864 HH
Fireplace
Featuring the
Burner
Tested and Listed by
OMNI-Test Laboratories, Inc.
Beaverton, Oregon
Report # 028-F-59b-5
ANSI Z21.88b-2003
• Built-In Direct Vent Fireplace
• Natural Gas or Propane
• Residential or Mobile Home
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
-Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone in your building.
•Immediately call gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
•If you cannot reach your gas supplier, call the fire department.
-Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is supplied with the appliance.
Installation Manual
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
Copyright 2008, T.I. |
$10.00 |
100-01182_003 |
4080214 |
4800 Harbour Pointe Blvd. SW |
Mukilteo, WA 98275 |
2 |
Introduction |
|
Overview |
|
|
This manual details the installation |
|
|
requirements for the 864 HH (Home Heater) |
|
|
fireplace. For operating and maintenance |
|
|
instructions, refer to the 864 HH Owner's Manual |
|
|
(part # 100-01181). |
|
|
Listing Details |
|
|
This appliance was listed by OMNI-Test |
|
|
Laboratories, Inc. to ANSI Z21.88 - report # 028- |
|
|
F-59b-5. The listing label is attached to the |
|
|
appliance near the gas control valve. A copy is |
|
|
shown to the right. |
|
|
IAS (ICBO) Approval |
|
|
This appliance was listed by OMNI-Test |
|
|
Laboratories, Inc. - IAS # TL130 (previously |
|
|
ICBO). |
|
|
Massachusetts Approval |
|
|
This manual has been submitted to the |
|
|
Massachusetts Board of State Examiners of |
|
|
Plumbers and Gas Fitters |
|
|
National Fireplace |
Institute |
|
© Travis Industries |
4080214 |
100-01182_003 |
Table of Contents |
3 |
Introduction |
|
Overview................................................................. |
2 |
Listing Details.......................................................... |
2 |
Safety Precautions |
|
Safety Precautions................................................... |
4 |
Features and Specifications |
|
Features................................................................. |
6 |
Installation Options................................................... |
6 |
Heating Specifications .............................................. |
6 |
Dimensions............................................................. |
6 |
Installation |
|
Packing List............................................................. |
7 |
Additional Items Required.......................................... |
7 |
Installation Overview................................................. |
7 |
Recommended Installation Procedure ......................... |
7 |
............................................................................. |
8 |
Converting the Fireplace to Top Vent Configuration.... |
9 |
Fireplace Placement Requirements............................. |
11 |
Clearances........................................................... |
11 |
Raised Fireplaces ................................................. |
11 |
Min. Framing Dims. - Rear Vent Configuration........... |
12 |
Min. Framing Dims. - Top Vent Configuration ............ |
13 |
Nailing Brackets.................................................... |
14 |
Corner Installations - Rear Vent Configuration........... |
15 |
Corner Installations - Top Vent Configuration............. |
16 |
Gas Line Requirements............................................. |
17 |
Fuel .................................................................... |
17 |
Gas Line Connection ............................................. |
17 |
Gas Inlet Pressure ................................................ |
17 |
Gas Line Location ................................................. |
17 |
Electrical Connection (required).................................. |
19 |
Wall Switch or Thermostat Installation ......................... |
20 |
Wiring Diagram (Millivolt System) ............................ |
20 |
Wall Switch Installation........................................... |
20 |
Vent Requirements................................................... |
21 |
Vent Clearances ................................................... |
21 |
Altitude Considerations .......................................... |
21 |
Approved Vent...................................................... |
22 |
Vent Installation.................................................... |
22 |
Approved Vent Configurations.................................... |
23 |
Restrictor Position................................................. |
23 |
Exhaust Restrictor Adjustment................................ |
23 |
Intake Restrictor Adjustment................................... |
24 |
Diffuser Plate Adjustment....................................... |
25 |
Rear Vent Config. W Horizontal Term. (no vertical rise) . 26 |
|
Rear Vent Config. W Horizontal Term. (w vertical rise)... |
27 |
Rear Vent Configuration with Vertical Termination.......... |
28 |
Top Vent Configuration with Horizontal Termination........ |
29 |
Top Vent Configuration with Vertical Termination ........... |
30 |
Termination Requirements......................................... |
31 |
Installation (continued) |
|
Hearth Requirements ............................................... |
32 |
Facing Requirements ............................................... |
33 |
