FireplaceXtrordinair 864 HH User Manual

0 (0)

864 HH

Fireplace

Featuring the

Burner

Tested and Listed by

OMNI-Test Laboratories, Inc.

Beaverton, Oregon

Report # 028-F-59b-5

ANSI Z21.88b-2003

Built-In Direct Vent Fireplace

Natural Gas or Propane

Residential or Mobile Home

WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

-Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

If you cannot reach your gas supplier, call the fire department.

-Installation and service must be performed by a qualified installer, service agency or the gas supplier.

This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.

This appliance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is supplied with the appliance.

Installation Manual

INSTALLER: Leave this manual with the appliance.

CONSUMER: Retain this manual for future reference.

Copyright 2008, T.I.

$10.00

100-01182_003

4080214

4800 Harbour Pointe Blvd. SW

Mukilteo, WA 98275

FireplaceXtrordinair 864 HH User Manual

2

Introduction

 

Overview

 

 

This manual details the installation

 

requirements for the 864 HH (Home Heater)

 

fireplace. For operating and maintenance

 

instructions, refer to the 864 HH Owner's Manual

 

(part # 100-01181).

 

 

Listing Details

 

 

This appliance was listed by OMNI-Test

 

Laboratories, Inc. to ANSI Z21.88 - report # 028-

 

F-59b-5. The listing label is attached to the

 

appliance near the gas control valve. A copy is

 

shown to the right.

 

 

IAS (ICBO) Approval

 

This appliance was listed by OMNI-Test

 

Laboratories, Inc. - IAS # TL130 (previously

 

ICBO).

 

 

Massachusetts Approval

 

This manual has been submitted to the

 

Massachusetts Board of State Examiners of

 

Plumbers and Gas Fitters

 

 

National Fireplace

Institute

 

© Travis Industries

4080214

100-01182_003

Table of Contents

3

Introduction

 

Overview.................................................................

2

Listing Details..........................................................

2

Safety Precautions

 

Safety Precautions...................................................

4

Features and Specifications

 

Features.................................................................

6

Installation Options...................................................

6

Heating Specifications ..............................................

6

Dimensions.............................................................

6

Installation

 

Packing List.............................................................

7

Additional Items Required..........................................

7

Installation Overview.................................................

7

Recommended Installation Procedure .........................

7

.............................................................................

8

Converting the Fireplace to Top Vent Configuration....

9

Fireplace Placement Requirements.............................

11

Clearances...........................................................

11

Raised Fireplaces .................................................

11

Min. Framing Dims. - Rear Vent Configuration...........

12

Min. Framing Dims. - Top Vent Configuration ............

13

Nailing Brackets....................................................

14

Corner Installations - Rear Vent Configuration...........

15

Corner Installations - Top Vent Configuration.............

16

Gas Line Requirements.............................................

17

Fuel ....................................................................

17

Gas Line Connection .............................................

17

Gas Inlet Pressure ................................................

17

Gas Line Location .................................................

17

Electrical Connection (required)..................................

19

Wall Switch or Thermostat Installation .........................

20

Wiring Diagram (Millivolt System) ............................

20

Wall Switch Installation...........................................

20

Vent Requirements...................................................

21

Vent Clearances ...................................................

21

Altitude Considerations ..........................................

21

Approved Vent......................................................

22

Vent Installation....................................................

22

Approved Vent Configurations....................................

23

Restrictor Position.................................................

23

Exhaust Restrictor Adjustment................................

23

Intake Restrictor Adjustment...................................

24

Diffuser Plate Adjustment.......................................

25

Rear Vent Config. W Horizontal Term. (no vertical rise) . 26

Rear Vent Config. W Horizontal Term. (w vertical rise)...

27

Rear Vent Configuration with Vertical Termination..........

28

Top Vent Configuration with Horizontal Termination........

29

Top Vent Configuration with Vertical Termination ...........

30

Termination Requirements.........................................

31

Installation (continued)

 

Hearth Requirements ...............................................

32

Facing Requirements ...............................................

