SER’S MANUAL
GARAGE
S
UGGESTED AREAS FOR INSTALLING ADDITIONAL CO ALARMS
B
EDROOM
BEDROOM
HALL
LIVING ROOM
KITCHEN
BASEMENT
BEDROOM
REQUIRED TO MEET NFPA RECOMMENDATIONS
U
120V PLUG-IN CARBON MONOXIDE ALARM WITH
ATTERY BACK-UP AND SILENCE FEATURE
B
Model
CO606
120V AC
~,
60 Hz, 0.09A
M08-0206-003 S 08/10 Printed in Mexico
PLEASE READ CAREFULLY AND SAVE.
This user’s manual contains important information about your Carbon
Monoxide (CO) Alarm’s operation. If you are installing this CO Alarm
for use by others, you must leave this manual—or a copy of it—with
the end user.
ABLE OF CONTENTS
T
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Basic Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
How Your CO Alarm Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Understanding Your CO Alarm . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Where to Install CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Where CO Alarms Should NOT Be Installed . . . . . . . . . . . . . . . .2
How to Install Your CO Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . .3
If Your CO Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
If the Alarm Signal Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Using the Silence Features . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
esting and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
T
Weekly Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Regular Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Replacing the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
What You Need To Know About CO . . . . . . . . . . . . . . . . . . . . . . . .4-6
What is CO? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Symptoms of CO Poisoning . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Finding the Source of CO After an Alarm . . . . . . . . . . . . . . . . . .4
How Can I Protect My Family? . . . . . . . . . . . . . . . . . . . . . . . . . .4
Potential Sources Of CO In The Home . . . . . . . . . . . . . . . . . .5-6
Regulatory Information for CO Alarms . . . . . . . . . . . . . . . . . . . . . .5-6
General Limitations Of CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . .5-6
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
© 2010 BRK Brands, Inc. All rights reserved.
Distributed by BRK Brands, Inc.
3901 Liberty Street Road, Aurora, IL 60504-8122
Consumer Affairs: (800) 323-9005 • www.firstalert.com
IMPORTANT!
LISTED TO
UL 2034
STANDARD
INTRODUCTION
ASIC SAFETY INFORMATION
B
• Dangers, Warnings, and Cautions alert you to important
operating instructions or to potentially hazardous situations.
Pay special attention to these items.
• THIS IS NOT A SMOKE ALARM! This CO Alarm is designed to
detect carbon monoxide from ANY source of combustion. It is
NOT designed to detect smoke, fire, or any other gas.
• This CO Alarm is approved for use in single-family residences.
This CO Alar
•
monoxide gas at the sensor. Carbon monoxide gas may be
present in other areas.
•
The Silence Feature is for your convenience only and will not
c
orrect a CO problem. Always check your home for a potential
p
roblem after any alarm. Failure to do so can result in injury or
d
eath.
• This CO Alarm should receive continuous 120VAC, 60 Hz, pure
sine wave electrical power. (The battery is meant for emergency
back-up only). Do not use in an extension cord or outlet
controlled by a dimmer or switch. In order for the emergency
battery back-up to work, a working (fresh) battery must be
properly installed.
• NEVER ignore your Carbon Monoxide Alarm if it alarms. Refer
to “If Y
do so can r
• Test the CO Alarm once a week. If the CO Alarm ever fails to
test correctly, have it replaced immediately! If the CO Alarm is
not working pr
• This product is intended for use in ordinary indoor locations of
family living units. It is not designed to measure CO levels in
compliance with Occupational Safety and Health Administration
(OSHA) commercial or industrial standards. Individuals with
medical conditions that may make them more sensitive to
carbon monoxide may consider using warning devices which
pr
ovide audible and visual signals for carbon monoxide concentrations under 30 ppm. For additional information on carbon
monoxide and your medical condition contact your physician.
m will only indicate the pr
our CO Alar
m Sounds” for mor
esult in injury or death.
, it cannot aler
operly
HOW YOUR CO ALARM WORKS
GENERAL INFORMATION
Leave your CO Alarm plugged in year-round. CO problems can
occur any time during the year, and this Alarm can only alert you if
it is plugged in and receiving power.
