The reproduction, distribution and utilization of this document
as well as the communication of its contents to others without
express authorization is prohibited. Offenders will be held
liable for the payment of damages. All rights reserved in the
event of the grant of a patent, utility module or design.
Festo P.BE-CPX-CP-EN en 1211b
I
Contents and general instructions
PROFIBUS®,PROFIBUS-DP®,INTERBUS®, DeviceNet®, CC-Link®,TORX®are registered
trademarks of the respective trademark owners in certain countries.
The CPX-CP interface described in this description has been
designed exclusively for use in combination with CPX
terminals from Festo. The designated CP modules from Festo
(CP valve terminals and CPI I/O modules) can be connected
to the CPX-CP interface. The CPX terminal and the connected
CPI modules are only to be used as follows:
–asintended
–without unauthorised modifications
–in excellent technical condition.
If standard ancillary components, such as sensors and actuators, are connected, the specified limits for pressures, temperatures, electrical data, torques, etc. must be complied with.
Comply with the legal rules and regulations and standards,
rules of the testing organisations and insurance companies
and national specifications applicable for the location.
Warning
•
Only use PELV circuits in accordance with
IEC/EN 60204-1 (protective extra-low voltage, PELV)
for the electrical power supply.
•
Also observe the general requirements for PELV circuits
in accordance with IEC EN 60204-1.
•
Use only voltage sources that guarantee reliable
electrical isolation of the operating voltage according to
IEC DIN EN 60204-1.
Festo P.BE-CPX-CP-EN en 1211b
VII
Contents and general instructions
Ranges of application and certifications
The products fulfil the requirements of EU directives and bear
the CE certification.
Standards and test values, which the products must comply
with and fulfil, can be found in the technical appendix section.
The product-relevant EU directives can be found in the declaration of conformity.
Certificates and declarations of conformity for these products
can be found at www.festo.com.
Target group
Service
This description is intended exclusively for technicians
trained in control and automation technology, who have
experience in installation, commissioning, programming and
diagnostics of programmable logic controllers (PLC) and
fieldbus systems/networks.
Please consult your local Festo repair service if you have any
technical problems.
VIII
Festo P.BE-CPX-CP-EN en 1211b
Contents and general instructions
Important user instructions
Danger categories
This manual contains instructions on the possible dangers
which may occur if the product is not used correctly. These
instructions are marked (Warning, Caution, etc.), printed on a
shaded background and marked additionally with a pictogram. A distinction is made between the followi ng danger
warnings:
Warning
This means that failure to observe this instruction may
result in serious personal injury or damage to property.
Caution
This means that failure to observe this instruction may
result in personal injury or damage to property.
Note
This means that failure to observe this instruction may
result in damage to property.
The following pictogram marks passages in the text which
describe activities with electrostatically sensitive components.
Festo P.BE-CPX-CP-EN en 1211b
Electrostatically sensitive components may be damaged if
they are not handled correctly.
IX
Contents and general instructions
Marking special information
The following pictograms mark passages in the text
containing special information.
Pictograms
Information:
Recommendations, tips and references to other sources of
information.
Accessories:
Information on necessary or sensible accessories for the
Festo product.
Environment:
Information on environment-friendly use of Festo products.
Text markings
•
Bullet points denote activities that may be carried out in
any sequence desired.
1. Figures denote activities which must be carried out in the
numerical order specified.
–Hyphens indicate general activities.
X
Festo P.BE-CPX-CP-EN en 1211b
Contents and general instructions
Notes on the use of this manual
This manual contains specific information on the method of
operation, and on fitting, installing and commissioning the
CPX-CP interface.
Special information on commissioning, programming and
diagnostics of a CPX terminal with the CPX fieldbus node or
CPX-FEC used can be found in the relevant description.
General basic information on the method of operation, on
fitting, installing and commissioning CPX terminals can be
found in the CPX system manual.
An overview of the structure of the CPX terminal user
documentation is contained in the CPX system description.
www.festo.com Support portal: search term “CPX
system description”
Festo P.BE-CPX-CP-EN en 1211b
XI
Contents and general instructions
Information on the CPI modules and the valve terminals with
a CPI connection can be found in the manual for the relevant
module. An overview is shown in Tab. 0/1.