33

Drywall Installation ................................................

33

Facing Overview ...................................................

34

Optional Faceplates – Sizing Chart..........................

34

Thin Facing Installation..........................................

35

Thick Facing Installation.........................................

37

Thick Facing Installation with FPX Arched Faces........

38

Mantel Requirements................................................

40

Install Example - Build-Out (Dog-House) w Hor. Term....

41

Install Example - Build-In w Hor. Term.........................

42

Finalizing the Installation

 

Steps for Finalizing the Installation .............................

43

Starting the Pilot Flame .........................................

43

Pilot Flame Inspection...........................................

43

Air Shutter Adjustment...........................................

44

Glass Frame Removal and Installation........................

45

Fireback and Grate Installation...................................

47

Log Set Installation ..................................................

48

LP Conversion Instructions .......................................

52

Optional Equipment

 

Grill Installation........................................................

55

Remote Control Receiver Installation (2 Options) .........

56

Extra Room Power Heat Duct ....................................

57

Accent Light Installation (sku 94400100)...................

64

Index

 

Index......................................................................

68

© Travis Industries

4080214

100-01182_003

4

Safety Precautions

Safety Warnings:

Failure to follow all of the requirements may result in property damage, bodily injury, or even death.

This unit must be installed by a qualified installer to prevent the possibility of an explosion.

This appliance must be installed in accordance with all local codes, if any; if not, in U.S.A. follow ANSI Z223.1 and NFPA 54(88).

In Manufactured or Mobile Homes must confirm with: In USA, Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a standard is not applicable, the Standard for Manufactured Home Installations, ANSI/NCSBCS A225.1. This appliance may be installed in Manufactured Housing only after the home is site located.

All exhaust gases must be vented outside the structure of the living-area. Combustion air is drawn from outside the living-area structure.

Notify your insurance company before hooking up this fireplace.

The room heater should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.

The instructions in this manual must be strictly adhered to. Do not use makeshift methods or compromise in the installation. Improper installation will void the warranty and safety listing.

This heater is approved for use with natural gas (NG) or propane (LP). Burning the incorrect fuel will void the warranty and safety listing and may cause an extreme safety hazard. Direct questions about the type of fuel used to your dealer. Check the label and flame adjust knob on the gas control valve.

Contact your local building officials to obtain a permit and information on any installation restrictions or inspection requirements in your area.

If the flame becomes sooty, dark orange in color, or extremely tall, do not operate the heater. Call your dealer and arrange for proper servicing.

It is imperative that control compartments, screens, or circulating air passageways of the heater be kept clean and free of obstructions. These areas provide the air necessary for safe operation.

Do not operate the heater if it is not operating properly in any fashion or if you are uncertain. Call your dealer for a full explanation of your heater and what to expect.

Do not store or use gasoline or other flammable liquids in the vicinity of this heater.

Do not operate if any portion of the heater was submerged in water or if any corrosion occurs.

Do not place clothing or other flammable items on or near the heater. Because this heater can be controlled by a thermostat there is a possibility of the heater turning on and igniting any items placed on or near it.

Light the heater using the built-in piezo igniter. Do not use matches or any other external device to light your heater.

Never remove, replace, modify or substitute any part of the heater unless instructions are given in this manual. All other work must be done by a trained technician. Don't modify or replace orifices.

The viewing glass should be opened only for lighting the pilot or conducting service.

Any safety screen or guard removed for servicing must be replaced prior to operating the heater.

© Travis Industries

4080214

100-01182_003

Safety Precautions

5

Safety Warnings (continued):

Allow the heater to cool before carrying out any maintenance or cleaning.

Operate the heater according to the instructions included in this manual.

If the main burners do not start correctly turn the gas off at the gas control valve and call your dealer for service.

The pilot flame must contact the thermopile and thermocouple. If it does not, turn the gas control valve to "OFF" and call your dealer.

This unit is not for use with solid fuel.

Do not place anything inside the firebox (except the included logs).

If the fiber logs become damaged, replace with Travis Industries log set.

