BG12face.wmf
Description:
The BG-12LA Pull Station is a non-coded manual pull station
which provides a Fire Alarm Control Panel (FACP) with a single
alarm initiating input signal. The pull station also provides a
second set of contacts rated up to 3 Amps at 30 volts (AC or
DC), for auxiliary functions. The BG-12LA is a dual action
model equipped with a key lock reset. It is UL listed and meets
the ADA requirement of a 5-lb. maximum pull down force to
activate. Operating instructions are molded into the handle.
Molded terminal numbers can also be found adjacent to the
wiring terminals.
Mounting
Surface mount the BG-12LA pull station to a SB-10 surface
backbox. Semi-flush mount the BG-12LA to a standard singlegang, double-gang, or 4-inch (10.16 cm) square electrical box.
Dual Action BG-12LA
BG-12LA Manual Pull Station
Document 51381 Revision A ECN 00-215 06/13/2000
UL
Product ID
Label
Door ‘keys’ into
backplate at this point
Post
Hole
Post
Hole
Post
Switch Contact Rating
FACP Circuit (Terminals 1 & 2):
Rated to .25 Amp at 30 Volts (AC or DC).
Auxiliary Contact Circuit (Terminals 3 & 4):
Rated to 3 Amps at 30 Volts (AC or DC).
Door Reattachment
If the door becomes detached, complete the following steps to
reattach the door to the backplate. The door cannot be connected
to the pull station if the unit is mounted to a backbox.
With the door and backplate
aligned and ‘keyed’ together,
slide the holes down onto the
posts.
UL
Product ID
Label
1. Position the door and backplate side
by side in the full open position. (i.e.
180-degrees with respect to each
other.)
2. With the backplate position fixed,
move the door behind the backplate,
as shown in the illustration, part A.
3. Align the hinge posts and holes by
bringing the door up to meet the
backplate, paying particular attention
to the ‘keying’ that occurs when the
door’s post hole is aligned to the
backplate’s hinge post. Refer to the
illustration, part B.
Door mated to Backplate
at this stage.
Closing the door slightly
locks the door and
backplate together.
4. With the two pieces aligned and
12LAdoormount.wmf
‘keyed’ together, slide the holes
down onto the posts. Refer to the
illustration, part C.
5. Holding the backplate, close the door
slightly to lock the door and backplate
together.
Wiring Instructions
Operation
1) Before mounting the pull station, pull all necessary wiring
through the backbox.
2) Remove the correct amount of wire insulation. The pull
station’s backplate is molded with a strip gauge to measure
the amount of insulation to be removed.
3) Connect the wiring from the fire alarm control panel’s
Initiating Device Circuit (IDC), or any previous device on
the IDC to terminals 1 and 2 located on the pull station’s
terminal strip. Connect the next device on the IDC or Endof-Line Resistor (ELR) to terminals 1 and 2. Note: Maintain
consistent polarity with all connections throughout the IDC.
4) Connect the wiring for the normally open (N/O) auxiliary
switch circuit to terminals 3 & 4.
From FACP
IDC
23
23
23
234567
To Next Device
IDC
Aux. Contact
Aux. Contact
To activate the dual-action station, first push in the handle, and
then pull the handle down. The handle locks into the activated
position. The word ‘ACTIVATED’ appears after the handle is
pulled down. The pull station remains in the activated position
until reset with the key lock.
1) Reset the BG-12LA by inserting the key into the lock and
turning it ¼ turn (counter-clockwise).
2) Open the door until the handle returns to the ‘NORMAL’
position.
3) Close and lock the door. Closing the door automatically
resets the switch to the ‘NORMAL’ position. Note: Opening
the pull station door will not activate or deactivate the FACP
alarm switch or the auxiliary function switch.
BG12activated.wmf
12LAwiring.wmf
BG-12LA Pull Station
(Shown Activated)
BG-12LA Wiring
CAUTION
Install the pull station in accordance with the supplied instructions, applicable NFPA standards, national and local Fire and Electrical
codes and the requirements of the Authority Having Jurisdiction (AHJ). Conduct regular testing of the devices using appropriate
NFPA standards. Fire•Lite is not responsible for devices that have not been properly installed, tested or maintained. For ADA
compliance, if the clear floor space only allows forward approach to an object, the maximum forward reach height allowed is
48 inches (121.92cm). If the clear floor space allows parallel approach by a person in a wheelchair, the maximum side reach height
allowed is 54 inches (137.16cm).
Document 51381 Revision A ECN 00-215 06/13/2000