Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/
or inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service,
or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72-1993 Chapter
7 after any programming operation or change in sitespecific software. Reacceptance testing is required after
any change, addition or deletion of system components,
or after any modification, repair or adjustment to system
hardware or wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices
that are not directly affected by the change, up to a
maximum of 50 devices, must be tested and proper
system operation verified.
This system meets NFPA requirements for
operation at 0-49
humidity of 85% RH (non-condensing) at 30O C/86
F. However, the useful life of the system's standby
batteries and the electronic components may be
adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an
environment with a nominal room temperature of 1527O C/60-80O F.
O
C/32-120O F and at a relative
O
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making
modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over
tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always
ground yourself with a proper wrist strap before handling any
circuits so that static charges are removed from the body. Use
static suppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.
Fire Alarm System Limitations
An automatic fire alarm system - typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability can provide early warning of a developing fire. Such
a system, however, does not assure protection against property damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in walls, or roofs, or
on the other side of closed doors. Smoke detectors also may
not sense a fire on another level or floor of a building. A
second floor detector, for example, may not sense a first floor
or basement fire. Furthermore, all types of smoke detectors
- both ionization and photoelectric types, have sensing limitations. No type of smoke detector can sense every kind of
fire caused by carelessness and safety hazards like smoking
in bed, violent explosions, escaping gas, improper storage of
flammable materials, overloaded electrical circuits, children
playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the
system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm
system, crippling its ability to report a fire.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance!
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from
standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise feature
of each detector should be tested at least once per year by
a qualified fire protection specialist.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system
wiring should be tested and maintained by professional fire
alarm installers following written procedures supplied with
each device. System inspection and testing should be scheduled monthly or as required by National and/or local fire codes.
Adequate written records of all inspections should be kept.
Figure 5: Mounting the Trim Ring .............................................................17
Figure 6: Applying the Annunciator Label ................................................17
Figure 7: Ann unciator Options .................................................................18
Figure 8: Main Power Supply Connections ...............................................19
Section Five: Operating the Annunciators ................................................20
Figure 9: Operating the AFM-16ATX........................................................20
Figure 10: Operating the AEM-16ATF......................................................21
Figure 11: Operating the AFM-32AX .......................................................22
Figure 12: Operating the AEM-32AF .......................................................23
Section Six: Annunciators and the Sensiscan 2000 .................................24
Figure 13: Connecting the EIA-485 Loop..................................................24
Figure 14: Configuring Annunciators f or Sensiscan 2000.........................26
Table 6-1: Annunciator Point Functions.....................................................27
Slide-in Labels..................................................................... Center of Manual
15390 Rev D 8/2/96 P/N 15390:D
3
Section One: Annunciators
Fire•Lite annunciator modules provide the Sensiscan 2000 with up to 32 remote serially
connected annunciators, each with a capacity of 64 points.
The annunciator modules provide arrays of LEDs to indicate, at a remote location, the
status of circuits within the system. Annunciator points in a Sensiscan 2000 directly follow
the circuit arrangement of modules installed in the cabinet.
Control of common system functions such as signal silence, system reset, and local
annunciation controls (local acknowledge and lamp test) may be accomplished through
the annunciator's integral membrane push switches.
Communication between the FACP and the annunciators is accomplished over a powerlimited two-wire serial interface employing an EIA-485 communication standard. Power
is provided via a separate power-limited power loop from the control panel which is
inherently supervised by the FACP (loss of power results in an annunciator communication failure at the control panel). The annunciator can also be powered from a remote UL
listed power-limited power supply.
There are two basic annunciator types, alarm and alarm/trouble, each with its own
expander module.
4
15390 Rev D 8/2/96 P/N 15390:D
Section T wo:
Annunciator Inventory
AFM-16ATX
The Annunciator Control Module-16ATX contains 16 red
alarm and 16 yellow trouble LEDs, 16 momentary touch-pad
switches for controlling each point, a system trouble LED,
an ON LINE/POWER LED, and a local piezo sounder with
a silence/acknowledge switch for audible indication of alarm
and trouble conditions at each annunciator.
AEM-16ATF
The Annunciator Expander Module-16ATF expands the
AFM-16ATX by 16 system points. The AEM-16ATF is
identical in size and in frontal appearance to the AFM16ATX. One to three of these expander modules can be
supported by an AFM-16ATX, to a maximum of 64 system
points. Note: The AEM-16ATF cannot be used to expand
the AFM-32AX.
