Festo CPX-FB39 Description

Terminal CPX
Electronics description
Network protocol Sercos III
8028633
1504NH
[8028639]
Bus node CPX-FB39
Translation of the original instructions P.BE-CPX-FB39-EN
CODESYS®, SERCOS®, SPEEDCON® are registered trademarks of the respective trademark owners in certain countries.
Identification of hazards and instructions on how to prevent them:
Warning
Hazards that can cause death or serious injuries.
Caution
Hazards that can cause minor injuries or serious material damage.
Other symbols:
Note
Material damage or loss of function.
Recommendations, tips, references to other documentation.
Essential or useful accessories.
Information on environmentally sound usage.
Text designations:  Activities that may be carried out in any order.
1. Activities that should be carried out in the order stated. – General lists.
2 Festo – P.BE-CPX-FB39-EN – 1504NH – English
Bus node CPX-FB39
Table of Contents – Bus node CPX-FB39
1 Safety and requirements for product use 7......................................
1.1 Safety 7..................................................................
1.1.1 General safety instructions 7.........................................
1.1.2 Use for intended purpose 7...........................................
1.2 Requirements for product use 8...............................................
1.2.1 Technical requirements 9............................................
1.2.2 Qualification of the specialized personnel (requirements for the personnel) 9...
1.2.3 Range of application and certifications 9................................
1.2.4 Quoted guidelines and standards 9....................................
2 Installation 10..............................................................
2.1 General instructions on installation 10...........................................
2.2 Electrical connections and indicators 11..........................................
2.3 Mounting and dismantling 12..................................................
2.3.1 Mounting 12.......................................................
2.3.2 Dismantling 12.....................................................
2.3.3 Complying with degree of protection IP65/IP67 13.........................
2.4 Settings of the DIL switches on the bus node 14...................................
2.4.1 Removing and attaching the DIL switch cover 14...........................
2.4.2 Arrangement of the DIL switches 14.....................................
2.4.3 Setting the DIL switches 15...........................................
2.4.4 Setting the operating mode 15.........................................
2.4.5 Setting of the diagnostic mode (remote I/O) 16...........................
2.4.6 Setting of the I/O mode (remote controller) 17............................
2.4.7 Set the Sercos address 18............................................
2.5 Connecting to the network 19..................................................
2.5.1 General notes about Sercos networks 19.................................
2.5.2 Overview of connection technology and network plugs 19...................
2.5.3 Cable specification 20................................................
2.5.4 Network connections 20..............................................
2.5.5 Setting the IP address 21.............................................
2.5.6 Webserver function 22...............................................
2.6 Power supply 23.............................................................
3 Commissioning 24...........................................................
3.1 General points about Sercos III 24..............................................
3.2 Depiction of the CPX system on the Sercos-device model 25..........................
3.3 Device description 25........................................................
Festo – P.BE-CPX-FB39-EN – 1504NH – English 3
Bus node CPX-FB39
3.4 Address assignment 26.......................................................
3.4.1 Bus node 27........................................................
3.4.2 Digital modules 28..................................................
3.4.3 Analogue modules 31................................................
3.4.4 Technology modules 32...............................................
3.4.5 Determination of the address assignment 34..............................
3.5 Addressing 35..............................................................
3.5.1 Basic rules for addressing 35..........................................
3.5.2 Example 1: CPX terminal with electronic modules VMPA1 and VMPA2 36........
3.5.3 Example 2: CPX terminal with electrical interface (CP interface) 37............
3.5.4 Example 3: CPX terminal with analogue module and pneumatic interface 38.....
3.5.5 Address assignment after extension/conversion 39........................
3.6 Incorporation in the host system 40.............................................
3.6.1 Codesys control software 40...........................................
3.6.2 Installing device description files (SDDML files) 40.........................
3.6.3 Inserting field bus 42.................................................
3.6.4 Insert bus node 44..................................................
3.6.5 Inserting other modules 47............................................
3.6.6 I/O assignment 48...................................................
3.6.7 Changing parameters in Codesys 49.....................................
3.7 Parameterisation 50.........................................................
3.7.1 Introduction to parameterisation 50.....................................
3.7.2 Prerequisite for parameterization 51....................................
3.7.3 Methods of parameterisation 51.......................................
3.7.4 Parameterisation via the Festo Maintenance Tool (CPX-FMT) software 52.......
3.7.5 Parameterization with the control device (CPX-MMI) 52.....................
3.7.6 Parameterization via Sercos III 52......................................
4 Diagnostics and error handling 53..............................................
4.1 Summary of diagnostics options 53.............................................
4.2 Diagnostics via LED displays 54.................................................
4.2.1 Standard operating status 55..........................................
4.2.2 CPX-specific LEDs 55.................................................
4.2.3 Network-specific LEDs 57.............................................
4.3 Diagnostics via status bits 59..................................................
4.4 Diagnostics via the I/O diagnostics interface 60....................................
4.5 Diagnostics via Sercos III 61...................................................
4.5.1 Basic diagnostic functions 61..........................................
4.5.2 I/O diagnostics 61...................................................
4.5.3 I/O diagnostics with Festo-specific extensions 62..........................
4.6 Error handling 63............................................................
4 Festo – P.BE-CPX-FB39-EN – 1504NH – English
Bus node CPX-FB39
A Technical appendix 64........................................................
A.1 Technical data 64............................................................
A.2 List of abbreviations 65.......................................................
B Identification Numbers (IDNs) 67...............................................
B.1 Sercos Communication Profile (SCP) 67..........................................
B.1.1 Function Group - SCP Identification 67...................................
B.1.2 Function Group - Timing 67............................................
B.1.3 Function Group - Telegram Setup 67.....................................
B.1.4 Function Group - Control 68...........................................
B.1.5 Function Group - Bus Diagnosis 68......................................
B.1.6 Function Group - Connection 69........................................
B.1.7 Function Group - NRT 69..............................................
B.2 Generic Device Profile (GDP) 70................................................
B.2.1 Function Group - Diagnosis 70.........................................
B.2.2 Function Group - Administration 70.....................................
B.2.3 Function Group - Identification 71......................................
B.2.4 Function Group - Time 71.............................................
B.3 Function Specific Profile IO (FSP IO) 72...........................................
B.3.1 Function Group - Generic I/O 72........................................
B.3.2 Function Group - Bus Coupler 72.......................................
B.3.3 Manufacturer-specific extensions to the Function Specific Profile IO (FSP IO) 73..
B.4 Overview of the supported classes 74...........................................
B.4.1 Supported classes of the Sercos Communication Profile (SCP) 74.............
B.4.2 Supported classes of the Generic Device Profile (GDP) 74...................
C Diagnostic messages 75......................................................
C.1 Depiction of CPX diagnostic classes on Sercos diagnostic classes 75...................
C.2 Depiction of CPX diagnostic messages on Sercos status codes 75.....................
Index 79........................................................................
Festo – P.BE-CPX-FB39-EN – 1504NH – English 5
Bus node CPX-FB39
Instructions on this documentation
This description contains specific information about the installation, commissioning and diagnostics of the CPX bus node for Sercos III as well as specific information about Sercos III relating to the paramet erization, commissioning, programming and diagnostics of a CPX terminal in a Sercos III network.
You will find further information about Sercos III on the Internet: è www.sercos.org
General basic information about the mode of operation, mounting, installation and commissioning of CPX terminals can be found in the CPX system description (è P.BE-CPX-SYS-…). Information about additional CPX modules can be found in the description for the respective module.
An overview of the structure of user documentation for the CPX terminal can be found in the CPX system description (è P.BE-CPX-SYS-…).
Service
Please consult your regional Festo contact if you have any technical problems.
6 Festo – P.BE-CPX-FB39-EN – 1504NH – English

1 Safety and requirements for product use

1 Safety and requirements for product use

1.1 Safety

1.1.1 General safety instructions

 The general safety information in the corresponding chapters must be observed.
Special safety and danger warnings are written directly before the action instruction.
Please Note Damage to the product from incorrect handling.
 Switch off the supply voltage before mounting and installation work. Switch on sup
ply voltage only when mounting and installation work are completely finished.  Never unplug or plug in a product when powered!  Observe the handling specifications for electrostatically sensitive devices.

1.1.2 Use for intended purpose

The module described in this document, used in conjunction with a CPX terminal, makes it possible to connect up as a participant on a Sercos III network. The module is intended for use in an industrial environment. Outside of industrial environments, e.g. in commercial and mixed-residential areas, actions to suppress interference may have to be taken.
The module is intended exclusively for use in CPX terminals from Festo for installation in machines or automated systems and may be used only in the following ways: – In perfect technical condition – in original status without unauthorised modifications, except for the adaptations described in this
documentation
– within the limits of the product defined through the technical data (è A.1 Technical data).
Festo – P.BE-CPX-FB39-EN – 1504NH – English 7
1 Safety and requirements for product use
Warning
Electrical voltage Injury caused by electric shock, damage to machine and to system  For the electrical power supply, use only PELV circuits in accordance with
IEC 60204-1 (Protective Extra-Low Voltage, PELV).  Observe the general requirements of IEC 60204-1 for PELV circuits.  Use only voltage sources which guarantee reliable electrical isolation of the operat
ing and load voltage in accordance with IEC 60204-1.
, U
 Always connect all circuits for operating and load voltage supply U
U
.
OUT
EL/SEN
VAL
and
Through the use of PELV circuits, protection against electric shock (protection against direct and indir ect contact) is ensured in accordance with IEC 60204-1.
 Note the information about the power supply and about the applicable grounding
measures provided in the CPX system description (è P.BE-CPX-SYS-…).
Please Note
In the event of damage caused by unauthorised manipulation or other than intended use, the guarantee is invalidated and the manufacturer is not liable for damages.

1.2 Requirements for product use

 Make this documentation available to the design engineer, installer and personnel responsible for
commissioning the machine or system in which this product is used.
 Make sure that the specifications of the documentation are always complied with. Consider also the
documentation for other components and modules (e.g. CPX system description, P.BE-CPX-SYS-…).
 Take into consideration the legal regulations applicable for the location as well as:
– Regulations and standards – Regulations of the testing organisations and insurers – national specifications.
8 Festo – P.BE-CPX-FB39-EN – 1504NH – English
1 Safety and requirements for product use

1.2.1 Technical requirements

General conditions for the correct and safe use of the product, which must be observed at all times:  Comply with the connection and ambient conditions specified in the technical data of the product
(è Appendix A.1) and for all connected components. Only compliance with the limit values or load limits permits operation of the product in accordance with the relevant safety regulations.
 Observe the notes and warnings in this documentation.

1.2.2 Qualification of the specialized personnel (requirements for the personnel)

This description is directed exclusively to technicians trained in control and automation technology, who are experienced in: – the installation, commissioning, programming and diagnosis of programmable controllers (PLCs)
and field bus systems – the applicable regulations for operating safety-engineered systems – the applicable regulations for accident prevention and industrial safety – the documentation for the product.

1.2.3 Range of application and certifications

Standards and test values, which the product complies with and fulfils, can be found in the “Technical data” section (è Appendix A.1). The product-relevant EU directives can be found in the declaration of conformity.
Certificates and declaration of conformity on this product can be found at www.festo.com.

1.2.4 Quoted guidelines and standards

Issue status
ANSI/TIA-568-B.1-3:2003-02 IEC 61076-2:2011-06 IEC 60204-SER:2013-04 IEEE 802.3:2012 IEC 60204-1:2009-02 ISO/IEC 11801:2008-09 IEC 60529:2001-02
Tab. 1.1
Festo – P.BE-CPX-FB39-EN – 1504NH – English 9

2 Installation

2 Installation

2.1 General instructions on installation

Warning
Uncontrolled movement of the actuators, loose tubing, undefined switching states of the electronics Injury caused by moving parts, damage to machine and to system Before mounting and installation work:  Switch off the power supply  Switch off the compressed air supply  Vent the pneumatics.
Caution
The CPX bus node contains electrostatically sensitive devices.  Therefore, do not touch any components.  Observe the handling specifications for electrostatically sensitive devices. They will help you avoid damage to the electronics.
Please Note
Ensuring degree of protection IP65/IP67  Use cover caps or dummy plugs to seal unused connections
(è 2.3.3 Complying with degree of protection IP65/IP67).
10 Festo – P.BE-CPX-FB39-EN – 1504NH – English
2 Installation

2.2 Electrical connections and indicators

The following connections and displays are located on the bus node:
1 Network status and CPX-specific LEDs 2 Network connection X1 3 Network connection X2
1)
1)
4 DIL switch cover 5 Service interface2) for the control device
(CPX-MMI) or the Festo Maintenance Tool software (CPX-FMT)
1) Connection bush M12, D-coded, 4-pin
2) Connection bush M12, A-coded, 5-pin
Fig. 2.1
5
4
1
2
3
Festo – P.BE-CPX-FB39-EN – 1504NH – English 11
2 Installation

2.3 Mounting and dismantling

Warning
Electrical voltage Injury caused by electric shock, damage to machine and to system  Switch supply power off before assembly work.

2.3.1 Mounting

Please Note
Material damage due to incorrect mounting  Select screws that are suitable for the material of the interlinking block:
– plastic: thread-cutting tapping screws – metal: screws with metric thread.
When ordering an individual module, all the screws required are enclosed.
1. Check seal and sealing surface. Replace damaged parts.
2. Push the module carefully and without tilting into the interlinking block up to the stop.
3. Turn the screws into the existing thread.
4. Tighten the screws in diagonally opposite sequence. Tightening torque: 0.9 … 1.1 Nm.
1 Screws 2 Module 3 Interlinking block
Fig. 2.2
Please Note
In the Remote I/O operating mode, the bus node must be placed as the first module (slot 0) to the far left of the CPX terminal.