Drywall Installation ................................................ |
33 |
Facing Overview ................................................... |
34 |
Optional Faceplates – Sizing Chart.......................... |
34 |
Thin Facing Installation.......................................... |
35 |
Thick Facing Installation......................................... |
37 |
Thick Facing Installation with FPX Arched Faces........ |
38 |
Mantel Requirements................................................ |
40 |
Install Example - Build-Out (Dog-House) w Hor. Term.... |
41 |
Install Example - Build-In w Hor. Term......................... |
42 |
Finalizing the Installation |
|
Steps for Finalizing the Installation ............................. |
43 |
Starting the Pilot Flame ......................................... |
43 |
Pilot Flame Inspection........................................... |
43 |
Air Shutter Adjustment........................................... |
44 |
Glass Frame Removal and Installation........................ |
45 |
Fireback and Grate Installation................................... |
47 |
Log Set Installation .................................................. |
48 |
LP Conversion Instructions ....................................... |
52 |
Optional Equipment |
|
Grill Installation........................................................ |
55 |
Remote Control Receiver Installation (2 Options) ......... |
56 |
Extra Room Power Heat Duct .................................... |
57 |
Accent Light Installation (sku 94400100)................... |
64 |
Index |
|
Index...................................................................... |
68 |
© Travis Industries |
4080214 |
100-01182_003 |
4 |
Safety Precautions |
Safety Warnings:
•Failure to follow all of the requirements may result in property damage, bodily injury, or even death.
•This unit must be installed by a qualified installer to prevent the possibility of an explosion.
•This appliance must be installed in accordance with all local codes, if any; if not, in U.S.A. follow ANSI Z223.1 and NFPA 54(88).
•In Manufactured or Mobile Homes must confirm with: In USA, Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a standard is not applicable, the Standard for Manufactured Home Installations, ANSI/NCSBCS A225.1. This appliance may be installed in Manufactured Housing only after the home is site located.
•All exhaust gases must be vented outside the structure of the living-area. Combustion air is drawn from outside the living-area structure.
•Notify your insurance company before hooking up this fireplace.
•The room heater should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
•The instructions in this manual must be strictly adhered to. Do not use makeshift methods or compromise in the installation. Improper installation will void the warranty and safety listing.
•This heater is approved for use with natural gas (NG) or propane (LP). Burning the incorrect fuel will void the warranty and safety listing and may cause an extreme safety hazard. Direct questions about the type of fuel used to your dealer. Check the label and flame adjust knob on the gas control valve.
•Contact your local building officials to obtain a permit and information on any installation restrictions or inspection requirements in your area.
•If the flame becomes sooty, dark orange in color, or extremely tall, do not operate the heater. Call your dealer and arrange for proper servicing.
•It is imperative that control compartments, screens, or circulating air passageways of the heater be kept clean and free of obstructions. These areas provide the air necessary for safe operation.
•Do not operate the heater if it is not operating properly in any fashion or if you are uncertain. Call your dealer for a full explanation of your heater and what to expect.
•Do not store or use gasoline or other flammable liquids in the vicinity of this heater.
•Do not operate if any portion of the heater was submerged in water or if any corrosion occurs.
•Do not place clothing or other flammable items on or near the heater. Because this heater can be controlled by a thermostat there is a possibility of the heater turning on and igniting any items placed on or near it.
•Light the heater using the built-in piezo igniter. Do not use matches or any other external device to light your heater.
•Never remove, replace, modify or substitute any part of the heater unless instructions are given in this manual. All other work must be done by a trained technician. Don't modify or replace orifices.
•The viewing glass should be opened only for lighting the pilot or conducting service.
•Any safety screen or guard removed for servicing must be replaced prior to operating the heater.
© Travis Industries |
4080214 |
100-01182_003 |
Safety Precautions |
5 |
Safety Warnings (continued):
•Allow the heater to cool before carrying out any maintenance or cleaning.
•Operate the heater according to the instructions included in this manual.
•If the main burners do not start correctly turn the gas off at the gas control valve and call your dealer for service.
•The pilot flame must contact the thermopile and thermocouple. If it does not, turn the gas control valve to "OFF" and call your dealer.
•This unit is not for use with solid fuel.
