First Co CLP-AQ User Manual

Page 1
CLQ FAN COIL UNIT
****** W ARNING ******
Unit must not be operated during building construction due to excessive airborne dust and debris. The unit must not be operated under any circumstances without an air filter in place.
****** W ARNING ******
Any devices such as fan switches or thermostats that have been furnished by the factory for field installation must be wired in strict accor­dance with the wiring diagram that is supplied with the unit. Failure to do so could result in damage to components and will void all warranties.
****** W ARNING ******
Extreme caution must be taken that no internal damage will result if screws or holes are drilled into the cabinet.
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
**WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER**
Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty
and may result in adverse operational performance and/or a possible hazardous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning. Current Maintenance Program is available at www.firstco.com under "Product Information".
GENERAL
The manufacturer assumes no re­sponsibility for equipment installed in violation of any code requirement.
These instructions give information relative to the installation of these fan coil units only. For other related equipment refer to the proper instruc­tions.
Material in this shipment has been inspected at the factory and released to the transportation agency in good condition. When received, a visual inspection of all cartons should be made immediately. Any evidence of rough handling or apparent damage should be noted on the delivery re­ceipt and the material inspected in the presence of the carrier’s repre­sentative. If damage is found, a claim should be filed against the carrier immediately.
Note: State of MA.-248 CMR code of the state of MA. requires a pump timer (60 seconds on every 6 hours). See dia­gram.
FAN COIL UNIT
The installer must adhere strictly to all local and national code require­ments pertaining to the installation of this equipment.
ance to combustible materials. This includes the unit cabinet, discharge plenum and connecting ducts. Suffi­cient clearance must be provided at the front of the unit to allow access to the air filter, electrical controls and removal of the motor / blower assem­bly for servicing. This clearance dis­tance should be approximately the same depth as the fan coil unit.
NOTE: It is important at this point to
consider noise and vibration. If this installation in a noise sensitive area then placement of resilient isolators or other means of sound deadening may be necessary. These fan coils are designed for quiet operation, however, all air condi­tioning equipment will transfer some amount of noise to the conditioned space. This should be taken into con­sideration when planning the location of the equipment as well.
ducting of the same size as the fan coil connections. However, unique arrangements or long duct runs must be confirmed by a local professional. The manufacturer will not be respon­sible for misapplied equipment. See fig. 3.
ELECTRICAL
All wiring must comply with local and national code requirements. Units are provided with wiring dia­grams and nameplate data to provide information required for necessary field wiring. Knockouts are provided on both sides of cabinet for connection to the power supply.
These units may be provided with a Class 2 transformer for 24-volt control circuits. Should any add-on equip­ment also have a Class 2 transformer furnished, care must be taken to pre­vent interconnecting outputs of the two transformers by using a thermo­stat with isolating contacts.
INSTALLATION PRECAUTIONS
Installation of this fan coil should only be performed by a licensed con­tractor to ensure proper installation and the safety of the installer. The following are some precautions to be
These units are designed to be installed in a vertical, upflow position either hung on a wall or set on a platform within an equipment closet.
All fan coil units are U.L. listed for installation with zero inches clear-
AIR DISTRIBUTION DUCTS
All duct work must be installed in accordance with National Fire Protec­tion Association Codes 90A and 90B. Ducts should be adequately insulated to prevent condensation during the cooling cycle and to minimize heat loss during the heating cycle. All return air must be filtered to prevent dirt buildup on the coil surface. In many cases it is acceptable to use
L2398 10/09
Page 2
followed for typical installations.
****** WARNING ******
When connecting piping to fan coil units, do not bend or reposition the coil header tub­ing for alignment purposes. This could cause a tubing frac­ture resulting in a water leak when water pressure is ap­plied to the system.
****** W ARNING ******
R-410a can become combus­tible if mixed with air at el­evated temperatures and/or pressures. Property damage, personal injury or death could result if this warning is ig­nored.
• Always use proper tools and equip­ment.
• No wiring or other work should be attempted without first ensuring that the fan coil is completely discon­nected from the power source and locked out. Always verify that a good ground connection exists prior to en­ergizing any power sources.
• Always review the nameplate on each unit for proper voltage and con­trol configurations. This information is determined from the components and wiring of the unit and may vary from unit to unit.
• When soldering or brazing to the unit, it is recommended to have a fire extinguisher readily available. When soldering close to the cabinet wall or near heat labile components, heat shields or wet rags are required to prevent damage.
• When the fan coil unit is in opera­tion components are rotating at high speeds.
• Units must be installed level to ensure proper drainage and opera­tion.
• Check unit prior to operation to ensure that the condensate water will drain toward the drain connection. An overflow drain or an auxiliary drain pan under the fan coil may be required as a back up to a clogged primary drain.
• Check filter media installation to ensure that it is installed correctly. Use the directional arrows or other information on the filter to determine the proper flow direction.
• Ensure that the air distribution sys­tem does not exceed the external static rating of the unit.