Do not throw this manual away. This manual has important operating and maintenance instructions that you will need at a later time. Always follow the instructions in this manual.

Do not touch the hot surfaces of the heater. Educate all children of the danger of a high-temperature heater. Young children should be supervised when they are in the same room as the heater.

Due to the high temperature, the heater should be located out of traffic and away from furniture and draperies.

Instruct everyone in the house how to shut gas off to the appliance and at the gas main shutoff valve. The gas main shutoff valve is usually next to the gas meter or propane tank and requires a wrench to shut off.

Travis Industries, Inc. grants no warranty, implied or stated, for the installation or maintenance of your heater, and assumes no responsibility of any consequential damage(s).

© Travis Industries

4080214

100-01182_003

6

Features and Specifications

Installation Options

Residential or Mobile Home

Raised or Floor Placement

Straight or Corner Placement

Internal or External Chase

Flush or Recessed Face

Horizontal or Vertical Vent

 

 

Bedroom Approved

Heating Specifications

 

Natural Gas

Propane

Approximate Heating Capacity (in square feet)*

1,200 to 2,250

1,200 to 2,250

Maximum BTU Input Per Hour

40,000

39,000

Steady State Efficiency** (with blowers on)

Up to 80 %

Up to 81 %

*Heating capacity will vary with floor plan, insulation, and outside temperature.

**Efficiency rating is a product thermal efficiency rating determined under continuous operation independent of installed system.

Dimensions

Top Vent Configuration

Optional "Extra Room

 

8" Diameter Vent

Power Heat Duct"

Weight: 225 Lbs.

 

Connection

1-1/2"

 

 

 

7-1/4"

Rear Vent Configuration

 

 

38-1/4"

 

8" Diameter Vent

 

 

38-3/8"

 

 

36-3/4"

 

 

35-1/4"

37"

 

 

of

Fireplace

 

 

 

 

 

 

Back

 

 

 

 

 

 

1"

 

 

30-3/4"

 

 

 

 

 

 

 

 

 

 

29-1/4"*

41"

19-3/4"*

* Includes the required 1/2" clearance.

© Travis Industries

4080214

100-01182_003

 

 

Installation (for qualified installers only)

7

 

 

Packing List

 

 

 

 

Propane Conversion Kit

Wall Switch with Wire (see page 20 for details)

 

 

 

Log Set (9 piece)

Firestop (sku 93006094

 

 

Grate

Additional Items Required

FIREBACKS ARE REQUIRED – See page 47. (sku 98500662, 98500663, 98500664, or 98500665)

Direct Vent

Gas Line Equipment (shutoff valve, pipe, etc.)

Electrical Equipment (min. 14 gauge, grounded line)

Grill or Face

Installation Overview

All requirements below must be met.

Top Vent

Configuration

See the section "Mantel Requirements"

 

Drywall

 

Drywall

Side

1" Min.

Wall

 

See "Facing

Requirements"

See "Optional Non-

 

 

Combustible Hearth"

 

See the section

 

"Electrical Connection"

See the section

Rear Vent

 

Configuration

 

"Vent Requirements"

 

Required

Travis

 

See the section

Firestop (sku

93006094)

 

"Approved Vent

 

 

 

Configurations"

 

 

Insulation must not fill

 

 

the 1/2" clearance

 

 

around the back and

 

 

sides of the fireplace.

 

 

Nailing Brackets

 

 

See the section "Minimum

 

 

Framing Dimensions"

 

 

See the section

 

 

"Gas Line Installation"

 

 

Recommended Installation Procedure

Frame the opening for the fireplace. Make sure to allow for vent installation.

This fireplace is designed to accommodate 1/2" or 5/8" drywall (see "Nailing Brackets" on page 14 for details). Secure the fireplace to the framing.

Install the vent, gas line and electrical hook-up.

Install the wall switch (see page 20) or thermostat (if applicable).

Install the drywall.

Install the hearth (if applicable).

Install

the

facing

(if

applicable).