Version
CP modules,
Electronics
description
Modules
with
CP
connection,
Electronics
description
Description
Pneumatics
TitleContents
“CPI-CL modules, CPI-EL
modules”
Type P.BE-CPX-EA-CL...
“CPV Direct”
Type P.BE-CP-DI...
“CDVI ...”
Type P.BE-CDVI-DN-...
“CPA-SC / CPV-SC ...”
Type P.BE-CPASCCPVSC-...
“CPV valve terminal”
Type P.BE-CPV-...
“CPA valve terminals”
Type P.BE-CPA-...
Mounting, installation and commissioning of CP
input and output modules, type CP-...-CL and
CPI-…-EL
Instructions on mounting, installation,
commissioning and diagnostics for the
corresponding CPV valve terminal with direct
link
Instructions on mounting, installation,
commissioning and diagnostics of the CDVI with
fieldbus direct link “DeviceNet”
Instructions on mounting, installation,
commissioning and diagnostics of the CPV-SC
or CPA-SC valve terminal with fieldbus direct
link for PROFIBUS DP or DeviceNet.
Mounting, installation, c ommissioning,
servicing and conversion of the CPV pneumatics
(type 10)
Mounting, installation, c ommissioning,
servicing and conversion of the CPA pneumatics
(type 12)
“MPA valve terminal”
Type P.BE-MPA-...
Tab. 0/1:Descriptions for CP I/O modules and CP valve terminals from Festo
XII
Mounting, installation, c ommissioning,
servicing and conversion of the CPA pneumatics
(type 32)
Festo P.BE-CPX-CP-EN en 1211b
Contents and general instructions
The following product-specific terms and abbreviations are
used in this manual:
Term/abbreviation
CP cableSpecial cable for connecting the various CPI/CP modules in a CP string.
CP functionalitySupports the CP protocol without extended functions
CP moduleCollective term for modules without extended functions which can be in-
CP stringCPI or CP modules which are connected by CPI/CP cable to the CPX-CP
CP valve terminalCPV valve terminal (type 10) or CPA valve terminal ( type 12), each with CP
CP systemComplete electrical installation system consisting of a CP master with one
CPI cableSpecial cable for connecting the various CPI/CP modules in a CP string.
CPI connectionSocket or plug on the CPI modules which allows the modules to be connec-
Meaning
Colour: black, type KVI-CP1-... and type KVI-CP2-...
tegrated into a CPI/CP system.
interface. For reasons of simplicity, only the term “CP string” is used, even
if it has CPI functions.
connection (also regarded as CP modules). Basic electric unit, black.
or more CP strings. The system consists of CP modules (without extended
functions).
Colour: white, type KVI-CP3-. ..
ted using the CPI or CP cable.
CPI field bus interfaceTerm for a CPI capable interface with field bus connection (e.g.
CPI field bus moduleDefined combination of a CPX field bus node and a CPX-CP interface.
CPI functionalitySupports the CPI protocol with extended functions
CPI moduleCollective term for modules with extended functions which can be integ-
CPI systemAlso: “CPI installation system”
Tab. 0/2: Specific terms and abbreviations
Festo P.BE-CPX-CP-EN en 1211b
combination of CPX field bus node and CPX-CP interface (CPI field bus
module) or CPV with CPI string extension (CPV Direct)).
connects a CPI system with a field bus.
rated into a CPI/CP system.
Complete electrical installation system consisting of a CP master with one
or more CP strings. The system consists of CPI/CP modules with and
without extended functions. The system need not consist exc lusively of CPI
modules.
XIII
Contents and general instructions
Term/abbreviationMeaning
CPX-CP interfaceCPX module with 4 CP strings for connecting CPI/CP modules and CP valve
terminalstotheCPXterminal.
CPX modulesCollective term for the various modules which can be integrated into a CPX
terminal.
CPX terminalComplete system comprising CPX modules with or without pneumatics
Extended functions– Additional options in string assignment:
Up to 4 modules per string with a maximum of 32 inputs and 32 outputs.
Without extended functions, only 1 output and 1 input module is possible.