2.3.2 Dismantling

1. Unscrew screws.
2. Pull the module without tilting out of the interlinking block.
1
2
3
12 Festo – P.BE-CPX-FB39-EN – 1504NH – English
2 Installation

2.3.3 Complying with degree of protection IP65/IP67

 Use connection technology with type of protection IP65/IP67 (è www.festo.com/catalogue,
examples in Tab. 2.1).
 Use cover caps to seal unused connections.
connection
Network connection Plug connector NECU-M-S-D12G4-C2-ET ISK-M12 Service interface Connecting cable KV-M12-M12-…
1) Connecting cable for operator unit (CPX-MMI)
2) Included in the scope of delivery
Connection technology Cover cap
2)
1)
Tab. 2.1
Festo – P.BE-CPX-FB39-EN – 1504NH – English 13
2 Installation

2.4 Settings of the DIL switches on the bus node

In order to set the bus node, you must first remove the cover for the DIL switches.
Caution
The CPX bus node contains electrostatically sensitive devices.  Therefore, do not touch any components.  Observe the handling specifications for electrostatically sensitive devices. They will help you avoid damage to the electronics.

2.4.1 Removing and attaching the DIL switch cover

 Use an appropriate tool to remove or attach the DIL switch cover.
Please Note
Observe the following notes when removing or attaching the DIL switch cover:  Disconnect the power supply before removing the cover.  Make sure that the seal is seated correctly when attaching the cover!  Tighten the two mounting screws with a max. torque of 0.4 Nm.

2.4.2 Arrangement of the DIL switches

There are 3 DIL switches available for configuring the bus node. These are located under the DIL switch cover (è 2.4.1 Removing and attaching the DIL switch cover).
12
3
1 DIL switch 1:
– operating mode “remote I/O” – operating mode “remote controller”
2 DIL switch 2:
1)
– diagnostics mode (remote I/O) – I/O mode (remote controller)
3 DIL switch 3:
– Sercos address (1 … 255)
1) The function is dependent on the set operating mode (è DIL switch 1)
Fig. 2.3
14 Festo – P.BE-CPX-FB39-EN – 1504NH – English
2 Installation

2.4.3 Setting the DIL switches

1. Switch supply power off.
2. Remove DIL switch cover (è 2.4.1).
3. Perform required settings (è 2.4.4 … 2.4.7).
4. Reinstall DIL switch cover (è 2.4.1).
Please Note
Parameterisation via DIL switch settings is taken over only when the power supply is switched on.

2.4.4 Setting the operating mode

With the DIL switch element 1.1 on DIL switch 1 the operating mode of the bus node is set.
Operating mode Setting DIL switch 1
Remote I/O operating mode
All functions of the CPX terminal are controlled directly by the
1.1: OFF
(factory setting) Sercos controller or by a superordinate PLC/IPC. The bus node takes charge of connection to the Sercos III network.
Remote Controller operating mode
1.1: ON An FEC or CEC integrated into the CPX terminal controls all functions of the CPX terminal, i.e. the FEC or CEC undertakes the I/O control. The bus node takes charge of connection to the Sercos III network.
Tab. 2.2
Please Note
Setting of the operating mode via DIL switch 1 has priority over all other settings.
The switch element 1.2 of DIL switch 1 is reserved and without function.
Festo – P.BE-CPX-FB39-EN – 1504NH – English 15
2 Installation

2.4.5 Setting of the diagnostic mode (remote I/O)

The diagnostic mode is available only in the remote I/O operating mode.
Diagnostic mode (remote I/O operating mode) Setting DIL switch 2
I/O diagnostics interface and status bits are switched off 2.1 OFF
2.2 OFF (factory setting)
I/O diagnostics interface is switched on
1)
2.1 ON
2.2 OFF
Status bits are switched on
2)
2.1 OFF
2.2 ON
Reserved 2.1 ON
2.2 ON
1) The I/O diagnostic interface occupies an additional 16 input and 16 output bits
2) The status bits occupy an additional 16 input bits
Tab. 2.3
Please Note
The diagnostics mode reduces the available address space.  When planning your CPX terminal, consider that the number of input and output bits
available for communication is reduced with usage of the diagnostic mode. Subsequent activation of the diagnostics mode requires a reconfiguration.  Observe that the CPX-internal I/O image can be displaced during subsequent activa
tion of the diagnostics mode.  In this case, repeat the network configuration.
16 Festo – P.BE-CPX-FB39-EN – 1504NH – English
2 Installation

2.4.6 Setting of the I/O mode (remote controller)

The I/O mode is available only in the remote controller operating mode.
Number of I/O bytes (Remote Controller operating mode) Setting DIL switch 2
8 byte I/8 byte O for communication of the bus node with the CPX-FEC or CPX-CEC.
2.1 OFF
2.2 OFF (factory setting)
Reserved 2.1 ON
2.2 OFF
16 byte I/16 byte O for communication of the bus node with the CPX-FEC or CPX-CEC.
2.1 OFF
2.2 ON
Reserved 2.1 ON
2.2 ON
Tab. 2.4
Festo – P.BE-CPX-FB39-EN – 1504NH – English 17
2 Installation

2.4.7 Set the Sercos address

DIL switch elements 3.1 to 3.8 are used for setting the binary coding of the Sercos address.
If all switch elements of DIL switch 3 are in the OFF setting, the Sercos address can altered dynamically by write accesses to parameter S-0-1040.
Sercos address
Permitted addresses: – 1 … 255 (via DIL switches) – 0 … 511 (dynamically via S-0-1040)
1)
Factory reset: – 0 (DIL switch) – 254 (dynamic)
1) Only with dynamic address issue (all switch elements in the OFF setting)
Setting DIL switch 3
3.8: 2
3.7: 2
3.6: 2
3.5: 2
3.4: 2
3.3: 2
3.2: 2
12 34 56 78
3.1: 2
7
128
6
64
5
32
4
16
3
8
2
4
1
2
0
1
Tab. 2.5
Address 05 Address 38 Address 55 Address 106 Address 239
– –
– – + –
1234 5678
+
Address:–5
4
1
Address:+38
1234 5678
– –
32 – – +
4
+
2
Address:+55
1234 5678
– –
32
+
16 – +
4
+
2
+
1
Address:+106
1234 5678
– +
64
32 – +
8 – +
2 –
1234 5678
Address:
Tab. 2.6
+
128
+
64
+
32 – +
8
+
4
+
2
+
1
239
18 Festo – P.BE-CPX-FB39-EN – 1504NH – English
2 Installation

2.5 Connecting to the network

2.5.1 General notes about Sercos networks

Please Note
A Sercos network must always be structured as as ring or line topology. For this reason, the use of hubs or switches is not permitted.
Please Note
Connecting a PC to the Sercos network (e.g. to use the bus node with the CPX-FMT soft ware). – With line topology:
 Connect the PC to the free port of the Sercos slave.
– With ring topology:
 Use a network tap suitable for Sercos.
Please Note
Sub-assemblies with Ethernet interfaces should only be operated in networks if all con nected network components are supplied by PELV circuits or integrated power circuits with equivalent protection.
Installation guidelines
Installation guidelines can be sourced from the Sercos user organization (è http://www.sercos.org).

2.5.2 Overview of connection technology and network plugs

Note
Faulty installation and high transmission rates may cause data transmission errors as a result of signal reflections and attenuations.  Note wiring specification (è Tab. 2.8). Transmission errors can be caused by: – faulty screened connection – branches – transmission over distances which are too long – unsuitable cables.
Connection technology Network connectors
2 x M12 bush, D-coded, 4-pin, in accordance with IEC 61076-2, SPEEDCON compatible
Tab. 2.7
Festo – P.BE-CPX-FB39-EN – 1504NH – English 19
Plug connector NECU-M-S-D12G4-C2-ET
2 Installation

2.5.3 Cable specification

 Use sheathed Industrial Ethernet wiring of category Cat 5 or higher.
The bus node supports the “crossover detection” function (Auto-MDI/MDI-X). To connect the bus node to the network or to a PC, this means you can choose between patch cables or crossover cables. The circuitry for network connections X1 and X2 is adapted automatically.
CPX-FB39
Cable specification
Cable type Industrial Ethernet cable, screened Transmission class Category Cat 5 Cable diameter 6 … 8 mm Wire cross section 0.14 … 0.75 mm², AWG 22 Connection length Maximum 100 m
1) Required for maximum connection length between the network participants
2) corresponding to specification for Ethernet networks, based on ISO/IEC 11801, ANSI/TIA/EIA-568
2)
1)
Tab. 2.8
Please Note
When mounting the CPX terminal on a moving part of a machine.  Use network wiring with tension relief.  Note corresponding stipulations of IEC 60204.

2.5.4 Network connections

There are two 4-pin, D-coded M12 sockets on the bus node for the network connection. The sockets are compatible with SPEEDCON plugs.
1)
Socket M12, 4-pin Pin
1 2 3 4
1) Functional earth is accomplished via the housing.
Connection [X1] Connection [X2] Signal Explanation Signal Explanation
TX+ RX+ TX– RX–
Transmitted data + Received data + Transmitted data – Received data –
RX+ TX+ RX– TX–
Received data + Transmitted data + Received data – Transmitted data –
Tab. 2.9
Functional earth
Please Note
The shielded connection for both network connections is linked by RC element to the ground potential of the CPX terminal.  Connect the ground connection of left-hand terminal plate in a low-current and
low-impedance manner to the ground potential (è CPX system description P.BE-CPX-SYS-…).
20 Festo – P.BE-CPX-FB39-EN – 1504NH – English
2 Installation

2.5.5 Setting the IP address

Alternatively the IP address for the bus node can be set via: – Dynamic addressing via DHCP/BOOTP – Stored network setting.
The IP address is factory-set to 192.168.1.20.
Dynamic addressing via DHCP/BOOTP
Make sure that a DHCP/BOOTP server is located in the network.  Alternatively activate dynamic addressing by DHCP/BOOTP via:
– Operator unit (CPX-MMI) – Festo Maintenance Tool (CPX-FMT) software – Sercos IDNs.
Saved network settings
The bus node CPX-FB39 offers the option of saving network settings in a non-volatile memory unit. DHCP/BOOTP is thereby deactivated.  Alternatively change the network settings via:
– Operator unit (CPX-MMI) – Festo Maintenance Tool (CPX-FMT) software – Higher-order system – Sercos IDNs.
This activates saving of the network settings.
Festo – P.BE-CPX-FB39-EN – 1504NH – English 21
2 Installation

2.5.6 Webserver function

A web server is integrated in the bus node CPX-FB39. It makes available read access to the most im portant parameters and diagnostic functions of the CPX terminal.
Procedure
1. Open an Internet browser on a PC with a connection to the network.
2. Enter the set/identified IP address of the bus node in the address line of the Internet browser (è 2.5.5 Setting the IP address).
Fig. 2.4
22 Festo – P.BE-CPX-FB39-EN – 1504NH – English
2 Installation

2.6 Power supply

The operating and load voltage supply is directed via the interlinking blocks (è CPX system descrip tion P.BE-CPX-SYS-…).
Warning
Electrical voltage Injury caused by electric shock, damage to machine and to system  For the electrical power supply, use only PELV circuits in accordance with
IEC 60204-1 (Protective Extra-Low Voltage, PELV).  Observe the general requirements of IEC 60204-1 for PELV circuits.  Use only voltage sources which guarantee reliable electrical isolation of the operat
ing and load voltage in accordance with IEC 60204-1.  Always connect all circuits for operating and load voltage supply U
U
.
OUT
/SEN, U
EL
Through the use of PELV circuits, protection against electric shock (protection against direct and indir ect contact) is ensured in accordance with IEC 60204-1.
Note the information about the power supply and about the applicable grounding meas ures (è CPX system description P.BE-CPX-SYS-…).
VAL
and
Festo – P.BE-CPX-FB39-EN – 1504NH – English 23

3 Commissioning

3 Commissioning
Please Note
Only commission a correctly installed CPX terminal (è 2 Installation).
Please Note
A firmware update can be performed by the Festo Field Device Tool (FFT). The current version is available on the Festo Support Portal on the Internet (è www.festo.com/sp).
– General information on commissioning the CPX terminal as well as a detailed
description of individual parameters is found in the CPX system description (è P.BE-CPX-SYS-…).
– Information on commissioning the analogue pneumatic interfaces and I/O modules
can be found in the description (è P.BE-CPX-EA-…).
– Instructions on commissioning the pneumatic components can be found in the corres
ponding description of pneumatics.

