
11. Connect all piping per accepted industry standards and observe all regulations governing installation of piping systems. When all connec-
Loading...
+ 2 hidden pages