Fire-Lite AFM-16ATX, AEM-16ATF, ABM-16ATF, AFM-32AX, AEM-32AF User Manual

...
Annunciator
12 Clintonville Road Northford, CT 06472 203-484-7161 FAX: 203-484-7118
Modules
Fire Alarm Control Panels
Document # 15390 8/2/96 Revision:
P/N 15390:D ECN 9
D
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/ or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72-1993 Chapter 7 after any programming operation or change in site­specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49
humidity of 85% RH (non-condensing) at 30O C/86 F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal room temperature of 15­27O C/60-80O F.
O
C/32-120O F and at a relative
O
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased suscep­tibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or en­countered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Fire Alarm System Limitations
An automatic fire alarm system - typically made up of smoke
detectors, heat detectors, manual pull stations, audible warn­ing devices, and a fire alarm control with remote notification capability can provide early warning of a developing fire. Such a system, however, does not assure protection against prop­erty damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors
- both ionization and photoelectric types, have sensing limi­tations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
While installing a fire alarm system may make lower insur­ance rates possible, it is not a substitute for fire insurance!
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, how­ever, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be sched­uled monthly or as required by National and/or local fire codes. Adequate written records of all inspections should be kept.
Technical Publishing Document PRECAUSM.PM6 07/12/96
Table of Contents
Section One: Annunciators...........................................................................4
Section Two: Annunciator Inventory .............................................................5
Section Three: Design Considerations..........................................................8
Table 3-1: Typical Wire Resistance Chart...................................................8
Section Four: Annunciator Installation......................................................11
Figure 1: Installing the Enclosure.............................................................13
Figure 2: Terminating the Shield ..............................................................13
Figure 3: Slide-In Labels ..........................................................................16
Figure 4: Terminal Wiring ..........................................................................16
Figure 5: Mounting the Trim Ring .............................................................17
Figure 6: Applying the Annunciator Label ................................................17
Figure 7: Ann unciator Options .................................................................18
Figure 8: Main Power Supply Connections ...............................................19
Section Five: Operating the Annunciators ................................................20
Figure 9: Operating the AFM-16ATX........................................................20
Figure 10: Operating the AEM-16ATF......................................................21
Figure 11: Operating the AFM-32AX .......................................................22
Figure 12: Operating the AEM-32AF .......................................................23
Section Six: Annunciators and the Sensiscan 2000 .................................24
Figure 13: Connecting the EIA-485 Loop..................................................24
Figure 14: Configuring Annunciators f or Sensiscan 2000.........................26
Table 6-1: Annunciator Point Functions.....................................................27
Slide-in Labels..................................................................... Center of Manual
15390 Rev D 8/2/96 P/N 15390:D
3
Section One: Annunciators
Fire•Lite annunciator modules provide the Sensiscan 2000 with up to 32 remote serially connected annunciators, each with a capacity of 64 points.
The annunciator modules provide arrays of LEDs to indicate, at a remote location, the status of circuits within the system. Annunciator points in a Sensiscan 2000 directly follow the circuit arrangement of modules installed in the cabinet.
Control of common system functions such as signal silence, system reset, and local annunciation controls (local acknowledge and lamp test) may be accomplished through the annunciator's integral membrane push switches.
Communication between the FACP and the annunciators is accomplished over a power­limited two-wire serial interface employing an EIA-485 communication standard. Power is provided via a separate power-limited power loop from the control panel which is inherently supervised by the FACP (loss of power results in an annunciator communica­tion failure at the control panel). The annunciator can also be powered from a remote UL listed power-limited power supply.
There are two basic annunciator types, alarm and alarm/trouble, each with its own expander module.
4
15390 Rev D 8/2/96 P/N 15390:D
Section T wo:
Annunciator Inventory
AFM-16ATX
The Annunciator Control Module-16ATX contains 16 red alarm and 16 yellow trouble LEDs, 16 momentary touch-pad switches for controlling each point, a system trouble LED, an ON LINE/POWER LED, and a local piezo sounder with a silence/acknowledge switch for audible indication of alarm and trouble conditions at each annunciator.
AEM-16ATF
The Annunciator Expander Module-16ATF expands the AFM-16ATX by 16 system points. The AEM-16ATF is identical in size and in frontal appearance to the AFM­16ATX. One to three of these expander modules can be supported by an AFM-16ATX, to a maximum of 64 system points. Note: The AEM-16ATF cannot be used to expand the AFM-32AX.
