First Co FWA-HW User Manual

Page 1
FWA-AQ SERIES
****** W ARNING ******
Unit must not be operated during building construction due to excessive airborne dust and debris. The unit must not be operated under any circumstances without an air filter in place.
****** W ARNING ******
Any devices such as fan switches or thermostats that have been furnished by the factory for field installation must be wired in strict accor­dance with the wiring diagram that is supplied with the unit. Failure to do so could result in damage to components and will void all warranties.
****** W ARNING ******
Extreme caution must be taken that no internal damage will result if screws or holes are drilled into the cabinet.
HOT WATER FURNACE
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
**WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER**
Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty
and may result in adverse operational performance and/or a possible hazardous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning. Current Maintenance Program is available at www.firstco.com under "Product Information".
GENERAL
The manufacturer assumes no re­sponsibility for equipment installed in violation of any code requirement.
These instructions give information relative to the installation of these fan coil units only. For other related equipment refer to the proper instruc­tions.
Material in this shipment has been inspected at the factory and released to the transportation agency in good condition. When received, a visual inspection of all cartons should be made immediately. Any evidence of rough handling or apparent damage should be noted on the delivery re­ceipt and the material inspected in the presence of the carrier’s repre­sentative. If damage is found, a claim should be filed against the carrier immediately.
Note: State of MA.-248 CMR code of the state of MA. requires a pump timer (60 seconds on every 6 hours). See dia­gram.
FAN COIL UNIT
The installer must adhere strictly to all local and national code require-
ments pertaining to the installation of this equipment.
These units are designed to be installed in either an upflow, downflow or horizontal position.
All fan coil units are U.L. listed for installation with zero inches clear­ance to combustible materials. This includes the unit cabinet, discharge plenum and connecting ducts. Suffi­cient clearance must be provided at the front of the unit to allow access to
electrical controls and removal of the motor / blower assembly for servicing. This clearance distance should be approximately the same depth as the fan coil unit.
AIR DISTRIBUTION DUCTS
All duct work must be installed in accordance with National Fire Protec­tion Association Codes 90A and 90B. Ducts should be adequately insulated to minimize heat loss during the heat­ing cycle. All return air must be filtered to prevent dirt buildup on the coil sur­face. If there is no ducted return, applicable installation codes may
limit the unit to installation only in a single story residence. In many cases it is acceptable to use ducting of the same size as the fan coil connections. However, unique ar­rangements or long duct runs must be confirmed by a local professional. The manufacturer will not be respon­sible for misapplied equipment.
ELECTRICAL
All wiring must comply with local and national code requirements. Units are provided with wiring dia­grams and nameplate data to provide information required for necessary field wiring. Knockouts are provided on each side of the cabinet for con­nection of power supply.
These units may be provided with a Class 2 transformer for 24-volt control circuits. Should any add-on equip­ment also have a Class 2 transformer furnished, care must be taken to pre­vent interconnecting outputs of the two transformers by using a thermo­stat with isolating contacts.
L2462 02/09
Page 2
INSTALLATION
****** WARNING ******
Do not touch any rotating component with any object. Damage to the equipment and personal injury can occur.
****** WARNING ******
When connecting piping to fan coil units, do not bend or reposition the coil header tub­ing for alignment purposes. This could cause a tubing frac­ture resulting in a water leak when water pressure is ap­plied to the system.
PRECAUTIONS
Installation of this fan coil should only be performed by properly trained personnel to ensure proper installa­tion and the safety of the installer. The following are some precautions to be followed for typical installations.
• Always use proper tools and equip­ment.
• No wiring or other work should be attempted without first ensuring that the fan coil is completely discon­nected from the power source and locked out. Always verify that a good ground connection exists prior to en­ergizing any power sources.
• Always review the nameplate on each unit for proper voltage and con­trol configurations. This information is determined from the components and wiring of the unit and may vary from unit to unit.
• When soldering or brazing to the unit, it is recommended to have a fire extinguisher readily available. When soldering close to valve packages or other components, heat shields or wet rags are required to prevent dam­age.
• When the fan coil unit is in opera­tion components are rotating at high speeds.
• Units must be installed level to ensure proper operation.
