Festo CPX-E-PB Instructions For Use Manual

Page 1
Bus module CPX-E-PB
Festo AG & Co. KG
Ruiter Straße 82 73734 Esslingen Germany +49 711 347-0 www.festo.com
Instructions for use Original instructions
8071115 2017-07 [8071117]
Bus module CPX-E-PB (PROFIBUS DP) English.............................
1 About this document
This document describes the use of the above-mentioned product. Certain aspects of use are described in other documents and must be observed è 1.1 Further applicable documents. PI PROFIBUS PROFINET® is a registered trademark of its respective trademark holder in certain countries.
1.1 Further applicable documents Document Content
Description of system CPX-E (CPX-E-SYS) Detailed description of the system CPX-E
Instructions for use of system CPX-E (CPX-E-SYS)
Instructions and important notes on mounting, electrical installation and maintenance tasks for a system CPX-E
Description of bus module CPX-E-PB (CPX-E-PB) Detailed description of product function and
parameterisation options
Device description file (GSD) Definition of the modules of a system CPX-E for
integration into the higher-order controller
Documentation for the components in a system CPX-E and the connected peripherals
Information on use of the components
Documentation for the higher-order controller and the additional participants in the network
Information on commissioning and parameterisation of the components
Fig. 1
All available documents for the product è www.festo.com/pk.
1.2 Product version
This document refers to the following product versions:
Product Version number
CPX-E-PB Bus module CPX-E-PB, revision 3 onward
Fig. 2
The product version can be identified from the product label or with the help of appropriate software from Festo.
Appropriate software for identifying the product version can be found in the Festo Support Portal è www.festo.com/sp. Information on using the software can be found in the integrated Help function.
There may be an updated version of this document for these or later product versions.  Check whether a corresponding version of this document is available
inthe Festo Support Portal è www.festo.com/sp.
1.3 Product labelling
The product label is located on the left-hand side of the module. Scanning the printed Data Matrix Code with an appropriate device opens the Festo Support Portal with the relevant documents for the product. Alternatively, the Product Key (11-character alphanumeric code on the product label) can be entered in the Support Portal search box.
Detailed information about product labelling can be found in the module description è 1.1 Further applicable documents.
1.4 Specified standards Version status
EN 60529:2013-10 IEC 60204-1:2014-10
EN 61000-6-2:2009-04 IEC 61158:2014-07
EN 61000-6-4:2011-09 NE 21:2012-05
Fig. 3
2 Safety
2.1 General safety information
 Take into consideration the legal regulations for the respective location.  Use the product only within the defined values è 13 Technical data.  Observe product labelling.  Observe further applicable documents è 1.1 Further applicable documents.  Store the product in a cool, dry, UV-protected and corrosion-protected
environment. Ensure storage times are short.
 Before working on the product: Switch off the power supply and secure it
against being switched on again.
 Observe the handling specifications for electrostatically sensitive devices.
2.2 Use for intended purpose
The product described in this document is intended solely for use as an interface between a system CPX-E and a higher-order controller through participation in aPROFIBUS DP network. The products must be used only as follows: – Use only in an industrial environment: Outside of industrial environments, e.g. in
commercial and mixed-residential areas, actions to suppress interference may have to be taken.
– Use only in combination with modules and components that are permissible for
the respective product variant è www.festo.com/catalogue. – Only use the product if it is in perfect technical condition. – Only use the product in its original condition without unauthorised
modifications. Only the conversions or modifications described in this and the
further applicable documents are permitted.
2.3 Training of specialised personnel
Installation, commissioning, maintenance and disassembly should only be conducted by qualified personnel. The qualified personnel must be familiar with installation of electrical control systems.
3 Further information
– Accessories è www.festo.com/catalogue – Spare parts è www.festo.com/spareparts
4 Service
 Contact your regional Festo contact if you have technical questions
è www.festo.com.
5 Product overview
5.1 Function
The product establishes, as a participant in a PROFIBUS DP network, the connection between a higher-order controller and the modules of a system CPX-E.