– Revised data communication:
Inputs report change in status when data arrive or a diagnostic message
is present. Message is queried specifically. Additionally, the system
monitors the participants for TimeOut.
Without extended functions, the system, queries information from the
stations cyclically (so-called polling).
Fieldbus node sProvide the connection to spe cific fieldbuses. Tra nsmit control signals to
the connected modules and monitor their operational ability.
IDigital input
I/O modulesCollective term for the modules which provide digital inputs and outputs
Festo can assist you in solving your automation task at the
machine level with the aid of valve terminals. Due to its
modular structure, the CPI system from Festo enables you to
integrate valve terminals and I/O modules optimally in your
machines and systems.
1
CPX terminal with
CP interface as CP
master
2
CP modules
3
CP string
12
3
4
4
CP input module
5
CPV valve terminal
6
CPA valve terminal
7
CP string exclusively
with CPI modules
(modules with extended functions)
Fig. 1/1:Example 1 for design of a CPI system
Note
Observe that only products from Festo can be connected.
5
4
6
7
Festo P.BE-CPX-CP-EN en 1211b
1-3
1. System summary – CPI system
3
2
1
CPI fieldbus node
1
2
MPA-CPI valve terminal
3
CPV-CPI valve terminal
4
CP-CL module
5
CP-EL module
Fig. 1/2:Example 2 for design of a CPI system
45
1-4
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
A CPI system consists of individual modules which are connected to each other by means of CPI cables. In this way it is
possible to decentralise the configuration of the CPI modules.
The compact CP valve terminals and I/O modules can be
mounted very close to the cylinders to be controlled. This
enables short compressed air lines to be used.
System losses can be minimized if short compressed air
tubing is used and the times required for pressurising and
exhausting the tubing can be reduced.
This enables smaller valves with sufficient flow to be used,
thereby helping to reduce costs.
Festo P.BE-CPX-CP-EN en 1211b
1-5
1. System summary – CPI system
1.1.1Method of operation of the CPI/CP system
CPI/CP systems are composed of the following modules:
Modules
CPI/CP masterSpecial CP fieldbus nodes and CP
Function
interfaces are available for the various fieldbuses.
– As electrical modules are an in-
tegral part of a CPX terminal or a
modular valve terminal (CPX-CP
interface/CPI interface).
– Provide the connection to specif-
ic fieldbuses (CPI node, CPV direct)
– These offer connections for up to
four strings to which I/O modules and CP valve terminals are
connected.
– They transmit control signals to
the c onnected modules and
monitor their functioning
1-6
CPV/CPV-SC valve terminals
with CPI connection
– These provide different valve
functions via valve sub-bases for
controlling pneumatic actuators
– Relay plates, pressure zone sep-
aration plates and blanking
plates can also be integrated
Tab. 1/1:Overview of the CPI modules - Part 1
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
ModulesFunction
MPA valve terminals
with CPI connection
CP-/CPI input modules (type CL, EL, RL)
CP-/CPI output
modules (type CL,
EL, RL)
– These provide different valve functions
via valves for controlling pneumatic actuators.
– Provide inputs for connecting sensors
and thus enable, for example, cylinder
positions to be interrogated
– These provide universally effective elec-
tric outputs for controlling low-current
consuming devices (in addition, valves,
lamps, etc.)
Festo P.BE-CPX-CP-EN en 1211b
Tab. 1/2: Overview of CPI modules - part 2
1-7
1. System summary – CPI system
123
In the capacity of CPI master, each CPX-CP interface controls
data transfer to a wide variety of controller systems in a CPX
terminal. In principle, several CPX-CP interfaces can be used
in a CPX terminal.
1
Field bus (incoming)
2
Field bus (continuing)
3
CPI master
(CPX-CP interface)
4
CP string
5
CP input module
6
CP valve terminal
7
Sensor
8
Cylinder
9
CP output module
Fig. 1/3:Method of operation of the CPI system
4
5
6
7
8
9
Cable lengthsThe complete length of cable on a string must not exceed
1-8
I/O data exchange between the CPX terminal and the modules
connected to the CPX-CP interface takes place constantly via
the CPX-CP interface.
10 m.
