Festo CPX-E Instructions For Use Manual

CPX-E System
Festo AG & Co. KG
Ruiter Straße 82 73734 Esslingen Germany +49 711 347-0 www.festo.com
8070967 2017-07 [8070969]
CPX-E System English.................................................
Reproduction, distribution or sale of this document or communication of its con tents to others without express authorization is prohibited. Offenders will be liable for damages. All rights reserved in the event that a patent, utility model or design patent is registered.
1 About this document
This document describes the use of the above-mentioned product family. Certain aspects of use are described in other documents and must be observed è 1.1 Further applicable documents.
1.1 Further applicable documents Document Table of contents
Description of the CPX-E system (CPX-E-SYS) Detailed description of the CPX-E system
Documentation of the components in a CPX-E system and the connected periphery
Information on use of the components
Special documentation on ATEX Information on the use of the product in explos
ive gas atmospheres
Device description files Definition of the modules of a CPX-E system for
integration into the higher-order controller
Documentation of the higher-order controller and additional participants in the network
Information on commissioning and paramet erisation of the components
Fig. 1
All available documents for the product è www.festo.com/pk.
1.2 Product version
This document refers to the system consisting of CPX-E modules. The product version can be determined by the product labelling or using suitable Festo software.
Suitable software for determining the product version is available on the support portal of Festo è www.festo.com/sp. Information for the use of the software is included in the integrated help function.
1.3 Product labelling
The CPX-E modules are labelled on the left lateral surface. The product labelling is described in the documentation supplied with the product.
1.4 Specified standards Version status
DIN 46228-1:1992-08 EN 60529:2013-10 DIN 46228-4:1990-09 EN 60715:2001-09 EN 60068-2-27:2010-02 IEC 60204-1:2014-10
Fig. 2
2 Safety
2.1 General safety information
 Take into consideration the legal regulations for the respective destination.  Use the product only within the defined values è 15 Technical data.  Take into account labelling on the product.  Observe the further applicable documents
è 1.1 Further applicable documents.
 Store the product in a cool, dry, UV-protected and corrosion-protected
environment. Ensure storage times are short.
 Before working on the product: Switch off the power supply and secure it
against being switched on again.
 Observe the handling specifications for electrostatically sensitive devices.
2.2 Intended use
The product family described in this document is intended only for use within a protected range in the vicinity of a machine and/or automated system. The products must be used only as follows: – Use only in an industrial environment. Outside of industrial environments, e.g. in
commercial and mixed-residential areas, actions to suppress interference may have to be taken.
– Use only in combination with modules and components that are permissible for
the respective product variant è www.festo.com/catalogue. – Only use the product if it is in perfect technical condition. – Only use the product in original status without unauthorised modifications. Only
the conversions or modifications described in this and the other applicable doc
uments are permitted.
2.3 Training of specialized personnel
Installation, commissioning, maintenance and disassembly should only be conduc ted by qualified personnel. The qualified personnel must be familiar with installation and operation of elec trical control systems.
3 Further information
– Accessories è www.festo.com/catalogue – Spare parts è www.festo.com/spareparts
4 Service
 Contact your regional Festo contact person if you have technical questions
è www.festo.com.
5 Product overview
5.1 Function
The CPX-E system is a modular system for the connection of electrical periphery. The individual modules in a CPX-E system are used, for example, to detect sensor signals and control actuators. Using a bus module or controller, the CPX-E system can be connected to a higher-order controller through a network or operated autonomously. Various interfaces and functions are available for diagnosis.
5.2 Product design
CPX-E system
A CPX-E system consists of a bus module or controller on the left side and at least one I/O module for signal processing. The connection between the modules is implemented using linking elements. The contacts of both external linking elements are protected by end supports.
2 end supports are included with a bus module or controller.