3.1 General points about Sercos III

Please Note
The bus node CPX-FB39 is a remote I/O system that communicates with the Sercos controller via the Sercos IO profile (Function Specific Profile IO).
Sercos III is an Ethernet-based communication protocol for automation applications. Communication on a Sercos III network is based on the time-stop process with cyclical data transmis sion in the form of telegrams based on the master-slave principle. This combines real-time and non­real-time communication channels in a communication system.
Real Time Channel (RTC)
During transmission in real-time, a distinction is made between two types of telegram. – Master data telegram (MDT): For communication of nominal/setpoint data from master to slaves. – Acknowledge telegram (AT): For communication of status data from slaves to master and for trans
verse communication between the individual controllers or slaves.
Non-real-time channel (Universal Communication Channel - UCC)
For the exchange of standard Ethernet telegrams between any participants on the network.
You will find further information about Sercos III on the Internet: è www.sercos.org
24 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning

3.2 Depiction of the CPX system on the Sercos-device model

The underlying depiction of the CPX system on Sercos is illustrated by the next graphic (è Fig. 3.1). The CPX system is illustrated here as a Sercos device with a Sercos interface, a Sercos slave and the associated sub device. Communication is performed by the Sercos interface and the Sercos slave. Gen eric parts of the device application are implemented as part of the sub device. The resource IO is as signed to the sub device: It depicts the Sercos function profile (Function Specific Profile IO) and in cludes a depiction of the individual CPX modules on Sercos.
CPX system CPX modules
1
corresponds
Device (logical)
owns owns
11
Sercos interface
consists uses
1
Generic Device Profile Function Specific Profile IO
11
1
Sub Device Resource IO
includes
Sercos slave
Sercos Communication Profile
0…n1 1…n
includesincludes
11
11
0…n1
Physical structure
Application
communication
Sercos-III network
Fig. 3.1

3.3 Device description

During initial commissioning of a Sercos participant, the controller software is notified of certain prop erties of the participant. These properties are administered in what are known as device description files in standardized XML format. The device description of Sercos-III devices is in the form of SDDML files (Sercos Device Description Markup Language) and is based on the Sercos-III device model. This provides a separate device de scription file for each device.
The device description files (SDDML files) are available on the Festo support portal on the Internet (è www.festo.com/sp).
Festo – P.BE-CPX-FB39-EN – 1504NH – English 25
3 Commissioning

3.4 Address assignment

A CPX terminal consists of a different number of inputs and outputs, depending on your order and the configuration of the bus node. The inputs and outputs are assigned automatically within the CPX terminal.
When using device description files (SDDML files) the controller software can extrapolate the complete address assignment automatically.
Warning
Uncontrolled movement of the actuators, undefined switching statuses. Injury to people, damage to the machine and system. The byte sequence of the process data is Little Endian.  Ensure that the process data is interpreted correctly.
Please Note
– Including bus nodes, a maximum of 10 electrical modules plus a pneumatic interface
and/or MPA pneumatic module is permitted in a CPX terminal.
– The address space of a CPX terminal is limited. The bus node provides the CPX ter
minal a maximum address space of 64 bytes for inputs and 64 bytes for outputs. – An activated diagnostic mode reduces the number of available I/O bytes. – Each module of the CPX terminal occupies a specific number of bits, bytes or words
for module communication.
 Establish the address assignment (number of allocated inputs/outputs) on the CPX terminal prior to
commissioning.
Tab. 3.8 serves to determine the address assignment and/or the number of assigned inputs and outputs on the CPX terminals. The number of assigned inputs and outputs for modules can be found in the following tables: – Bus node CPX-FB39:
– FG S-0-1500.SI.0 – Bus Coupler (è Tab. 3.1)
– Digital modules:
– FG S-0-1502.SI.0 – Digital Output (è Tab. 3.2) – FG S-0-1503.SI.0 – Digital Input (è Tab. 3.3).
– Analog modules:
– FG S-0-1504.SI.0 – Analog Output (è Tab. 3.4) – FG S-0-1505.SI.0 – Analog Input (è Tab. 3.5).
– Technology modules:
– FG S-0-1507.SI.0 – Complex Protocol (è Tab. 3.6) – FG S-0-1508.SI.0 – Sub Bus Master(è Tab. 3.7).
26 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning

3.4.1 Bus node

FG S-0-1500.SI.0 (Bus Coupler)
Bus node CPX-FB39 Module type Module
identifiers
Allocated address space
1)
Inputs Outputs
Remote I/O operating mode
without diagnostics mode CPX-FB39 FB39-RIO – Status bits
I/O diagnostics interface Remote Controller operating mode
1) Module identifier in the operator unit or in the hardware configuration of the programming software.
2) The additional input data are set up as FG S-0-1503.SI.0 (Digital Inputs).
3) Diagnostic mode status bits assigns 2 byte address space (8 inputs and/or 8 bits remain unused).
4) The additional input and output data are set up as FG S-0-1507.SI.0 (Complex Protocol).
5) Assigned address space depends upon the setting of DIL switch 2.2.
2)
4)
1x 16 bit3)– 1x 16 bit 1x 16 bit
CPX-FB39 FB39-RC 8x 8bit
4)
8x 16 bit
Tab. 3.1
If the bus node is operated in Remote Controller operating mode, then only the FG Bus Coupler with additional FG Complex Protocol is depicted on structural entity 0. No depic tion of I/O modules takes place on Sercos objects.
5)
8x 8 bit 8x 16 bit
5)
Festo – P.BE-CPX-FB39-EN – 1504NH – English 27
3 Commissioning

3.4.2 Digital modules

FG S-0-1502.SI.0 (Digital Output)
Module designation Module type Module
identifiers
Allocated address space
1)
Inputs Outputs
Output module
4-fold CPX-4DA 4DO 4x 1 bit 8-fold CPX-8DA 8DO 8x 1 bit 8-fold (high current) CPX-8DA-H 8DO-H 8x 1 bit
Input/output module
each 8x CPX-8DE-8DA 8DI/8DO 8x 1 bit each 8-fold (with terminal strip)
CPX-L-8DE-8DA-16-KL­3POL
L-8DI8DO-PI 8x 1 bit
3)
3)
Electronics module
for MPA1 pneumatics module
VMPA1-FB-EMS-8 MPA1S 8x 1 bit (1 … 8 valves) for MPA2 pneumatic module
VMPA2-FB-EMS-4 MPA2S 8x 1 bit (1 … 4 valves)
Electronics module (electrically isolated)
for MPA1 pneumatics module
VMPA1-FB-EMG-8 MPA1G 8x 1 bit (1 … 8 valves) for MPA2 pneumatic module
VMPA2-FB-EMG-4 MPA2G 8x 1 bit (1 … 4 valves)
Electrical module with diagnostic function
for MPA1 pneumatics module
VMPA1-FB-EMS-D2-8 MPA1S-D 8x 1 bit (1 … 8 valves) for MPA2 pneumatic module
VMPA2-FB-EMS-D2-4 MPA2S-D 8x 1 bit (1 … 4 valves)
Electrical module with diagnostic function (electrically isolated)
for MPA1 pneumatics module
VMPA1-FB-EMG-D2-8 MPA1G-D 8x 1 bit (1 … 8 valves) for MPA2 pneumatic module
VMPA2-FB-EMG-D2-4 MPA2G-D 8x 1 bit (1 … 4 valves)
1) Module identifier in the operator unit or in the hardware configuration of the programming software.
2) Digital 4x output modules (CPX-4DA) always occupy 8 outputs or 1 byte of address space.
3) Input data è FG S-0-1503.SI.0 (Digital Input)
4) VMPA1 modules always occupy 8 outputs regardless of the number of valves fitted.
5) VMPA2 modules always occupy 8 outputs, although only 4 bits are used.
6) Setting via DIL switches of the pneumatic interface.
2)
8x 1 bit 8x 1 bit
4)
5)
4)
5)
4)
5)
4)
5)
28 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning
Module designation Allocated address spaceModule
Module typeModule designation
Module type
Module identifiers
identifiers
1)
1)
End plate (pneumatic interface
for valve terminal MPA-S VMPA-FB-EPL-… – for valve terminal MPA-F VMPAF-FB-EPL-… – for valve terminal MPA-L VMPAL-FB-EPL-…
1 ... 4 solenoid coils 8x 1 bit 1 ... 8 solenoid coils 8x 1 bit 1 ... 16 solenoid coils 16x 1 bit 1 ... 24 solenoid coils 24x 1 bit 1 ... 32 solenoid coils 32x 1 bit
Pneumatic interface
for valve terminal VTSA-/VTSA-F with setting:
6)
VABA-… VTSA -
type 44/45
1 ... 8 solenoid coils 8x 1 bit 1 ... 16 solenoid coils 16x 1 bit 1 ... 24 solenoid coils 24x 1 bit 1 ... 32 solenoid coils 32x 1 bit
1) Module identifier in the operator unit or in the hardware configuration of the programming software.
2) Digital 4x output modules (CPX-4DA) always occupy 8 outputs or 1 byte of address space.
3) Input data è FG S-0-1503.SI.0 (Digital Input)
4) VMPA1 modules always occupy 8 outputs regardless of the number of valves fitted.
5) VMPA2 modules always occupy 8 outputs, although only 4 bits are used.
6) Setting via DIL switches of the pneumatic interface.
Tab. 3.2
OutputsInputs
Festo – P.BE-CPX-FB39-EN – 1504NH – English 29
3 Commissioning
FG S-0-1503.SI.0 (Digital Input)
Module designation Module type Module
identifiers
Allocated address space
1)
Inputs Outputs
input module
4-fold CPX-4DE 4DI 4x 1 bit
2)
8 valves CPX-8DE 8DI 8x 1 bit – 8-fold (n-switching) CPX-8NDE 8NDI 8x 1 bit – 8-fold (with channel
CPX-8DE-D 8DI-D 8x 1 bit – diagnostics) 16 valves CPX-16DE 16DI 16x 1 bit – 16-fold (with channel
CPX-M-16DE-D 16DI-D 16x 1 bit – diagnostics) 16-fold (with terminal strip) CPX-L-16DE-16-KL-3POL L-16DI-PI 16x 1 bit
INPUT/OUTPUT MODULE
each 8x CPX-8DE-8DA 8DI/8DO 8x 1 bit 8x 1 bit each 8-fold (with terminal strip)
1) Module identifier in the operator unit or in the hardware configuration of the programming software.
2) Digital quadruple input modules (CPX-4DE ) always occupy 8 inputs.
3) Output data è FG S-0-1502.SI.0 (Digital Output)
CPX-L-8DE-8DA-16-KL-
3POL
L-8DI8DO-PI 8x 1 bit 8x 1 bit
Tab. 3.3
– The address assignment within the individual CPX I/O modules can be found in the
description for the I/O modules (è P.BE-CPX-EA-…).
– Information about pneumatic interfaces and pneumatic modules can be found in the
corresponding pneumatics descriptions.
– An overview of the “Descriptions of the CPX terminal” documentation can be found in
the CPX system description (è P.BE-CPX-SYS-…).
– From the technical point of view, the individual pneumatic modules each represent an
electric module for controlling the attached valves.
3)
3)
30 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning

3.4.3 Analogue modules

FG S-0-1504.SI.0 (Analog Output)
Module designation Module type Module
identifiers
Allocated address space
1)
Inputs Outputs
Analog module (2 outputs) CPX-2AA-U-I 2AO 2x 16 Bit Proportional pressure regulator VPPM-…TA-L-1-F… VPPM 1x 16 bit2)1x 16 bit
1) Module identifier in the operator unit or in the hardware configuration of the programming software.
2) Input data è FG S-0-1505.SI.0 (analog input)
Tab. 3.4
FG S-0-1505.SI.0 (Analog Input)
Module designation Module type Module
identifiers
Allocated address space
1)
Inputs Outputs
Pressure sensors VMPA-FB-PS-… MPA-P 1x 16 bit – Proportional pressure regulator VPPM-…TA-L-1-F… VPPM 1x 16 bit 1x 16 bit Analogue module
2 inputs CPX-2AE-U-I 2AI 2x 16 Bit – 4 inputs CPX-4AE-U-I 4AI 4x 16 bit – 4 inputs CPX-4AE-I 4AI-I 4x 16 bit – 4 inputs (temperature module for RTD sensors) 4 inputs (temperature module
CPX-4AE-T 4AI-T 2x 16 Bit
3)
4x 16 bit
CPX-4AE-TC 4AI-TC 4x 16 bit
for TC sensors) 4 inputs (pressure sensor
CPX-4AE-P-D10 4AI-P-D10 4x 16 bit – module 0 … 10 bar) 4 inputs (pressure sensor
CPX-4AE-P-B2 4AI-P-B2 4x 16 bit – module –1 … 1 bar)
1) Module identifier in the operator unit or in the hardware configuration of the programming software.
2) Output data è FG S-0-1504.SI.0 (analog output)
3) Depending on the configuration.
Tab. 3.5
2)
The address assignment within the individual CPX analogue I/O modules can be found in the description for the analogue I/O modules (è P.BE-CPX-AX-…).
Festo – P.BE-CPX-FB39-EN – 1504NH – English 31
3 Commissioning