ABM-16ATF
The Annunciator Blank Module-16ATF is a dress plate identical in appearance to the front panel of the AFM-16ATX and AEM-16ATF modules. The blank module is used to cover unused module positions in an annunciator backbox.
AFM-32AX
The Annunciator Control Module-32AX contains 32 red alarm LEDs, a system trouble LED, an ON LINE/POWER LED, and a local piezo sounder with a silence/acknowledge switch for audible indication of alarm and trouble conditions at each annunciator.
AEM-32AF
The Annunciator Expander Module-32AF expands the AFM­32AX by 32 system points. The AEM-32AF is identical in frontal appearance to the AFM-32AX. One expander mod­ule can be supported by an AFM-32AX, providing a maxi­mum of 64 points. Note: The AEM-32AF cannot be used to expand the AFM-16ATX.
ABM-32AF
The Annunciator Blank Module-32AF is a dress plate iden­tical in appearance to the front panel of the AFM-32AX and AEM–32AF modules. The blank module is used to cover unused module positions in an annunciator backbox.
15390 Rev D 8/2/96 P/N 15390:D
5
ABS-1F
The Annunciator Surface Box-1F provides for the remote mount­ing of a single AFM-16ATX or AFM-32AX annunciator in a surface­mount enclosure. Knockouts are provided for use with 1/2" con­duit. The annunciator mounts directly to the ABS-1F without a dress plate. (H = 8-1/2" W = 4-1/2" D = 1-3/8")
ABS-2F
(not illustrated) The Annunciator Surface Box-2F provides for the surface mount­ing of one AFM-16ATX/AEM-16ATF combination or one AFM­32AX/AEM-32AF combination. Knockouts are provided for use with 1/2" conduit. The annunciator module mounts directly to the ABS-2F without a dress plate. (H=8-1/2" W=8-15/16" D=1-3/8")
Note: The ABS-1F and ABS-2F will not support the installation of the AKS-1F Annunciator Key Switch.
ABF-1F
The Annunciator Flush Box-1F provides for the remote mounting of a single AFM-16ATX or AFM-32AX annunciator in a flush-mount enclo­sure. Knockouts are provided for use with 1/2" conduit. The ABF-1F includes a trim plate (height=11" width=6-1/4"), mounting hardware, and an adhesive-backed Annunciator Label for the dress plate. (H = 9-15/16" W = 4-5/8" D = 2-1/2")
ABF-2F
(not illustrated) The Annunciator Flush Box-2F provides for the flush mounting of one AFM-16ATX/AEM-16ATF combination or one AFM-32AX/AEM-32AF com­bination. Includes a trim plate (H=11" W=10-5/ 8") and adhesive-backed Annunciator Label. (H=9-15/16" W=9-3/16" D=2-1/2")
6
Annunciator Label
15390 Rev D 8/2/96 P/N 15390:D
Annunciator Label
ABF-4F
The Annunciator Flush Box-4F provides for the remote mounting of one to four AFM-16ATX/AEM-16ATF modules. Knockouts are provided for use with 1/2" conduit. The flush-mounted ABF-4F includes a trim plate (H=11" W=19-3/8") and an Annunciator Label. (H=9 - 15/16" W=17 - 3/8" D=2 - 1/2")
AKS-1F
The Annunciator Key Switch-1F provides access security for the control switches on the AFM-16ATX. The key switch kit includes a key and hardware for mounting to the trim plate of one of the flush-mount type annunciator enclosures. Also included is an adhesive-backed Annunciator Label for use with the key switch/ dress plate assembly.
Note: The AKS-1F can only be employed with a flush-mount type backbox.
Annunciator Label
15390 Rev D 8/2/96 P/N 15390:D
7
Section Three:
Design Considerations
Limits
Up to 32 annunciators may be installed on an EIA-485 circuit. The actual number of annunciator modules may be larger depending on the number of expander modules employed.
Wire Runs
Communication between the Control Panel and the annunciator is accomplished over a power-limited two-wire EIA-485 serial interface. This communication, including the wiring, is supervised by the fire alarm control panel. Power for the annunciators is provided via a separate power-limited power loop from the control panel which is inherently supervised (loss of power also results in a communication failure at the control panel).