•Do not place anything inside the firebox (except the included logs).
•If the fiber logs become damaged, replace with Travis Industries log set.
•Do not throw this manual away. This manual has important operating and maintenance instructions that you will need at a later time. Always follow the instructions in this manual.
•Do not touch the hot surfaces of the heater. Educate all children of the danger of a high-temperature heater. Young children should be supervised when they are in the same room as the heater.
•Due to the high temperature, the heater should be located out of traffic and away from furniture and draperies.
•Instruct everyone in the house how to shut gas off to the appliance and at the gas main shutoff valve. The gas main shutoff valve is usually next to the gas meter or propane tank and requires a wrench to shut off.
•Travis Industries, Inc. grants no warranty, implied or stated, for the installation or maintenance of your heater, and assumes no responsibility of any consequential damage(s).
© Travis Industries |
4080214 |
100-01182_003 |
6 |
Features and Specifications |
Installation Options
• Residential or Mobile Home |
• |
Raised or Floor Placement |
|
• |
Straight or Corner Placement |
• |
Internal or External Chase |
• |
Flush or Recessed Face |
• |
Horizontal or Vertical Vent |
|
|
• |
Bedroom Approved |
Heating Specifications
|
Natural Gas |
Propane |
Approximate Heating Capacity (in square feet)* |
1,200 to 2,250 |
1,200 to 2,250 |
Maximum BTU Input Per Hour |
40,000 |
39,000 |
Steady State Efficiency** (with blowers on) |
Up to 80 % |
Up to 81 % |
*Heating capacity will vary with floor plan, insulation, and outside temperature.
**Efficiency rating is a product thermal efficiency rating determined under continuous operation independent of installed system.
Dimensions
Top Vent Configuration |
Optional "Extra Room |
|
8" Diameter Vent |
Power Heat Duct" |
Weight: 225 Lbs. |
|
Connection |
1-1/2" |
|
|
|
|
7-1/4" |
Rear Vent Configuration |
|
|
|
38-1/4" |
|
8" Diameter Vent |
|
|
38-3/8" |
|
|
36-3/4" |
|
|
35-1/4" |
37"
|
|
of |
Fireplace |
|
|
|
|
|
|
|
|
Back |
|
|
|
|
|
|
|
1" |
|
|
30-3/4" |
|
|
|
|
|
|
|
|
|
|
|
29-1/4"*
41"
19-3/4"*
* Includes the required 1/2" clearance.
© Travis Industries |
4080214 |
100-01182_003 |
|
|
Installation (for qualified installers only) |
7 |
|
|
|
Packing List |
|
|
|
|
|
• |
Propane Conversion Kit |
• Wall Switch with Wire (see page 20 for details) |
|
|
|
• |
Log Set (9 piece) |
• Firestop (sku 93006094 |
|
|
•Grate
Additional Items Required
• FIREBACKS ARE REQUIRED – See page 47. (sku 98500662, 98500663, 98500664, or 98500665)
•Direct Vent
•Gas Line Equipment (shutoff valve, pipe, etc.)
•Electrical Equipment (min. 14 gauge, grounded line)
•Grill or Face
Installation Overview
•All requirements below must be met.
Top Vent
Configuration
See the section "Mantel Requirements"
|
Drywall |
|
Drywall |
Side |
1" Min. |
Wall |
|
See "Facing
Requirements" |
See "Optional Non- |
|
|
|
Combustible Hearth" |
|
See the section |
|
"Electrical Connection" |
See the section |
Rear Vent |
|
|
Configuration |
|
||
"Vent Requirements" |
|
||
Required |
Travis |
||
|
|||
See the section |
Firestop (sku |
||
93006094) |
|
||
"Approved Vent |
|
||
|
|
||
Configurations" |
|
|
|
Insulation must not fill |
|
|
|
the 1/2" clearance |
|
|
|
around the back and |
|
|
|
sides of the fireplace. |
|
|
|
Nailing Brackets |
|
|
|
See the section "Minimum |
|
|
|
Framing Dimensions" |
|
|
|
See the section |
|
|
|
"Gas Line Installation" |
|
|
Recommended Installation Procedure
•Frame the opening for the fireplace. Make sure to allow for vent installation.
•This fireplace is designed to accommodate 1/2" or 5/8" drywall (see "Nailing Brackets" on page 14 for details). Secure the fireplace to the framing.