Install

the

mantel

(if

applicable).

Finalize the installation (see page 43) and install the grill or face.

© Travis Industries

4080214

100-01182_003

8

Installation (for qualified installers only)

Massachusetts Requirements

NOTE: The following requirements reference various Massachusetts and national codes not contained in this document.

Requirements for the Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

Installation ofCarbon MonoxideDetectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon MonoxideDetectors

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight

(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

GasEquipmentVenting SystemProvided

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

Detailed instructions for the installation of the venting system design or the venting system components; and

A complete parts list for the venting system design or venting system.

GasEquipmentVenting SystemNOT Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

See Gas Connection section for additional Commonwealth of Massachusetts requirements.

© Travis Industries

4080214

100-01182_003

Installation (for qualified installers only)

9

Top Vent or Rear Vent Configuration

This appliance is shipped in the rear vent configuration. To change to the top vent configuration, follow the directions below.

NOTE: the vent configuration affects several aspects of installation (framing, maximum vent rise, maximum vent run). When reviewing the installation requirements make sure to pay attention to the type of configuration being used.

Converting the

Fireplace to Top Vent

Configuration

Remove the 4 screws securing the cover plate. Remove it and place it aside.

Fireplace

of

Top

ofFireplace Back

Remove the 4 screws

securing the cover plate (with

hole).

This part may be discarded.

Remove the 4 screws securing the intake cover plate. Remove it and place it aside.

Remove and discard all of the insulation found near the flue assembly (make sure to remove every piece).

© Travis Industries

4080214

100-01182_003

10

Installation (for qualified installers only)

Converting the Fireplace to Top Vent (continued)

NOTE: Use a magnetictipped nutdriver on these screws - take care to prevent the screws from falling into the fireplace.

Remove the 12 screws

securing the flue assembly.

Rotate the flue assembly so the flue points upwards. Secure using the twelve screws removed earlier.

DO NOT OVER-

TIGHTEN THE

SCREWS.

Attach the intake cover plate with the screws removed earlier.

Attach the cover plate with the screws removed earlier.

NOTE: flatten the four legs before insaling the cover plate.

© Travis Industries

4080214

100-01182_003

Installation (for qualified installers only)

11

Fireplace Placement Requirements

The fireplace requires a 1/2" clearance from the angled sides and back of the fireplace to the framing members. No material (insulation, framing, etc.) may be placed into this area.

Fireplace must be installed on a level surface capable of supporting the fireplace and vent

Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)

This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance produces when determining a location.

Clearances

When installed, walls in front of the fireplace must be a minimum 1" to the side of the fireplace.

Due to the high temperature, the heater should be located out of traffic and away from furniture and draperies.

Fireplace must be placed so the vents below and above the glass do not become blocked.

Raised Fireplaces

The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace (225 Lbs.) and vent.

Min. 49”

Fireplace

Enclosure

Height

Platform

Optional Raised Hearth (see “Hearth Requirements” for details)

© Travis Industries

4080214

100-01182_003

12

Installation (for qualified installers only)

Minimum Framing Dimensions - Rear Vent Configuration

HINT: place the fireplace so the center line is at least 5" from both vertical framing members at the rear (this allows the vent to pass through the framing without modfications)

Minimum 49” Fireplace

Enclosure Height

Route the

electrical line to

a position to the

left rear of the

38-1/2"

fireplace.

Included Firestop (required)

Part # 93006094

Vent Clearances (8" dia. Vent):

1" to the sides, 1" below, and 3" above the vent to combustibles.

Center of Rear Vent

30-3/4"

38"

25-3/4"

41-1/4" 20"

The on/off switch/thermostat wire (if used) should be routed to a location near the right front of the fireplace.

© Travis Industries

4080214

100-01182_003

Installation (for qualified installers only)

13

Minimum Framing Dimensions - Top Vent Configuration

Minimum 49” Fireplace

Enclosure Height

Route the

electrical line to

a position to the

left rear of the

fireplace.