3.4.4 Technology modules

FG S-0-1507.SI.0 (Complex Protocol)
Module designation Module type Module
identifiers
Allocated address space
1)
Inputs Outputs
INPUT/OUTPUT MODULE CPX-2ZE2DA 2CI2DO 3x 32 bit 3x 32 bit Axis controller CPX-CMAX-C1-1 CMAX-C1-C 8x 8bit 8x 8 bit Control block
CPX-CMXX CMXX 8x 16 bit 8x 16 bit (multi-axis interface) End-position controller CPX-CMPX-C-1-H1 CMPX-C-1 6x 8 bit 6x 8 bit Control block
CPX-CM-HPP CM-HPP 32x 8 bit 32x 8 bit (FHPP interface) Measuring module CPX-CMIX-CM-M1-1 CMIX 3x 16 bit 3x 16 bit
1) Module identifier in the operator unit or in the hardware configuration of the programming software.
Tab. 3.6
FG S-0-1508.SI.0 (Sub bus Master)
Module designation Module type Module
identifiers
Electrical interface
CPX-CP-4-FB CPI maximum (CP interface) Electrical interface
CPX-CTEL-4-M12-5POL CTEL
Allocated address space
1)
Inputs Outputs
maximum
2)
16x 8 bit
16x 8 bit
with setting:
0E/0A byte – 0E/8A byte 8x 8bit 0E/16A byte 16x 8 bit 0E/24A byte 24x 8 bit 0E/32A byte 32x 8 bit 8E/0A byte 8x 8bit – 16E/0A byte 16x 8 bit – 24E/0A byte 24x 8 bit – 32E/0A byte 32x 8 bit – 8E/8A byte 8x 8bit 8x 8bit 16E/16A byte 16x 8 bit 16x 8 bit 24E/24A byte 24x 8 bit 24x 8 bit 32E/32A byte 32x 8 bit 32x 8 bit
1) Module identifier in the operator unit or in the hardware configuration of the programming software.
2) Maximum assigned address space is dependent on the string allocation
2)
32 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning
Module designation Allocated address spaceModule
Electrical interface with setting:
Module typeModule designation
Module type
Module identifiers
identifiers
CPX-CTEL-2-M12-5POL-LK CTEL-2-LK
I-port LK
1)
1)
master 8E/8A byte 8x 8bit 8x 8bit 16E/16A byte 16x 8 bit 16x 8 bit 24E/24A byte 24x 8 bit 24x 8 bit
1) Module identifier in the operator unit or in the hardware configuration of the programming software.
2) Maximum assigned address space is dependent on the string allocation
Tab. 3.7
Details on the technology modules can be found in the corresponding descriptions (è P.BE-CPX-…).
OutputsInputs
Festo – P.BE-CPX-FB39-EN – 1504NH – English 33
3 Commissioning

3.4.5 Determination of the address assignment

Tab. 3.8 serves to determine the address assignment and/or the number of assigned inputs and outputs on the CPX terminals.
Modules (analogue/digital) and diagnostics mode Inputs Outputs
bus node
With status bits + 16 I + _____ I
with I/O diagnostics interface + 16 I/O + _____ I + _____ O
Analogue modules
CPX-2AE-U-I + ___ x 32 I + _____ I
CPX-4AE-I, CPX-4AE-U-I, CPX-4AE-P-…, CPX-4AE-TC + ___ x 64 I + _____ I
CPX-4AE-T + ___ x 32/64 I1)+ _____ I
CPX-2AA-U-I + ___ x 32 O + _____ O
VMPA-FB-PS-… (pressure sensors) + ___ x 16 I + _____ I
VPPM-…TA-L-1-F… (Proportional pressure regulators) + __ x 16 I/O + _____ I + _____ O
Technology modules
e.g. CPX-CMAX-C1-1, CPX-2ZE2DA, CPX-CP-4-FB + ___ I/O + _____ I + _____ O
Digital modules
CPX-4DE, CPX-8DE, CPX-8NDE, CPX-8DE-D + ___ x 8 I
2)
+ _____ I
CPX-16DE, CPX-M-16DE-D, CPX-L-16DE-16-KL-3POL + ___ x 16 I + _____ I
CPX-4DA, CPX-8DA, CPX-8DA-H + ___ x 8 O
2)
+ _____ O
CPX-8DE-8DA, CPX-L-8DE-8DA-16-KL-3POL + __ x 8 I/O + _____ I + _____ O
VMPA1-…, VMPA2-… (Pneumatic modules) + ___ x 8 O
2)
+ _____ O
VMPAL-…, VABA-… (pneumatic interfaces) Number of configured valve solenoid coils (+8 O … 32 O)
3)
+ _____ O
Sum total of the assigned inputs and outputs of your CPX terminal (maximum 512 I and 512 O): = _____ I = _____ O
1) The number of inputs is dependent on the setting.
2) Digital modules with 4 inputs or outputs (CPX-4DE, CPX-4DA ) as well as electric modules and electronic modules VMPA2 always
occupy 8 inputs or 8 outputs.
3) At the factory, 32 O (VABA, VMPAL) are configured.
Tab. 3.8
34 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning

3.5 Addressing

3.5.1 Basic rules for addressing

– The address assignment of the inputs does not depend on the address assignment of the outputs. – Counting is byte-wise from left to right, in ascending order without gaps.
Even modules with less than 8 bits occupy 8 bits of address space, but do not use all this space.
– The bus node counts as a module with 0 inputs and 0 outputs when the status bits and the I/O dia
gnostic interface are deactivated.
Please Note
Address assignment with activated status bits or activated I/O diagnostics interface. – If the 8 status bits are activated, these occupy the first 16 inputs in the address
range, although only 8 inputs are used.
– If the I/O diagnostics interface is activated, it will occupy the first 16 inputs and
outputs in the address range.
– The inputs and outputs of various different types of module are assigned separately from one an
other, and the sequence depends on the arrangement of modules in the CPX terminal. – Input data: S-0-1500.SI.9 (Container Input Data) – Output data: S-0-1500.SI.5 (Container Output Data).
Please Note
In the Remote I/O operating mode, the bus node must be placed as the first module (slot 0) to the far left of the CPX terminal.
Festo – P.BE-CPX-FB39-EN – 1504NH – English 35
3 Commissioning

3.5.2 Example 1: CPX terminal with electronic modules VMPA1 and VMPA2

The following graphic shows a CPX terminal with electronic modules VMPA1 and VMPA2 and the follow ing setting: – status bits and I/O diagnostics interface deactivated.
Module no.: 0
1
8DI 4DO
23456
12
1 Bus node CPX-FB39 2 End plate VMPAL (pneumatic interface)
3
4
3 Electronic module VMPA1 (8DA) 4 Electronic module VMPA2 (4DA)
Fig. 3.2
The following diagram shows an example of the address assignment for the CPX terminal depicted:
No. Module Function group
0 CPX-FB39 1 CPX-8DE S-0-1503.1.9 2 CPX-4DA S-0-1502.2.5 3 VMPA-1 (8DA) S-0-1502.3.5 4 VMPA-1 (8DA) S-0-1502.4.5 5 VMPA-2 (4DA) S-0-1502.5.5 6 VMPA-2 (4DA) S-0-1502.6.5
1) 8 bit assigned, 4 bit used
S-0-1500.0.9 (input data 1 byte)
S-0-1503.1.9 (module 1) 8 bit
S-0-1500.0.5 (output data 5 byte)
S-0-1502.2.5 (module 2) 8 bit
1)
S-0-1502.3.5 (module 3) 8 bit S-0-1502.4.5 (module 4) 8 bit S-0-1502.5.5 (module 5) 8 bit S-0-1502.6.5 (module 6) 8 bit
1)
1)
Fig. 3.3
36 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning
)

3.5.3 Example 2: CPX terminal with electrical interface (CP interface)

The following graphic shows a CPX terminal with electrical interface and the following setting: – status bits and I/O diagnostics interface deactivated.
123 4 5
8DI 4DO 8DI 8DO
1
2
3
6Module no.: 0
4
5
6
1 Bus node CPX-FB39 2 CPV valve terminal (16DO) on string 1 of the
electrical interface
3 cylinders
4 CP input module (16DI) 5 Sensor 6 CP output module (16DO) on string 4 of the
electrical interface
Fig. 3.4
The following diagram shows an example of the address assignment for the CPX terminal depicted:
No. Module Function group
0 CPX-FB39 1 CPX-8DE S-0-1503.1.9 2 CPX-4DA S-0-1502.2.5 3 CPX-CP-4-FBI
1)
S-0-1508.3.9 S-0-1508.3.5
4 CPX-8DE-8DA S-0-1503.4.9
S-0-1502.4.5 5 VMPA-1 (8DA) S-0-1502.5.5 6 VMPA-1 (8DA) S-0-1502.6.5
1) Here 4 byte inputs and 16 byte outputs 2) 8 bit assigned, 4 bits used
S-0-1500.0.9 (input data 6 byte
S-0-1503.1.9 (module 1) 8 bit S-0-1508.3.9 (module 3) 4x 8 bit S-0-1503.4.9 (module 4) 8 bit
S-0-1500.0.5 (output data 20 byte)
S-0-1502.2.5 (module 2) 8 bit S-0-1508.3.5 (module 3) 16x 8 bit
2)
S-0-1502.4.5 (module 4) 8 bit S-0-1502.5.5 (module 5) 8 bit S-0-1502.6.5 (module 6) 8 bit
Fig. 3.5
Festo – P.BE-CPX-FB39-EN – 1504NH – English 37
3 Commissioning

3.5.4 Example 3: CPX terminal with analogue module and pneumatic interface

The following graphic shows a CPX terminal with pneumatic interface and the following setting: – status bits activated and I/O diagnostic interface deactivated – pneumatic interface set with DIL switch to 1 ... 8 solenoid coils (8 DO).
Module no.: 0 1 2 3 4 5 6
8DI 8DI 4DO 8DI 2AO
12
1 Bus node CPX-FB39 (status bits activated)
8DO
3
3 VTSA pneumatics
2 Pneumatic interface (set with DIL switch to
1 ... 8 solenoid coils)
Fig. 3.6
The following diagram shows an example of the address assignment for the CPX terminal depicted:
No. Module Function group
0 CPX-FB39 S-0-1503.0.9 1 CPX-8DE S-0-1503.1.9 2 CPX-8DE S-0-1503.2.9 3 CPX-4DA S-0-1502.3.5 4 CPX-8DE-8DA S-0-1503.4.9
S-0-1502.4.5 5 CPX-2AA-U-I S-0-1504.5.5 6 VABA (8DA)
1) 16 bit assigned, 8 bit used
2) 8 bit assigned, 4 bits used
3)
S-0-1502.6.5
S-0-1500.0.9 (input data 5 byte)
S-0-1503.0.9 (module 0) 16 bit S-0-1503.1.9 (module 1) 8 bit S-0-1503.2.9 (module 2) 8 bit S-0-1503.4.9 (module 4) 8 bit
S-0-1500.0.5 (output data 7 byte)
S-0-1502.3.5 (module 3) 8 bit S-0-1502.4.5 (module 4) 8 bit S-0-1504.5.5 (module 5) 2x 16 bit S-0-1502.6.5 (module 6) 8x 1 bit
3) Set via DI L switches to 1 … 8 valve coils
1)
2)
Fig. 3.7
38 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning

3.5.5 Address assignment after extension/conversion

If the requirements for the machine or system change, the CPX terminal can be adapted as required due to its modular design.
Caution
If the CPX terminal is extended or converted at a later stage, input/output addresses may be shifted. This applies in the following cases: – Additional modules are inserted between existing modules. – Existing modules are removed or replaced by other modules which have fewer or
more input/output addresses.
– Interlinking blocks or pneumatic connection blocks for monostable valves are re
placed by interlinking blocks/connection blocks for bistable valves or vice versa
(è Pneumatics description). – Additional interlinking blocks or connection blocks are inserted between existing ones. – Status bits or the I/O diagnostic interface are activated/deactivated. – The configured addresses of the pneumatic interface are modified.
Please Note
If the configuration of a CPX terminal was changed, new requirements for the CPX ter minal that may be necessary must be checked and adjusted, if necessary.
Moreover, it should be noted that the needed address space may increase due to modific ation of the CPX terminal and thus the slave addresses of the following slaves in the net work must be checked and adjusted if necessary.
Festo – P.BE-CPX-FB39-EN – 1504NH – English 39
3 Commissioning

3.6 Incorporation in the host system

3.6.1 Codesys control software

To incorporate a CPX terminal in a Sercos-III network you can for example use Codesys control software from 3S (Smart Software Solution) (è www.codesys.com).
The contents of this documentation serve as an example of the use of Codesys software and relate to version 3.5 SP4 in the Professional presentation format and an English language setting.
The user interface for this software can be adapted individually and the window arrangement can be changed. The following illustration shows a possible layout for the user interface.
4
1
2
3
1 Parameter register (“Parameter tab”) 2 Editor window (“Editor window”)
Fig. 3.8

3.6.2 Installing device description files (SDDML files)

To insert the module extension of your CPX terminal in the control software and to be able to configure it, the device description files (SDDML files) of all modules used in the CPX terminal need to be installed once.
The device description files (SDDML files) are available on the Festo support portal on the Internet (è www.festo.com/sp).
Please Note
Requirements for execution of the subsequent steps: – Device description files (SDDML files) downloaded from the Festo Support Portal
and unpacked.
40 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Device window (“Device window”) 4 Device tab (“Device tab”)
3 Commissioning
Approach:
1. Start Codesys software.
2. Menu Tools (“Tools”) > Device Repository… (“Device Repository…”). The device repository dialog (“Device Repository”) opens up.
Fig. 3.9
3. Press the Install button … (“Install…”). The “Install Device Description”dialog opens up.
Fig. 3.10
4. Mark the required XML files and press the “Open”button. The selected device description files (SDDML files) are then installed.
The device description files (SDDML files) are then available in the Codesys control software.
Festo – P.BE-CPX-FB39-EN – 1504NH – English 41
3 Commissioning

3.6.3 Inserting field bus

Please Note
Requirements for execution of the subsequent steps: – Codesys project set up with programmable controller (PLC) – Device description files (SDDML files) available in Codesys
(è 3.6.2 Installing device description files (SDDML files)).
Procedure
1. Highlight entry of device in device window (“Device window”).
2. Project menu (“Project”) > Add device… (“Add Device…”). The “Add Device”dialog opens up.
Fig. 3.11
3. Extend the “sercos”entry and highlight the “sercos Master”entry.
4. Press the “Add Device”button. The “sercos Master”entry appears in the device window (“Device window”).
The Sercos master is now available as field bus in the Codesys project and the bus node can be added to the device tree (è 3.6.4 Insert bus node).
42 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning
Setting the cycle time
1. Highlight “sercos_Master (sercos Master)”entry in the device window (“Device window”).
2. Project menu (“Project”) > Edit object (“Edit Object”). The device tab (“Device tab”) “sercos_Master”appears in the Editor window (“Editor window”).
Fig. 3.12
3. In the parameter tab (“Parameter tab”) “sercos Master”, set the Sercos cycle time (“sercos Cycle time”).
Festo – P.BE-CPX-FB39-EN – 1504NH – English 43
3 Commissioning