1
2
3
1 Input and output modules 2 Linking element
3 Bus module (here: CPX-E-PN)
Fig. 3
CPX-E modules
The CPX-E modules are designed in such a way that an exchange of individual com ponents is possible without dismantling the CPX-E system. By disengaging the interlock of the terminal strips, you can remove them from the module. By disenga ging the interlock of the module, you can remove an individual module from the system. The link remains on the H-rail.
1
2
3
4
5
6
7
8
1 LED display components 2 Terminal strips 3 Interlock of terminal strips 4 Interlock of module
5 Linking element 6 Contact of functional earth (FE) 7 Housing 8 DIL switch
1)
1) Module-dependent
Fig. 4
5.3 Display components
The CPX-E modules have LED indicators specific to the module, network or system: – LED indicators specific to the module or network are described in the document
ation for the respective module.
– An overview of the system-specific LED displays is displayed in the following
table è Fig. 5.
– The behaviour of the system-specific LED indicators is described in “Description
of the CPX-E system” (è 1.1 Further applicable documents) and further below è 11 Diagnostics and fault clearance.
LED Significance
PS (green)
Power System Monitoring of the operating voltage supply U
EL/SEN
PL (green)
Power Load Monitoring of the logic and load voltage supply U
OUT
SF (red)
System Failure System fault
1)
M (yellow)
Modify Force mode active or system start with saved para
meterisation and saved CPX expansion have been set.
1) Display of 3 error classes through different flashing behaviours.
Fig. 5
Detailed information on the error classes can be found in “Description of the CPX-E system” è 1.1 Further applicable documents.
5.4 Control elements
A CPX-E module has interlocks for engaging and disengaging the module terminal strips and connected conductors.
1
2
3
1 Interlock of spring-loaded terminal 2 Interlock of terminal strips 3 Interlock of module
Fig. 6
5.5 Connecting components
Connection of the CPX-E system
The individual modules of a CPX-E system are connected to each other through the link. The contact to the link is established when the modules are hung into the H-rail è 7 Mounting. If a module is removed, the connection to the other modules is interrupted.
Connecting peripheral equipment
For the connection of the peripheral equipment, the modules have terminal strips with spring-loaded terminals è 8 Installation.
6 Function examples
1
2
3
4
5
6
1 Higher-order controller 2 valve terminal VTUG 3 Standards-based cylinder with
proximity sensors for position sensing
4 Flow sensor 5 Signal lamp 6 CPX-E system with bus module and
I/O modules
Fig. 7
7 Mounting
7.1 H-rail mounting
The modules can be mounted to an H-rail 35 × 7.5 mm according to EN 60715.
When selecting screws for H-rail mounting, a distance between the H-rail and the linking elements of 3 mm must be observed. The distance between the mounting screws of the H-rail may be a max imum of 50 mm.
7.2 Mounting clearances
To guarantee a sufficient pressurisation of the modules, the following minimum distances must be observed for the mounting of the CPX-E system è Fig. 8.
1
2
1 CPX-E system 2 End supports
Dimensions [mm]: a = 40
b = 20 c = 30 d = 106 e = 195
Fig. 8
7.3 Link
Hanging the linking element into place
1. Place the linking element into the correct position on the H-rail.
2. Clip the linking element to the H-rail.
3. Push together the linking elements until they engage.
1
2
1.
2.
3.
1
1 Linking element 2 H-rail
Fig. 9
7.4 Clamping and drilling
Hanging the module into place and engaging it
1. Place the module above the linking element(s)1) on the H-rail.
2. Press the module onto the H-rail until the module interlock engages.
1
2
3
1.
2.
4
1 Module 2 Interlock of module 3 H-rail 4 Linking element
1) In the case of bus modules, 2 linking elements are required. In the case of controllers, 4 linking ele
ments are required.
Fig. 10
Disengaging and removing the module
1. Disengage the module interlock (e.g., with a slotted screwdriver).
2. Tilt up the module and remove it from the H-rail.
1
2
3
4
1.
2.