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
1.1.2Variants and extension rules for the CPI-/CP system
Modules can be divided into two groups:
–CPI modules (extended functions)
–CP modules (no extended functions)
Tab. 1/3 shows the number of supported modules and rules
dependent on the type of the master and the CPI/CP modules.
Rules and properties
CPI system– Max. 4 modules on the CP string
– Max. 32 inputs and 32 outputs per CP string
CPI modules– There is an incoming and continuing interface on all CPI modules and valve
terminals
– Any sequence of the CPI modules/valve terminals within the CP string
CP modules– There is an incoming and continuing interface on CP output modules and CP
valve terminals
– Only incoming interface at CP input modules. They can therefore only be
placed at the end of a CP string.
CPI/CP masterThe CPX-CP interface and the CPV Direct are CPI masters.
A mixture of CPI/CP modules is possible on CPI masters:
– Only one CP input module is possible at the end of a string
– Per CP string, only one CP valve terminal
– “Unused” locations on the CP string can be “filled” with CPI modules2).
1)
Without extended functions2)With extended functions
1)
or one CP output module
1)
Tab. 1/3: Rules for extending the CPI system
Festo P.BE-CPX-CP-EN en 1211b
Note
Independent of the type of CPI/CP modules, not more than
32 inputs and 32 outputs may be connected (sum of all
modules on a CP string).
That is, a CP string can be extended with a maximum of 2
CP valve terminals with extended functions, since they
always occupy 16 output addresses.
1-9
1. System summary – CPI system
CP master
VT / OI
VT / O
I
VT / O: CP valve terminal or
CP output module
I:CP input module
Fig. 1/4:Example: Setting up a CP system
(without extended functions)
All CPI modules (with extended functions) can also be connected to CP masters (without extended functions) as shown
in Fig. 1/4.
1-10
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
CPI master
CPI master
CP (O)CPI (I/O)
CPI (I/O)
CPI (I/O)
CPI (I/O)
CP (O)
CPI (I/O)
CPI (I/O)
CPI (I/O)
CPI (I/O)CPI (I/O)
CPI (I/O)
CP (O)
CPI (I/O)CPI (I/O)
CPI (I/O)
CPI (I/O)
CPI (I/O)
CPI (I/O)
CP (O)
CP (I)
CP (I)CP (O)CPI (I/O)
Grey:CPI (with extended functions)
CP (I):CP input module
CP (O):CP output module or CP valve terminal
CPI (I/O):CPI input or output module (with extended functions) or CP valve terminal
with CPI ability (for valve terminals: max. 2 possible)
Rules:
CP:For the CP master, the rules remain valid.
CPI:Max. 32 inputs and 32 outputs per string, max. 4 modules per string
Max. 1 CP output module or 1 CP valve terminal
Max. 1 CP input module always at the end of the string
Max. 2 valve terminals with CPI functions per string
Fig. 1/5:Example: expansion of a CPI/CP system
Festo P.BE-CPX-CP-EN en 1211b
CPI (I/O)CPI (I/O)
CPI (I/O)
CP (O)
CPI (I/O)
CP (O)
CP (I)
CP (I)
1-11
1. System summary – CPI system
1.1.3Assigned I/Os of the CPI/CP modules
Tab. 1/4 provides an overview of the assigned addresses for
the various CPI/CP modules (status at November 2012).
Assignment dependent on equipment. CPV..-GE-FB-4/6/6 dynamically occupies 8 or 16 outputs
2)
Assignment depe ndent on equipment. CPI-MPA dynamically occupies 8, 16, 24 or 32 outputs
3)
No function on CP master
Tab. 1/4:Assigned I/Os of the CPI/CP modules
1-12
Yes
Yes
No
No
–
–
–
–
8O
8O
16 O
16 O
Festo P.BE-CPX-CP-EN en 1211b
–
–
–
–
16 O
16 O
16 O
16 O
1. System summary – CPI system
1.2CPI system with the CPX-CP interface
The CPX-CP interface supports CPI systems with extended
functions. CPI systems with CP modules with extended
functions are distinguished by the following features:
–moreI/Osperstringarepossible(max.32I/32O)
–up to 4 CPI/CP modules are possible
–modules can be in any order.
