Fieldpiece SRL2K7 User Manual

Infrared Refrigerant Leak Detector Model: SRL2
OPERATOR’S MANUAL
Description
The SRL2 uses infrared optics to create a portable refrigerant leak detector technology that has a superior combination of sensitivity, speed, sensor life, battery life, portability, and ease of use.
Gas is pumped through the tip of the wand into the sensor within the SRL2 body. The sensor detects changes in concentration, not absolute con­centration, making it easy to detect leaks even in areas with refrigerant in the air.
The SRL2 detects leaks as small as 0.1 oz/year, which exceeds the toughest SAE J1627 standards. The SRL2 comes with wall and car charger for its ultra-compact Lithium-ion battery which powers the SRL2 for 8hrs of continuous operation before a recharge is needed. That’s long enough to last your entire workday.
Unlike many leak detectors, oil vapor does not trigger the SRL2.
The SRL2 has vari­able sensitivity set­tings, keeping ‘nui­sance tripping’ to a minimum. A quick and automatic 30 second self-calibration upon power-up ensures optimal performance. Abuilt in replaceable filter blocks moisture and harmful particulates. The SRL2 also has a mute button and a peak hold func­tion.
Quick Tips
1.
Keep the wand tip moving past suspected leak locations.
2. Once a leak is detected, sweep the wand back
over to pinpoint.
3. To pinpoint larger leaks adjust sensitivity.
Filter Assessment & Replacement
The filter blocks moisture and other contaminants from the sensor. When it gets wet, it constricts flow of air and it will have to be replaced. Unscrew the sensor tip and replace the white filter so that the rounded end is closest to the tip of the wand. Use only the Fieldpiece supplied filter.
You can order from a distributor extra bags of replacement parts (model RFL2) are available from Fieldpiece. Model RFL2 contains 10 filters and 5 O­rings.
Comparing Leak Detectors
Fieldpiece has two leak detectors. The SRL2 uses an infrared (IR) sensor. It detects a CHANGE in concentration, so the wand must keep moving. The main advantages of the Fieldpiece IR sensor are that its sensitivity will remain the same over the life of the instrument, the sensor will last the lifetime of the instru ment, it will not trigger on humidity or on oil, and it has nearly the same sensitivity to most refrigerants.The main disadvantage of infrared sensors is their sensitivity to mechanical disturbances.
The SRL8 uses a heated diode sensor. The heated diode'sadvantage is that it detects absolute concentration levels so it can be held on a leak and will continue to beep. It is also initially very sensitive. Its disadvantages are that the sensor becomes less sensitive over life, eventually needing replacement and it is more sensitive to some refrigerants than others.
T2
SENSITIVITY
H
M
L
PEAK
LOW-BATT
Operation
ON/OFF Protection
To turn on/off the SRL2 press and hold the ON/OFF button for one second. This slight delay protects against inadvertent pressing. If you forget to turn it off, it will automatically go off in 10 minutes.
LED Bar Graph Display
The eight segment LED display indicates the
degree of change
in refrigerant concentration. As the concentration of refrigerant in the air increases, so does the number of lit bars on the display.
L/M/H Button (Sensitivity)
Set the sensitivity level by pressing the L/M/H but­ton. Low(L), medium(M), or high(H) sensitivity will be indicated by their respective LED.
The higher the concentration of refrigerant in the ambient air, the lower the sensitivity setting should be to minimize false trips.
Mute Button
Pressing the MUTE button toggles the sound of the SRL2 off and on.
Peak Button
The PEAK function holds the highest change in concentration achieved while continuing to detect leaks. Press PEAK to toggle this function on and off.
Turning the PEAK function off will clear the peak change. The PEAK LED will light when PEAK func­tion is on.
Turbo Mode
The TURBO function is an additional 4th sensitiv­ity that pushes the SRL2 to it highest possible sen­sitivity. This feature is activated by pressing the PEAK button four times in succession, and can only be activated while on the high(H) sensitivity level.
When in the TURBO mode the first green LED on SRL2 will strobe, and the audio detection sound will be a solid tone.
To exit the TURBO mode, press the PEAK button again four times in succession, or switch from high(H) to one of the other sensitivities levels.
Beware: While in TURBO mode the SRL2 is extremely sensitive and will more easily trigger on abrupt or violent motions as well as very small changes in refrigerant levels. Handle with care when in TURBO mode.
Leak Detection Procedure
Keep the SRL2 away from any areas of potential refrigerant leakage until the warm-up and calibration period is over. The warm-up and calibration sequence lasts about 30 seconds after ON/OFF is pressed. Allow the SRL2 to fully warm-up before using to avoid false triggering. On startup, meter defaults to high sensitivity.
The most likely points for refrigerant leaks are at the soldered joints in refrigerant lines and changes in cross section or direction of these lines.