5
1 Module 2 Slotted head screwdriver 3 Interlock of module 4 H-rail 5 Linking element
Fig. 11
8 Installation
Note
Malfunction due to electromagnetic interference.  Connect screening to the connection for functional earth FE.  Connect the H-rail to the earth potential with low impedance.
8.1 Power supply concept
A CPX-E system uses separate voltages to supply the electronic and sensors (U
EL/
SEN
) and to supply outputs (U
OUT
). The voltage potentials (+24 V DC and 0 V DC) are respectively connected to each other in the terminal strips. It respective voltage can be conducted from one module to another.
Warning
Risk of injury due to uncontrolled movements of the connected actuators. A feedback loop through the sensor and/or actuator supply of the modules can supply the CPX-E system and lead to unwanted functions.  Keep the range of movement of the connected actuators unobstructed.
Operating voltage supply U
EL/SEN
The operating voltage supply U
EL/SEN
to supply the electronics and sensors is fed at the bus module or controller and distributed internally to the entire CPX-E system though the link.
Load voltage supply U
OUT
The load voltage supply U
OUT
to supply the outputs is fed separately directly at
every module with outputs.
1 23456
78
9
1 Bus module CPX-E-PN 2 Input module CPX-E-16DI 3 Output module CPX-E-8DO 4 Input module CPX-E-4AI-U-I 5 Output module CPX-E-4AO-U-I
6 IO-Link® master module
CPX-E-4IOL
7 Load voltage supply U
OUT
8 Operating voltage supply U
EL/SEN
9 Link
Fig. 12
The operating voltage supply U
EL/SEN
and load voltage supply U
OUT
are implemented separately from each other within the CPX-E system. If this separation is not required for the respective use case, both voltages can also be supplied from a common voltage source. In this case, the load voltage supply must be able to be disconnected separately.
8.2 Connect lines
Warning
Electric voltage Injury caused by electric shock, damage to machine and to system  For the electrical power supply, use only PELV circuits in accordance with
IEC 60204-1/EN 60204-1 (Protective Extra-Low Voltage, PELV).
 Observe the general requirements IEC 60204-1/EN 60204-1 of the PELV
power circuits.
 Use only voltage sources that ensure a reliable electric separation from the
mains network in accordance with IEC 60204-1/EN 60204-1.
 Always connect all circuits for the operating and load voltage supplies U
EL/SEN
and U
OUT
.
1. Make sure the module and line are de-energised.
2. Strip the end of the line and fit wire end sleeves if required.
3. Disengage the spring-loaded ter minal interlock (e.g., with a slotted screwdriver).
4. Insert the end of the line into the ter minal strip to the limit stop.
5. Engage the spring-loaded terminal interlock.
1
2
3
4
3.
4.
1 Slotted head screwdriver 2 Interlock of spring-loaded terminal 3 Terminal strip 4 Cable
Fig. 13
8.3 Disconnecting cables
1. Make sure the module and line are de-energised.
2. Disengage the spring-loaded ter minal interlock (e.g., with a slotted screwdriver).
3. Pull the line from the terminal strip.
1
2
3
4
2.
3.
1 Slotted head screwdriver 2 Interlock of spring-loaded terminal 3 Terminal strip 4 Cable
Fig. 14
9 Commissioning
The behaviour of the CPX-E system during commissioning is largely determined by the parameterisation of the bus module.  Observe information on parameterisation in the description of the bus node
è 1.1 Further applicable documents.
Warning
Risk of injury due to uncontrolled movements of the connected actuators. The CPX-E system starts even if the parameterisation process is incomplete.  Keep the range of movement of the connected actuators unobstructed.  Check the parameterisation and address allocation of the inputs and/or
outputs (e.g., using Force mode).
In order to avoid connecting and addressing errors, you must carry out the commissioning steps as follows.