•Install the vent, gas line and electrical hook-up.
•Install the wall switch (see page 20) or thermostat (if applicable).
•Install the drywall.
•Install the hearth (if applicable).
• |
Install |
the |
facing |
(if |
applicable). |
• |
Install |
the |
mantel |
(if |
applicable). |
•Finalize the installation (see page 43) and install the grill or face.
© Travis Industries |
4080214 |
100-01182_003 |
8 |
Installation (for qualified installers only) |
Massachusetts Requirements
NOTE: The following requirements reference various Massachusetts and national codes not contained in this document.
Requirements for the Commonwealth of Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
Installation ofCarbon MonoxideDetectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon MonoxideDetectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
Signage
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
•The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
•Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
GasEquipmentVenting SystemProvided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
•Detailed instructions for the installation of the venting system design or the venting system components; and
•A complete parts list for the venting system design or venting system.
GasEquipmentVenting SystemNOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
•The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
•The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.
© Travis Industries |
4080214 |
100-01182_003 |
Installation (for qualified installers only) |
9 |
Top Vent or Rear Vent Configuration
This appliance is shipped in the rear vent configuration. To change to the top vent configuration, follow the directions below.
NOTE: the vent configuration affects several aspects of installation (framing, maximum vent rise, maximum vent run). When reviewing the installation requirements make sure to pay attention to the type of configuration being used.
Converting the
Fireplace to Top Vent
Configuration
Remove the 4 screws securing the cover plate. Remove it and place it aside.
Fireplace |
of |
Top |
ofFireplace Back
Remove the 4 screws
securing the cover plate (with
hole).
This part may be discarded.
Remove the 4 screws securing the intake cover plate. Remove it and place it aside.
Remove and discard all of the insulation found near the flue assembly (make sure to remove every piece).
© Travis Industries |
4080214 |
100-01182_003 |
10 |
Installation (for qualified installers only) |
Converting the Fireplace to Top Vent (continued)
NOTE: Use a magnetictipped nutdriver on these screws - take care to prevent the screws from falling into the fireplace.
Remove the 12 screws
securing the flue assembly.
Rotate the flue assembly so the flue points upwards. Secure using the twelve screws removed earlier.
DO NOT OVER-
TIGHTEN THE
SCREWS.
Attach the intake cover plate with the screws removed earlier.
Attach the cover plate with the screws removed earlier.
NOTE: flatten the four legs before insaling the cover plate.
© Travis Industries |
4080214 |
100-01182_003 |
Installation (for qualified installers only) |
11 |
Fireplace Placement Requirements
•The fireplace requires a 1/2" clearance from the angled sides and back of the fireplace to the framing members. No material (insulation, framing, etc.) may be placed into this area.
•Fireplace must be installed on a level surface capable of supporting the fireplace and vent
•Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
•This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance produces when determining a location.
Clearances
•When installed, walls in front of the fireplace must be a minimum 1" to the side of the fireplace.
•Due to the high temperature, the heater should be located out of traffic and away from furniture and draperies.
•Fireplace must be placed so the vents below and above the glass do not become blocked.
Raised Fireplaces
•The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace (225 Lbs.) and vent.
Min. 49”
Fireplace
Enclosure
Height
Platform
Optional Raised Hearth (see “Hearth Requirements” for details)
© Travis Industries |
4080214 |
100-01182_003 |
12 |
Installation (for qualified installers only) |
Minimum Framing Dimensions - Rear Vent Configuration
HINT: place the fireplace so the center line is at least 5" from both vertical framing members at the rear (this allows the vent to pass through the framing without modfications)
Minimum 49” Fireplace
Enclosure Height
Route the
electrical line to
a position to the
left rear of the
38-1/2"
fireplace.
Included Firestop (required)
Part # 93006094
Vent Clearances (8" dia. Vent):
1" to the sides, 1" below, and 3" above the vent to combustibles.
Center of Rear Vent
30-3/4"
38"
25-3/4"
41-1/4" 20"
The on/off switch/thermostat wire (if used) should be routed to a location near the right front of the fireplace.