The CPX-CP interface, in the capacity of technology module
(also termed function module), assigns I/O addresses in the
CPX terminal. The number of addresses assigned depends
on:
–the field bus node or FEC used and the operating mode of
the CPX terminal,
–the saved configuration (string assignment).
Address assignment is carried out as follows:
Field bus node/FEC
CPX field bus node with Remote I/O
operating mode, e.g.:
–
CPX-FB11, DeviceNet
–
CPX-FB13, PROFIBUS
–
CPX-FB14, CANopen
–
CPX-FB23, CC-Link
CPX front end controller with Stand Alone
or Remote Controller operating mode:
–
CPX-FEC
CPX field bus node for Interbus with
operating mode Remote I/O, e.g.:
–
CPX-FB6
Addressing see
Section 1.2.2
Section B.1.1
Festo P.BE-CPX-CP-EN en 1211b
Tab. 1/5:Addressing
1-13
1. System summary – CPI system
1.2.1Address range of the CPI system with the CPX-CP interface
Size of the assigned address range
The following rules apply to the address range occupied by
the CPX-CP interface ( Tab. 1/6):
–The size of the assigned address range depends on the
number of the last string used.
–The assignment for inputs is independent of the assign-
ment for outputs.
–Each string on the CP interface has an address range of
32 bits for inputs and 32 bits for outputs at its disposal.
Unused address rangeUnused address range is reserved for extensions.
Last string used
No string assigned0INo module with inputs
String 1
1
2
3
4
Assigned address rangeAssigned address range
InputsDescriptionOutputsDescription
0ONo module with
connected.
32 IAt least one input
module on string 1.
No input modules on
strings 2 to 4.
32 OAt least one output
outputs connected.
module on string 1.
No output modules on
strings 2 to 4.
String 2
String 3
String 4
1
2
3
4
1
2
3
4
1
2
3
4
64 IAt least one input
96 IAt least one input
128 IAt least one input
Tab. 1/6:Assigned address range
1-14
module on string 2.
No input modules on
strings 3 and 4.
module on string 3.
No input modules on
string 4.
module on string 4.
64 OAt least one output
module on string 2.
No output modules on
strings 3 and 4.
96 OAt least one output
module on string 3.
No output modules on
string 4.
128 OAt least one output
module on string 4.
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
1.2.2 Address assignment
The assignment of the addresses of the CPI/CP modules
depends on the CPX field bus node or CPX-FEC used. The
following representation applies to the field bus nodes (e.g.
CPX-FB13) as well as for the Front End Controller CPX-FEC, but
not for Interbus field bus nodes. The assignment for Interbus
field bus nodes (e.g. CPX-FB6) can be found in appendix B.1.
Address assignment of the individual modules takes places
according to the following rules:
–A CP interface provides four strings with a total of
128 input addresses and 128 output addresses.
–A used string occupies 32 input addresses and 32 output
addresses.
–The addresses are assigned fixed to the individual CP
strings and CPI modules in ascending order.
String
Input addressesOutput addresses
number
1I0 ... I31O0 ... O31
2I32 ... I63O32 ... O63
3I64 ... I95O64 ... O95
4I96 ... I127O96 ... O127
–Address assignment of the individual modules is there-
fore determined by the string to which they are connected
and by the number of I/Os the existing modules occupy
on the string.
Festo P.BE-CPX-CP-EN en 1211b
–Unused address range (due to modules not being
available) remains reserved for later CPI extensions.
The diagram below shows as an example the address
assignment of a CPI system.
1-15
1. System summary – CPI system
PROFIBUS addresses starting at input/output word 45 are
used. The CPX-CP interface thus occupies 12 bytes of input
addresses and 16 bytes of output addresses.
Fig. 1/6: Address assignment of a CPI system, example
1-16
The address assignment (method of counting, sequence of
the I/Os) within the individual CP valve terminals and CPI/CP
modules can be found in the relevant description for the
module.
Overview of the address assignments Appendix A.4.
2.3.2Ascertaining the current consumption2-12.......................
2.3.3Power supply arrangement – formation of power zones2-16........
2.4Complying with protection class IP65/IP672-19..........................