38-1/2"

41-1/4"

20"

The on/off switch/thermostat wire (if used) should be routed to a location near the right front of the fireplace.

© Travis Industries

4080214

100-01182_003

14

Installation (for qualified installers only)

Nailing Brackets

There are four nailing brackets on the front of the fireplace. Follow the directions below to prepare the nailing brackets. Once in place, nail or screw the nailing brackets to the framing.

NOTE: Additional nailing brackets are provided along the base of the fireplace. Use these brackets if not using the front brackets.

1/2” Drywall

For installations using

1/2” facing fold the larger

tab out 90° (use a

screwdriver if necessary).

5/8” Drywall

For installations using 5/8” drywall fold the shorter tab out 90° (use a screwdriver if necessary).

Make sure the fireplace is square and plumb when placed in the framing. Measured corner-to- corner, the fireplace should be square (approx. 54-7/8” for each dimension). Use shims to insure the fireplace is square.

TOP VIEW

Framing

Nailing Bracket

Fireplace

Drywall

TOP VIEW

Framing

Nailing Bracket

Fireplace

Drywall

© Travis Industries

4080214

100-01182_003

Installation (for qualified installers only)

15

Corner Installations - Rear Vent Configuration

A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply)

 

 

Travis Firestop

Minimum 1" Clearance

Minimum 1/2" Clearance

(sku 93006094)

 

 

 

 

 

 

7-1/2" Approximate (varies due to vent installation)

NOTE: Most

installations use:

6" Section for 2x6 Walls

4" Section for 2x4 Walls

(Travis # 98900166)

48" Min.

© Travis Industries

4080214

100-01182_003

16

Installation (for qualified installers only)

Corner Installations - Top Vent Configuration

A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply)

Minimum 1/2" Clearance

15-1/2"

48" Min.

© Travis Industries

4080214

100-01182_003

Installation (for qualified installers only)

17

Gas Line Requirements

MASSACHUSETTS INSTALLATIONS - WARNING:

THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE COMMONWEALTH OF MASSACHUSETTS.

OTHER MASSACHUSETTS CODE REQUIREMENTS:

Flexible connector must not be longer than 36 inches.

Shutoff valve must be a “T” handle gas cock.

Only direct vent sealed combustion products are approved for bedrooms or bathrooms.

Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas log.

A carbon monoxide (CO) detector is required in the same room as the appliance.

The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and the requirements listed below.

The fireplace and gas control valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig, isolate the gas supply piping by closing the manual shutoff valve.

Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.

Fuel

This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on the top of the gas control valve to make sure the correct fuel is used.

Gas Line Connection

Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a licensed plumber/gasfitter).

Gas Inlet Pressure

Standard Input Pressure

Minimum Input Pressure

Maximum Input Pressure

 

 

 

 

 

 

 

Natural Gas

7" W.C. (1.74 kPA)

3.5" W.C. (0.87 kPA)

13.85" W.C. (3.45 kPA)

Propane

13" W.C. (2.73 kPA)

8" W.C. (1.99 kPA)

14" W.C. (3.48 kPA)

If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately adjusted, and the total gas load for the residence does not exceed the amount supplied.

The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.

© Travis Industries

4080214

100-01182_003

18

Installation (for qualified installers only)

Gas Line Location

Left Side Gas Inlet (preferred)

A 2" high by 3" wide opening is located behind the gas inlet cover plate (it is 2" above the base of the fireplace).

The Gas Inlet is 3/8" FPT

6-3/4"

You may remove this cover plate to install the gas line. The cover plate has a 7/8" diameter hole (covered with a push plug). By rotating the plate 180° the hole may be re-located. You may also secure the plate in a customized location using the self-drilling screws.

Right Side Gas Inlet

A 12" flex tube and shutoff valve is included with the fireplace. The shutoff valve accepts a 1/2"MPT.

A 2" high by 3" wide opening is located behind the gas inlet cover plate (it is 1-3/8" above the base of the fireplace).