This CO Alarm is intended for use in a standard, unswitched 120V AC
wall outlet. It is not intended for use in extension cor
outlets contr
uous power to the unit. When fully power
and takes a new r
unit stor
exposed to over time. The Alarm sounds when it has been exposed to
a “critical” level of CO (measur
specified time (measur
nently installed sensor
has a Silence Featur
olled by a switch or dimmer. These may not provide contin-
eading about every second. A micr
es each reading, and remembers the levels of CO it has been
ed in parts per million or “ppm”) within a
ed in minutes). This CO Alarm features a perma-
, an indicator light, and an 85dB alarm hor
e to temporarily quiet the alarm hor
MALFUNCTION WARNING
This unit performs self-diagnostic tests. If the Alarm malfunctions, it
should be r
OPERATING PROPERLY" for more information.
eplaced immediately. See "IF THE CO ALARM IS NOT
THE PARTS OF YOUR CO ALARM
5
esence of carbon
mation. Failur
e infor
t you to a problem.
ds, power strips, or
ed, the unit samples the air
1
2
4
1 2 3 4 5
ochip inside the
Open door here
1
2
Test/Silence Button
POWER/ALARM Light
3
(Red)
Battery Compartment
4
5 (Behind Cover) Alarm
3
n: 85 dB audible
Hor
alarm for test, alarm,
and unit malfunction
ning.
war
e to
n. It also
n.
UNDERSTANDING YOUR CO ALARM
WHAT YOU SEE AND HEAR DURING INSTALLATION
WHEN YOU FIRST INSTALL THE BATTERY:
UNDER NORMAL CONDITIONS (AC POWER):
W
WHAT YOU SEE AND HEAR UNDER DIFFERENT CONDITIONS
DURING A POWER FAILURE (IN BATTERY BACK-UP):
WHEN THE ELECTRICITY COMES BACK ON AFTER A POWER FAILURE:
IF BATTERY BECOMES LOW OR IS MISSING:
IF THE CO ALARM IS NOT OPERATING PROPERLY (MALFUNCTION
SIGNAL):
IF THE CO ALARM HAS REACHED ITS END OF LIFE:
WHAT YOU SEE AND HEAR IF CO IS DETECTED
ALARM LEVELS OF CO ARE DETECTED:
IF YOU SILENCE THE ALARM:
IF THE CO LEVELS RETURN TO NORMAL:
Chirps once
HORN:
POWER/ALARM LIGHT: Flashes once
HORN: Silent
POWER/ALARM LIGHT: Shines continuously
HEN YOU TEST THE CO ALARM:
HORN: Sounds loudly - 4 beeps, pause, 4 beeps, pause
POWER/ALARM LIGHT: The LED flashes with the same pattern as
the horn.
HORN:
Silent
P
OWER/ALARM LIGHT: Flashes once a minute.
HORN: Silent
POWER/ALARM LIGHT: Shines continuously.
Chirps once a minute
HORN:
POWER/ALARM LIGHT: Shines continuously if AC is present or
flashes coincident with the horn-chirp if AC is not present.
3 chirps every minute
HORN:
POWER/ALARM LIGHT: Flashes three times with the horn.
HORN: 5 chirps every minute
POWER/ALARM LIGHT: 5 flashes approximately once a minute.
HORN:
Sounds loudly - 4 beeps, pause, 4 beeps, pause.
This sequence repeats for as long as the unit is in alarm.
POWER/ALARM LIGHT: The LED flashes with the same pattern as
the horn.
HORN:
Silent for about 4 minutes
POWER/ALARM LIGHT:Flashes rapidly
Note: After 4 minutes, if CO levels drop below alarm levels, the unit
will r
emain silent and return to normal operation.
If CO presence still indicates a potentially dangerous situation, the
horn will sound again.
Silent
HORN:
POWER/ALARM LIGHT: Shines continuously
INSTALLATION
HERE TO INSTALL CO ALARMS
W
The National Fire Protection Association (NFPA) recommends that a CO
Alarm should be centrally located outside of each separate sleeping
area in the immediate vicinity of the bedrooms. For added protection,
install additional CO Alarms in each separate bedroom, and on every
level of your home.
If your bedroom hallway is longer than 40 feet (12 meters), install a CO
Alarm at BOTH ends of the hallway
In a Single-level Home:
Install at least one CO Alarm near or within each separate sleeping
•
area.
For added pr
•
(
6 meters) away fr
In a Multi-level Home:
Install at least one CO Alarm near or within each separate sleeping
•
ar
For added pr
•
the home. If you have a basement, install that CO Alarm at the top
of the basement stairs.
For added pr
•
(6 meters) away fr
This unit should receive continuous electrical power. (The battery
is meant for emer
cannot be accidentally unplugged or switched off by children. Keep
small children away from the unit. Teach them not to play with it or
unplug it. Explain what the alar
otection, install an additional CO Alarm at least 20 feet
om the fur
ea.
otection, install at least one CO Alarm on each level of
otection, install an additional CO Alarm at least 20 feet
om the fur
gency back-up only). Choose an outlet wher
WHERE CO ALARMS SHOULD NOT BE
INSTALLED
DO NOT LOCATE THIS CO ALARM:
In garages, kitchens, furnace rooms, or in any extremely dusty,
•
dirty or greasy areas.