© Travis Industries |
4080214 |
100-01182_003 |
Installation (for qualified installers only) |
13 |
Minimum Framing Dimensions - Top Vent Configuration
Minimum 49” Fireplace
Enclosure Height
Route the
electrical line to
a position to the
left rear of the
fireplace.
38-1/2"
41-1/4"
20"
The on/off switch/thermostat wire (if used) should be routed to a location near the right front of the fireplace.
© Travis Industries |
4080214 |
100-01182_003 |
14 |
Installation (for qualified installers only) |
Nailing Brackets
There are four nailing brackets on the front of the fireplace. Follow the directions below to prepare the nailing brackets. Once in place, nail or screw the nailing brackets to the framing.
NOTE: Additional nailing brackets are provided along the base of the fireplace. Use these brackets if not using the front brackets.
1/2” Drywall
For installations using
1/2” facing fold the larger
tab out 90° (use a
screwdriver if necessary).
5/8” Drywall
For installations using 5/8” drywall fold the shorter tab out 90° (use a screwdriver if necessary).
Make sure the fireplace is square and plumb when placed in the framing. Measured corner-to- corner, the fireplace should be square (approx. 54-7/8” for each dimension). Use shims to insure the fireplace is square.
TOP VIEW
Framing
Nailing Bracket
Fireplace
Drywall
TOP VIEW
Framing
Nailing Bracket
Fireplace
Drywall
© Travis Industries |
4080214 |
100-01182_003 |
Installation (for qualified installers only) |
15 |
Corner Installations - Rear Vent Configuration
A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply)
|
|
Travis Firestop |
Minimum 1" Clearance |
Minimum 1/2" Clearance |
|
(sku 93006094) |
||
|
|
|
|
|
|
7-1/2" Approximate (varies due to vent installation)
NOTE: Most
installations use:
6" Section for 2x6 Walls
4" Section for 2x4 Walls
(Travis # 98900166)
48" Min.
© Travis Industries |
4080214 |
100-01182_003 |
16 |
Installation (for qualified installers only) |
Corner Installations - Top Vent Configuration
A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply)
Minimum 1/2" Clearance
15-1/2"
48" Min.
© Travis Industries |
4080214 |
100-01182_003 |
Installation (for qualified installers only) |
17 |
Gas Line Requirements
MASSACHUSETTS INSTALLATIONS - WARNING:
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE COMMONWEALTH OF MASSACHUSETTS.
OTHER MASSACHUSETTS CODE REQUIREMENTS:
•Flexible connector must not be longer than 36 inches.
•Shutoff valve must be a “T” handle gas cock.
•Only direct vent sealed combustion products are approved for bedrooms or bathrooms.
•Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas log.
•A carbon monoxide (CO) detector is required in the same room as the appliance.
•The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and the requirements listed below.
•The fireplace and gas control valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig, isolate the gas supply piping by closing the manual shutoff valve.
•Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
Fuel
•This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on the top of the gas control valve to make sure the correct fuel is used.
Gas Line Connection
•Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a licensed plumber/gasfitter).
Gas Inlet Pressure |
Standard Input Pressure |
Minimum Input Pressure |
Maximum Input Pressure |
|
|
|
|
|
|
|
|
Natural Gas |
7" W.C. (1.74 kPA) |
3.5" W.C. (0.87 kPA) |
13.85" W.C. (3.45 kPA) |
Propane |
13" W.C. (2.73 kPA) |
8" W.C. (1.99 kPA) |
14" W.C. (3.48 kPA) |
•If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately adjusted, and the total gas load for the residence does not exceed the amount supplied.
•The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.
© Travis Industries |
4080214 |
100-01182_003 |
18 |
Installation (for qualified installers only) |
Gas Line Location
Left Side Gas Inlet (preferred)
A 2" high by 3" wide opening is located behind the gas inlet cover plate (it is 2" above the base of the fireplace).
The Gas Inlet is 3/8" FPT
6-3/4"
You may remove this cover plate to install the gas line. The cover plate has a 7/8" diameter hole (covered with a push plug). By rotating the plate 180° the hole may be re-located. You may also secure the plate in a customized location using the self-drilling screws.
Right Side Gas Inlet
A 12" flex tube and shutoff valve is included with the fireplace. The shutoff valve accepts a 1/2"MPT.
A 2" high by 3" wide opening is located behind the gas inlet cover plate (it is 1-3/8" above the base of the fireplace).