The Gas Inlet is 3/8" FPT

6-1/4"

18"

A 12" flex tube and shutoff valve is included with the fireplace. The shutoff valve accepts a 1/2"MPT.

You may remove this cover plate to install the gas line. The cover plate has a 7/8" diameter hole (covered with a push plug) in line with the gas inlet on the gas control valve. By rotating the plate 180° the hole may be re-located. You may also secure the plate in a customized location using the selfdrilling screws.

© Travis Industries

4080214

100-01182_003

Installation (for qualified installers only)

19

Electrical Connection (required)

The electrical line to the grounded receptacle inside the fireplace must be installed by a qualified installer and must meet all local codes.

Make sure the household breaker is shut off prior to working on any electrical lines.

The fireplace must be properly grounded in accordance with local codes (or ANSI/NFPA 70-1987)

The electrical line must be a min. 14 gauge, and supply 120 Volts at 60 Hz (2 Amps)

Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

Left Side of Fireplace

Grounded Receptacle

Junction Box Assembly

Receptacle Cover Plate

Grounded 110V

 

Power Supply

Strain Relief

© Travis Industries

4080214

100-01182_003

20

Installation (for qualified installers only)

Wall Switch or Thermostat Installation

Wiring Diagram (Millivolt System)

Do not connect 110-120 VAC to the gas control valve or wiring system of this fireplace. The switch must be installed by a qualified installer.

The included wall switch may be installed following the directions below. An optional thermostat may also be installed. It is attached to the gas control valve in the same manner.

Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

 

Thermocouple

Thermopile

Piezo Igniter

On/Off Switch (on fireplace)

 

 

Red

Brown

 

 

 

Copper Co-Axial

 

 

 

Wire

 

 

 

 

 

Orange

 

Red

 

Spark Electrode

 

White

 

Pilot Hood

 

 

 

 

 

Optional Wall Switch,

 

 

 

Thermostat, or

 

 

 

Remote Control

 

Wall Switch Installation

1. Attach the included wire to the gas control valve.

Attach the two wires to the top and bottom posts on the gas control valve (orientation does not matter).

2.Determine a location for the wall switch (the wire is a maximum 25' long). Route the wire through the gas inlet hole (either side) to the junction box and attach following the directions below. Set the on/off switch on the appliance to "OFF" to control the appliance with the wall switch.

Insert the wire

a through the back of the mounted junction box (your junction box may look different). Expose 1/2" of each wire. Secure the wires to the posts on the side of the on/off switch (orientation does not matter).

From

Appliance

Standard

Screwdriver

Carefully pack the wires into the b junction box. Attach the switch

to the junction box. Attach the switchplate to the switch.

Standard

Screwdriver

© Travis Industries

4080214

100-01182_003

Installation (for qualified installers only)

21

Vent Requirements

The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas appliance must use it's own separate vent system.

In addition to the requirements listed here, follow the requirements provided with the vent.

A firestop is required whenever the vent penetrates a wall, floor, or ceiling (passes through framing members). Horizontal vent less than 48" above the fireplace must use the Travis Firestop (sku 93006094 - it incorporates a 3" clearance above, 1" clearance below and to the sides of the vent). Other penetrations only require a 1" clearance and may use a standard firestop (make sure the required 1" clearance is met).

Always use the high-wind termination (if available from the vent manufacturer).

Vent Clearances

The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill air spaces with insulation.

 

Before 48" Rise

After 48" Rise

Sides

1"

1"

Above

3"

1"

Below Horizontal or 45° Section

1"

1"

Vertical Termination

Use a roof flashing and storm collar whenever passing through the roof

Use a firestop whenever passing through a ceiling

Use a support box on exposed vent

Required Firestop

Min. 1"

Horizontal

Termination

Min. 3"

(1" if a minimum 48" above the fireplace)

Min. 1"

Min. 1"

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 6,000 feet. In this testing we have found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.

Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard. Consult your dealer or installer if you suspect an improperly adjusted air shutter.

© Travis Industries

4080214

100-01182_003

Loading...
+ 47 hidden pages