• Closer than 15 feet (4.6 meters) from a furnace or other fuel burning
• Within 5 feet (1.5 meters) of any cooking appliance.
• In extremely humid areas. This Alarm should be at least 10 feet
• In areas where temperature is colder than 40˚ F (4˚ C) or hotter
•
•
• In outlets covered by curtains or other obstruction.
• This CO Alarm is designed for use inside a single-family home
• This CO Alarm alone is not a suitable substitute for complete
•
ce, or fuel burning appliances like a water heater.
heat sour
(3 meters) fr
washer, laundry room, utility room or other source of high humidity.
than 100˚ F (38˚ C). These ar
spaces, unfinished attics, uninsulated or poorly insulated ceilings,
porches, and garages.
In turbulent air
fresh air returns, or open windows. Blowing air may prevent CO
from reaching the sensors.
In dir
or apar
hallways, or basements of multi-family buildings unless working
CO Alarms are also installed in each family living unit.
CO Alar
individual family living units.
detection systems in places which house many people, like hotels
or dor
DO NOT use this CO Alarm in warehouses, industrial or commercial buildings, special-purpose non-residential buildings, or
airplanes. This CO Alar
use, and may not provide adequate protection in non-residential
applications.
om a bath or shower
, like near ceiling fans, heat vents, air conditioners,
ect sunlight.
tment. It is not meant to be used in common lobbies,
ms in common areas may not be heard from inside
mitories, unless a CO Alarm is also placed in each unit.
.
nace or fuel bur
nace or fuel bur
ms mean.
, sauna, humidifier, vaporizer, dish-
eas include non-air
m is specifically designed for r
ning heat sour
ning heat sour
conditioned crawl
ce.
ce.
e it
esidential
HOW TO INSTALL YOUR CO ALARM
Read “Where To Install CO Alarms” before starting.
Before you start installation,
included with this CO Alarm. On each label write in the phone number
of your emergency responder (like 911) and a qualified appliance technician. Place one label near the CO Alarm, and the other label in the
“fresh air” location you plan to go if the alarm sounds.
Tools you will need: Screwdriver, drill.
1. Determine the best location for your CO Alarm.
2. Your Alarm is equipped to be mounted as a corded unit or a direct
plug unit. The unit can be plugged directly into a wall outlet. If your
outlets are mounted horizontally, refer to “If Outlet is Mounted
Horizontally (Sideways)”.
If the adapter is taken out of the unit, the Alarm can be installed
high on the wall, while the adapter is plugged into a wall outlet.
ACTIVATING THE BATTERY BACK-UP
Activate the battery back-up by
installing the two (2) AA batteries.
The battery is for back-up only and
is not intended to power the Alarm
for an extended period of time in
the absence of AC.
IRECT PLUG ALARM INTO AN OUTLET
D
This Alarm can be plugged directly into a wall outlet located close to
the floor.
1. Choose a standard UNSWITCHED 120V AC outlet.
2. Plug Alarm in.
F OUTLET IS MOUNTED HORIZONTALLY (SIDEWAYS)
I
If you are going to use your Alarm as a direct plug into an outlet that is
mounted horizontally (sideways), you may want to rotate the adapter
90º, as follows:
1. With back of unit facing you (AC blades on your left), place your left
thumb on adapter release and grab AC blades with your right hand
to release the left side.
2. Repeat for the other side adapter thumb release. This will allow
adapter to slide out.
3. Remove adapter.
4. Rotate the adapter 90º and snap firmly back into place.
5. Plug Alarm into AC outlet.
ALL MOUNTED ALARM
W
Installation tips for power cord models: The power cord option
provides more flexibility in mounting locations and allows the Alarm to
be easily installed at or above eye level.
NOTE: If you mount the Alarm high on a wall, make sure it is at least 4
inches (102 mm) down from the ceiling. Any higher than this, it will be
in “dead air” space and carbon monoxide may not reach the sensor.
NOTE: Do not cover the Alarm with a curtain.
To install for a wall-mount, you will need to pull out the removable
adapter and power cord, as follows:
1. Repeat steps 1 to 3 as described above in
2. With adapter out, pull out power cord and unwrap it.
3. Insert the screws provided until head is approx. 1/8 inch (3 mm)
from wall (if mounting in plaster board or drywall, drill 3/16 inch (5
mm) hole and use plastic anchor provided).
Hook the Alarm over the screw onto the keyhole in back of unit.
4.
5
. Plug power cord into AC outlet.
find the pair of self-adhesive labels
“to rotate the adapter”.
IF YOUR CO ALARM SOUNDS
Actuation of your CO Alar
monoxide (CO) which can kill you. In other wor
Alarm sounds, you must not ignore it!