• Check filter media installation to ensure that it is installed correctly. Use the directional arrows or other information on the filter to determine the proper flow direction.
• Ensure that the air distribution sys­tem does not exceed the external static rating of the unit.
HOT WATER COIL PIPING PRECAUTIONS
• Flush all field piping prior to connec­tion to remove all debris.
• Use wet cotton rags to cool valve bodies when soldering.
• Open all valves (midway for hand valves, manually open on motorized valves) prior to soldering.
• When soldering to bronze or brass, heat the piping while in the socket/ cup and begin introducing the solder when the flux boils rapidly. Avoid direct flame into the solder joint.
• Heat can only be applied to the cup of the valve body for a minimal time before damage occurs (even with the use of wet rags.
• Avoid rapid quenching of solder joints as this will produce joints of inferior quality.
• Connect all piping per accepted industry standards and observe all regulations governing installation of piping systems. When all connec­tions are complete the system must be pressure tested. Repair any sol­der joint leaks and gently tighten any leaking valve packing nuts and piping accessories as required. Hydronic systems are not designed to hold pressurized air and should only be tested with water.
HOT WATER COIL PIPING
Figure 1 illustrates a typical piping schematic for an Aqua Therm Sys­tem.
The hot water coil connections are 3/4 inch nominal (7/8” OD) copper. The hot water supply to the fan coil should be on the right when facing the fan coil upright and from the front.
****** WARNING ******
An expansion tank may be
required if a back-flow
preventer is installed in the
system.
All piping between the water heater and fan coil unit should be copper and should not exceed 200 feet of total piping. It is recommended that 3/4” nominal (7/8” OD) piping be used to prevent excessive head pressure losses. (Consult the factory for other piping applications.)
It is also recommended that all piping be adequately insulated to pre­vent freezing when piping is run in an unconditioned space. Solder Connections - All copper joints in the water lines must be made with low temperature - non lead
solder. "T" Connections (at the water
heater)­ Water lines to and from the fan coil unit must be taken from the horizontal connection of the "T" fittings in the vertical hot and cold water supply lines at the water heater. This en­sures that any air in the system will be purged each time water is used in the dwelling. (See figure 1)
Isolation Valves - Two valves are recommended to be installed within the circulating loop to permit servicing of the system if required and to assist in purging the system.
NOTE: Hot water coil freeze protec­tion is available for applications where the fan coil is located in ambi­ent air locations (attics, crawl spaces, etc.) or within structures that may be unoccupied during freezing conditions. Consult the factory for additional information.
Page 3
OPERATION AND
****** W ARNING ******
Always wear eye protection.
When fan coil is operating,
some components are operating at high speeds. Personal injury can result from touching these items with any object
All electrical and service access panels must be returned and secured in their proper place.
Clear surrounding area of all tools, equipment and debris.
Check the entire unit to ensure it's cleanliness.
****** W ARNING ******
The manufacturer does NOT WARRANT equipment sub­jected to abuse. Metal chips, dust, drywall tape, paint over spray, etc. can void warranties and liability for equipment failure, personal injury and property damage.
****** W ARNING ******
To prevent pump damage, the fan coil unit should not be energized for heating until the hot water coil and all water lines have been purged of air.
****** W ARNING ******
Hot water can cause scalding. A hot water mixing valve can be applied to the system to temper domestic water draw.
**MAINTENANCE UPDATES**
For a current copy of the Maintenance Program log on to www.firstco.com and look under "Product Informa­tion"
MAINTENANCE
Pre-start Check
• Check that supply voltage matches nameplate data.
• Ensure that the unit is properly grounded.
• With power off, check blower wheel set screw for tightness and ensure that the blower wheel rotates freely and quietly. Remove the motor blower shipping brace on the 60MBQ blower assembly.
Check that the water coil, valves
and piping have been leak checked and insulated as required.
Ensure that all air has been vented
from the hot water coil.
NOTE: It may require purging several gallons of water so have a means of discarding the water.
Install all panels.
NOTE: The blower door must be in place for the unit to operate due to the door safety switch.
Install any filters which may have
been removed during the installation process.