3.6.4 Insert bus node

Please Note
Requirements for execution of the subsequent steps: – Codesys project set up with programmable controller (PLC) – Device description files (SDDML files) available in Codesys
(è 3.6.2 Installing device description files (SDDML files))
– Field bus inserted in project (è 3.6.3 Inserting field bus).
Procedure
1. Highlight “sercos_Master (sercos Master)”entry in the device window (“Device window”).
2. Project menu (“Project”) > Add device… (“Add Device…”). The “Add Device”dialog opens up.
Fig. 3.13
Please Note
Depending on the diagnostics mode, there is a choice of 3 entries: – CPX-FB39-RIO (without diagnostic mode) – CPX-FB39-RIO-ST (with status bits) – CPX-FB39-RIO-STI (with diagnostic interface).
3. Highlight corresponding bus node entry.
4. Press the “Add Device”button.
44 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning
In the device window (“Device window”), 2 entries appear for the bus node (è Fig. 3.14). – First entry: Bus node gateway – Second entry: Bus node module.
1
2
1 Bus node gateway 2 Bus node module
Fig. 3.14
The CPX-FB39 module is now available as a bus node in the Codesys project and other modules of the CPX terminal can be added to the device tree (è 3.6.5 Inserting other modules).
Festo – P.BE-CPX-FB39-EN – 1504NH – English 45
3 Commissioning
Setting the Sercos address
1. Highlight bus node gateway entry in the device window (“Device window”).
2. Project menu (“Project”) > Edit object (“Edit Object”). The corresponding device tab (“Device tab”) appears in the editor window (“Editor window”).
Fig. 3.15
3. Enter the correct Sercos address in the “sercos Slave”parameter tab (“Parameter tab”).
Please Note
The entry for the Sercos address must match the setting of DIL switch 3 on the bus node (è 2.4.7 Set the Sercos address).
46 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning

3.6.5 Inserting other modules

Please Note
Requirements for execution of the subsequent steps: – Codesys project set up with programmable controller (PLC) – Device description files (SDDML files) available in Codesys
(è 3.6.2 Installing device description files (SDDML files)) – Field bus inserted in project (è 3.6.3 Inserting field bus) – Bus node inserted in project (è 3.6.4 Insert bus node).
Procedure
1. Highlight bus node gateway entry (upper entry) in the device window (“Device window”).
2. Project menu (“Project”) > Add device… (“Add Device…”). The “Add Device”dialog opens up.
Fig. 3.16
3. Highlight the module.
4. Press the “Add Device”button.
5. Insert other modules in accordance with steps 3. and 4.
Expansion of the CPX terminal is now available in the Codesys project and assignment of the inputs and outputs to variables in the higher-level controller (I/O mapping) is now possible (è 3.6.6 I/O assignment).
Festo – P.BE-CPX-FB39-EN – 1504NH – English 47
3 Commissioning

3.6.6 I/O assignment

Once all devices on the CPX terminal have been inserted in the Codesys controller software project, the inputs and outputs on the individual modules can be depicted on a higher-level control unit.
Procedure
1. Click entry of device in the device window (“Device window”) with the right-hand mouse button. A context menu appears on screen.
2. In the context menu, select “Edit IO mapping”. The device tab (“Device tab”) “Edit IO mapping”appears in the editor window (“Editor window”).
Fig. 3.17
All inputs and outputs on the individual modules are displayed in the Editor window (“Editor window”) and can be assigned to the variables in the higher-level controller.
48 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning

3.6.7 Changing parameters in Codesys

With the help of Codesys software, the user-defined parameters (“User Parameters”) of the modules inserted in a project can be displayed and changed.
Procedure
1. Highlight the entry of a module in the device window (“Device window”).
2. Project menu (“Project”) > Edit object (“Edit Object”). The corresponding device tab (“Device tab”) appears in the editor window (“Editor window”).
3. Select parameter tab (“Parameter tab”) for user-defined parameters (“User Parameters”). The parameter appear in the editor window (“Editor window”).
Fig. 3.18
4. Select the parameter settings by double-clicking “Value”in the (“Value”) column and edit the value using the pulldown menu.
The parameter settings can be displayed as a symbolic value (standard) or as a numerical value. Refer to the corresponding CPX modules to find the meaning of the applicable numerical values. The changeover of display involves setting or not setting the tick on Symbolic Values (“Symbolic values”).
Festo – P.BE-CPX-FB39-EN – 1504NH – English 49
3 Commissioning

3.7 Parameterisation

3.7.1 Introduction to parameterisation

The CPX terminal is supplied with factory-preset parameters (default parameterisation). The system characteristics of a CPX terminal and of individual modules and channels can be parameter ized individually. A distinction is made here between the following parameters:
Parameter Description Examples
System parameters Global system functions for the
complete CPX terminal
Module parameters Module and channel-specific functions
of the respective module Diagnostic memory parameters
Tab. 3.9
Operating method of the diagnostic
memory
A detailed description of the individual parameters as well as basic principles of applica tion can be found in the CPX system description (è P.BE-CPX-SYS-...). Which parameters stand for the modules used are found in the description for the re spective module.
Caution
If the Modify-LED (M) lights up permanently, the parameterisation is not stored locally in the bus node and is not restored automatically by the higher-order system upon re placement.  In these cases, check before replacement to see which settings are required and
carry out these settings. Changes in parameterisation or application-specific parameter settings result in changes to the module or system behaviour.  Check especially when replacing CPX terminals to see which settings are necessary
and make sure that these are restored, if necessary (e.g. by appropriate system-
start parameterisation).
– Short-circuit monitoring – System start – Input debounce time – Signal extension time – Remaining entries with Power ON – Error number filter
Warning
The connected actuators can move unexpectedly! Modification of the signal statuses and parameters can trigger dangerous movements of the connected actuator technology.  Make sure that nobody is in the positioning range of connected actuators, and be
very careful with the parameterisation or manipulation of signal statuses.  Always note the instructions relating to “Force”, “Idle Mode”and “Fail Safe”in the
CPX system description (è P.BE-CPX-SYS-…), in the description for the CPX-MMI
(è P.BE-CPX-MMI-1-…) and in the online help for the CPX-FMT.
50 Festo – P.BE-CPX-FB39-EN – 1504NH – English
3 Commissioning

3.7.2 Prerequisite for parameterization

Please Note
A CPX terminal can be parameterised only if the function “System start with default parameterisation and current CPX expansion” is activated.  Set the system parameter “System start”accordingly.
With the system parameter “System start”, you can define the starting characteristics of the CPX ter minal. Factory settings are used unless parameterization is altered.  Select the setting “System start with default parameterization and current CPX expansion”to permit
the required parameterization.
 To conduct the parameterization, use the Festo Maintenance Tool (CPX-FMT) software or the control
device (CPX-MMI).
 After parameterization, change the setting of the system parameter “System start”to “System start
with stored parameterization and stored CPX expansion”to define the settings and to save them in
the module. After a reboot of the CPX terminal, the Modify-LED (M) lights up continuously on the bus node. The terminal uses the saved parameter settings.
Caution
If the Modify-LED (M) is lit continuously, the parameterization during replacement is not set up automatically by the higher-level controller.  In such cases, examine before replacement which settings are required and imple
ment them.

3.7.3 Methods of parameterisation

A CPX terminal with the bus node CPX-FB39 can be parameterised with various methods.
Method Benefits Disadvantages
Festo Maintenance Tool (CPX-FMT) Menu-guided parameter entries via PC software Operator unit (CPX-MMI) Menu-guided parameter entry
Easy parameter entry guided by menu in plain text.
Easy parameter entry guided by menu in plain text.
Parameterisation is saved locally in the CPX terminal and is lost if the CPX terminal or bus node is replaced. Parameterisation is saved locally in the CPX terminal and is lost if the CPX terminal or bus node is replaced.
Sercos III Parameterisation can be carried
out via the control system.
The controller must support the configuration via SDDML files.
Tab. 3.10
Festo – P.BE-CPX-FB39-EN – 1504NH – English 51
3 Commissioning

3.7.4 Parameterisation via the Festo Maintenance Tool (CPX-FMT) software

With the Festo Maintenance Tool (CPX-FMT) software, a CPX terminal can be parameterized via a USB or Ethernet connection.
Please Note
To run the software on the bus node via a USB connection, you need a USB connector cable and the USB adapter NEFC-M12G5-0.3-U1G5.
The current version of the Festo Maintenance Tool (CPX-FMT) software is available for download in the Festo Support Portal (è www.festo.com/sp).

3.7.5 Parameterization with the control device (CPX-MMI)

With the operator unit (CPX-MMI), a CPX terminal can be parameterised through a menu even without controller software.
Information on general operation of the operator unit can be found in the corresponding description (è P.BE-CPX-MMI-1-…).
Please Note
The last parameterisation set or received in the CPX terminal is always valid.

3.7.6 Parameterization via Sercos III

The bus node can be parameterized directly by the controller via Sercos III.
This has the advantage that all parameters are saved in the controller software and auto matically transferred to the bus node at run-up of the controller. As a result, parameterisation remains intact if the bus node is replaced.
52 Festo – P.BE-CPX-FB39-EN – 1504NH – English

4 Diagnostics and error handling

4 Diagnostics and error handling

4.1 Summary of diagnostics options

The CPX terminal provides comprehensive and user-friendly options for diagnostics and error handling. The following options are available, depending on the configuration:
Diagnostic possibility
LED display The LEDs show directly
Status bits Internal inputs that supply
I/O diagnostics interface
Diagnostics via the operator unit (CPX-MMI)
Diagnostics via Sercos III
Tab. 4.1
Brief description Benefits Detailed
Description
configuration errors, hardware errors, bus errors, etc.
coded common diagnostic messages. Bus-independent diagnostic interface at I/O level, which enables access to the internal data of the CPX terminal (16 inputs and 16 outputs). Diagnostic information can be displayed on the operator unit in a convenient and menu-driven manner. Access to all system data of the CPX terminal over the network.
Fast “on-the-spot” error detection
Fast access to error messages, irrespective of the module and master. Detailed error recognition: the diagnostic data can be processed further, e.g. with a PLC user program.
Fast “on-the-spot” recognition of errors
Detailed error detection Section 4.5
Section 4.2
Section 4.3 and CPX system description (è P.BE-CPX-SYS-…) Section 4.4 and CPX system description (è P.BE-CPX-SYS-…)
Operator unit description (è P.BE-CPX-MMI-1-…)
Please Note
Note that the available diagnostic information is dependent on the DIL switch settings on the bus node, (è 2.4.5 Setting of the diagnostic mode (remote I/O)) as well as on the parameterisation of the CPX terminal.
You can find additional information on general diagnostics of the CPX terminal in the CPX system description (è P.BE-CPX-SYS-…). Information on diagnostics of the pneumatics, of the pneumatic interface and of the I/O module are found in the corresponding descriptions.
Festo – P.BE-CPX-FB39-EN – 1504NH – English 53
4 Diagnostics and error handling

4.2 Diagnostics via LED displays

LED displays for the diagnostics of the CPX terminal are available on the bus node as well as on the individual modules.
The significance of the LED displays on the electric modules can be found in the descrip tion for the relevant module.
LED displays on the bus node CPX-FB39
PS
S
PL
SD
TP1
TP2
S
SD
TP1
TP2 M
SF
M
PS
PL
SF
1
2
1 Network-specific LEDs:
– S (green, orange, red) – SD (green, orange, red)
1)
1)
– TP1 (green) – TP2 (green)
1) This figure depicts a green LED as an example.
2 CPX-specific LEDs:
– PS (green) – PL (green) – SF (red) – M (yellow)
Fig. 4.1
In the following sections, the different statuses of the LED displays are represented as follows:
LED lights up; LED flashes; LED is out
54 Festo – P.BE-CPX-FB39-EN – 1504NH – English
4 Diagnostics and error handling

4.2.1 Standard operating status

LED display
These LEDs light up green:
operating status
Standard
–S
PS
S
SD
TP1
PL
SF
TP2 M
1) Depending on the data communication or configuration.
–SD –PS –PL These LEDs flash green: – TP1 and TP2 The yellow LED (M) lights up, flashes or is dark. The red LED (SF) is dark.
1)