F THE ALARM SIGNAL SOUNDS:
I
1
. Operate the Test/Silence button.
Call your emer
2.
the number of your local emer
____________________________________________________________
3. Immediately move to fresh air—outdoors or by an open door or
window. Do a head count to check that all persons are accounted
for. Do not re-enter the premises, or move away from the open
door or window until the emergency services responder has
arrived, the premises have been aired out, and your CO Alarm
remains in its normal condition.
After following steps 1-3, if your CO Alarm reactivates within a
4.
24-hour period, repeat steps 1-3 and call a qualified appliance
technician to investigate for sources of CO from fuel-burning
equipment and appliances, and inspect for pr
equipment. If problems are identified during this inspection have the
equipment serviced immediately. Note any combustion equipment
not inspected by the technician, and consult the manufactur
instructions, or contact the manufacturers directly, for more
information about CO safety and this equipment. Make sure that
motor vehicles ar
garage or adjacent to the residence. Write down the number of a
qualified appliance technician here:
____________________________________________________________
If you hear the alarm horn and the red light is flashing, move
everyone to a source of fresh air. DO NOT unplug the CO Alarm!
Alarms have various limitations. See "General Limitations of CO
ms" for details.
Alar
USING THE SILENCE FEA
The Silence Featur
•
not correct a CO problem. Always check your home for a
potential pr
y or death.
in injur
• NEVER remove the batteries from your CO Alarm to silence
the horn. Use the silence feature. Removing the batteries
removes your protection! See “If Your CO Alarm Sounds” for
details on responding to an alarm.
The Silence Feature is intended to temporarily silence your CO Alarm’s
n while you corr
alarm hor
lem. While the alarm is silenced it will continue to monitor the air for CO.
When CO reaches alarm levels the alarm will sound— repeating horn
pattern: 4 beeps, a pause, 4 beeps, etc. Press and hold the Test/Silence
button until the horn is silent. The initial Silence cycle will last approximately 4 minutes.
NOTE: After initial 4-minute Silence cycle, the CO Alarm r
present CO levels and responds accordingly. If CO levels remain potentially dangerous—or start rising higher—the horn will start sounding again.
While the detector is silenced:
If the CO Alar
If the CO Alar
SILENCING THE LOW BA
essing the silence button can stop the low battery “chirp” for up to 8
Pr
hours; do not remove the battery or unplug the Alarm, unless changing
the battery. Activation of low battery silence is acknowledged with a
“chirp”.
Once the low battery war
unit continues to flash the red light once a minute for 8 hours. After 8
hours, the low battery “chirp” will resume.
soon as possible.
If you cannot silence the low battery warning, replace the
batteries immediately.
m...
Is silent for only 4 minutes,
then starts sounding loudly—
4 beeps, pause,
4 beeps, pause
m...
Remains silent after you
essed the T
pr
button
m indicates the presence of carbon
gency services, firedepartment or 911. W
e not, and have not, been operating in an attached
“ALARM-MOVE TO FRESH AIR”
gency service here:
ds, when your CO
rite down
oper operation of this
TURES
e is for your convenience only and will
e to do so can r
oblem after any alar
ect the pr
est/Silence
m. Failur
oblem—it will not corr
This means...
CO levels ar
ous.
danger
This means...
CO levels are dropping.
ect a CO prob-
e-evaluates
e still potentially
TTERY WARNING
ning “chirp” silence feature is activated, the
Replace the batteries as
ers’
esult
U
SING THE SILENCE FEATURES,Continued
ILENCING THE END OF LIFE SIGNAL
S
This silence feature can temporarily quiet the End of Life warning
“chirp” for up to 2 days. You can silence the End of Life warning “chirp”
by pressing the Test/Silence button. The horn will chirp, acknowledging
that the End of Life silence feature has been activated.
A
fter approximately 2 days, the End of Life “chirp” will resume. After
a
pproximately 2-3 weeks the End of Life warning cannot be silenced.
TESTING AND MAINTENANCE
WEEKLY TESTING
Press the Test/Silence button on the Alarm cover until alarm sounds.
During testing, you will hear a loud alarm sequence – 4 beeps, pause,
4 beeps, pause.
The alarm sequence should last 5-6 seconds. If it does not alarm, make
sure the unit is fully plugged into an unswitched outlet. If the unit still
does not alarm, replace it immediately.
• If the Alarm ever fails to test properly, replace it immediately.
Products under warranty may be returned to the manufacturer for
replacement. See “Limited Warranty” at the end of this manual.
• DO NOT stand close to the Alarm when the horn is sounding.
Exposure at close range may be harmful to your hearing.