2-2
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
2.1General instructions on installation
Warning
Accidental movements of the connected actuators and
loose tubing can cause injury to persons and/or damage
to property.
Before carrying out mounting, installation and maintenance work, switch off the following:
– Compressed air supply
– Operating voltage supply for the electronics/sensors
– Load voltage supply for the outputs/valves.
Caution
Electrostatically sensitive components!
• D o not therefore touch the contacts of the components.
• Observe the regulations for handling electrostatically
sensitive components.
You will then prevent the electronics from being damaged.
Note
Handle all modules and components with great care. Pay
particular attention to the following:
– The specified torques must be complied with.
For information on mounting the CPX terminal CPX system
description (P.BE-CPX-SYS-..).
Festo P.BE-CPX-CP-EN en 1211b
2-3
2. Installation
1
CPI system and
CP string-specific
status LEDs
2
CPI connections
X1 … X4
3
Identification plates
(accessories)
Electrical connecting and display elements
The following connecting and display elements can be found
on the CPX-CP interface:
4
L1
PS
L2
PL
L3
RN
L4
X1
X2
1
2
4
Save key
X3
X4
3
Fig. 2/1:Connecting and display elements on the CPX-CP interface
Dismantling and fitting
The CPX-CP interface is mounted in an interlinking block of
the CPX terminal ( Fig. 2/2).
DismantlingDismantle the CPX-CP interface as follows:
1. Loosen the four screws with a Torx screwdriver size T10.
2. Pull the CPX-CP interface carefully and without tilting
away from the contact rails of the manifold block.
2-4
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
1
Screws, tightening
torque 0.9 … 1.1 Nm
2
CPX-CP interface
1
3
Contact rails
4
Interlinking block
(any, here with additional power supply
as an example)
3
Fig. 2/2:Dismantling/fitting the CPX-CP interface
FittingFit the CPX-CP interface as follows:
1. Place the CPX-CP interface in the manifold block. Make
sure that the grooves with the terminals for electrical
contact on the bottom of the CPX-CP interface lie directly
above the contact rails.
2. Press the CPX-CP interface carefully and without tilting as
far as possible into the manifold block.
2
4
Festo P.BE-CPX-CP-EN en 1211b
3. Tighten the screws at first only by hand. Place the screws
so that the self-cutting threads can be used.
4. Tighten the screws with a Torx screwdriver size T10 with
torque 0.9 ... 1.1 Nm.
2-5
2. Installation
2.2CPI connections
Note
Operative malfunction due to impermissible cabling.
•
For connecting the CPI/CP modules to the CP string,
use only the special CPI/CP cables from Festo
( www.festo.com/catalogue).
•
Observe that the total cable length on a string must not
exceed 10 m.
•
Dependent on the CPI/CP modules and CPI/CP cables
used as well as the current consumption, the
permissible modules and string length per CP st ring may
be limited ( section 2.2.1).
•
Observe the maximum permissible current consumption
per CP string, ( section 2.3.2).
In this way, you can avoid:
– Errors in data exchange between the CPX-CP interface
and the connected modules.
2-6
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
2.2.1Permissible CPI/CP modules and string lengths dependent on the
CPI cables
Use for CPI systems the special CPI cables type KVI-CP-3-...
(colour white).
Note
When using the CPI cable type KVI-CP-3-… (colour white)
the following restriction applies, dependent on the modules used and the current consumption:
– The maximum permissible string length of 10 m may be
limited further. An overview shows Tab. 2/1 and
Tab. 2/2.
Note
When using the CPI cable Type KVI-CP-1-… or
KVI-CP-2-... (colour black) additional restrictions apply
for the string length and max. current consumption
( Appendix A.6).
Festo recommends the use of CP cable
type KVI-CP-3-… (colour white).
Tip:
PlaceCPvalveterminalsorCPoutputmodulesasthefirst
module on the string if possible.
Festo P.BE-CPX-CP-EN en 1211b
2-7
2. Installation
CP string without
CPI output module
with maximum one
CP valve terminal
type
CPV10-.../CPA10-...0.5 A . .. 1.5 A10 m10 m10 m
CPV14-.../CPA14-...0.5 A ... 1.5 A10 m10 m10 m
CPV18-...
