Fieldpiece Fieldpiece SRL2K7 Manual

Page 1
Infrared
T2
T2
PEAK
MUTE
ON/OFF
ON/OFF
L/M/H
SENSITIVITY
H
M
L
PEAK
LOW-BATT
PRESS FOR
1 SECOND
SRL2
Infrared Refrigerant Leak Detector
BATTERY CHECK
SENSITIVITY
H
M
L
PEAK
LOW-BATT
!
!
Refrigerant Leak Detector Model: SRL2
OPERATOR’S MANUAL
Operation
ON/OFF Protection
To  turn  on/off  the  SRL2  press  and  hold  the ON/OFF  button  for  one  second.  This  slight  delay protects against  inadvertent  pressing.  If  you forget to turn it off, it will automatically go off in 10 minutes.
LED Bar Graph Display
The  eight  segment  LED  display  indicates  the degree  of  change the concentration of refrigerant in the air increases, so does the number of lit bars on the display.
L/M/H Button (Sensitivity)
Set the sensitivity level by pressing the L/M/H but­ton.  Low(L),  medium(M),  or  high(H)  sensitivity  will be indicated by their respective LED. 
The higher  the concentration  of refrigerant  in the ambient air, the  lower  the  sensitivity setting should be to minimize false trips.
Mute Button and Battery Check
Pressing the  MUTE  button  toggles  the  sound  of the SRL2 on and off. In addition, holding the MUTE button down for one second will display the remain­ing percent of battery charge on the LED bar graph. 
in  refrigerant  concentration.  As
Description
The  SRL2  uses  infrared  optics  to  create  a portable  refrigerant  leak  detector  technology  that has  a  superior  combination  of  sensitivity,  speed, sensor life, battery life, portability, and ease of use.  
Gas is pumped through  the  tip  of  the  wand into the  sensor  within  the  SRL2  body.  The  sensor detects changes in concentration, not absolute con­centration,  making  it  easy  to  detect  leaks  even  in areas with refrigerant in the air. 
The SRL2 detects leaks as small as 0.1 oz/year, which exceeds the toughest SAE J1627  standards. The SRL2 comes with wall and car charger for its ultra-compact Lithium-ion battery which powers the SRL2  for  8hrs  of  continuous  operation  before  a recharge is needed. That’s long enough to last your entire workday.
Unlike  many  leak  detectors,  oil  vapor  does  not trigger the SRL2.
The  SRL2  has  vari­able  sensitivity  set­tings,  keeping  ‘nui­sance  tripping’  to  a minimum. A  quick  and automatic 30 second self-calibration upon power-up ensures optimal performance. A built in replaceable filter blocks  moisture and harmful  particulates. The SRL2 also has a mute button and a peak hold func­tion.
Peak Button
The  PEAK  function  holds  the  highest change  in concentration  achieved  while  continuing  to  detect leaks. Press PEAK to toggle this function on and off. Turning  the  PEAK  function  off  will  clear  the  peak change. The PEAK LED will light when PEAK func­tion is on. 
Turbo Mode
The TURBO function is an additional 4th sensitiv­ity that pushes the SRL2 to it highest possible sen­sitivity.  This  feature  is  activated  by  pressing  the PEAK button four times in succession, and can only be activated while on the high(H) sensitivity level. 
When in the TURBO mode the first green LED on SRL2 will strobe, and the audio detection sound will be a solid tone. 
To exit the TURBO mode, press the PEAK button again  four  times  in  succession,  or  switch  from high(H) to one of the other sensitivities levels.
Beware:  While  in  TURBO  mode  the  SRL2  is extremely  sensitive  and  will  more easily  trigger  on abrupt  or  violent  motions  as  well  as  very  small changes  in  refrigerant  levels.    Handle  with  care when in TURBO mode.
Leak Detection Procedure
Keep the SRL2 away from any  areas of potential refrigerant leakage until the warm-up and calibration period  is  over.  The  warm-up  and  calibration
Quick Tips
1.
Keep the wand tip moving past suspected leak locations.
2. Once a leak is detected, sweep the wand back
over to pinpoint.
3. To pinpoint larger leaks adjust sensitivity.
Filter Assessment & Replacement
The filter blocks moisture and other contaminants from the sensor. When it gets wet, it constricts flow of air and it will have to  be  replaced. Unscrew  the sensor  tip  and  replace  the  white  filter  so  that  the rounded end is  closest to the tip  of  the wand. Use only the Fieldpiece supplied filter. 
You  can  order  from  a  distributor  extra  bags  of replacement parts (model RFL2) are available from Fieldpiece. Model RFL2 contains 10 filters and 5 O­rings. 
WARNING
DO NOT use the SRL2 without the proper fil-
ter correctly installed. 
sequence lasts about 30 seconds after ON/OFF is pressed.  Allow  the  SRL2  to  fully  warm-up  before using  to  avoid  false  triggering.  On  startup,  meter defaults to high sensitivity.