When testing, step away when horn starts sounding.
• NEVER use vehicle exhaust! Exhaust may cause permanent
damage and voids your warranty.
REGULAR MAINTENANCE
To keep the CO Alarm working properly:
• Test it every week as described in “Weekly Testing.”
• Vacuum the CO Alarm cover at least once a month, using the soft
brush attachment. Never use water, cleaners, or solvents, since
they may damage the unit. Test the Alarm again after vacuuming.
Replace the battery immediately when you hear the “Low Battery
•
Warning”.
The Low (or Missing) Battery Warning: The horn will “chirp” once a
minute.
EPLACING THE BAT
R
Choosing a Replacement Battery:
Alarm requires two standard AA batteries. The following
This CO
batteries are acceptable as replacements: Energizer E91. These
eplacement batteries are commonly available at local retail stores.
r
U
se only the alkaline replacement battery listed. The unit may not
o
perate properly with other batteries. Never use rechargeable batteries
s
ince they may not provide a constant charge.
To Replace The Batteries:
1. Open the battery compartment.
2. Use the thumb guide to remove the old batteries.
3. Insert the new batteries, making sure they snap completely into the
battery compartment and cannot be shaken loose.
4. Close the battery compartment, then test the battery back-up by
pressing the Test/Silence button.
5. Plug the CO Alarm back into the outlet.
DO NOT spray cleaning chemicals or insect sprays directly on or
near the CO Alarm. DO NOT paint over the CO Alarm. Doing so
may cause permanent damage.
• Household cleaners, aerosol chemicals and other contaminants
can affect the sensor. When using any of these materials near the
CO Alarm, make sure the room is well ventilated.
If your home is being fumigated, unplug the unit temporarily and
•
put it where it will not be exposed to chemicals or fumes. When
fumigation is complete and all traces of fumes clear, plug the unit
back in and retest it.
TERY
WHAT YOU NEED TO KNOW ABOUT CO
HAT IS CO?
W
CO is an invisible, odorless, tasteless gas produced when fossil fuels
do not burn completely, or are exposed to heat (usually fire). Electrical
appliances typically do not produce CO.
These fuels include: Wood, coal, charcoal, oil, natural gas, gasoline,
kerosene, and propane.
Common appliances ar
maintained, ar
quickly. CO is a real danger now that homes are more energy efficient.
-tight” homes with added insulation, sealed windows, and other
“Air
weatherproofing can “trap” CO inside.
SYMPTOMS OF CO POISONING
These symptoms ar
discussed with ALL household members.
Mild Exposure:
Slight headache, nausea, vomiting, fatigue (“flu-like” symptoms).
M
edium Exposur
T
hrobbing headache, drowsiness, confusion, fast heart rate.
Extreme Exposure:
Convulsions, unconsciousness, heart and lung failure. Exposure to
carbon monoxide can cause brain damage, death.
Some individuals are more sensitive to CO than others, including
people with cardiac or respiratory problems, infants, unborn babies,
egnant mothers, or elderly people can be mor
pr
severely affected by CO. Members of sensitive populations should
consult their doctors for advice on taking additional precautions.
FINDING THE SOURCE OF CO AFTER AN ALARM
Carbon monoxide is an odorless, invisible gas, which often makes it
ficult to locate the sour
dif
the factors that can make it dif
• House well ventilated before the investigator arrives.
oblem caused by “backdrafting.”
Pr
•
ransient CO pr
T
•
Because CO may dissipate by the time an investigator arrives, it may
be difficult to locate the source of CO.
obligated to pay for any carbon monoxide investigation or service
call.
HOW CAN I PROTECT MY F
A CO Alarm is an excellent means of pr
sounds a loud alarm before carbon monoxide levels become threatening
for average, healthy adults.
m is not a substitute for proper maintenance of home
A CO Alar
appliances.
event CO pr
o help pr
T
Clean chimneys and flues yearly
•
and nests for pr
rust and corr
event pr
pr
or cover a chimney in any way that would block air flow
est and maintain all fuel-bur
T
•
local gas or oil companies and HV
inspections for a nominal fee.
egular visual inspections of all fuel-bur
Make r
•
Check appliances for excessive rust and scaling. Also check the
flame on the bur
A yellow flame means fuel is not being bur
may be pr
vents or fans when they ar
Make sur
barbecue indoors, or in garages or on scr
• Check for exhaust backflow from CO sources. Check the draft
hood on an operating fur
nace heat exchangers.
fur
• Check the house or garage on the other side of shared wall.
• Keep windows and doors open slightly. If you suspect that CO is
escaping into your home, open a window or a door
windows and doors can significantly decrease CO levels.