Fire Alarm Control Panel
Annunciator Power
(14 to 18 AWG )
Two-wire EIA-485 Circuit
(Maximum of 6,000 feet)
Annunciator
Wiring Specifications
The EIA-485 circuit cannot be T-Tapped; it must be wired in a continuous fashion from the control panel to the annunciator. The maximum wiring distance between the panel and the last annunciator is 6,000 feet @ 16 AWG. The wiring size must be a 14 AWG to 18 AWG twisted shielded pair cable having a Characteristic Impedance of 120 ohms, +/- 20%. Limit the total wire resistance to 100 ohms on the EIA­485 circuit, and 10 ohms on the annunciator power circuit. Do not run cable adjacent to, or in the same conduit as, 120 volts AC service, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 volts (RMS), motor control circuits, or SCR power circuits. Twisted-shielded wiring should be used for EIA-485 circuits that are not contained entirely in conduit.
STANDARD ANNEALED COPPER WIRE
Wire Size
A.W.G.
14 64 4110 0.00323 2.58 2.97 12.4 16 51 2580 0.00203 4.09 4.73 7.82 18 40 1620 0.00128 6.51 7.51 4.92
Diameter in
Mils
Circ. Mils Sq. Inch @ 77 F. @ 149 F.
Table 3-1: Typical Wire Resistance Chart
8
Cross Section Ohms per 1000 ft.
15390 Rev D 8/2/96 P/N 15390:D
Pounds per
1000 ft.
5
5
5
5
1234
1234
1234
1234
1234
1234
Receive Only Annunciators
For redundant annunciation of system points, annunciators can be configured as "Receive Only" annunciators. Receive Only annunciators are not fully supervisable. Receive Only annunciators intercept information being transmitted to a "Receive/ Transmit" annunciator so that information can be duplicated at an intermediate display location. When configured for Receive Only operation, they cannot send information to the system, therefore they cannot perform remote functions such as Acknowledge, Silence, or Reset. Control switches on Receive Only annunciators can be used only for local functions, such as lamp test. Wiring to Receive Only annunciators may be supervised by installing the modules "upstream" of fully-supervised Receive/Transmit annunciators along the EIA-485 line.
Receive/Transmit Annunciators
Annunciators that are configured to serve as full function annunciators can both receive status information as well as transmit commands to the control panel. This allows the annunciator to remotely execute functions of the control panel in addition to displaying the status of the system.
Fire Alarm
Control Panel
Two-wire
EIA-485
Circuit
"Receive Only" Annunciator
Annunciator Expander
Full Function "Receive/ Transmit"
234
234
234
234
15390 Rev D 8/2/96 P/N 15390:D
Annunciator Expander
9
Electrical Ratings
Input Voltage: 24 volts DC (power-limited). Current Draw from 24 volt DC Input: Standby Alarm
AFM-16ATX/AFM-32AX 0.040 amps 0.056 amps AEM-16ATF/AEM-32AF 0.002 amps 0.018 amps
Data Communications Port: EIA-485 operating at 20 Kbaud (power-limited).
Annunciator Power Requirements
Annunciators draw their power from the control panel and must be considered when calculating the primary and secondary power supply requirements for the system. Each annunciator module is accounted for in the power calculations outlined in the respective installation manual. However, if the current draw dedicated to the annunciators must be calculated as a separate figure, use the equations below.
Column A
Number of AFM modules [ ] X 0.040 = amps
The 0.040 amps can be reduced to 0.030 for modules with Piezo Disable or Flash Inhibit modes selected.
Number of AEM modules [ ] X 0.002 = amps
Column B
Sum Column A for Total Annunciator Standby Current = amps
Number of AFM and AEM modules assumed to be in alarm simultaneously [ ] X 0.018 = amps
Entering the total
Number of AFM and AEM modules
in above will allow for the simultaneous illumination of all LEDs. When the alarm system specification permits, calculations can be based on a 10% alarm loading capacity. For 10% capacity, enter 10% of the total number of AFM and AEM modules multiplied by the number of remote annunciator locations, but do not enter less than one.
Sum Column B for Total Annunciator Alarm Current = amps
The Total Annunciator Alarm Current cannot exceed 200 mA from the MPS-24BF, or
1 amp from the MPS-24AF.
10
15390 Rev D 8/2/96 P/N 15390:D
Section Four:
Annunciator Installation
Mounting the cabinet or backbox
Select an appropriate knockout on the enclosure. Mount the cabinet or backbox. Ground the enclosure to a solid metallic ground, such as a grounded cold water pipe. Pull all annunciator wiring into the enclosure as illustrated in Figures 1 and 2. Connect annunciator wiring to the removable terminal blocks as illustrated in Figure 4.
