First Co CDXQ User Manual

CDXQ SERIES
****** W ARNING ******
Unit must not be operated during building construction due to excessive airborne dust and debris. The unit must not be operated under any circumstances without an air filter in place.
****** W ARNING ******
Any devices such as fan switches or thermostats that have been furnished by the factory for field installation must be wired in strict accor­dance with the wiring diagram that is supplied with the unit. Failure to do so could result in damage to components and will void all warranties.
Fan Coil Units
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
**WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER**
Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty
and may result in adverse operational performance and/or a possible hazardous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning. Current Maintenance Program is available at www.firstco.com under "Product Information".
GENERAL
The manufacturer assumes no re­sponsibility for equipment installed in violation of any code requirement.
These instructions give information relative to the installation of these fan coil units only. For other related equipment refer to the proper instruc­tions.
Material in this shipment has been inspected at the factory and released to the transportation agency in good condition. When received, a visual inspection of all cartons should be made immediately. Any evidence of rough handling or apparent damage should be noted on the delivery re­ceipt and the material inspected in the presence of the carrier’s repre­sentative. If damage is found, a claim should be filed against the carrier immediately.
Note: State of MA.-248 CMR code of the state of MA. requires a pump timer (60 seconds on every 6 hours). See dia­gram.
FAN COIL UNIT
The installer must adhere strictly
to all local and national code require­ments pertaining to the installation of this equipment.
These units are designed for instal­lation in a horizontal position. The CDXQ is designed for free return installation (non-ducted return air), therefore the furred down area must be completely sealed (except return air grille) to ensure that all return air is pulled from the conditioned space and not from other areas of the build­ing structure. Access must be provided for servic­ing the unit. If this access is provided by a removable ceiling panel, ample space must be allowed for removal of the blower panel and to provide ac­cess to electrical and plumbing con­trols. All CDXQ units are U.L. listed for installation with zero inches clear­ance to combustible materials. This includes the unit cabinet, discharge plenum and connecting ducts.
AIR DISTRIBUTION DUCTS
All duct work must be installed in accordance with National Fire Pro­tection Association Codes 90A and 90B. Ducts should be adequately insulated to prevent condensation during the cooling cycle and to mini­mize heat loss during the heating cycle. All return air must be filtered to prevent dirt buildup on the coil sur­face. If there is no ducted return, applicable installation codes may limit the unit to installation only in a single story residence. In many cases it is acceptable to use ducting of the same size as the fan coil connections. However, unique ar-
rangements or long duct runs must be confirmed by a local professional. The manufacturer will not be respon­sible for misapplied equipment.
ELECTRICAL
All wiring must comply with local and national code requirements. Units are provided with wiring dia­grams and nameplate data to provide information required for necessary field wiring. These units are provided with a Class 2 transformer for 24-volt control circuits. Should any add-on equip-
ment also have a Class 2 transformer furnished, care must be taken to pre­vent interconnecting outputs of the two transformers by using a thermo­stat with isolating contacts.
INSTALLATION PRECAUTIONS
Installation of this fan coil should only be performed by properly trained personnel to ensure proper installa­tion and the safety of the installer.
L250 2/09
The following are some precautions to
****** WARNING ******
Do not touch any rotating component with any object. Damage to the equipment and personal injury can occur.
****** WARNING ******
When connecting piping to fan coil units, do not bend or reposition the coil header tub­ing for alignment purposes. This could cause a tubing frac­ture resulting in a water leak when water pressure is ap­plied to the system.
be followed for typical installations.
Always use proper tools and equip-
ment.
No wiring or other work should be
attempted without first ensuring that the fan coil is completely discon­nected from the power source and locked out. Always verify that a good ground connection exists prior to en­ergizing any power sources.
Always review the nameplate on
each unit for proper voltage and con­trol configurations. This information is determined from the components and wiring of the unit and may vary from unit to unit.
When soldering or brazing to the
unit, it is recommended to have a fire extinguisher readily available. When soldering close to valve packages or other components, heat shields or wet rags are required to prevent dam­age.
When the fan coil unit is in opera-
tion components are rotating at high speeds.
Units must be installed level to
ensure proper drainage and opera­tion. These fan coils have a pitched drain pan for improved condensate drainage.
Check unit prior to operation to
ensure that the condensate water will drain toward the drain connection. An overflow drain or an auxiliary drain pan under the fan coil may be re­quired as a back up to a clogged primary drain.
Be sure that the drain pan is free
from foreign material prior to start up.
Check filter media installation to
ensure that it is installed correctly. Use the directional arrows or other information on the filter to determine the proper flow direction.
Ensure that the air distribution sys-
tem does not exceed the external
static rating of the unit.
COOLING COIL PIPING
The CDXQ fan coil units are sup­plied with a direct expansion refriger­ant coil. The refrigerant metering device is a fixed orifice piston and is installed at the factory. This permits the unit to be matched with either a standard condensing unit or heat pump. The suction and liquid refriger­ant lines must be sized in accordance with the outdoor unit manufacturer’s recommendations.
Condensate drain lines must be installed with adequate slope away from the unit to assure positive drain­age. Since the drain pan is located on the suction side of the blower, a negative pressure exists at the drain pan and a minimum trap of 1-1/2 inches should be provided in the drain line to assure proper drainage. The fan coil unit may be located where the return air space is large enough that a negative pressure is not present, however, a trapped condensate line is recommended in case a negative condition should occur, the unit would drain properly.
NOTE: If a Condensate Overflow Shut-off Switch, that is designed to be installed in the drain line, is used in place of a secondary drain line, then the cut-off switch should be located in the primary drain line between the fan coil unit and the P-trap.
HOT WATER COIL PIPING PRECAUTIONS
Flush all field piping prior to connec-
tion to remove all debris.
Use wet cotton rags to cool valve
bodies when soldering.
Open all hand valves midway prior to
soldering.
When soldering to bronze or brass,
heat the piping while in the socket/ cup and begin introducing the solder when the flux boils rapidly. Avoid direct flame into the solder joint.
Heat can only be applied to the cup
of the valve body for a minimal time before damage occurs (even with the use of wet rags.
Avoid rapid quenching of solder
joints as this will produce joints of inferior quality.
Connect all piping per accepted
industry standards and observe all regulations governing installation of
piping systems. When all connec­tions are complete the system must be pressure tested. Repair any sol­der joint leaks and gently tighten any leaking valve packing nuts and piping accessories as required. Water sys­tems are not designed to hold pres­surized air and should only be tested with water.
NOTE: A water heater is designed to produce hot water. Hot water repre­sents a serious safety hazard due to potential scalding. The temperature of water normally required to provide space heating (135 to 140 degrees) may be hotter than certain codes allow for domestic hot water. An “anti­scald valve” can be installed in the hot water piping that would allow the do­mestic water to be supplied at a lower temperature than the space heating water. These can be obtained locally and should be installed according to the manufacturer’s installation in-
structions.
HOT WATER COIL PIPING
The hot water coil connections are 1/2” inch nominal (5/8” OD) copper. All piping between the water heater and fan coil unit should be 3/4” nomi­nal (7/8” OD) to prevent excessive head pressure losses and should not exceed 200 feet of total piping. (Con­sult the factory for other piping appli­cations.)
It is also recommended that all piping be adequately insulated to pre-
****** WARNING ******
An expansion tank may be
required if a back-flow
preventer is installed in the
system.
Loading...
+ 3 hidden pages