In addition, familiarize yourself with all enclosed materials. Read
this manual in its entirety, and make sure you understand what to
do if your CO Alar
e often sour
operly ventilated, or malfunction, CO levels can rise
e impr
elated to CO POISONING and should be
e r
e:
oblem caused by special cir
oblems and r
oper air flow
osion, cracks, or separations. These conditions can
oper air movement and cause backdrafting. Never “cap”
ner and pilot lights. The flame should be blue.
esent. Keep the blower door on the fur
e appliances are vented to the outside. Do not grill or
m sounds.
ces of CO. If they ar
e quickly and
ce of CO after an alarm. These ar
ficult to locate sour
AMIL
educe the risk of CO poisoning:
. Keep them free of debris, leaves,
. Also, have a pr
ning equipment annually
AC companies of
e available on all fuel-bur
nace for a backdraft. Look for cracks on
ces of CO:
cumstances.
BRK Brands, Inc. shall not be
Y?
otection. It monitors the air and
ofessional check for
ning appliances.
ned completely and CO
een por
operly
e not pr
e a few of
.
. Many
fer appliance
nace closed. Use
ning appliances.
ches.
. Opening
OTENTIAL SOURCES OF CO IN THE HOME
Fuel-burning appliances like:
portable heater, gas or wood
burning fireplace, gas kitchen
range or cooktop, gas clothes
dryer.
Damaged or insufficient
venting: corroded or discon-
nected water heater vent pipe,
leaking chimney pipe or flue,
or cracked heat exchanger,
blocked or clogged chimney
opening.
Improper use of appliance/
device: operating a barbecue
grill or vehicle in an enclosed
area (like a garage or screened
porch).
Transient CO Problems: “transient” or on-again-off-again CO problems
can be caused by outdoor conditions and other special circumstances.
The following conditions can result in transient CO situations:
P
1. Excessive spillage or reverse venting of fuel appliances caused by
outdoor conditions such as:
• Wind direction and/or velocity, including high, gusty winds. Heavy
air in the vent pipes (cold/humid air with extended periods
between cycles).
• Negative pressure differential resulting from the use of exhaust fans.
• Several appliances running at the same time competing for limited
fresh air.
• Vent pipe connections vibrating loose from clothes dryers,
furnaces, or water heaters.
• Obstructions in or unconventional vent pipe designs which can
amplify the above situations.
2. Extended operation of unvented fuel burning devices (range, oven,
fireplace).
3. Temperature inversions, which can trap exhaust close to the ground.
4. Car idling in an open or closed attached garage, or near a home.
These conditions are dangerous because they can trap exhaust in your
home. Since these conditions can come and go, they are also hard to
recreate during a CO investigation.
REGULATORY INFORMATION FOR CO ALARMS
HAT LEVELS OF CO CAUSE AN ALARM?
W
Underwriters Laboratories Inc. Standard UL2034 requires residential CO
Alarms to sound when exposed to levels of CO and exposure times as
described below. CO levels are measured in parts per million (ppm) of
CO over time (in minutes).
UL2034 Required Alarm Points*:
• If the alarm is exposed to 400 ppm of CO, IT MUST ALARM
BETWEEN 4 and 15 MINUTES.
• If the alarm is exposed to 150 ppm of CO, IT MUST ALARM
BETWEEN 10 and 50 MINUTES.
•
If the alarm is exposed to 70 ppm of CO, IT MUST ALARM
B
ETWEEN 60 and 240 MINUTES.
* Approximately 10% COHb exposure at levels of 10% to 95% Relative
Humidity (RH).
The unit is designed not to alarm when exposed to a constant level
of 30 ppm for 30 days.
CO Alarms are designed to alarm before there is an immediate life
eat. Since you cannot see or smell CO, never assume it’s not present.
thr
• An exposure to 100 ppm of CO for 20 minutes may not affect
average, healthy adults, but after 4 hours the same level may
cause headaches.
• An exposure to 400 ppm of CO may cause headaches in average,
healthy adults after 35 minutes, but can cause death after 2 hours.
This CO Alarm measures exposure to CO over time. It alarms if CO
levels are extremely high in a short period of time, or if CO levels reach
a certain minimum over a long period of time. The CO Alarm generally
sounds an alarm before the onset of symptoms in average, healthy adults.
Why is this important? Because you need to be warned of a potential
CO problem while you can still react in time. In many reported cases of
CO exposure, victims may be aware that they are not feeling well, but
become disoriented and can no longer react well enough to exit the
building or get help. Also, young children and pets may be the first
affected. The average healthy adult might not feel any symptoms when
the CO Alarm sounds. However, people with cardiac or respiratory
problems, infants, unborn babies, pregnant mothers, or elderly people
can be more quickly and severely affected by CO. If you experience
even mild symptoms of CO poisoning, consult your doctor immediately!
ds:
Standar
carbon monoxide alarms UL2034.