COOLING COIL PIPING
The CLQ fan coil unit is supplied with a direct expansion refrigerant coil. The suction and liquid refrigerant lines must be sized in accordance with the outdoor unit manufacturer’s recommendations.
Condensate drain lines must be installed with adequate slope away from the unit to assure positive drain­age. Since the drain pan is located on the suction side of the blower, a negative pressure exists at the drain pan and a minimum trap of 1-1/2 inches must be provided in the drain line to assure proper drainage.
NOTE: If a Condensate Overflow Shut-off Switch, that is designed to be installed in the drain line, is used in place of a secondary drain line, then the cut-off switch should be located in the primary drain line between the fan coil unit and the P-trap.
HOT WATER COIL PIPING PRECAUTIONS
• Flush all field piping prior to connec­tion to remove all debris.
• Use wet cotton rags to cool valve bodies when soldering.
• Open all valves (midway for hand valves, manually open on motorized valves) prior to soldering.
• When soldering to bronze or brass, heat the piping while in the socket/ cup and begin introducing the solder when the flux boils rapidly. Avoid direct flame into the solder joint.
• Heat can only be applied to the cup of the valve body for a minimal time before damage occurs (even with the use of wet rags.
• Avoid rapid quenching of solder joints as this will produce joints of inferior quality.
• Connect all piping per accepted industry standards and observe all regulations governing installation of piping systems. When all connec­tions are complete the system must be pressure tested. Repair any sol­der joint leaks and gently tighten any leaking valve packing nuts and piping accessories as required. Hydronic systems are not designed to hold pressurized air and should only be tested with water.
****** WARNING ******
An expansion tank may be required if a back-flow preventer is installed in the system.
HOT WATER COIL PIPING
Figure 1 illustrates a typical piping schematic for an Aqua Therm Sys­tem.
The hot water coil connections are 1/2 inch nominal (5/8” OD) copper. The hot water supply to the fan coil is on the left when facing the fan coil from the front.
All piping between the water heater and fan coil unit should be copper and should not exceed 200 feet of total piping using 3/4” nominal pipe. It is recommended that 3/4” nominal (7/8” OD) piping be used on CLQ units to prevent excessive head pressure losses, so a 7/8” to 5/8” bell reducer will then be needed. (Consult the factory for other piping applications.)
It is also recommended that all piping be adequately insulated to pre-
vent freezing when piping is run in an unconditioned space. Solder Connections - All copper joints in the water lines must be made with low temperature - non lead
solder. "T" Connections (at the water
heater)­ Water lines to and from the fan coil unit must be taken from the horizontal connection of the "T" fittings in the vertical hot and cold water supply lines at the water heater. This en­sures that any air in the system will be purged each time water is used in the dwelling. (See figure 1)
Isolation Valves - Two valves are recommended to be installed within the circulating loop to permit servicing of the system if required and to assist in purging the system.
Page 3
NOTE: Hot water coil freeze protec-
****** W ARNING ******
Always wear eye protection.
When fan coil is operating,
some components are operating at high speeds. Personal injury can result from touching these items with any object
All electrical and service access panels must be returned and secured in their proper place.
Clear surrounding area of all tools, equipment and debris.
Check the entire unit to ensure it's cleanliness.
****** W ARNING ******
The manufacturer does NOT WARRANT equipment sub­jected to abuse. Metal chips, dust, drywall tape, paint over spray, etc. can void warranties and liability for equipment failure, personal injury and property damage.
****** W ARNING ******
To prevent pump damage, the fan coil unit should not be energized for heating until the hot water coil and all water lines have been purged of air.
****** W ARNING ******
Hot water can cause scalding. A hot water mixing valve can be applied to the system to temper domestic water draw.
****** W ARNING ******
Do not touch any rotating component with any object. Damage to the equipment and personal injury can occur .
tion is available for applications where the fan coil is located in ambi­ent air locations (attics, crawl spaces, etc.) or within structures that may be unoccupied during freezing conditions. Consult the factory for additional information.
OPERATION AND MAINTENANCE
Pre-start Check
• Check that supply voltage matches nameplate data.
• Ensure that the unit is properly grounded.
• With power off, check blower wheel set screw for tightness and ensure that the blower wheel rotates freely and quietly.
Check that the water coil, valves
and piping have been leak checked and insulated as required.
Ensure that all air has been vented
from the hot water coil.
NOTE: It may require purging several gallons of water so have a means of discarding the water.
Start-up
Before start-up all of the compo­nents should be given a thorough check. Optimal operation of this equipment requires cleanliness. Of­ten after installation of this equipment additional construction activities oc­cur. Care must be taken to protect the equipment from debris during these construction phases.
Heating Cycle Start-up
1) Fill the water heater. Open a hot water faucet while filling the water heater to vent the air. When the tank is full and all the air is purged, close the faucet.
2) Ignite the water heater and set the thermostat to 140 degrees.
3) Purge the air handler’s hot water coil and lines.
NOTE: It may require purging several gallons of water so have a means of discarding the water.