The Gas Inlet is 3/8" FPT
6-1/4"
18"
A 12" flex tube and shutoff valve is included with the fireplace. The shutoff valve accepts a 1/2"MPT.
You may remove this cover plate to install the gas line. The cover plate has a 7/8" diameter hole (covered with a push plug) in line with the gas inlet on the gas control valve. By rotating the plate 180° the hole may be re-located. You may also secure the plate in a customized location using the selfdrilling screws.
© Travis Industries |
4080214 |
100-01182_003 |
Installation (for qualified installers only) |
19 |
Electrical Connection (required)
•The electrical line to the grounded receptacle inside the fireplace must be installed by a qualified installer and must meet all local codes.
•Make sure the household breaker is shut off prior to working on any electrical lines.
•The fireplace must be properly grounded in accordance with local codes (or ANSI/NFPA 70-1987)
•The electrical line must be a min. 14 gauge, and supply 120 Volts at 60 Hz (2 Amps)
Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Left Side of Fireplace
Grounded Receptacle
Junction Box Assembly
Receptacle Cover Plate
Grounded 110V |
|
Power Supply |
Strain Relief |
© Travis Industries |
4080214 |
100-01182_003 |
20 |
Installation (for qualified installers only) |
Wall Switch or Thermostat Installation
Wiring Diagram (Millivolt System)
Do not connect 110-120 VAC to the gas control valve or wiring system of this fireplace. The switch must be installed by a qualified installer.
The included wall switch may be installed following the directions below. An optional thermostat may also be installed. It is attached to the gas control valve in the same manner.
Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
|
Thermocouple |
Thermopile |
Piezo Igniter |
On/Off Switch (on fireplace) |
|
|
|
Red |
Brown |
|
|
|
Copper Co-Axial |
|
|
|
Wire |
|
|
|
|
|
Orange |
|
Red |
|
Spark Electrode |
|
White |
|
Pilot Hood |
|
|
|
|
|
|
Optional Wall Switch, |
|
|
|
Thermostat, or |
|
|
|
Remote Control |
|
Wall Switch Installation
1. Attach the included wire to the gas control valve.
Attach the two wires to the top and bottom posts on the gas control valve (orientation does not matter).
2.Determine a location for the wall switch (the wire is a maximum 25' long). Route the wire through the gas inlet hole (either side) to the junction box and attach following the directions below. Set the on/off switch on the appliance to "OFF" to control the appliance with the wall switch.
Insert the wire
a through the back of the mounted junction box (your junction box may look different). Expose 1/2" of each wire. Secure the wires to the posts on the side of the on/off switch (orientation does not matter).
From
Appliance
Standard
Screwdriver
Carefully pack the wires into the b junction box. Attach the switch
to the junction box. Attach the switchplate to the switch.
Standard
Screwdriver
© Travis Industries |
4080214 |
100-01182_003 |
Installation (for qualified installers only) |
21 |
Vent Requirements
•The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas appliance must use it's own separate vent system.
•In addition to the requirements listed here, follow the requirements provided with the vent.
•A firestop is required whenever the vent penetrates a wall, floor, or ceiling (passes through framing members). Horizontal vent less than 48" above the fireplace must use the Travis Firestop (sku 93006094 - it incorporates a 3" clearance above, 1" clearance below and to the sides of the vent). Other penetrations only require a 1" clearance and may use a standard firestop (make sure the required 1" clearance is met).
•Always use the high-wind termination (if available from the vent manufacturer).
Vent Clearances
•The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill air spaces with insulation.
|
Before 48" Rise |
After 48" Rise |
Sides |
1" |
1" |
Above |
3" |
1" |
Below Horizontal or 45° Section |
1" |
1" |
Vertical Termination
Use a roof flashing and storm collar whenever passing through the roof
Use a firestop whenever passing through a ceiling
Use a support box on exposed vent
Required Firestop
Min. 1"
Horizontal
Termination
Min. 3"
(1" if a minimum 48" above the fireplace)
Min. 1"
Min. 1"
Altitude Considerations
•This heater has been tested at altitudes ranging from sea level to 6,000 feet. In this testing we have found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
•Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard. Consult your dealer or installer if you suspect an improperly adjusted air shutter.
© Travis Industries |
4080214 |
100-01182_003 |