According to Underwriters Laboratories Inc. UL2034, Section 1-1.2:
“Carbon monoxide alarms covered by these requirements are intended
to respond to the presence of carbon monoxide from sources such as,
but not limited to, exhaust from internal-combustion engines, abnormal
operation of fuel-fired appliances, and fireplaces. CO Alarms are
intended to alarm at carbon monoxide levels below those that could
cause a loss of ability to react to the dangers of Carbon Monoxide
exposure.” This CO Alarm monitors the air at the Alarm, and is designed
to alarm before CO levels become life threatening. This allows you
precious time to leave the house and correct the problem. This is only
possible if Alarms are located, installed, and maintained as described in
this manual.
Gas Detection at Typical Temperature and Humidity Ranges: The
CO Alarm is not formulated to detect CO levels below 30 ppm typically.
UL tested for false alarm resistance to Methane (500 ppm), Butane (300
ppm), Heptane (500 ppm), Ethyl Acetate (200 ppm), Isopropyl Alcohol
(
200 ppm) and Carbon Dioxide (5000 ppm). Values measure gas and
v
Audible Alarm: 85 dB minimum at 10 feet (3 meters).
Underwriters Laboratories Inc. Single and Multiple Station
apor concentrations in parts per million.
GENERAL LIMITATIONS OF CO ALARMS
This CO Alarm is intended for residential use. It is not intended for
u
se in industrial applications where Occupational Safety and Health
A
dministration (OSHA) requirements for carbon monoxide detectors
m
ust be met.
CO Alarms may not waken all individuals.
readily waken to the sound of the CO Alarm, or if there are infants or
family members with mobility limitations, make sure that someone is
assigned to assist them in the event of an emergency.
CO Alarms will not work without power. This CO Alarm requires a continuous supply of AC power. Plug into an unswitched 120V AC outlet only.
CO Alarms for Solar or Wind Energy users and battery backup
power systems: AC power
true or pure sine wave inverters. Operating this CO Alarm with most
battery-powered UPS (uninterruptible power supply) products or square
wave or “quasi sine wave” inverters will damage the Alarm. If you ar
not sure about your inverter or UPS type, please consult with the
manufacturer to verify.
This CO Alarm will not sense carbon monoxide that does not reach
the sensor. This CO Alarm will only sense CO at the sensor. CO may be
present in other areas. Doors or other obstructions may affect the rate
at which CO reaches the CO Alarm. For this reason, if bedroom doors
are usually closed at night, we recommend you install a CO Alarm in
each bedroom and in the hallway between them.
CO Alarms may not sense CO on another level of the home. For
example, a CO Alarm on the second level, near the bedrooms, may not
sense CO in the basement. For this reason, one CO Alarm may not give
adequate warning. Complete coverage is recommended. Place CO
Alarms on each level of the home.
ed CO Alarms should only be operated with
If children or others do not
e
CO Alarms may not be heard. The alarm horn loudness meets or
e
xceeds current UL standards of 85 dB at 10 feet (3 meters). However,
i
f the CO Alarm is installed outside the bedroom, it may not wake up a
s
ound sleeper or one who has recently used drugs or has been drinking
a
lcoholic beverages. This is especially true if the door is closed or only
p
artly open. Even persons who are awake may not hear the alarm horn
i
f the sound is blocked by distance or closed doors. Noise from traffic,
s
tereo, radio, television, air conditioner, or other appliances may also
p
revent alert persons from hearing the alarm horn. This CO Alarm is not
intended for people who are hearing impaired.
CO Alarms are not a substitute for a smoke alarm. Although fire is a
source of carbon monoxide, this CO Alarm does not sense smoke or
fire. This CO Alarm senses CO that may be escaping unnoticed from
malfunctioning fur
fire requires the installation of smoke alarms.
CO Alarms are not a substitute for life insurance. Though these CO
Alarms war
warrant or imply in any way that they will pr
Homeowners and renters must still insure their lives.
C
O Alar
p
arts have passed many stringent tests and ar
r
eliable as possible, any of these parts could fail at any time. Therefore,
y
ou must test your CO Alarm weekly
CO Alarms ar
Alarms have limitations. They can only detect CO that reaches their
sensors. They may not give early war
is coming fr
naces, appliances, or other sources. Early warning of
n against incr
ms have a limited life.
om a remote part of the home, away from the CO Alarm.
easing CO levels, BRK Brands, Inc. does not
e not foolproof.
Like all other electronic devices, CO
otect lives from CO poisoning.