4.2.2 CPX-specific LEDs

PS (power system) – power sensor/logic supply LED (green) Process Status Significance / error handling
LED
ON OFF
No error. Operating voltage/ sensor supply applied.
illuminated
ON OFF
LED flashes
ON OFF
Operating voltage/sensor supply outside the toler ance range. Internal fuse for the operat ing voltage/sensor supply has responded.
 Eliminate undervoltage.
1. Eliminate short circuit/overload.
2. Depending on the parameterisation:  Sensor power supply is
switched back on automatically after remedying the short circuit (factory setting).
 Power OFF/ON necessary.
LED
ON OFF
Operating voltage/sensor supply is not applied.
 Check the operating voltage
connection of the electronics.
not illuminated
PL (power load) – power load supply (outputs/valves) LED (green) Process Status Significance / error handling
LED
ON OFF
No error. Load voltage applied.
illuminated
ON OFF
LED flashes
Festo – P.BE-CPX-FB39-EN – 1504NH – English 55
Load voltage at the system supply or additional supply outside the tolerance range.
 Eliminate undervoltage.
4 Diagnostics and error handling
SF (system failure) – system fault LED (red) Sequence1)Status Significance/error handling
LED flashes
ON OFF
ON OFF
ON OFF
ON OFF
Simple error/information (error class 1) Error (error class 2) Serious error (error class 3) No error
Description of error numbers in the CPX system description (è P.BE-CPX-SYS-…).
LED not illuminated
1) The system fault LED flashes depending on the class of fault which has occurred.
Error class 1 (slight error): 1× flash, pause time
Error class 2 (error): 2× flashes, pause time
Error class 3 (severe error): 3× flashes, pause time
M (modify) – parameterisation modified or Force active LED (yellow) Process Status Significance / error handling
ON OFF
LED illuminated
Setting: System start with saved parametrisation and saved CPX expansion; Parameters and CPX expansion are stored permanently.
For replacement of the bus node or CPX terminal in case of service, parameterisation is not created automatically by the higher-order system (PLC/IPC).  Save and apply the parameterisa
tion when the bus node is re placed.
1)
The Force function is enabled. Further information can be found in the CPX system description
LED flashes
ON OFF
Force is active
(è P.BE-CPX-SYS-…).
ON OFF
LED not illuminated
Setting: System start with default parameterisation (factory setting) and cur rent CPX expansion;
external parameterisation is possible (presetting).
1) The display of the Force function (LED flashing) has priority over the display of the setting for the system start (LED illuminated).
56 Festo – P.BE-CPX-FB39-EN – 1504NH – English
4 Diagnostics and error handling

4.2.3 Network-specific LEDs

S – Sercos III LED status Process State Priority Significance / error handling
Dark
lights up Orange
Alternates Orange/ Green
Alternates Orange/ Green
Alternates Orange/ Green
lights up Green
Alternates Green/ Orange
Alternates Green/ Orange
Alternates Green/ Orange
FLASHES Green
Alternates Red/ Orange
Alternates green/red
lights up red,
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
UCC mode 0 No Sercos communication
CP0 0 Communication phase 0 is active.
CP1 0 Communication phase 1 is active.
The green LED flashes every 3 seconds once.
CP2 0 Communication phase 2 is active.
The green LED flashes twice every 3 seconds.
CP3 0 Communication phase 3 is active.
The green LED flashes 3 times every 3 seconds.
CP4 0 Communication phase 4 is active.
HP0 1 Device is in hot-plug phase 0.
HP1 1 Device is in hot-plug phase 1.
The orange LED flashes once every 3 seconds.
HP2 1 Device is in hot-plug phase 2.
The orange LED flashes twice every 3 seconds.
Fast Forward è Loopback
2 RT status has changed from
Fast-Forward to Loopback.
Application Error 3 Application Error
è GDP and FSP status codes
MST Losses (IDN S-0-1003)/2
Communication error
4 MST failures (IDN S-0-1003)/2
(è B.1.5)
5 Communication error
è SCP status codes
Festo – P.BE-CPX-FB39-EN – 1504NH – English 57
4 Diagnostics and error handling
S – Sercos III LED status Significance / error handlingPriorityStateProcess
FLASHES Orange FLASHES red,
ON OFF
ON OFF
Identification 6 Identification (address assignment
or configuration fault) (C-DEV.Bit15)
Watchdog Error 7 Watchdog Error
SD – Sub Device LED status Process State Priority Significance / error handling
lights up red, lights up Orange lights up Green
Dark
ON OFF
ON OFF
ON OFF
ON OFF
Application Error (C1D) Parameterization Level (PL) Operating Level (OL) Sub Device not active
1 Application Error
è GDP and FSP status codes
0 Sub Device in Parameterization
Level
0 Sub Device in Operating Level
0
TP1 – Traffic Port 1 (connection port 1 active) LED status Process Status Significance / error handling
lights up Green FLASHES Green
Dark
ON OFF
ON OFF
ON OFF
Network connection OK
Data traffic
No network connection or Ethernet cable not connected.
 Check Ethernet connection.
TP2 – Traffic Port 2 (connection port 2 active) LED status Process Status Significance / error handling
lights up Green FLASHES Green
Dark
58 Festo – P.BE-CPX-FB39-EN – 1504NH – English
ON OFF
ON OFFOFFOFF
ON OFF
Network connection OK
Data traffic
No network connection or Ethernet cable not connected.
 Check Ethernet connection.
4 Diagnostics and error handling

4.3 Diagnostics via status bits

Status bits are internal inputs that serve to display common diagnostic messages (global error mes sages).
Please Note
The diagnostic mode “Status bits” must be activated via DIL switch 2.2 on the bus node (è 2.4.5 Setting of the diagnostic mode (remote I/O)).
Status bits are treated as inputs and there can be queried, linked and processed as “standard” inputs.
In the case of activated “Status bits” diagnostics mode, the first 16 inputs are assigned although only 8 inputs are used (è 3.5.1 Basic rules for addressing).
Status bits are treated as “normal” inputs. – If all status bits supply a 0-signal, no error is reported. – If at least one status bit delivers a 1-signal, there is a fault. The diagnostic information when there is
a 1-signal is shown in the following table.
Bit Diagnostic information with a 1-signal Description
0 Fault at valve or pneumatic module Module type in which an error has occurred 1 Error on output module 2 Error on input module 3 Error on analogue module or technology module 4 Undervoltage Error type 5 Short circuit/overload 6 Wire break 7 Other error
Tab. 4.2
Please Note
If various errors occur simultaneously on different types of modules, these errors can not be assigned via the status bits. Errors can be uniquely defined via the I/O diagnostics interface, if needed.
Further notes on the function and content of the status bits are found in the CPX system description (è P.BE-CPX-SYS-…).
Festo – P.BE-CPX-FB39-EN – 1504NH – English 59
4 Diagnostics and error handling

4.4 Diagnostics via the I/O diagnostics interface

Detailed diagnostic information on the CPX terminal can be accessed via the “I/O diagnostics interface” diagnostics mode. You can ascertain this exactly, e.g. by noting on which module and channel an error has occurred. To call up this information, 16 input bits and 16 output bits enable all diagnostic informa tion to be read out.
Please Note
To use the “I/O diagnostic interface” diagnostics mode, it must be activated via DIL switch 2 on the bus node (è 2.4.5 Setting of the diagnostic mode (remote I/O)).
If the “I/O diagnostic interface” is activated, it will occupy the first 16 inputs and outputs in the address range (è 3.5.1 Basic rules for addressing).
The following table provides an overview of the available diagnostic information.
Diagnostic information Description
Global diagnostic data – General overview of errors Diagnostic data module – Detailed diagnostics per module Diagnostic data status – Number of entries in the diagnostic memory
– Operating mode
Diagnostic memory data – Long-term memory
– Detailed diagnostics and relative time stamp per fault event
Tab. 4.3
Further notes on the function and content of the I/O diagnostics interface can be found in the CPX system description (è P.BE-CPX-SYS-…).
60 Festo – P.BE-CPX-FB39-EN – 1504NH – English
4 Diagnostics and error handling

4.5 Diagnostics via Sercos III

Various diagnostic options are available for diagnostics via Sercos III and these can be selected by their corresponding IDNs. – Basic diagnostic functions (è 4.5.1 Basic diagnostic functions) – Diagnostic basic functions with I/O-specific extensions (è 4.5.2 I/O diagnostics) – Diagnostics acc. to the CPX standard of Festo
(è 4.5.3 I/O diagnostics with Festo-specific extensions).

4.5.1 Basic diagnostic functions

The basic diagnostic functions are supported by every Sercos device. This involves predefined status codes being transmitted via S-0-0390. Error messages can be acknowledged by S-0-0099.
To interrogate the characteristics and chronological sequence of diagnostic messages, a trace function is available via S-0-1303.
IDNs for the basic diagnostic function (function group diagnostics)
IDN Designation Explanation
S-0-0099 Reset Class 1 Diagnostic Acknowledge diagnostic event S-0-0390 Diagnostic Number Current diagnostic event as a status code S-0-1303 Diagnostic trace Diagnostic record S-0-1303.0.03 Diagnosis Trace State Status of diagnostic record S-0-1303.0.10 Diagnosis Trace Buffer 1 Diagnostic memory 1 S-0-1303.0.11 Diagnosis Trace Buffer 2 Diagnostic memory 2
Tab. 4.4

4.5.2 I/O diagnostics

I/O diagnostics involve Sercos standard diagnostics with I/O-specific extensions (e.g. channel-precise localization).
Only the highest priority (S-0-1500.0.32) and the current (S-0-1500.0.33) diagnostic message are displayed. If several faults occur simultaneously, a few messages are not visible.
IDNs for I/O diagnostics (Bus Coupler function group)
IDN Designation Explanation
S-0-1500.0.02 IO Status Current status of inputs and outputs S-0-1500.0.32 IO Diagnosis Message I/O diagnostic message with the highest
priority
S-0-1500.0.33 Current I/O Diagnosis Message Current I/O diagnostic message
Tab. 4.5
Festo – P.BE-CPX-FB39-EN – 1504NH – English 61
4 Diagnostics and error handling

4.5.3 I/O diagnostics with Festo-specific extensions

The Festo-specific extensions for I/O diagnostics provide access to all available diagnostic functions in accordance with the CPX standard. The division into system, module and channel diagnostics provides access at any time to all diagnostic messages (è Tab. 4.6). That means that no diagnostic messages remain undetected, even in the pres ence of simultaneously occurring faults.
IDNs for Festo-specific extensions
IDN
Designation Explanation
S-0-1500.SI.150 CPX System Diagnostics CPX system diagnostics S-0-1500.0.151
Module Diagnostics Module diagnosis IO_FG.SI.151 S-0-1500.0.152
Channel Diagnostics Channel diagnostics IO_FG.SI.152
Tab. 4.6
62 Festo – P.BE-CPX-FB39-EN – 1504NH – English
4 Diagnostics and error handling

4.6 Error handling

With the following malfunctions, the behaviour of the CPX terminal depends on the configured beha viour of the master module and the parameterised fail-safe setting: – Telegram failure – stop of the master – interruption in the bus cable.
Depending upon the configuration, the outputs (valves and electrical outputs) are switched off (factory setting), switched on or they retain their existing status. Further information can be found in the CPX system description (è P.BE-CPX-SYS-…).
These characteristics can be altered using the Festo Maintenance Tool (CPX-FMT) software, the control device (CPX-MMI) or Sercos mechanisms.
Change via Sercos
 Change configuration of fallback values (è Tab. B.12 (IO_FG.SI.22 - Fallback Value Output)).  Change configuration of fallback values (è Tab. B.12 (IO_FG.SI.02 - Configuration Of IO_FG).
Change via CPX-FMT/CPX-MMI
 Change configuration of failsafe values (è CPX system description P.BE-CPX-SYS-…, online help
with CPX-FMT software or description of control device P.BE-CPX-MMI-1-…).
Please Note
A change in the fallback and backup values via Sercos also has a corresponding impact on the failsafe entries in the CPX system table (è Tab. B.14). In the event of any retrospective adjustment of fallback values via CPX-FMT or CPX-MMI, the backup value characteristics provided for in the Sercos standard no longer apply.
Warning
Accidental activation of actuators! An incorrect status of the valves and outputs can lead to dangerous situations!  Ensure that valves and outputs relating to the aforementioned problems are placed
in a safe condition.
Please Note
If the outputs are reset in conjunction with PLC-Stop, field bus interruption or a fault, pay attention to the following: – monostable valves move to the initial position. – Double solenoid valves remain in the current position. – Mid-position valves go into mid-position (pressurized, exhausted or closed, depend
ing on valve type).
Festo – P.BE-CPX-FB39-EN – 1504NH – English 63

A Technical appendix

A Technical appendix

A.1 Technical data

General information
General technical data è CPX system description (P.BE-CPX-SYS-…) Degree of protection in accordance with IEC 60529, completely mounted, plug connector in accordance with accessories plugged in or equipped with cover cap Protection against electric shock (Protection against direct and indirect contact in accordance with IEC 60204-1) Module code (CPX-specific) Remote I/O Remote controller Module identifier (in operator unit CPX-MMI) Remote I/O Remote controller
Power supply
Operating voltage/load voltage è CPX system description (P.BE-CPX-SYS-…) Intrinsic current consumption at 24 V from operating voltage supply for electronics/sensors (U Galvanic isolation between bus interface and CPX periphery (power supplies) Mains buffering time at least 25 ms
EL/SEN
)
IP65/IP67
through the use of PELV circuits (Protected Extra Low Voltage)
224 (sub-module code 3) 171 (sub-module code 3)
FB39-RIO FB39-RC
typ. 100 mA (internal electronics)
Yes
Network-specific characteristics
Network protocol Sercos III Specification Standards/norms with reference to Sercos III:
– IEEE 802.3
– IP-based protocols (UDP, TCP, ICMP, …) Transmission rate 100 Mbit/s full duplex Input/output size 64 byte/64 byte (operating-mode-independent) Crossover detection Auto-MDI/MDI-X
64 Festo – P.BE-CPX-FB39-EN – 1504NH – English
A Technical appendix