The most  likely points  for refrigerant  leaks are at the soldered joints  in refrigerant lines and  changes in cross section or direction of these lines.  
The  SRL2  detects  changes refrigerant, not  the absolute concentration  of refrig­erant. This lets the user easily detect leaks in places that may have refrigerant in the air, such as a refrig­erator leaking into  an enclosed space. Because the SRL2  detects  change,  there  is  a  specific  “double­pass” method used to find leaks. 
1. The tip of the wand should be fairly close to the
line. You may need to be within 1/4” (0.63cm) of
a small leak to detect it. In this case, using a
second hand to guide the tip along refrigerant
lines may be helpful.
2. Keep the tip moving along refrigerant lines at a
rate of 1-3 inches per second.
3. Once the SRL2 indicates a change in concentra-
tion, note the spot on the line and keep the tip
moving past the potential leak to refresh the air
space within the SRL2 with clean air. (Note: If
the SRL2 wand moves through a very high con-
centration of refrigerant, you may need to use in
in  concentration  of
Comparing Leak Detectors
Fieldpiece has two leak detectors.  The SRL2 uses an infrared (IR) sensor. It detects a CHANGE in concentration, so the wand  must keep moving. The main advantages of the Fieldpiece IR sensor are that its sensitivity will  remain the same over the life of the instrument,  the sensor will last the lifetime of the instru ment, it will not trigger on humidity or on oil,  and it has nearly the same sensitivity to most  refrigerants.The main disadvantage of infrared  sensors is their sensitivity to mechanical  disturbances.
The SRL8 uses a heated diode sensor.  The heated diode'sadvantage is that it detects absolute concentration levels so it can be held on a leak and will continue to beep. It is also initially very sensitive. Its disadvantages are that the  sensor becomes less sensitive over life, eventually needing replacement and it is more sensitive to some refrigerants than others.
99 Washington Street Melrose, MA 02176
Phone 781-665-1400 Toll Free 1-800-517-8431
Visit us at www.TestEquipmentDepot.com
fresh air for 4 seconds before moving to step 4 in order to clear the refrigerant within the SRL2.)
4. Return the tip back to, and past, the spot first indicated. When the SRL2 indicates a second change, note the spot on the line. The source of the leak will be near the midpoint between the two noted spots of indication.
5. Very high concentrations of refrigerant can cause an overload which can take a few sec­onds to clear.
1/4”
(0.63cm)
SRL2 testing an A-coil in an evaporator, 1/4” from the line.
Page 2
CAT.III
300V
400A
CLAMP
ACH4
AC Current Clamp
1AAC / 1mVAC 400AAC MAX
!
AirVelocity
&Temperature
Head
English
READLOBATT
ON
LCDX 100
Average
(16sec)
Metric
Real time
AAV3
AUTO- OFF
English
Metri
c
Ft/min M/s
KM/hrMPH
ºF ºC
OF
F
AOX2
Combustion
Check
%
O
%
CO
TEMP
ON
GAS
OIL
Lo Batt
°C °F
AUTO
OFF
STABLE
Fuel Type
2
2
T/C CAL
AUTO-
OFF
T/C
Cal
STABLE
Pressu re
Temp
SH or SC
ON
LOBATT
Refriger ation Superhea t
and Subcooling
ENGLIS H
METRIC
R134A
R404A
Set ATM
ASX24
SH
SC
Lithium Battery Care
T2
T2
P1
P1 P2
ZERO
HOLD UNIT
ON/OFF
P2
88.88
88.88
APO
88.8888.88
inWC
mmWC
mbar
psi
HOLD
PRESS FOR 1 SECOND
AUTO-OFF BATTERY
CHECK
80
80
SC57
AUTO OFFTRUE RMS
CAT III 600V
TEMP
K-TYPE
30V
MAX
SC57
OO
FF FF
WIRELESS ENABLED
SEL
SYNC
The  SRL2  contains  a  very  powerful  lithium  ion battery.  For  a  long battery life  and safe operation, you must observe the following:
Cautions
1. Do not expose the battery to temperatures high-
er than 140ºF (60°C).
2. Do not charge the battery in or nearby heated
places, such as fire, hot vehicles, or direct sun-
light.
3. Do not solder directly on battery.
4. Do not expose the battery to direct impact or
throw it.
5. Do not get the battery wet.
6. Do not deform or pierce the battery in any way.
7. If there is any battery leakage, do not touch the
battery. In the case that electrolyte gets into the
eyes, flush with fresh water, do not rub, and see
a physician immediately.
8. Replace immediately if there is any deformity,
bad smell, color change, or other abnormality.
9. The battery is user-replaceable and can be pur-
chased at most electronic stores. The following
batteries are known to be compatible with the
SRL2: Fuji Film:NP-120, PENTAX: DLI-7,
RICON: DB-43
Charging
Two chargers  are  included  with  the  SRL2.  The AC  charger  plugs  into  a  wall  outlet  and  the  car charger plugs into a car cigarette lighter DC plug.