ABM-16ATF
The Annunciator Blank Module-16ATF is a dress plate
identical in appearance to the front panel of the AFM-16ATX
and AEM-16ATF modules. The blank module is used to
cover unused module positions in an annunciator backbox.
AFM-32AX
The Annunciator Control Module-32AX contains 32 red
alarm LEDs, a system trouble LED, an ON LINE/POWER
LED, and a local piezo sounder with a silence/acknowledge
switch for audible indication of alarm and trouble conditions
at each annunciator.
AEM-32AF
The Annunciator Expander Module-32AF expands the AFM32AX by 32 system points. The AEM-32AF is identical in
frontal appearance to the AFM-32AX. One expander module can be supported by an AFM-32AX, providing a maximum of 64 points. Note: The AEM-32AF cannot be used to
expand the AFM-16ATX.
ABM-32AF
The Annunciator Blank Module-32AF is a dress plate identical in appearance to the front panel of the AFM-32AX and
AEM–32AF modules. The blank module is used to cover
unused module positions in an annunciator backbox.
15390 Rev D 8/2/96 P/N 15390:D
5
ABS-1F
The Annunciator Surface Box-1F provides for the remote mounting of a single AFM-16ATX or AFM-32AX annunciator in a surfacemount enclosure. Knockouts are provided for use with 1/2" conduit. The annunciator mounts directly to the ABS-1F without a
dress plate. (H = 8-1/2" W = 4-1/2" D = 1-3/8")
ABS-2F
(not illustrated)
The Annunciator Surface Box-2F provides for the surface mounting of one AFM-16ATX/AEM-16ATF combination or one AFM32AX/AEM-32AF combination. Knockouts are provided for use
with 1/2" conduit. The annunciator module mounts directly to the
ABS-2F without a dress plate. (H=8-1/2" W=8-15/16" D=1-3/8")
Note: The ABS-1F and ABS-2F will not support the installation of
the AKS-1F Annunciator Key Switch.
ABF-1F
The Annunciator Flush Box-1F provides for the
remote mounting of a single AFM-16ATX or
AFM-32AX annunciator in a flush-mount enclosure. Knockouts are provided for use with 1/2"
conduit. The ABF-1F includes a trim plate
(height=11" width=6-1/4"), mounting hardware,
and an adhesive-backed Annunciator Label for
the dress plate. (H = 9-15/16" W = 4-5/8" D =
2-1/2")
ABF-2F
(not illustrated)
The Annunciator Flush Box-2F provides for the
flush mounting of one AFM-16ATX/AEM-16ATF
combination or one AFM-32AX/AEM-32AF combination. Includes a trim plate (H=11" W=10-5/
8") and adhesive-backed Annunciator Label.
(H=9-15/16" W=9-3/16" D=2-1/2")
6
Annunciator Label
15390 Rev D 8/2/96 P/N 15390:D
Annunciator Label
ABF-4F
The Annunciator Flush Box-4F provides for the remote mounting of one to four
AFM-16ATX/AEM-16ATF modules. Knockouts are provided for use with 1/2"
conduit. The flush-mounted ABF-4F includes a trim plate (H=11" W=19-3/8")
and an Annunciator Label. (H=9 - 15/16" W=17 - 3/8" D=2 - 1/2")
AKS-1F
The Annunciator Key Switch-1F provides access security for the control switches
on the AFM-16ATX. The key switch kit includes a key and hardware for mounting
to the trim plate of one of the flush-mount type annunciator enclosures. Also
included is an adhesive-backed Annunciator Label for use with the key switch/
dress plate assembly.
Note: The AKS-1F can only be employed with a flush-mount type backbox.
Annunciator Label
15390 Rev D 8/2/96 P/N 15390:D
7
Section Three:
Design Considerations
Limits
Up to 32 annunciators may be installed on an EIA-485 circuit. The actual number of
annunciator modules may be larger depending on the number of expander modules
employed.
Wire Runs
Communication between the Control Panel and the annunciator is accomplished over a
power-limited two-wire EIA-485 serial interface. This communication, including the
wiring, is supervised by the fire alarm control panel. Power for the annunciators is
provided via a separate power-limited power loop from the control panel which is
inherently supervised (loss of power also results in a communication failure at the control
panel).