A.2 List of abbreviations

The following product-specific terms and abbreviations are used in this manual:
Term/abbreviation Meaning
Address space The sum of available addresses, independent of the assignment. AI Analogue input (input channel, 16 bits) AO Analogue output (output channel, 16 bits) AT Acknowledge telegram Bus node Create the connection to certain networks and fieldbuses, conduct
control signals to the connected modules and monitor their functioning
capability. C-CON Connection Control C-DEV Device Control CEC Control block CPX-CEC for configuration, commissioning and
programming of various components and equipment from Festo. CFG Configuration CP Communication Phase CPX modules Collective term for the various modules which can be integrated into a
CPX terminal. CPX system description (è P.BE-CPX-SYS-…)
CPX terminal Modular electrical terminal Diag Diagnostics Diagnostic data Detailed diagnostics information DIL switches Miniature switch that consists of several switching elements, with
FEC Control block, e.g. CPX-FEC, usable as:
FG Function Group FSP Function Specific Profile GDP Generic Device Profile I Digital input IDN Identification Number IO Input/output I/O diagnostics interface The I/O diagnostics interface is a bus-independent diagnostics interface
I/O modules Common term for the CPX modules which provide digital inputs and
MDT Master Data Telegram
1) The designation NRT channel is no longer used on Sercos units and has been replaced by the designation UCC.
Description that gives an overview of structure, components, function,
installation and commissioning as well as basic information on
parameterisation of CPX terminals (è www.festo.com).
which, for example, basic settings can be made; DIL = dual in-line
– fieldbus slave (remote I/O operating mode)
– system controller (PLC, remote controller operating mode)
– stand-alone system controller (PLC, stand-alone operating mode)
at I/O level, permitting access to internal data of the CPX terminal.
outputs (CPX input modules and CPX output modules)
Festo – P.BE-CPX-FB39-EN – 1504NH – English 65
A Technical appendix
Term/abbreviation Meaning
MTU Maximum Transfer Unit NRT channel
1)
Non Real Time è UCC O Digital output Parameter With the aid of parameterisation, the characteristics of the CPX terminal
or the characteristics of the individual modules and I/O channels can be
adapted to each particular application. Parameters can be read and
modified. PDIN Process Data Input PDOUT Process Data Output PLC/IPC Programmable logic controller/industrial PC Pneumatics interface The pneumatics interface is the interface between the modular
electrical peripherals and the pneumatics. SCP Sercos Communication Profile S-DEV Device Status Status bits Internal inputs that supply coded common diagnostic messages. SVC Service Channel SYNC Synchronization UCC Universal Communication Channel Var Variables
1) The designation NRT channel is no longer used on Sercos units and has been replaced by the designation UCC.
Tab. A.1
66 Festo – P.BE-CPX-FB39-EN – 1504NH – English

B Identification Numbers (IDNs)

B Identification Numbers (IDNs)
To provide a better overview, the IDNs at Sercos are sorted into function groups and classes. Sorting into function groups depicts the view of the specification. Here, the IDNs are sorted by func tionality. Sorting in classes depicts the view of the application. For this, the IDNs are assembled in groups that are needed for defined applications.

B.1 Sercos Communication Profile (SCP)

B.1.1 Function Group - SCP Identification

IDN Designation Class Explanation
S-0-1000 SCP Type & Version SCP_VarCFG SCP type and SCP version
Tab. B.1

B.1.2 Function Group - Timing

IDN Designation Class Explanation
S-0-1002 Communication Cycle Time
(tScyc)
Tab. B.2

B.1.3 Function Group - Telegram Setup

IDN Designation Class Explanation
S-0-1009 Device Control (C-Dev) Offset
In MDT
S-0-1010 Lengths Of MDTs SCP_VarCFG Lengths of Master Data
S-0-1011 Device Status (S-Dev) Offset
In AT
S-0-1012 Lengths Of ATs SCP_VarCFG Lengths of Acknowledge
S-0-1013 SVC Offset In MDT SCP_VarCFG – S-0-1014 SVC Offset In AT SCP_VarCFG
Tab. B.3
SCP_VarCFG Cycle time (0.5 … 65 ms)
SCP_VarCFG
Telegrams MDT
SCP_VarCFG
Telegrams AT
Festo – P.BE-CPX-FB39-EN – 1504NH – English 67
B Identification Numbers (IDNs)

B.1.4 Function Group - Control

IDN
S-0-0021 IDN List Of Invalid Operation
Name Class Explanation
SCP_VarCFG
Data For CP2
S-0-0022 IDN List Of Invalid Operation
SCP_VarCFG
Data For CP3
S-0-0127 CP3 Transition Check SCP_VarCFG Procedure Command to
check all parameters needed for CP3
S-0-0128 CP4 Transition Check SCP_VarCFG Procedure Command to
check all parameters needed for CP4
Tab. B.4

B.1.5 Function Group - Bus Diagnosis

IDN Name Class Explanation
S-0-0014 Interface Status SCP_VarCFG – S-0-1003 Allowed MST Losses In
SCP_VarCFG
CP3/CP4
S-0-1026 Version Of Communication
Hardware
SCP_VarCFG SERCON100S Version:
V04 R11 S-0-1028 Error Counter MST-P&S SCP_Sync_0x02 – S-0-1035 Error Counter Port 1 & Port 2 SCP_VarCFG – S-0-1040 Sercos Address SCP_VarCFG Sercos Address of CPX-FB39
Factory setting: 254 (0xFE) S-0-1044 Device Control (C-DEV) SCP_Diag – S-0-1045 Device Status (S-DEV) SCP_Diag – S-0-1046 List Of Sercos Addresses In
SCP_VarCFG Value of parameter S-0-1040
Device
Tab. B.5
68 Festo – P.BE-CPX-FB39-EN – 1504NH – English
B Identification Numbers (IDNs)

B.1.6 Function Group - Connection

IDN
S-0-0187 IDN List Of Configurable Data
Name Class Explanation
SCP_VarCFG Contains the following IDNs:
As Producer
S-0-1500.0.2 (è B.3.2) S-0-1500.0.9 (è B.3.2) S-0-1500.0.150 (è B.3.3) S-0-1500.0.151 (è B.3.3) IO_FG.SI.9 (è B.3.1) IO_FG.SI.151 (è B.3.3)
S-0-0188 IDN List Of Configurable Data
As Consumer
SCP_VarCFG Contains the following IDNs:
S-0-1500.0.1 (è B.3.2) S-0-1500.0.5 (è B.3.2) IO_FG.SI.5 (è B.3.1)
S-0-1050.SI.1 Connection Setup SCP_VarCFG
1)
SCP_Sync S-0-1050.SI.2 Connection Number SCP_VarCFG – S-0-1050.SI.3 Telegram Assignment SCP_VarCFG – S-0-1050.SI.4 Maximum Length Of
Connection
SCP_VarCFG Total length of the IDNs
stored in S-0-0187 and S-0-0188 less the length of
S-0-1500.0.5 + S-0-1500.0.9 S-0-1050.SI.5 Current Length Of Connection SCP_VarCFG – S-0-1044.SI.6 Configuration List SCP_VarCFG – S-0-1050.SI.8 Connection Control (C-CON) SCP_Diag – S-0-1050.SI.9 Connection State SCP_VarCFG_0x02 – S-0-1050.SI.10 Producer Cycle Time SCP_Sync – S-0-1050.SI.11 Allowed Data Losses SCP_Sync – S-0-1050.SI.12 Error Counter Data Losses SCP_Sync – S-0-1051 Image Of Connection Setups SCP_VarCFG
1) Also on SCP_Sync the local bus of the CPX terminal is not synchronized to the superimposed Sercos bus cycle.
Tab. B.6

B.1.7 Function Group - NRT

IDN Name Class Explanation
S-0-1017 NRT Transmission Time SCP_VarCFG
Tab. B.7
Festo – P.BE-CPX-FB39-EN – 1504NH – English 69
B Identification Numbers (IDNs)

B.2 Generic Device Profile (GDP)

B.2.1 Function Group - Diagnosis

IDN Designation Class Explanation
S-0-0095 Diagnostic Message unclassified Diagnostic event
(Sercos-specific) of IDN
S-0-0390 in clear text S-0-0099 Reset Class 1 Diagnostic GDP_Basic – S-0-0390 Diagnostic Number GDP_Basic Current diagnostic event with
highest priority in the CPX
system as a status code. S-0-1303.0.01 Diagnosis Trace Configuration GDP_DiagTAdv Contains IDN S-0-1500.SI.33
(è Tab. B.13) S-0-1303.0.02 Diagnosis Trace Control GDP_DiagT – S-0-1303.0.03 Diagnosis Trace State GDP_DiagT – S-0-1303.0.10 Diagnosis Trace Buffer 1 GDP_DiagT Maximal 100 entries S-0-1303.0.11 Diagnosis Trace Buffer 2 GDP_DiagT Maximal 100 entries S-0-1303.0.12 Diagnosis Trace Buffer 3 GDP_DiagTAdv Maximal 100 entries
Tab. B.8

B.2.2 Function Group - Administration

IDN Designation Class Explanation
S-0-0017 IDN List Of All Operation Data GDP_Basic – S-0-0025 IDN List Of All Procedure
Commands
Tab. B.9
unclassified
70 Festo – P.BE-CPX-FB39-EN – 1504NH – English
B Identification Numbers (IDNs)

B.2.3 Function Group - Identification

IDN
Designation Class Explanation
S-0-1300.SI.1 Component Name GDP_Id English module designation
(long) in UTF8 format
S-0-1300.SI.2 Vendor name GDP_Id Manufacturer name
Festo AG & Co. KG S-0-1300.SI.3 Vendor code GDP_Basic Manufacturer code 0xFE S-0-1300.SI.4 Device name GDP_Id English module designation
(short) in UTF8 format S-0-1300.SI.5 Vendor Device ID GDP_Basic Manufacturer device number
(unique ID for each type of
CPX module) S-0-1300.SI.6 Connected To Sub Device unclassified On all CPX modules 0 S-0-1300.SI.7 Function Revision GDP_Rev – S-0-1300.0.8 Hardware Revision GDP_Rev – S-0-1300.0.9 Software revision GDP_Rev – S-0-1300.0.10 Firmware Loader Revision GDP_Rev – S-0-1300.SI.11 Order Number GDP_Id Part number for the
electronics assembly S-0-1300.SI.12 Serial number GDP_Id – S-0-1301 List Of GDP Classes & Version GDP_Basic 0x00010001 S-0-1302.SI.01 FSP Type & Version GDP_Basic – S-0-1302.SI.02 Function Groups GDP_Basic IO Function Groups S-0-1302.SI.03 Application Type GDP_Id
Tab. B.10

B.2.4 Function Group - Time

IDN Name Class Explanation
S-0-1305.0.1 Sercos Current Time GDP_DiagT – S-0-1305.0.2 Sercos Current Fine Time – S-0-1305.0.3 Sercos Current Coarse Time
Tab. B.11
Festo – P.BE-CPX-FB39-EN – 1504NH – English 71
B Identification Numbers (IDNs)

B.3 Function Specific Profile IO (FSP IO)

B.3.1 Function Group - Generic I/O

IDN Name Explanation
IO_FG.SI.1 Name Of IO_FG Name of function group
S-0-1500.SI.0 S-0-1502.SI.0 S-0-1503.SI.0 S-0-1504.SI.0 S-0-1505.SI.0 S-0-1506.SI.0 S-0-1507.SI.0 S-0-1508.SI.0
S-0-1509.SI.0 IO_FG.SI.2 Configuration Of IO_FG – IO_FG.SI.3 Channel Quantity PDOUT Number of output channels IO_FG.SI.4 Channel Width PDOUT Width of output channels [Bit] IO_FG.SI.5 PDOUT Output data of the CPX module IO_FG.SI.7 Channel Quantity PDIN Number of input channels IO_FG.SI.8 Channel Width PDIN Width of input channels [Bit] IO_FG.SI.9 PDIN Input data for the CPX module IO_FG.SI.19 Parameter Channel Receive – IO_FG.SI.20 Parameter Channel Transmit – IO_FG.SI.22 Fallback Value Output
Tab. B.12
Bus Coupler Digital output Digital input Analog Output Analogue input counter Complex Protocol Sub Bus Master Sub Bus Slave

B.3.2 Function Group - Bus Coupler

IDN Name Explanation
S-0-1500.SI.1 IO Control Behaviour of inputs and outputs S-0-1500.SI.2 IO Status Status display of inputs and outputs S-0-1500.SI.3 List Of Module Type Code Display of module type code for all modules S-0-1500.SI.5 Container OutputData Container output data S-0-1500.SI.9 Container InputData Container input data S-0-1500.SI.19 Parameter Channel Receive Module-specific parameters of the bus node S-0-1500.SI.20 Parameter Channel Transmit Puffer for the module-specific parameters
1)
1)
2)
1) 3)
S-0-1500.SI.23 Local Bus Cycle Time Cycle time of the local bus S-0-1500.SI.32 IO Diagnostic Message Diagnostic message with the highest priority S-0-1500.SI.33 Current IO Diagnostic Message Current diagnostic message
1) This IDN is implemented as a byte list with variable length.
2) This IDN only permits read access and is implemented as a byte list with variable length.
3) This does not involve the current value for the module-specific parameters from the CPX system table. The current parameter
values can be interrogated via S-0-1500.SI.19.
Tab. B.13
72 Festo – P.BE-CPX-FB39-EN – 1504NH – English
B Identification Numbers (IDNs)

B.3.3 Manufacturer-specific extensions to the Function Specific Profile IO (FSP IO)