5.2 Product design
1 LED indicators 2 DIL switch 3 Diagnostic interface [DIAG]
(mini-USB)
4 Operating voltage supply terminal
block U
EL/SEN
[XD]
5 Terminal block lock 6 Linking 7 Network connection [XF1]
2
3
45
1
6
7
Fig. 4
5.3 Display components
1 Network-specific LED indicator:
– Bus error [BF] (red)
2 System-specific LED indicators:
– Operating voltage supply
U
EL/SEN
[PS] (green)
– Load voltage supply U
OUT
[PL]
(green) – System fault [SF] (red) – Force mode [M] (yellow)
2
1
Fig. 5
Page 2
The network-specific LED indicators are described later in the document è 10 Diagnostics and fault clearance. The system-specific LED indicators are described in “Instructions for use
ofsystem CPX-E” below è 1.1 Further applicable documents.
5.4 Control components DIL switches Function
1 The station number of the bus module is set binary coded using
DIL switches 1 ... 7 (permissible station numbers 1 ... 125). Factory setting: 3 Example: è Fig. 7
2
3
4
5
6
7
8 Device-specific diagnostics
ON = Active (factory setting) OFF = Inactive
Fig. 6
Example of setting the station number
DIL 1: OFF 20 = 1 Example:
DIL 2: ON 21 =2 21 + 22 + 24 = 2 + 4 + 16 = 22
DIL 3: ON 22 =4
DIL 4: OFF 23 =8 è Station number set = 22
DIL 5: ON 24 =16
DIL 6: OFF 25 =32
DIL 7: OFF 26 =64
Fig. 7
5.5 Connecting components Connection [XF1] Signal Designation
1 Shield Functional earth
2 n.c.
3 RxD/TxD-P Received/transmitted data P
4 CNTR-P Repeater control signal
1)
5 DGND Data reference potential (M5V)
6 VP Supply voltage positive (P5V)
7 n.c.
8 RxD/TxD-N Received/transmitted data N
9 n.c.
2)
Shield Functional earth
1) The repeater control signal CNTR-P is executed as a TTL signal.
2) Housing
Fig. 8
Connection [XD]
1)
Signal
0 +24 V DC operating voltage supply U
EL/SEN
1
2 0 V DC operating voltage supply U
EL/SEN
3
1) Ports XD.0 and XD.1 and por ts XD.2 and XD.3, respectively, are connected to each other in the
terminalblock.
Fig. 9
Diagnostic interface [DIAG]
Via the diagnostic interface [DIAG] (mini-USB), the bus module can be connected to a PC on which parameterisation and diagnostics software is installed.
6 Transport and storage
 Observe specifications for the environmental and storage conditions
è 13 Technical data.
7 Mounting
 The module is to be mounted in accordance with the “Instructions for use of
system CPX-E” è 1.1 Further applicable documents.
8 Installation
8.1 Network
 Use cables that meet the cable specification è Fig. 15.
You can find the corresponding connector plugs in the Festo catalogue è www.festo.com/catalogue.
Bus terminal with terminating resistors
If the bus module is at the start or end of a field bus segment, a bus terminal is required.  Make sure that the bus terminal contains a resistor network having the following
configuration:
390 W 390 W220 W
Pin 6 Pin 5
Pin 3 Pin 8
120 nH120 nH
Fig. 10
Connection with fibre-optic cables (FOC)
The PROFIBUS-DP interface of the module corresponds to the specification IEC 61158 and supports the control of network components for fibre-optic cables.
8.2 Operating voltage supply U
EL/SEN
1. Make sure that the power supply is switched off.
2. Connect cables to the terminal block in accordance with the “Instructions for use of system CPX-E” è 1.1 Further applicable documents.
9 Commissioning
Note
Malfunction due to the higher-order controller and system CPX-E being switched on in the incorrect order.  Switch on the higher-order controller and system CPX-E according to the
preset order of the network used.
1. Set up automation project for the higher-order controller with the help of the corresponding software.
2. Load the device description file into the software è www.festo.com/sp.
3. Configure the system CPX-E in the software: – System structure – Network addressing – I/O addressing
4. Transfer automation project to the higher-order controller.
Further information about commissioning the system CPX-E can be found in the “Instructions for use of system CPX-E”. Information about the parameters can be found in the “Description of system CPX-E” and in the descriptions of the modules used è 1.1 Further applicable documents.
Behaviour of display components following correct commissioning
[BF] (red) [PS] (green) [PL] (green) [SF] (red) [M] (yellow)
off lights up lights up off off
Fig. 11
Information about error elimination in the case of non-conforming behaviour can be found in the “Description of system CPX-E” and in the descriptions of the modules used è 1.1 Further applicable documents.