Fire Alarm Control Panel
Annunciator Power
(14 to 18 AWG )
Two-wire EIA-485 Circuit
(Maximum of 6,000 feet)
Annunciator
Wiring Specifications
The EIA-485 circuit cannot be T-Tapped; it must be wired in a continuous fashion from
the control panel to the annunciator. The maximum wiring distance between the
panel and the last annunciator is 6,000 feet @ 16 AWG.
The wiring size must be a 14 AWG to 18 AWG twisted
shielded pair cable having a Characteristic Impedance of
120 ohms, +/- 20%. Limit the total wire resistance to 100 ohms on the EIA485 circuit, and 10 ohms on the annunciator power circuit. Do not run cable adjacent to,
or in the same conduit as, 120 volts AC service, noisy electrical circuits that are powering
mechanical bells or horns, audio circuits above 25 volts (RMS), motor control circuits, or
SCR power circuits. Twisted-shielded wiring should be used for EIA-485 circuits that are
not contained entirely in conduit.
For redundant annunciation of system points, annunciators can be configured as
"Receive Only" annunciators. Receive Only annunciators are not fully supervisable.
Receive Only annunciators intercept information being transmitted to a "Receive/
Transmit" annunciator so that information can be duplicated at an intermediate display
location. When configured for Receive Only operation, they cannot send information to
the system, therefore they cannot perform remote functions such as Acknowledge,
Silence, or Reset. Control switches on Receive Only annunciators can be used only for
local functions, such as lamp test. Wiring to Receive Only annunciators may be
supervised by installing the modules "upstream" of fully-supervised Receive/Transmit
annunciators along the EIA-485 line.
Receive/Transmit Annunciators
Annunciators that are configured to serve as full function annunciators can both receive
status information as well as transmit commands to the control panel. This allows the
annunciator to remotely execute functions of the control panel in addition to displaying the
status of the system.
Fire Alarm
Control Panel
Two-wire
EIA-485
Circuit
"Receive Only" Annunciator
Annunciator Expander
Full Function "Receive/
Transmit"
234
234
234
234
15390 Rev D 8/2/96 P/N 15390:D
Annunciator Expander
9
Electrical Ratings
Input Voltage: 24 volts DC (power-limited).
Current Draw from 24 volt DC Input:Standby Alarm
Data Communications Port: EIA-485 operating at 20 Kbaud (power-limited).
Annunciator Power Requirements
Annunciators draw their power from the control panel and must be considered when
calculating the primary and secondary power supply requirements for the system. Each
annunciator module is accounted for in the power calculations outlined in the respective
installation manual. However, if the current draw dedicated to the annunciators must be
calculated as a separate figure, use the equations below.
Column A
Number of AFM modules [ ] X 0.040=amps
The 0.040 amps can be reduced to 0.030 for modules
with Piezo Disable or Flash Inhibit modes selected.
Number of AEM modules [ ] X 0.002=amps
Column B
Sum Column A for Total Annunciator Standby Current =amps
Number of AFM and AEM modules assumed to be
in alarm simultaneously [ ] X 0.018 =amps
Entering the total
Number of AFM and AEM modules
in above will allow for the
simultaneous illumination of all LEDs. When the alarm system specification permits,
calculations can be based on a 10% alarm loading capacity. For 10% capacity, enter 10%
of the total number of AFM and AEM modules multiplied by the number of remote
annunciator locations, but do not enter less than one.
Sum Column B for Total Annunciator Alarm Current=amps
The Total Annunciator Alarm Current cannot exceed 200 mA from the MPS-24BF, or
1 amp from the MPS-24AF.
10
15390 Rev D 8/2/96 P/N 15390:D
Section Four:
Annunciator Installation
Mounting the cabinet or backbox
Select an appropriate knockout on the enclosure. Mount the cabinet or backbox. Ground
the enclosure to a solid metallic ground, such as a grounded cold water pipe. Pull all
annunciator wiring into the enclosure as illustrated in Figures 1 and 2. Connect
annunciator wiring to the removable terminal blocks as illustrated in Figure 4.
Note: A 120-ohm End-of-Line Resistor (Part Number 71244 supplied with the annunciator) must be installed at the last annunciator on the EIA-485 circuit. Remove the ELRs
installed on all annunciators except the last.