1. Check the mounting and electrical connections è 9.1.
2. Make settings on the bus module or controller è 9.2.
3. Functional test (without higher-order controller) è 9.3.
4. Commissioning in network (with higher-order controller) è 9.4.
5. Parameterisation è 9.5.
Note
Addressing errors caused by changing address ranges during operation.  Do not connect the bus module/controller to the network until after the func
tional test (è 9.3).
9.1 Checking the mounting and electrical connections
1. Check the mounting of the CPX-E system.  Make sure the linking elements are clipped onto the H-rail and engaged in
each other.  Make sure all module interlocks are engaged to the H-rail.  Make sure all terminal strip interlocks are engaged to the H-rail.
2. Check the electrical installation of the CPX-E system.  Check the connections of the functional earth.  Check the connected lines for a firm seat.  Check the feed of the voltage supplies.  Check the allocation of the sensors and actuators to the modules.
9.2 Make settings on the bus module or controller
Settings are made on the bus module or controller independently of the module using rotary and/or DIL switches.
The functions and factor settings of the rotary and DIL switches (if existent on the module) are described in the respective documentation accompanying the product.
 Make the desired settings on the bus module or controller if they deviate from
the factory setting.
9.3 Functional test (without higher-order controller)
1. Switch on the power supplies (U
EL/SEN
, U
OUT
).
2. Check the behaviour of the CPX-E system: – LED displays – Connected actuators
9.4 Commissioning in network (with higher-order controller)
Note
Malfunction due to the activation of the higher-order controller and CPX-E system in the incorrect order.  Switch on the higher-order controller and CPX-E system according to the pre
set order of the network used.
Information on commissioning can be found in the “Instructions for use” for the respective bus module è 1.1 Further applicable documents.
9.5 Parameterisation
With the aid of parameterisation, the behaviour of the CPX-E system the individual modules and channels can be adapted to each particular application. Parameterisation can be performed using suitable software from Festo or using the higher-order controller. The parameters are preset at the factory.
The possibilities of parameterisation depend on the bus module or controller used (è Description of the respective bus module/controller). A list and description of the general parameters can be found in the “Description of the CPX-E system” è 1.1 Further applicable documents.
Parameterisation using Festo software
Suitable software for parameterisation can be found on the support portal of Festo è www.festo.com/sp. Information for the use of the software is included in the integrated help function.
Parameterisation using the higher-order controller
Information on parameterisation using the higher-order controller can be found in the description of the respective bus module or controller.
Start-up behaviour of the CPX-E system
The “System start” system parameter fundamentally influences the start-up behaviour of the CPX-E system. – “Standard parameters” setting (presetting):
The CPX-E system starts with the factory setting. The desired parameterisation can be established by the higher-order controller.
– “Stored parameters” setting
The CPX-E system starts with the parameters saved in the bus module. The setting is signaled by the lighting of the “Modify” LED indicator [M] è 5.3 Display components.
If the “Modify” LED indicator [M] is lit continuously, the parameterization of the system is not restored automatically by the higher-level controller after a replacement.  Before replacement, note the required parameters and re-establish
them again after replacement.
10 Operation
The behaviour of the system in case of an error with the following malfunctions is dependent on the parameterisation of the higher-order controller and the setting of the system parameters “Fail safe”: – Telegram failure – Network interruption Depending on the parameterisation, the electrical outputs are switched off (factory setting), switched on or retain their status.
Detailed information on the “Fail safe” can be found in the “Description of the CPX-E system” è 1.1 Further applicable documents.
11 Diagnostics and fault clearance
11.1 Diagnostics options
For the diagnosis of errors, various possibilities are available depending on the parameterisation and network protocol used: – Internal system diagnosis – LED indicators on the product
11.2 Internal system diagnosis
The internal system diagnosis is described in the “Description of the CPX-E system” and the module descriptions è 1.1 Further applicable documents.
11.3 LED indicators
Various LED indicators are available on every module for the visualisation of the statuses and errors. In the process, LED indicators specific to the system and module or network are differentiated.