Note: A 120-ohm End-of-Line Resistor (Part Number 71244 supplied with the annuncia­tor) must be installed at the last annunciator on the EIA-485 circuit. Remove the ELRs installed on all annunciators except the last.
Installing the annunciators
Insert the custom display labels into the annunciator and expanders (see Figure 3). Set the dip switches on the AFM-32AX or AFM-16ATX annunciator as outlined in Section Six. Turn the dress plate over and place down on a surface with the threaded studs facing up. Position the AFM-32AX or AFM-16ATX annunciator over the threaded studs on the dress plate and secure with the two nuts and lock washers provided as illustrated in Figure 5.
ABF-1F Installation Only
Remove the backing from the gummed Annunciator Label and affix the label to the dress plate as illustrated in Figure 6. If employing an AKS-1F, mount to the dress plate. Plug the AKS-1F switch leads to Connector J4 on the Annunciator (see Figure 7). Plug the two annunciator terminal blocks into the annunciator. Place the annunciator/dress plate assembly into the backbox and secure with two screws.
Annunciator installation in an ABF-1F is complete.
ABF-2F/ABF-4F Installation Only
Remove the backing from the gummed Annunciator Label and affix the label to the dress plate as illustrated in Figure 7. If employing an AKS-1F, mount to the dress plate. Plug the AKS-1F switch leads to Connector J4 on the Annunciator.
Installing the expanders
Plug one end of an Annunciator Expander Ribbon Cable into Connector J2 on the AFM­32AX or AFM-16ATX. Install the first AEM-16ATF or AEM-32AF expander module in the second dress plate position. Connect the expander ribbon from the annunciator to Connector J3 on this expander.
ABF-2F Installation Only
Plug the two annunciator terminal blocks into the AFM-16ATX or the first AFM­32AX. Place the annunciator/dress plate assembly into the ABF-2F backbox. Secure the assembly with the screws provided.
Annunciator installation in an ABF-2F is complete.
15390 Rev D 8/2/96 P/N 15390:D
11
Completing expander connections
AFM-16ATX/AEM-16ATF
Installation Only
If installing one AFM-16ATX with three AEM-16ATF expanders in the same dress plate, perform the following installation steps:
Connect one end of an expander ribbon to Connector J2 on the first expander. Install the second AEM-16ATF expander in the third dress plate position. Connect the other end of the expander ribbon from the first expander to Connector J3 on the second expander.
Connect one end of a ribbon cable to Connector J2 on the second expander. Install the third AEM-16ATF expander in the fourth dress plate position. Connect the other end of the ribbon cable from the second expander to Connector J3 on the third expander.
Completing installation in a cabinet or an ABF-4F
Plug the two annunciator terminal blocks into the AFM-16ATX or the first AFM-32AX. Place the annunciator/dress plate assembly into the cabinet or ABF-4F backbox. Secure the assembly with the screws provided. Apply primary (AC) power, followed by secondary (battery backup) power.
Programming and testing the annunciators
This completes annunciator installation. After programming the fire alarm control panel to accept the annunciators, fully test the Annunciator Control System by ensuring that each switch performs its intended function, that each LED lights, and that the annuncia­tors can perform the functions outlined in the section, "Operating the Annunciator."
12
15390 Rev D 8/2/96 P/N 15390:D
Figure 1:
Installing the Enclosure
Mount the backbox or cabinet and pull all annun­ciator wiring into the enclosure.
Enclosure
Annunciator
Figure 2: Terminating the Shield
The EIA-485 circuit must be wired using a twisted-shielded pair cable having a Charac­teristic Impedance of 120 ohms, +/- 20%. Do not run cable adjacent to, or in the same conduit as, 120-volt AC service, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 VRMS, motor control circuits, or SCR power circuits.
All enclosures, including the FACP backbox, must be connected to earth ground! Never use the shield for grounding purposes.
Control Panel only. When the EIA-485 shield is in conduit: connect it to system reference (
The shield can enter the cabinet, but must be insulated from the cabinet (not electrical contact). Between annunciators, wire-nut multiple shields together (which can be inside of the respective enclosure, but can not contact the enclosure.)
When the EIA-485 shield is not in conduit: Terminate the shield at the outside of the FACP backbox (ground). Do not allow the shield to enter or even touch the cabinet. Between annunciators, wire-nut multiple shields together
Terminate the EIA-485 shield at the Fire Alarm
system common).
outside of
the respective enclosures.
15390 Rev D 8/2/96 P/N 15390:D
13
Loading...
+ 28 hidden pages