Installing the annunciators
Insert the custom display labels into the annunciator and expanders (see Figure 3). Set
the dip switches on the AFM-32AX or AFM-16ATX annunciator as outlined in Section Six.
Turn the dress plate over and place down on a surface with the threaded studs facing up.
Position the AFM-32AX or AFM-16ATX annunciator over the threaded studs on the dress
plate and secure with the two nuts and lock washers provided as illustrated in Figure 5.
ABF-1F Installation Only
Remove the backing from the gummed Annunciator Label and affix the label to
the dress plate as illustrated in Figure 6. If employing an AKS-1F, mount to the
dress plate. Plug the AKS-1F switch leads to Connector J4 on the Annunciator
(see Figure 7). Plug the two annunciator terminal blocks into the annunciator.
Place the annunciator/dress plate assembly into the backbox and secure with
two screws.
Annunciator installation in an ABF-1F is complete.
ABF-2F/ABF-4F Installation Only
Remove the backing from the gummed Annunciator Label and affix the label to
the dress plate as illustrated in Figure 7. If employing an AKS-1F, mount to the
dress plate. Plug the AKS-1F switch leads to Connector J4 on the Annunciator.
Installing the expanders
Plug one end of an Annunciator Expander Ribbon Cable into Connector J2 on the AFM32AX or AFM-16ATX. Install the first AEM-16ATF or AEM-32AF expander module in the
second dress plate position. Connect the expander ribbon from the annunciator to
Connector J3 on this expander.
ABF-2F Installation Only
Plug the two annunciator terminal blocks into the AFM-16ATX or the first AFM32AX. Place the annunciator/dress plate assembly into the ABF-2F backbox.
Secure the assembly with the screws provided.
Annunciator installation in an ABF-2F is complete.
15390 Rev D 8/2/96 P/N 15390:D
11
Completing expander connections
AFM-16ATX/AEM-16ATF
Installation Only
If installing one AFM-16ATX with three
AEM-16ATF expanders in the same dress
plate, perform the following installation
steps:
Connect one end of an expander ribbon
to Connector J2 on the first expander.
Install the second AEM-16ATF expander
in the third dress plate position. Connect
the other end of the expander ribbon
from the first expander to Connector J3
on the second expander.
Connect one end of a ribbon cable to
Connector J2 on the second expander.
Install the third AEM-16ATF expander in
the fourth dress plate position. Connect
the other end of the ribbon cable from the
second expander to Connector J3 on the
third expander.
Completing installation in a cabinet or an ABF-4F
Plug the two annunciator terminal blocks into the AFM-16ATX or the first AFM-32AX.
Place the annunciator/dress plate assembly into the cabinet or ABF-4F backbox. Secure
the assembly with the screws provided. Apply primary (AC) power, followed by
secondary (battery backup) power.
Programming and testing the annunciators
This completes annunciator installation. After programming the fire alarm control panel
to accept the annunciators, fully test the Annunciator Control System by ensuring that
each switch performs its intended function, that each LED lights, and that the annunciators can perform the functions outlined in the section, "Operating the Annunciator."
12
15390 Rev D 8/2/96 P/N 15390:D
Figure 1:
Installing the Enclosure
Mount the backbox or cabinet and pull all annunciator wiring into the enclosure.
Enclosure
Annunciator
Figure 2: Terminating the Shield
The EIA-485 circuit must be wired using a twisted-shielded pair cable having a Characteristic Impedance of 120 ohms, +/- 20%. Do not run cable adjacent to, or in the same
conduit as, 120-volt AC service, noisy electrical circuits that are powering mechanical
bells or horns, audio circuits above 25 VRMS, motor control circuits, or SCR power circuits.
All enclosures, including the FACP backbox, must be connected to earth ground! Never
use the shield for grounding purposes.
Control Panel only.
When the EIA-485 shield is in conduit: connect it to system reference (
The shield can enter the cabinet, but must be insulated from the cabinet (not electrical
contact). Between annunciators, wire-nut multiple shields together (which can be inside
of the respective enclosure, but can not contact the enclosure.)
When the EIA-485 shield is not in conduit: Terminate the shield at the outside of the FACP
backbox (ground). Do not allow the shield to enter or even touch the cabinet. Between
annunciators, wire-nut multiple shields together
Terminate the EIA-485 shield at the Fire Alarm
system common).
outside of
the respective enclosures.
15390 Rev D 8/2/96 P/N 15390:D
13
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.