The system-specific LED indicators of the controllers and bus modules are described in this document. LED indicators specific to the module or network are described in the documentation for the respective module.
Power System [PS] – Operating voltage supply U
EL/SEN
LED (green) Significance Remedy
Lights up
ON OFF
Voltage supply present. No error.
Flashes
ON OFF
Voltage supply present, but outside of the tolerance range.
 Eliminate undervoltage.
The link on the bus module is missing or incomplete.
 Check the link.
Flashes
ON OFF
The internal fuse of the voltage supply has responded.
 Eliminate short circuit/overload.
Depending on the parameterisa tion, the voltage supply is then switched on automatically again (factory setting) or it must be switched off and then on again.
Off
ON OFF
Voltage supply not present.  Check connection of the power
supply.
Fig. 15
Power Load [PL] – Load voltage supply U
OUT
LED (green) Significance Remedy
Lights up
ON OFF
Voltage supply present. No error.
Flashes
ON OFF
Voltage supply present, but outside of the tolerance range.
 Eliminate undervoltage.
Off
ON OFF
Voltage supply not present.  Check connection of the power
supply.
Fig. 16
System Failure [SF] – System failure LED (red)
1)
Significance Remedy
Flashes
ON
OFF
Simple error/information (error class 1)
è Description of the CPX-E system
ON
OFF
Error (Error class 2)
ON
OFF
Serious error (Error class 3)
Off
ON OFF
No error
1) The LED indicator “System Failure” [SF] flashes depending on the error class.
Fig. 17
Modify [M] – Parameterisation modified or “Force” active. LED (yellow) Significance
Lights up
ON OFF
System start with saved parameterisation and saved CPX expansion set; parameters and CPX expansion are saved remanently; external parameterisation is blocked
1)
Caution when replacing systems with saved parameterisation. In the case of these systems, parameterisation is not carried out automatically by the higher-order controller on replacement.  Before replacement, note required settings and restore them
after replacement, if required.
Flashes
ON OFF
The Forcen function is enabled.
1)
Off
ON OFF
System start with default parameterisation (factory setting) and current CPX expansion set; external parameterisation is possible (presetting).
1) The indication of the “Forcen” function (LED flashing) has priority over indication of the setting for the
system start with the saved parameterisation and saved extension (LED lights up).
Fig. 18
12 Maintenance
Note
Accumulation of heat due to reduced air supply to electronics.  Keep the ventilation slots free and regularly remove contamination.
13 Conversion
13.1 Replacing the module
Note
When a bus module, controller or complete system is replaced, a different parameterisation will result in deviating behaviour.  Before replacement, check which settings are required and restore them after
the replacement.
Removing the terminal strips
If a module is exchanged within the course of a conversion or repair, the conductor remains in the terminal strip and the terminal strips are removed from the module.
1. Ensure that the module is de-energised.
2. Insert the screwdriver through the recess of the terminal strip interlock and into the module interlock.
3. Pull the screwdriver in the direction of the arrow to disengage the terminal strips.
4. Remove the terminal strips.
1
2
3
4
2.
3.
4.
1 Screwdriver 2 Terminal strip 3 Interlock of terminal strips 4 Interlock of module
Fig. 19
After the terminal is disengaged, it remains in a stopped position. The ter minal strips that are not removed must be pushed back in to the limit stop.
Disengaging and removing the module
è Fig. 11
Hanging the module into place and engaging it
è Fig. 10
Inserting terminal strips
1. Ensure that the module is de-energised.
2. Place the terminal strips in the appropriate positions on the module.
3. Press in the terminal strips to the limit stop.
1
2.
3.
1 Terminal strip
Fig. 20
To prevent connection faults, the terminal strips of the signals and terminal strips of the voltage supply have matching codes.
