First Co CLX-HW User Manual

CL FAN COIL UNITS
****** W ARNING ******
Unit must not be operated during building construction due to excessive airborne dust and debris. The unit must not be operated under any circumstances without an air filter in place.
****** W ARNING ******
Extreme caution must be taken that no internal damage will result if screws or holes are drilled into the cabinet.
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
**WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER**
Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty
and may result in adverse operational performance and/or a possible hazardous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning. Current Maintenance Program is available at www.firstco.com under "Product Information".
GENERAL
The manufacturer assumes no re­sponsibility for equipment installed in violation of any code requirement.
These instructions give information relative to the installation of these fan coil units only. For other related equipment refer to the proper instruc­tions.
Material in this shipment has been inspected at the factory and released to the transportation agency in good condition. When received, a visual inspection of all cartons should be made immediately. Any evidence of rough handling or apparent damage should be noted on the delivery receipt and the material inspected in the pres­ence of the carrier’s representative. If damage is found, a claim should be filed against the carrier immediately.
FAN COIL UNIT
The installer must adhere strictly to all local and national code require­ments pertaining to the installation of this equipment. These units are de­signed to be installed in a vertical, upflow position either hung on a wall or set on a platform within an equipment closet.
All fan coil units are U.L. Listed for installation with zero inches clear­ance to combustible materials. This includes the fan coil cabinet, dis­charge plenum and connecting ducts.
Sufficient clearance must be provided at the front of the fan coil to allow access to the air filter,electrical con­trols and removal of the motor/blower assembly for servicing. This clear­ance distance should be approxi­mately the same as the depth of the fan coil unit. The unit should be leveled in such a way that there is slope toward the condensate drain nipple to assure positive drainage.
NOTE: It is important at this point to
consider noise and vibration. If this installation is in a noise sensitive area then placement of resilient isolators or other means of sound deadening may be necessary. These fan coil units are designed for quiet operation, however, all air conditioning equipment will transfer some amount of noise to the condi­tioned space. This should be taken into consideration when planning the location of the equipment as well.
AIR DISTRIBUTION DUCTS
All duct work must be installed in accordance with National Fire Protec­tion Association Codes 90A and 90B. Ducts should be adequately insulated to prevent condensation during the cooling cycle and to minimize heat loss during the heating cycle. Provi­sion for connecting the return air duct is located on the side of the unit. The installer must cut out the center sec­tion and bend the 3/4” flanges out. The backing insulation must also be re­moved. See illustration p.3. Duct siz­ing for unique arrangements or long duct runs must be confirmed by a local professional . The manufacturer will not be responsible for misapplied equipment.
ELECTRICAL
All wiring must comply with local and national code requirements. Units are provided with wiring dia­grams and nameplate data to provide information required for necessary field wiring. Knockouts are provided on the cabinet for connection of power supply. These units are provided with a Class 2 transformer for 24-volt control circuits. Should any add-on equip­ment also have a Class 2 transformer furnished, care must be taken to pre­vent interconnecting outputs of the two transformers by using a thermo­stat with isolating contacts.
INSTALLATION PRECAUTIONS
Installation of this fan coil should only be performed by a licensed con­tractor to ensure proper installation and the safety of the installer. The following are some precautions to be followed for typical installations.
• Always use proper tools and equip­ment.
• No wiring or other work should be attempted without first ensuring that the fan coil is completely discon­nected from the power source and locked out. Always verify that a good ground connection exists prior to en­ergizing any power sources.
• Always review the nameplate on
L2399 10/09
each unit for proper voltage and con-
****** WARNING ******
When connecting piping to fan coil units, do not bend or reposition the coil header tub­ing for alignment purposes. This could cause a tubing frac­ture resulting in a refrigerant leak when pressure is applied to the system.
****** WARNING ******
Do not touch any rotating component with any object. Damage to the equipment and personal injury can occur.
****** WARNING ******
Any devices such as fan switches or thermostats that have been furnished by the factory for field installation must be wired in strict accor­dance with the wiring diagram that is supplied with the unit. Failure to do so could result in damage to components and will void all warranties.
****** W ARNING ******
R-410a can become combus­tible if mixed with air at elevated temperatures and/or pressures. Property damage, personal in­jury or death could result if this warning is ignored.
trol configurations. This information is determined from the components and wiring of the unit and may vary from unit to unit.
• When soldering or brazing to the unit, it is recommended to have a fire extinguisher readily available. When soldering close to metering devices or other components, heat shields or wet rags are required to prevent dam­age.
• When the fan coil unit is in operation components are rotating at high speeds.
• Units must be installed level to ensure proper drainage and opera­tion.
• Check unit prior to operation to ensure that the condensate water will drain toward the drain connection. An overflow drain or an overflow switch installed in the fan coil may be re­quired as a back up to a clogged primary drain.
• Be sure that the drain pan is free from foreign material prior to start up.
• Check filter media installation to ensure that it is installed correctly. Use the directional arrows or other information on the filter to determine the proper flow direction.
• Ensure that the air distribution sys­tem does not exceed the external static rating of the unit.
MOUNTING
It is important to ensure that the fan coil is securely mounted and the structure is sufficient to support the weight of the equipment. All anchors for mounting the equipment must be placed and sized to ensure a safe and durable installation.
COOLING COIL PIPING
This fan coil unit is supplied with a direct expansion refrigerant coil. The suction and liquid refrigerant lines must be sized in accordance with the outdoor unit manufacturer’s recom­mendations.
Condensate drain lines must be installed with adequate slope away from the unit to assure positive drain­age. Since the drain pan is located on the suction side of the blower, a negative pressure exists at the drain pan and a minimum trap of 1-1/2 inches must be provided in the drain line to assure proper drainage.
CAUTION: It is highly recom­mended that a condensate over­flow switch be installed to prevent damage which may result from an overflow of the condensate pan.
NOTE: If a Condensate Overflow
Shut-off Switch, that is designed to be installed in the drain line, is used in place of a secondary drain line, then the cut-off switch should be located in the primary drain line be­tween the fan coil unit and the P-trap.
OPERATION AND MAINTENANCE
set screws for tightness and ensure that the blower wheels rotates freely and quietly.
Check that the refrigerant coil con-
nections and piping have been leak checked and insulated as required.
Start-up and Maintenance Before start-up, all of the compo-
nents should be given a thorough check. Optimal operation of this equipment requires cleanliness. Of­ten after installation of this equipment additional construction activities oc­cur. Care must be taken to protect the equipment from debris during these construction phases. All ac­cess panels and filters must be in place before operation of the units.
Fan
The fan should be inspected and cleaned, in conjunction with mainte­nance of the motor and bearings. It is important to keep the wheels clean in order to avoid imbalance and vibra­tion.
Motor
Check motor connections to en­sure that they are secure and made in accordance with the wiring diagram.
The blower motor should be cleaned annually.
Filter
The air filter should be cleaned or replaced every 30 days or more fre­quently if severe conditions exist. Always replace the filter with the same type as originally furnished.
Pre-start Check
• Check that supply voltage matches nameplate data.
• Ensure that the unit is properly grounded.
• With power off, check blower wheel
Coil
Any dust or other contaminants which accumulate on the heat trans­fer surfaces interferes with the air flow and impairs heat transfer. The coil must be kept clean by any of the following methods.
Cleaning with low pressure com-
pressed air.
Flushing or rinsing with water (a
detergent is advisable for greasy sur­faces).
Loading...
+ 2 hidden pages