1)
Maximum sensor supply current used section 2.3.2, Tab. 2/5
2)
Nominal voltage or undervoltage of -10 %, 16 valve solenoid coils s witched simultaneously (high
current phase)
3)
Maximum undervoltage of -15 %, 8 valve solenoid coils switched simultan eously (high current
phase)
4)
Maximum undervoltage of -15 %, 16 valve solenoid coils switched simultaneously (high current
phase)
5)
Valve terminal installed at each string beginning
6)
Valve terminal installed at each string end
Maximum sensor
current con-
Maximum string length with CP cable, type
KVI-CP-3-...
sumption of the
U
CPI modules on
the CP string
0.5 A10 m10 m10 m
1.0 A10 m10 m10 m
1.5 A10 m10 m10 m
1)
= 21.6 ... 24 V;
VAL
16 valves
2)
U
= 20.4 V;
VAL
8 valves
U
3)
VAL
16 valves
8m
5m
= 20.4 V;
5)
6)
5)
6)
4)
Tab. 2/1: Permissible string lengths with CP cables, type KVI-CP-3- dependent on the CP
valve terminal used and the sensor current consumption
CP string without CP valve
terminal with maximum of
one CPI output module type
CP-A04-M12-CL0,5 A10 m
CP-A08...-M12-...1,5 A10 m
1)
Maximum sensor supply current used section 2.3.2, Tab. 2/5
Tab. 2/2: Permissible string lengths with CP cables, type KVI-CP-3- dependent on the CPI
output module used and the sensor current consumption
2-8
Maximum sensor current
consumption of the CPI
modules on the CP string
Maximum string length
with CP cable, type KVI-
1)
CP3-...
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
2.2.2Connecting CP strings
CP connectionsThere are four CPI connections for the CP strings on the
CPX-CP interface (X1 ... X4).
CPI/CP modules can be connected to each CPI connection
according to the rules described in section 1.2 .
Connecting CP modules
1. Check which address range is intended for the CPI/CP
module ( section 1.2).
2. Connect the modules with the CPI/CP cables to the string
which makes this address range available.
3. Fasten the plug and socket of the CPI/CP cable with the
union nut. In this way the electrical contact is guaranteed.
4. Use the identification labels (type IBS 6x10 or IBS 9x20)
to indicate the string to which the module is connected.
In this way you can avoid confusion during later repair
and maintenance work.
Festo P.BE-CPX-CP-EN en 1211b
2-9
2. Installation
2.3Connecting the power supply
Take the following aspects into consideration when installing
a CPI system with the CPX-CP interface:
–Power supply ( section 2.3.1)
–Current consumption ( section 2.3.2)
–Formation of power zones ( section 2.3.3).
Note
It is imperative that you observe the notes in section 2.3.3
when forming power zones in the CPX terminal by means
of several manifold blocks with power supply.
Recommendation:
•Provide the load voltage for the valve coils and, if necessary, for the outputs separately if you wish to implem ent
an EMERGENCY STOP function.
Note
Check whether pressure switch-off is also necessary for an
EMERGENCY STOP function on your machine/system.
Note
Observe the notes on earthing the CPI/CP modules in the
manual for the relevant module.
2-10
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
2.3.1Power supply
The power supply for the CPI system with the CPX-CP
interface is provided via the following connections on the
CPX terminal (manifold blocks with power supply):
Manifold block
type CPX-EV-S... (U
Manifold block
type CPX-EV-V... or
CPX-EV-S... (U
VAL
)
EL/SEN
The power supply for the following is provided via the oper-
)
ating voltage supply for the electronics/sensors (U
EL/SEN
the CPX terminal:
–the internal electronics of the CPX- CP interface
–the internal electronics of all the CPI modules connected
–the 24 V sensor supply of the inputs of the CPI input
modules connected.
The power supply for the following is provided via the load
supply for the valves (U
)oftheCPXterminal:
VAL
–the 24 V supply for the CP valve terminals and CPI/CP
output modules (output modules without load supply
connection).
Note
Malfunctioning due to power supply outside the tolerance
The module with the lowest tolerance always determines
the permitted voltage tolerances.