IDN
S-0-1500.SI.150 CPX System Diagnostics CPX System Diagnostics
Designation Explanation
1)
This IDN is implemented as an 8-byte value. Byte 0: Status bits (error type and source of error) Byte 1: Module number and diagnostic status
Byte 2: Error number S-0-1500.SI.151 IO_FG.SI.151
Module Diagnostics Diagnostic data of the CPX module to which the
IO function group is assigned.
1) 2)
Byte 0: Number of the first defective channel
Byte 1: Module error number
Byte 2: Info 2 (reserved)
Byte 3: Info 3 (reserved) S-0-1500.SI.152 IO_FG.SI.152
Channel Diagnostics Diagnostic data of all channels of the CPX module
to which the IO function group is assigned.
1) 3)
The content of the IDN is the fault number of the
corresponding channel. S-0-1500.SI.200 CPX system parameters Global system parameters of the CPX system
This IDN is implemented as a byte list with a
length of 8.
1) This IDN only permits read access.
2) All sessions of this IDN are implemented as a 4-byte value. One session corresponds to one CPX module.
3) All sessions of this IDN are implemented as a 1-byte list. The length of the list is computed from the total of I channels and O
channels for the corresponding IO function group.
4) Due to the fact that the behaviour of the outputs in the event of a fault with Sercos is specified by parameters IO_FG.SI.02 and
IO_FG.SI.22, the system parameter “Behaviour in response to a Fail State” is factory set to “Fault Mode”.
By setting this parameter to 00 (All Outputs Reset) or 01 (Hold Last State), the specific substitute value characteristics of Sercos
are disabled. The system parameter “Behaviour in an Idle Mode fail state” is not used.
4)
Tab. B.14
Festo – P.BE-CPX-FB39-EN – 1504NH – English 73
B Identification Numbers (IDNs)

B.4 Overview of the supported classes

B.4.1 Supported classes of the Sercos Communication Profile (SCP)

Class Description
SCP_VarCFG This class is needed to initialize the cyclical exchange of data between
master and slave. A slave that implements the class SCP_VarCFG provides the following functions: – Accesses via the service channel are completely supported – Cyclical transmission of “Device Control” and “Device Status” – The slave defines which data can be transmitted cyclically and how
many connections are possible. The slave provides the master with these data to enable the master to initialize all connections correctly.
SCP_WDCon A slave that implements the class SCP_WDCon provides a watchdog
function that enables connections to be monitored and, in the event of connection terminations, to initiate corresponding fault responses.
SCP_Diag A slave that implements class SCP_Diag provides information that helps to
run bus diagnostics.
SCP_NRTPC A slave that implements class SCP_NRTPC enables the UCC (Universal
Communication Channel) to be used for the transmission of non-Sercos-Ethernet telegrams.
SCP_Cyc A slave that implements the class SCP_Cyc provides all of the functions
needed to transmit and to receive cyclical data (produce and consume).
Tab. B.15

B.4.2 Supported classes of the Generic Device Profile (GDP)

Class Description
GDP_Basic Contains all the essential IDNs needed for a Sercos device. GDP_DiagT Basic function of the Sercos Diagnostic Trace. GDP_DiagTAdv Extended functions of the Sercos Diagnostic Trace. GDP_Id Contains IDNs with information for the identification of a device or module. GDP_Rev Contains IDNs with information for overhauling (hardware and firmware) of
the bus node.
Tab. B.16
74 Festo – P.BE-CPX-FB39-EN – 1504NH – English

C Diagnostic messages

C Diagnostic messages

C.1 Depiction of CPX diagnostic classes on Sercos diagnostic classes

CPX diagnostic class Sercos diagnostic class
Fault class 1: Information or minor fault Operational State Fault class 2: Standard/extended diagnostics Warning (C2D) Fault class 3: System fault, general Error (C1D)
Tab. C.1

C.2 Depiction of CPX diagnostic messages on Sercos status codes

CPX fault numbers that are not assigned to a Sercos status code in the following table are reported as manufacturer-specific status codes.
CPX­Error number
0 No Error 0x0000 No Error 1 General Diagnosis 0x1000 General Error 2 Short Circuit 0x2130 Short Circuit 3 Wire Fracture/Idling Current I/O 0x2360 Wire Break 4 Short Circuit In Actuator Supply 0x3420 Actuator Supply 5 Undervoltage In Power Supply 0x3400 Supply Voltage 9 Lower Limit Exceeded 0x8920 Measured Value Underrange 10 Upper Limit Exceeded 0x8910 Measured Value Overrange 11 Short Circuit Valve 0x2340 Short Circuit 12 Pilot Valve Function Warning – 13 Wire Fracture (Open Load) 0x2360 Wire Break 14 Condition Counter Exceeded 0x8B00 Preventive Maintenance Required
15 Module/Channel Failure 0xB010 Device Errors 16 Module Code Incorrect 0xB002 Incorrect Local Bus Slave Present 17 I/O Length Incorrect 0xB030 Local Bus Configuration Error 18 Address Range Exceeded 0xB030 Local Bus Configuration Error 19 Life Cycle Exceeded – 20 Fault In Parameterizing Signal Range 0x6320 Parameter Error 21 Fault In Parameterizing Data Format 0x6320 Parameter Error 22 Fault In Parameterizing Linear Scaling 0x6320 Parameter Error
Description Serco-
status code
Description
(Condition Monitoring)
Festo – P.BE-CPX-FB39-EN – 1504NH – English 75
C Diagnostic messages
CPX­Error number
Description
status code
DescriptionSerco-
23 Fault In Filter Measured Value 0x6320 Parameter Error 24 Fault In Parameterizing Lower Limit 0x6320 Parameter Error 25 Fault In Parameterizing Upper Limit 0x6320 Parameter Error 26 Fault In Actuator Supply 0x3420 Actuator Supply 27 Wrong Device Type Mounted – 28 Alarm Value Reached 0x8110 Process Data Monitoring 29 Fault In Parameterizing 0x6320 Parameter Error 30 No New Output Data (Slave) 0xB023 Local Bus I/O Data Communication
Error
31 No Bus Connection (Slave) 0xB000 Local Bus
(System Bus Of The Modular Station)
32 No STI Read Access (Slave) 0xB000 Local Bus
(System Bus Of The Modular Station)
33 No Parameter Access (Slave) 0xB000 Local Bus
(System Bus Of The Modular Station) 34 CP Module Lost/Fault 0xA001 Sub Bus Slave Missing 35 CP Configuration Failure 0xA002 Incorrect Sub Bus Slave Present 36 Short Circuit CP Line 0x2340 Short Circuit 37 Fault In Controlling – 38 Missing Valve – 39 Maintenance Required 0x8B00 Preventive Maintenance Required
(Condition Monitoring) 40 Life Guard – 41 Heart beat – 42 Com Cycle Period (Sync) – 43 CAN Overrun (Objects Lost) – 44 Invalid PDO Received – 45 CAN Warn Limit Reached – 46 CAN Recovered From Bus Off – 47 Bus Power Lost – 48 Fault In Calibration – 49 Lower Drop Out Signal – 50 Upper Drop Out Signal – 51 Sensor Limit Exceeded 0x8900 Sensors 52 Short Circuit Cold Junction Comp. – 53 Open Load Cold Junction Comp. – 54 Calibration Data Incorrect – 55 Invalid Process Value – 56 Short Circuit I-Port 0x2340 Short Circuit
76 Festo – P.BE-CPX-FB39-EN – 1504NH – English
C Diagnostic messages
CPX­Error number
Description
status code
DescriptionSerco-
57 Device Missing/Failure I-Port 0xA001 Sub Bus Slave Missing 58 I-Port Configuration Error 0xA030 Sub Bus Configuration Error 59 Input Overload – 60 Signal Underflow/Overflow 0x8000 Monitoring 61 Overvoltage In Power Supply Supply Voltage 64 Number Of Modules Incorrect 0xB004 Local Bus Devices Amount Error
(Too Many Devices) 65 F_Dest_Add Mismatch – 66 F-Communication Fault – 67 F-Communication Timeout – 68 Leakage Current – 69 F-Parameter Fault – 70 Station Equipment Status Incorrect – 71 Bus Connection Lost – 76 Reserve – 77 Reserve – 78 Value Out Of Range 0xA010 Device Errors 79 Another Function Failure 0xA010 Device Errors 80 Function Failure 0xA010 Device Errors 81 Monitoring Diag 1 0x8000 Monitoring 82 Monitoring Diag 2 0x8000 Monitoring 83 Monitoring Diag 3 0x8000 Monitoring 84 Monitoring Diag 4 0x8000 Monitoring 100 Configuration Error 0xB030 Local Bus Configuration Error 101 Execution Error 0x5010 Component Error 102 Record Error 0x5010 Component Error 103 Control Error 0x5200 Control System 104 System Error A 0x5010 Component Error 105 System Error B 0x5010 Component Error 106 Error In Valve 0x5010 Component Error 107 Controller Error 0x5200 Control System 108 Encoder Error 0x5010 Component Error 109 Error Motor Or Power Stage 0x5010 Component Error 115 Subsystem Module/Channel Failure 0xA010 Device Errors 128 Switch Unit Defective – 129 CBUS Asic Not Ready 0xB041 Local Bus Hardware Error 130 CPU Hardware Trap 0xB041 Local Bus Hardware Error 131 CBUS C-Manager Not Ready 0xB041 Local Bus Hardware Error 132 Watchdog Overflow 0x6010 Software Reset (Watchdog) 133 Remanent Memory Defective 0xB041 Local Bus Hardware Error
Festo – P.BE-CPX-FB39-EN – 1504NH – English 77
C Diagnostic messages
CPX­Error number
Description
status code
DescriptionSerco-
134 Flash System Memory Defective 0xB041 Local Bus Hardware Error 135 Number Of Module Parameters > 64 0xB030 Local Bus Configuration Error 136 Slave Not Ready 0xB020 Communication Errors 137 CBUS Diagnostic Telegram 0xB020 Communication Errors 138 CBUS Init Fault (Module Gap) 0xB020 Communication Errors 139 Order Queue Full 0xB020 Communication Errors 140 CBUS-EEPROM Error 0xB041 Local Bus Hardware Error 141 CBUS C-Timeout Error 0xB020 Communication Errors 142 CBUS Telegram Fault 0xB020 Communication Errors 143 BIU Access Error 0x6100 Internal Software (Firmware) 144 Licence Error – 145 Built-In Self Test Failed 0x5010 Component Error 150 NETOS Fatal Error 0x6100 Internal Software (Firmware) 200 Fault Parameter Transfer Module n – 201 Invalid Field Bus Address – 202 Protocol Asic Not Ready – 203 MMI Serves CPX Module – 204 Invalid Setting Switch Unit – 205 Module Set To Default Values – 255 Unknown Fault 0x1000 General Error
Tab. C.2
78 Festo – P.BE-CPX-FB39-EN – 1504NH – English
Bus node CPX-FB39

Index

A
Abbreviations, Product-specific 65............
Address assignment 26.....................
– Determination 34........................
– Technology modules 32...................
Addressing 35............................
C
Commissioning 24.........................
– Address assignment 26...................
– Addressing 35..........................
Connection technology 19..................
D
Device description files 40..................
Diagnostics mode 16......................
Diagnostics options, Overview 53............
Diagnostics via LED displays 54..............
Diagnostics via status bits 59................
Diagnostics via the I/O diagnostics interface 60. DIL switches
– Layout 14..............................
– Remove/attach cover 14..................
– Set 15.................................
Dismantling 12...........................
E
Edit, Sercos address 18....................
Electrical connections and indicators 11.......
Electrical interface (CP interface) 37..........
F
Fail safe 50..............................
Festo Maintenance Tool (CPX-FMT) software 52..
Force 50.................................
L
LED indicators 54.........................
– CPX-specific 55.........................
– Network-specific 57......................
Lines, network 20.........................
M
Module identifiers 64......................
Modules, Technology 32....................
Mounting 12.............................
N
Network 19..............................
– Cables 20..............................
– Connection technology 19.................
– Pin allocation 20........................
– Plug connector 19.......................
Notes on the documentation 6...............
O
Operating mode 15........................
– Remote controller 15.....................
– Remote I/O 15..........................
Operator unit (CPX-MMI) 52.................
P
Parameterization 50.......................
– Methods 51............................
– Requirements 51........................
– via the Festo Maintenance Tool (CPX-FMT)
software 52............................
– with the operator unit (CPX-MMI) 52........
PELV 23.................................
Pneumatic interface 38.....................
Power supply 23..........................
I
I/O diagnostics interface 60.................
Idle mode 50.............................
Intended use 7...........................
IP address, setting 21......................
IP65/IP67 13.............................
Festo – P.BE-CPX-FB39-EN – 1504NH – English 79
S
Safety instructions, General 7...............
SDDML files 40...........................
Sercos address 18.........................
Sercos III 24.............................
Servicing 6...............................
Bus node CPX-FB39
Set
– Diagnostics mode 16.....................
– DIL switches 15.........................
– IP address 21...........................
– Operating mode 15......................
Status bits 59............................
T
Technical data 64.........................
Technology modules 32....................
W
Web servers 22...........................
80 Festo – P.BE-CPX-FB39-EN – 1504NH – English
Reproduction, distribution or sale of this document or communica tion of its contents to others without express authorization is prohibited. Offenders will be liable for damages. All rights re served in the event that a patent, utility model or design patent is registered.
Copyright: Festo AG & Co. KG Postfach 73726 Esslingen Germany
Phone: +49 711 347-0
Fax: +49 711 347-2144
e-mail: service_international@festo.com
Internet: www.festo.com
Original: de
Loading...