A
lthough the CO Alarm and all of its
.
ning to rising CO levels if the CO
e designed to be as
TROUBLESHOOTING GUIDE
PROBLEM... THIS MEANS... YOU SHOULD...
The horn “chirps” once every minute. Low battery warning. Install 2 new AA batteries*.
Red light is OFF
press the Test/Silence button.
The light flashes (RED) and the horn sounds 3
“chirps” every minute.
The light flashes (RED) and the horn sounds 5
“chirps” every minute.
CO Alarm goes back into alarm 4 minutes after
you pr
CO Alarm sounds frequently even though no high
levels of CO are revealed in an investigation.
*For a list of acceptable r
If you have any questions that cannot be answer
BRK Brands, Inc. ("BRK") the maker of First Alert®brand products, warrants that for a period of 7 years from the date of purchase, this product will be free
from defects in material and workmanship. BRK, at its option, will repair or replace this product or any component of the product found to be defective during
the warranty period. Replacement will be made with a new or remanufactured product or component. If the product is no longer available, replacement may
be made with a similar product of equal or greater value This is your exclusive warranty.
This warranty is valid for the original retail purchaser from the date of initial retail purchase and is not transferable. Keep the original sales receipt. Proof of
chase is r
pur
or any way change the terms and conditions of this warranty
This warranty does not cover normal wear of parts or damage r
voltage or curr
Further, the warranty does not cover acts of God, such as fire, flood, hurricanes and tornadoes or any batteries that are included with this unit.
BRK shall not be liable for any incidental or consequential damages caused by the breach of any express or implied warranty. Except to the extent prohibited
by applicable law, any implied warranty of merchantability or fitness for a particular purpose is limited in duration to the duration of the above warranty.
Some states, provinces, or jurisdictions do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied
warranty lasts, so the above limitations or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights
that vary from state to state, or province to province.
How to Obtain Warranty Service
vice:
Ser
1-800-323-9005, 7:30 AM to 5:00 PM, Central Standard Time, Monday through Friday. To assist in serving you, please have the model number and date
of purchase available when calling. For Warranty Service return to: BRK Brands, Inc., 25 Spur Drive, El Paso, TX 79906
Battery:BRK Brands, Inc. make no warranty
espect to battery.
r
Date Pur
Date Installed: _____________/_____________Month/Year
First Alert®is a registered trademark of the First Alert Trust.
. Unit will not alarm when you
est/Silence button.
ess the T
eplacement batteries, see “Page 4: Regular Maintenance.”
ed to obtain warranty performance. BRK dealers, service centers, or r
equir
ent, use contrary to the operating instructions, disassembly
ed, do not r
If service is r
chased: ___________Wher
equir
For your r
eturn the product to your retailer. In order to obtain warranty service, contact the Consumer Affairs Division at
ds, please r
ecor
chased: ___________________
e Pur
CO Alarm may not be plugged all the way in,
is not receiving power, and the batteries are
missing, dead, or not properly installed.
MALFUNCTION SIGNAL. CO Alarm needs to be
replaced.
END OF LIFE SIGNAL. CO Alarm needs to be
replaced.
CO levels indicate a potentially dangerous
situation.
The CO Alarm may be improperly located.
Refer to “Where to Install CO Alarms.”
eading this manual, call Consumer Af
ed by r
LIMITED W
.
esulting fr
ess or implied, written or oral, including that of merchantability or fitness for any particular purpose with
, expr
ecord:
ARRANTY
om any of the following: negligent use or misuse of the pr
epair or alteration by anyone other than BRK or an authorized service center
, r
fairs at 1-800-323-9005.
es selling BRK pr
etail stor
Replace alar
the space pr
The alarm will also provide an audible End-of-Life Signal approximately
7 years after installation to remind you to replace the unit.
The End-of-Life Signal can be silenced for up to 2 days. Do not unplug
the alarm or remove the batteries until you get replacement.
Gently push unit all the way into outlet. Make
sure it is not plugged into an outlet controlled
by a switch.
Make sure unit is plugged in securely.
CO Alarms under warranty should be returned to
manufactur
Warranty” for details.
Immediately replace the CO Alarm.
IF YOU ARE FEELING SYMPTOMS OF CO
POISONING, EV
e Department. If not, pr
the Fir
button again and keep ventilating your
Relocate your Alarm. If frequent alarms continue,
have home rechecked for potential CO problems.
You may be experiencing an intermittent CO
problem.
oducts do not have the right to alter, modify
m 7 years after installation. Please write the date in
ovided:
____________/___________Month/Year
Printed in Mexico M08-0206-003 S 08/10
eplacement. See “Limited
er for r
TE your home and call 911 or
ACUA
oduct, use on impr
6
ess the T
est/Silence
home.
oper
.