13.2 Replacing the linking element
1. Disengage and remove the module è Fig. 11.
2. Disconnect the linking elements by pulling them apart.
3. Release the lower lock of linking ele ment from the H-rail.
4. Remove the linking element from the H-rail.
5. Hang the new linking element into place è Fig. 9.
1
2
2.
3.
2.
4.
3
1 Linking element 2 H-rail 3 Lower lock of linking element
Fig. 21
14 Disposal
 Dispose of the packaging and the product at the end of its useful life through
environmentally friendly recycling in accordance with applicable specifications.
15 Technical data
General information Characteristic Specification/value
Assembly position Vertical/horizontal
Ambient temperature [°C] –5 … +60 (–5 … +50)
1)
Storage temperature [°C] –20 … +70
Air humidity (non-condensing) [%] 0 … 95
Max. permissible setup altitude above sea level [m] 2000
Max. number of modules per CPX-E system, including the bus module or controller
11
Address volume of the inputs/outputs [byte] 64/64 (maximum)
Degree of protection in accordance with EN 60529
IP20
Protection against electric shock (protection against direct and indirect contact to IEC 60204-1)
Through the use of PELV circuits (protected extra-low voltage)
CE marking (see declaration of conformity) è www.festo.com
To EU EMC Directive
Explosion prevention and protection (IECEx/ ATE X )
è Special documentation on ATEX
Certification certificate RCM compliance mark
Contamination level 2
Vibration and shock resistance in accordance with EN 60068
2)
Vibration (part 2-6) H-rail SG1
Shock (par t 2 - 27) H-rail SG1
Continuous shock (part 2-27) H-rail SG1
1) In case of horizontal mounting position
2) Explanation of the severity level è Fig. 23 … Fig. 25
Fig. 22
Vibration load Frequency range [Hz] Acceleration [m/s2] Deflection [mm] SL1 SL2 SL1 SL2 SL1 SL2
2 … 8 2 … 8 ±3.5 ±3.5
8 … 27 8 … 27 10 10
27 … 58 27 … 60 ±0.15 ±0.35
58 … 160 60 … 160 20 50
160 … 200 160 … 200 10 10
Fig. 23
Shock load Acceleration [m/s2] Duration [ms] Shocks per direction SL1 SL2 SL1 SL2 SL1 SL2
±150 ±300 11 11 5 5
Fig. 24
Continuous shock load Acceleration [m/s2] Duration [ms] Shocks per direction
±150 6 1000
Fig. 25
Power supply Characteristic Specification/value
Operating voltage supply U
EL/SEN
Nominal operating voltage [V DC] 24 ± 25 %
Trigger level, undervoltage identification [V DC] 17.5
Max. current load of terminal strip [A] 8
Mains buffering time Module-dependent
1)
Load voltage supply U
OUT
Nominal operating voltage [V DC] 24 ± 25 %
2)
Trigger level, undervoltage identification Module-dependent
1)
Max. current load of terminal strip [A] 8
1) è Documentation of the modules
2) The indication of tolerance deviates in case of some modules.
Fig. 26
Connection data of the terminal strips Key feature Specification/value
4-pin 6-pin
Conductor cross-section
Massive [mm2] 0.14 … 1.5
Flexible [mm2] 0.14 … 2.5 0.14 … 1.5
Flexible with wire end sleeve
Without plastic sleeve [mm2] 0.14 … 1.5
With plastic sleeve [mm2] 0.14 … 1.5 0.14 … 1.0
Length of the wire end sleeve without plastic sleeve
1)
Conductor cross section 0.14 … 1.0 mm2[mm] 8 … 10
Conductor cross-section 1.5 mm
2
[mm] 8 … 10 10
Length of the wire end sleeve with plastic sleeve
2)
Conductor cross-section 0.14 … 0.34 mm2[mm] 8 … 10
Conductor cross-section 0.5 … 1.0 mm
2
[mm] 8 … 10 10
1) in accordance with DIN 46228-1
2) in accordance with DIN 46228-4
Fig. 27
Loading...