10 Diagnostics and fault clearance
10.1 Diagnostics options
For the diagnostics of errors, various possibilities are available: – Internal system diagnostics – LED indicators on the product
10.2 Internal system diagnostics
 Activate internal system diagnostics via the corresponding catalogue input.
– Status bits: CPX-E-PB DP slave [status] – I/O diagnostic interface: CPX-E-PB DP slave [DP-V1]
The internal system diagnostics is described in the “Description of systemCPX-E” è 1.1 Further applicable documents.
Page 3
10.3 LED indicators
This document describes the network-specific LED indicators. The system­specific LED indicators are described in the documentation for the system CPX-E è 1.1 Further applicable documents.
Bus error [BF]
1)
LED (red) Meaning Remedy
flashes
Station number not correct (e.g.address assigned twice)
 Check address setting of the
DILswitches in the bus module. Bus interface faulty  Check bus interface of the master.
Bus connection interrupted or short-circuited
 Check bus connection.
Faulty configuration  Check configuration of the master.
Bus connection poor or transmission rate not detected
 Reduce transmission rate.
off
No error
1) The behaviour of the LED indicator is dependent on parameterisation.
Fig. 12
11 Maintenance
Note
Accumulation of heat due to reduced air supply to electronics.  Keep the ventilation slots clear and remove contamination regularly.
12 Disposal
 Dispose of the packaging, and of the product at the end of its useful life,
through environmentally friendly recycling in accordance with applicable specifications.
13 Technical data
General Feature Specification/value
General technical data, system CPX-E Description of system CPX-E
è 1.1 Further applicable documents Dimensions (length x width x height) [mm] 125.8 x 37.8 x 76.5
Product weight
1)
[g] 145
Mounting position Vertical/horizontal
Ambient temperature [°C] –5 … +60 (–5 … +50)
2)
Storage temperature [°C] –20 … +70
Air humidity (non-condensing) [%] 0 … 95
Assigned address space (inputs/outputs)
Without diagnostics [bit] –/–
With status bits [bit] 8/–
With I/O diagnostic interface [bit] 16/16
Module code/submodule code (CPX-E-specific) 222/13
Module identification E-PB
DP identifier/IEC 61158
Without diagnostics 0/00
h
With status bits 64/40h, 00
h
With I/O diagnostic interface 192/C0h, 81h, 81
h
Degree of protection in accordance with EN60529
IP20
Protection against electric shock (protectionagainst direct and indirect contact to IEC 60204-1)
Through the use of PELV circuits
(Protected extra-low voltage) Electromagnetic compatibility To EN 61000-6-2/-4 and N E 21
1) Including linking
2) With horizontal mounting position
Fig. 13
Power supply Feature Specification/value
Operating voltage supply U
EL/SEN
[V DC] 24 ± 25 %
Intrinsic current consumption at nominal operating voltage 24 V from U
EL/SEN
[mA] 50
Reverse polarity protection 24 V U
EL/SEN
against
0 V U
EL/SEN
Yes
Mains buffering time [ms] 20
Fig. 14
Network-specific Feature Specification/value
Connection technology Socket, Sub-D, 9-pin
Protocol PROFIBUS DP
Specification IEC 61158
PROFIBUS chip VPC3 with DVP1
Feature RS485
Type of transmission Serial asynchronous, half-duplex
Transmission rate [kbps] 9.6 … 12000
(automatic detection)
Maximum cable length per segment
1)
[m] 100 (at 3000 … 12000 kbps)
200 (at 1500 kbps) 400 (at 500 kbps) 1000 (at 187.5 kbps) 1200 (at 9.6 … 93.75 kbps)
Branch line length
1)
1500 kbps [m] . 6.6 , 1500 kbps [m] No branch line allowed
Cable specification
2)
Cable type Twisted-pair cable, screened
Surge impedance [Ω] 135 … 165 (3 … 20 MHz) Capacitance per unit length: [pF/m] . 30 Loop resistance [Ω/km]  110 Wire diameter [mm] , 0.64 Wire cross section [mm²] , 0.34
1) Dependent on transmission rate
2) To IEC 61158 (type A)
Fig. 15