Start-up and Maintenance
Before start-up, all of the compo­nents should be given a thorough check. Optimal operation of this equipment requires cleanliness. Of­ten after installlation of this equip­ment additional construction activi­ties occur. Care must be taken to protect the equipment from debris during these construction phases.
Fan
The fan should be inspected and cleaned, in conjunction with mainte­nance of the motor and bearings. It is important to keep the wheel clean in order to avoid imbalance and vibra­tion.
Motor
Check motor connections to en­sure that they are secure and made in accordance with the wiring diagram.
The blower motor should be cleaned annually.
Coil
Any dust or other contaminants which accumulate on the heat trans­fer surfaces interferes with the air flow and impairs heat transfer. The coil should be checked and cleaned an­nually by a licenced contractor.
Filter
The air filter should be cleaned or re-
placed every 30 days or more frequently if severe conditions exist.
place the filter with the same type as originally furnished.
Always re-
Preventative Maintenance
To achieve maximum performance and service life of each piece of equip­ment a formal schedule of regular maintenance should be established and maintained. The equipment should be checked annually by a licenced contractor.
HEATING CYCLE START - UP
1) Fill the water heater. Open a hot water faucet while filling the water heater to vent the air. When the tank is full and all the air is purged, close the faucet.
2) Ignite the water heater and set the thermostat to 140 degrees.
3) Purge the air handler's hot water coil and lines.
NOTE: It may require purging several gallons of water so either have a bucket available or a means of dis­carding the water.
Close valve number 1 and open valve number 2. (See figure 1 ) Next, open the air bleed valve. When all of the air is purged from the lines close valve number 2 and open valve number 1. After all the air is purged from the coil and lines, open both valve number 1 and 2 and close the air bleed valve.
Page 4
4) Switch the room thermostat to the "Heat" position and raise the tem-
perature setting to a position ap­proximately ten degrees above room temperature.
NOTE: The door switch must be
activated to operate the unit.
The pump should energize and be­gin circulating the hot water through the coil. If the pump is operating properly and the water temperature in the water heater has reached the set point, then the hot water inlet at the fan coil unit will be hot. If the pump is running but hot water is not circulating, open the air bleed valve long enough to purge any remaining air from the hot water lines and coil. This will allow the pump to begin circulating hot wa­ter.
5) The water heater thermostat should be adjusted so that the water tem­perature entering the hot water coil is as close to 140 degrees as pos­sible with the system energized and operating long enough for all temperatures to stabilize.
PUMP REPLACEMENT
Disconnect electrical power before
servicing the unit.
To replace the circulator pump,
close the isolation valves and relieve the water pressure within the heating loop. Disconnect the pump's 115 volt power lines within the control box and remove the four hex head screws se­curing the pump motor to the pump's volute.
Reverse the above steps for reas-
sembling the pump, however make sure that the pump or volute has the rubber o-ring in place before assem­bling.
CHECK VALVE REPLACEMENT
Disconnect electrical power before
servicing the unit.
To replace the internal check valve, close the isolation valves and relieve the water pressure within the heating loop. Remove the four hex head screws securing the pump motor to the pump's volute and remove. The check valve is located in the volute. Rotate the check valve to release and remove from the volute.
Reverse the above steps for rein­stalling a check valve, however make sure that the pump or volute has the rubber o-ring in place before assem­bling.
HOT WATER
TO
HEATING
LOOP
TEE FITTING MUST BE INSTALLED AS SHOWN. REFER TO INSTRUCTIONS FOR DETAILS
TYPICAL PIPING SCHEMATIC
SUPPLY TO
HOUSE
HEATER
WATER SUPPLY
TO HOT WATER
HEATER
HOT
WATER
1
FLOW
FAN COIL UNIT
HOT WATER COIL
2
PUMP
FLOW
CHECK
VALVE
AIR BLEED VALVE
1) ISOLATION VALVE: SUPPLY LINE (FIELD SUPPLIED)
2) ISOLATION VALVE: RETURN LINE (FIELD SUPPLEID)
Figure 1
Page 5
STATE OF MASSACHUSETTS PIPING DIAGRAM
UNITS WITH HOT WA TER HEA TING
Loading...