The SRL2 detects changes
in concentration of refrigerant, not the absolute concentration of refrig­erant. This lets the user easily detect leaks in places that may have refrigerant in the air, such as a refrig­erator leaking into an enclosed space. Because the SRL2 detects change, there is a specific “double­pass” method used to find leaks.
1. The tip of the wand should be fairly close to the
line. You may need to be within 1/4” (0.63cm) of a small leak to detect it. In this case, using a second hand to guide the tip along refrigerant lines may be helpful.
2. Keep the tip moving along refrigerant lines at a
rate of 1-3 inches per second.
3. Once the SRL2 indicates a change in concentra-
tion, note the spot on the line and keep the tip moving past the potential leak to refresh the air space within the SRL2 with clean air. (Note: If the SRL2 wand moves through a very high con­centration of refrigerant, you may need to use in fresh air for 4 seconds before moving to step 4 in order to clear the refrigerant within the SRL2.)
4. Return the tip back to, and past, the spot first indicated. When the SRL2 indicates a second change, note the spot on the line. The source of the leak will be near the midpoint between the two noted spots of indication.
5. Very high concentrations of refrigerant can cause an overload which can take a few sec­onds to clear.
SRL2 testing an A-coil in an evaporator, 1/4” from the line.
1/4”
(0.63cm)
WARNING
DO NOT use the SRL2 without the proper fil-
ter correctly installed.
!
!
SENSITIVITY
PEAK
H
LOW-BATT M
L
L/M/H
ON/OFF
MUTE
Infrared Refrigerant Leak Detector
ON/OFF
SRL2
PEAK
PRESS FOR
1 SECOND
T2
T2
Specifications
Sensing element: Enhanced infrared photo optics Sensor life: 10 years Refrigerants: HFC, CFC, HCFC, and blends Sensitivity: Min (Stationary): 0.1oz/yr (3g/yr)
Max (Stationary): >1.05oz/yr (>30g/yr) Min (In motion): 0.18oz/yr (5g/yr) Max (In motion): >1.05oz/yr (>30 g/yr) After exposure to (50g/yr): 0.1 oz/yr (3g/yr) In poluted environment: 0.1 oz/yr (3g/yr)
Response time: 1 second Recovery time: ~4 seconds Auto off: 10 minutes after no activity Battery: 7.4VDC(nominal), rechargeable lithium
ion technician replaceable battery.
Battery life: 8 hours continuous use prior to need-
ing a charge. Degradation (30%) after 500 charge/discharge cycles or two years, whichever comes first.
Low battery LED: Lights when approximately 1
hour of battery life remains.
Charge time: Less than 4 hours with either sup-
plied charger.
Operating environment: 32ºF (0°C) to 104ºF
(40°C) at <75%RH (non-condensing)
Storage environment: <80%RH meter and batt.
For 80% battery recovery:
-4ºF (-20°C) to 140ºF (60°C) less than 1 month
-4ºF (-20°C) to 113ºF (45°C) less than 3 months
-4ºF (-20°C) to 68ºF (20°C) less than 1 year
Patents: #6,791,088 and #7,022,993
Notice of Compliance
This instrument complies with the specifications
for an indicating, locating leak detector as described by the european standard EN 14624, EN 14624 (2005) with the assumption that the speed specification in section 7.2 should read as "2.0 cm/s" as was indicated to us by A. Beatrix Alke, project manager of Deutsches Institut fur Normung.
More Products From Fieldpiece Modular Expandability
Modular expandability is ability for accessory heads and meters to change configurations to match the various needs of an HVAC/R technician.
Accessory heads (the sensors) send out a mV signal, which represents the value of the measure-
ment, to whatever meter is attached to it. Heads can attach directly to the top of a Stick meter, DL2 data logger, or EHDL1. They can also plug into any meter with mV ranges using ASLS2 leads.
Warranty and Service
The product is warranted to the original purchas­er against defects in material or workmanship for a period of one (1) year from the date of purchase. During the warranty period, Fieldpiece Instruments will, at its option, replace or repair the defective unit.
This warranty does not apply to defects resulting from abuse, neglect, accident, unauthorized repair, alteration, or unreasonable use of the instrument. Any implied warranty arising out of the sale of Fieldpiece's products including but not limited to implied warranties of merchantability and fitness for purpose are limited to the above. Fieldpiece shall not be liable for incidental or consequential dam­ages.
Return any defective SRL2 to Fieldpiece for war­ranty service along with proof of purchase. Contact Fieldpiece for out of warranty repair charges.
v30
Lithium Battery Care
The SRL2 contains a very powerful lithium ion battery. For a long battery life and safe operation, you must observe the following:
Cautions
1. Do not expose the battery to temperatures high-
er than 140ºF (60°C).