1. The battery is partially charged when packaged.
Fully charge the battery before first use.
2. The LOW-BATT LED will light red when the bat-
tery is low.
3. To recharge the SRL2, plug one end of the
charger into the top of the SRL2 and the other
into the power source. LOW-BATT will blink
while charging until the battery is fully charged.
When the SRL2 battery is fully charged, LOW-
BATT turns off.
4. Charge within operating environment specified
in the Specifications section in this manual.
5. Avoid frequent full discharges. Several partial
discharges with frequent recharges are better
for lithium-ion batteries. Unlike nickel-based bat-
teries they have no charge memory, and do not
need to be discharged before charging.
Storage
The battery should have a 40%-50% charge dur­ing  prolonged  storage  of  a  month  or  longer. See Specifications section in this manual for proper stor­age environment. 
Battery life is  dramatically  reduced if the  battery is stored fully charged and/or at high temperatures.
Included Equipment
Use model RRE2 when detecting in tight spaces, such  as  through  a  condenser  grille.  Model  RFE2 extends the  wand to  25.5” (65cm). The blow  mold­ed case, model holds accessories and chargers.
All  accessories  shown  are  included  with  the SR2K7. 
9”(23cm) Flex
Extension
model RFE2
9”(23cm) Needle Tip Probe  model RRE2
Blow molded Carrying Case
w/ RRE2 and RFE2
Model ABMK3
Standalones from Fieldpiece
The SRL2   refrigerant  leak  detector  is designed for  HVAC/R  technicians.  Here  are  some  other standalone products from Fieldpiece Instruments.
SDMN5
Dual Port Manometer
SDP2
Dual In-duct Psychrometer
SC57
All-in-one Wireless Clamp-on Meter
Specifications
Sensing element: Enhanced infrared photo optics Sensor life: 10 years Refrigerants: HFC, CFC, HCFC, and blends  Sensitivity: Min (Stationary):  0.1oz/yr (3g/yr)
Max (Stationary): >1.05oz/yr (>30g/yr) Min (In motion): 0.18oz/yr (5g/yr) Max (In motion):  >1.05oz/yr (>30 g/yr) After exposure to (50g/yr): 0.1 oz/yr (3g/yr) In poluted environment: 0.1 oz/yr (3g/yr)
Response time: 1 second Recovery time: ~4 seconds Auto off: 10 minutes after no activity Battery: 3.7VDC(nominal), rechargeable lithium
ion user-replaceable battery.
Battery life: 8 hours continuous use prior to  need-
ing a charge. Degradation (30%) after 500 charge/discharge cycles or two years, whichever comes first.
Low battery LED: Lights when approximately 1
hour of battery life remains.
Charge time: Less than 4 hours (either charger) Operating environment: 32ºF (0°C) to 104ºF
Storage environment: <80%RH meter and batt.
(40°C) at <75%RH (non-condensing)
For 80% battery recovery:
-4ºF (-20°C) to 140ºF (60°C) less than 1 month
-4ºF (-20°C) to 113ºF (45°C) less than 3 months
-4ºF (-20°C) to 68ºF (20°C) less than 1 year
Notice of Compliance
More Products From Fieldpiece
This instrument  complies  with the specifications for an indicating, locating leak detector as described by  the  european  standard  EN  14624,  EN  14624 (2005)  with  the  assumption  that  the  speed specifi­cation  in  section  7.2  should  read as  "2.0  cm/s"  as was indicated to us by A. Beatrix Alke, project man­ager of Deutsches Institut fur Normung. 
Modular Expandability
Modular  expandability  is  ability  for  accessory heads  and  meters  to  change  configurations  to match the various needs of an HVAC/R technician.
Accessory  heads  (the  sensors)  send  out  a  mV signal, which represents  the value of the  measure­ment, to whatever meter is attached to it. Heads can attach directly to the  top of  a Stick meter, DL3 data logger, or EHDL1. They can also plug into any meter with mV ranges using ASLS2 leads.
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
Warranty and Service
The product is warranted to the original purchas­er against  defects in material or workmanship  for a period  of  one  (1)  year  from  the  date  of  purchase. During the  warranty  period,  Fieldpiece  Instruments will, at its option, replace or repair the defective unit. 
This warranty does not apply to defects resulting from abuse, neglect, accident,  unauthorized  repair, alteration,  or  unreasonable  use  of  the  instrument. Any  implied  warranty  arising  out  of  the  sale  of Fieldpiece's  products  including  but  not  limited  to implied warranties of merchantability and fitness for purpose  are  limited  to  the  above.  Fieldpiece  shall not  be  liable  for  incidental  or  consequential  dam­ages.
Return any defective SRL2 to Fieldpiece for war­ranty service  along with  proof of purchase. Contact Fieldpiece for out of warranty repair charges. 
v35, ©Fieldpiece Instruments, Inc. 2013
Loading...