Close valve number 1 and open valve number 2. (See figure 1) Next, open the air bleed valve. When all of the air is purged from the lines close valve number 2 and open valve number 1. After all the air is purged from the coil
Install all panels.
NOTE: The blower door must be in place for the unit to operate due to the door safety switch.
Install any filters which may have
been removed during the installation process.
TEE FITTINGS MUST BE INSTALLED AS SHOWN WITH "OFF LEG" TO FAN COIL
HOT WATER SUPPLY TO HOUSE
WATER SUPPLY TO HOT WATER HEATER
FLOW
# 1
# 2
AIR DISCHARGE
LOW VOLTAGE, L/R
POWER SUPPLY KNOCKOUTS, L/R
LIQUID & SUCTION FITTINGS
FILTER DOOR
DRAIN PAN FITTINGS
FLOW
ISOLATION VALVES (2)
METHOD FOR WATER HEATER INSTALLATION WITH CL*-AQ FAN COILS
(UNITS WITH INTEGRAL PUMP INSTALLED)
Figure 1
RETURN AIR
Page 4
and lines, open both valve number 1
****** WARNING ******
R-410a systems operate at much higher pressures than systems using former refriger­ants. Use only equipment cer­tified for use with R-410a.
**MAINTENANCE UPDATES**
For a current copy of the Maintenance Program log on to www.firstco.com and look under "Product Informa­tion"
and 2 and close the air bleed valve.
4) Switch the room thermostat to the "Heat" position and raise the tem­perature setting to a position approxi­mately ten degrees above room tem­perature.
NOTE: The door switch contacts must be closed to operate the unit.
NOTE: The heating cycle has a time delay relay to delay the blower on a call for heat.
The pump should energize and begin circulating the hot water through the coil. If the pump is operating properly and the water temperature in the water heater has reached the set point, then the hot water inlet at the fan coil unit will be hot. If the pump is running but hot water is not circulating, open the air bleed valve long enough to purge any remaining air from the hot water lines and coil. This will allow the pump to begin circulating hot water.
5)The water heater thermostat should be adjusted so that the water tempera­ture entering the hot water coil is as close to 140 degrees as possible with the system energized and operating long enough for all temperatures to stabilize.
Coil
The coils must be kept clean, any dust or other contaminants which ac­cumulate on the heat transfer surfaces interferes with the air flow and impairs heat transfer. Inspect annually or more frequently if required.
Filter
The air filter should be cleaned or replaced every 30 days or more fre­quently if severe conditions exist. Al­ways replace the filter with the same
type as originally furnished.
Drain Piping
The drain should always be:
Connected or piped to an accept-
able disposal point sloped away
from the unit at least 1/8" per foot
Checked before summer operation
Periodically checked during sum-
mer operation
Preventative Maintenance
To achieve maximum performance and service life of each piece of equip­ment a formal schedule of regular maintenance should be established and maintained.
PUMP REPLACEMENT
Disconnect electrical power before
servicing the unit.
To replace the circulator pump, close the isolation valves and relieve the water pressure within the heating loop. Disconnect the pump's 115 volt power lines within the control box and remove the four hex head screws se­curing the pump motor to the pump's volute.
Reverse the above steps for reas­sembling the pump, however make sure that the pump or volute has the rubber o-ring in place before assem­bling.
CHECK VALVE REPLACEMENT
Disconnect electrical power before servicing the unit.
To replace the internal check valve, close the isolation valves and relieve the water pressure within the heating loop. Remove the four hex head screws securing the pump motor to the pump's volute and remove. The check valve is located in the volute. Rotate the check valve to release and remove from the volute.
Reverse the above steps for rein­stalling a check valve, however make sure that the pump or volute has the rubber o-ring in place before assem­bling.
MAINTENANCE
Fan
The fan should be inspected and cleaned, in conjunction with mainte­nance of the motor and bearings. It is important to keep the wheel clean in order to avoid imbalance and vibration.
Motor
Check motor connections to ensure that they are secure and made in accordance with the wiring diagram.
The blower motor should be cleaned annually.
115 VAC Line
24VAC
Common
CL 12345
Motor speed taps, 24VAC, see
wiring diagram on unit for
proper speed connections
BRUSHLESS DC MOTOR CONNECTIONS
IF SO EQUIPPED
SEE WIRING DIAGRAM
Figure 2
Chassis Ground
115 VAC Neutral
GN
Page 5
TRIM AWAY INSULATION HERE TO AVOID FILTER BINDING
RIGHT HAND CL FAN COIL
FILTER COVER
REFRIGERANT FITTINGS
FOLD FOUR FLANGES OUT, 90°
CUT OUT THI S
SECTION
Figure 3
HOT WATER COIL
LOW VOLTAGE, L/R
DRAIN PAN FITTINGS
LEFT HAND CLQ FAN COIL
POWER SUPPLY KNOCKOUTS, L/R
ACCESS COVER
Figure 4
Page 6
STATE OF MASSACHUSETTS PIPING GDIAGRAM
UNITS WITH HOT WA TER HEA TING
Loading...