2. Do not charge the battery in or nearby heated
places, such as fire, hot vehicles, or direct sun-
light.
3. Do not solder directly on battery.
4. Do not expose the battery to direct impact or
throw it.
5. Do not get the battery wet.
6. Do not deform or pierce the battery in any way.
7. If there is any battery leakage, do not touch the
battery. In the case that electrolyte gets into the
eyes, flush with fresh water, do not rub, and see
a physician immediately.
8. Replace immediately if there is any deformity,
bad smell, color change, or other abnormality.
9. The battery is not user-replaceable, if the bat-
tery fail, contact Fieldpiece for replacement.
Charging
Two chargers are included with the SRL2. The AC charger plugs into a wall outlet and the car charger plugs into a car cigarette lighter DC plug.
1. The battery is partially charged when packaged.
Fully charge the battery before first use.
2. The LOW-BATT LED will light red when the bat-
tery is low. Charge can be checked at any time
the unit is on with the Battery Check function
(See Operation section).
3. To recharge the SRL2, plug one end of the
charger into the top of the SRL2 and the other
into the power source. LOW-BATT will blink
while charging until the battery is fully charged.
When the SRL2 battery is fully charged, LOW-
BATT turns off.
4. Charge within operating environment specified
in the Specifications section in this manual.
5. Avoid frequent full discharges. Several partial
discharges with frequent recharges are better
for lithium-ion batteries. Unlike nickel-based bat-
teries they have no charge memory, and do not
need to be discharged before charging.
Storage
The battery should have a 40%-50% charge dur­ing prolonged storage of a month or longer. See Specifications section in this manual for proper stor­age environment.
Battery life is dramatically reduced if the battery is stored fully charged and/or at high temperatures.
Included Equipment
Use model RRE2 when detecting in tight spaces, such as through a condenser grille. Model RFE2 extends the wand to 25.5” (65cm). The blow mold­ed case, model holds accessories and chargers.
All accessories shown are included with the SR2K7.
Standalones from Fieldpiece
The SRL2 refrigerant leak detector is designed for HVAC/R technicians. Here are some other standalone products from Fieldpiece Instruments.
T2T2T2
/O
SSX34
Superheat and
Subcooling for A/C
and Refrigeration
SRH2
Diagnostic Psychrometer
SC77
All-in-one Expandable Clamp-on Meter
9”(23cm) Needle Tip Probe model RRE2
9”(23cm) Flex
Extension
model RFE2
Blow molded Carrying Case
w/ RRE2 and RFE2
Model ABMK3
SC77
APO HOLD n m m F AC DC
m A K M Ω
m V V
NCV
HOLD
Auto 4000m
µ
400m
400
340
DISCONNECT TESTLEADS
ATM
TYPE
UNIT
TEMP.
T2
AUTO-OFF BATTERY
CHECK
ON/OFF
PRESS FOR 1 SECOND
Temp Cal
K
SH
SC
T/C
Diagnostic Psychrometer
°C °F
BATTERY CHECK
RH/DP/WB/DB
AUTO-OFF
MAX/MIN/H
ENTER
TSH/TEET/NORM
T/C Cal
ON/OFF
SRH2
T2
T2
Calculates Target SH and Target Evap Exit Temperature
NTC
SENSOR
T2
ON/OFF
OUTPUT
T2
T2
PRESS FOR 1 SECOND
T2
T2
CLAMP
300V
CAT.III
400A
AC Current Clamp
!
1AAC / 1mVAC 400AAC MAX
N
O
E
L
T
B
T A
H
A T S
OB L
LIS G
n
EN
g
SH
t
IC
n
TR
r atio
li
E
o
M
a
co
frige
34A
b
rhe
R1
SC
Re
Su
pe
Su
d
4A
an
40 R
C
p
rS
m
o
re e T
H S
u
s s e
r P
C / T
l a
C et S
M T
A
N
t t
O
a
B o L
E L
B A T S
Combustion
Check
ASX24
S A G
L I O
e p y T l
e
O
u
T
F
F
U
F
A
O
L
/C
A
T
P
2
C
2
O
M
O
C
E
°F
%
T
%
°C
2 X O A
ACH4
- O T
U
F
F
A
O
AirVelocit
&Tem
Head
O N
per
L C
y
L
D
1
O
X
0
atur
B
0
A
T T
E n
e
g
R
lis
E
E
A
h
F
n
D
t
g / m
l
is i
h
nM
Av
M
M
e
P
e
(1
t r
H
r
i
a
6
c
M
g
s
e
º
e
e
t
c
r
)
i
K
c
/ s
M
O
/ h
F
R
r
F
e
t
a
im
C
l
e
A U
T
O
O
F
-
F
AAV3
Loading...