)of
Festo P.BE-CPX-CP-EN en 1211b
If the CPX-CP interface is used, special tolerances according to Tab. 2/3 must be observed for the load supply for
the valves (U
Load supply for valves (U
CPX-CP interface20,4 ... 26.4 V
1)
If midi/maxi pneumatics are also supplied via the load supply for
the valves: 21.6 ... 26.4 V
) of the CPX-CP interface.
VAL
)Tolerance
VAL
1)
Tab. 2/3:Permitted voltage tolerance
2-11
2. Installation
2.3.2Ascertaining the current consumption
The current consumption of a CPÎ system depends on the
number and type of the CPI modules connected.
Recommendation:
•Use a closed-loop controlled power unit.
•When selecting the power unit, check that it has sufficient
output. Calculate the total current consumption, if
necessary.
CalculationTab. 2/5 and Tab. 2/7 show how to calculate the total current
consumption for a CPI system. Please refer to the relevant
technical specifications for the current consumption of the
CP valve terminals and the CPI/CP modules.
Note
Select a power unit which provides sufficient output for
later extensions to the CPI system.
If you are using CP output modules with a separa te load
voltage connection, take into account the appropriate current
consumption when selecting a power unit.
Observe the notes on selecting the power unit in the
CPX system manual.
2-12
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
Note
Operative malfunctions due to the maximum permitted
current consumption on a CP string being exceeded.
•
Make sure that the current consumption of all the modules in a CP string does not exceed the maximu m permissible value of 1.6 A.
•
Observe that the sensor current consumption from
U
EL/SEN
can be additionally restricted dependent on the
string assignment, string length and the CPI/CP cables
used section 2.2.1.
Festo P.BE-CPX-CP-EN en 1211b
2-13
2. Installation
Current consumption on CP string x of U
EL/SEN
of the CPX terminal
Current consumption for internal electronics of all the CPI/CP modules connected
(number of CPI/CP modules x 0.035 A)
Current consumption of all sensors connected to the CPI/CP input modules
(max. 1.5 A)
2)
1)
+ _____ A
Internal current consumption per input channel of the CPI/CP input modules
(number of all inputs x 0.01 A)
+ _____ A
Sum of current consumption on string x (max. 1.6 A)
= _____ A
1)
Refer to manufacturer's specifications
2)
Dependent on the string assignment, string length and the CPI/CP cables used, section 2.2.1
Tab. 2/4:Current consumption of U
Total current consumption of U
EL/SEN
EL/SEN
of the CPX terminal per CP string
of the CPX terminal
_____ A
Sum of current consumption on CP string 1 of Tab. 2/4
Sum of current consumption on CP string 2 of Tab. 2/4
Sum of current consumption on CP string 3 of Tab. 2/4
Sum of current consumption on CP string 4 of Tab. 2/4
Total current consumption of
Tab. 2/5:Total current consumption of U
U
EL/SEN
of the CPX terminal
EL/SEN
_____ A
+ _____ A
+ _____ A
+ _____ A
= _____ A
of the CPX terminal
2-14
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
Current consumption on CP string x of U
Current consumption of all simultaneously energized valve coils of the CP valve
terminals
Load current of all simultaneously activated ouputs of the CPI output modules
without load voltage connection
Sum of current consumption on string x (max. 1.6 A)
1)
Current consumption dependent on valve type ( Technical data of the valves)
1)
Tab. 2/6:Current consumption from U
Total current consumption of U
Sum of current consumption on CP string 1 as per Tab. 2/6
Sum of current consumption on CP string 2 as per Tab. 2/6
of the CPX terminal
VAL
of the CPX terminal
VAL
of the CPX terminal per CP string
VAL
_____ A
+ _____ A
= _____ A
_____ A
+ _____ A
Sum of current consumption on CP string 3 as per Tab. 2/6
Sum of current consumption on CP string 4 as per Tab. 2/6
Total current consumption of
Tab. 2/7:Current consumption of U
U
of the CPX terminal
VAL
of the CPX terminal
VAL
Note
The 24 V supply of the CP valve terminals and of the
CPI/CP output modules (output modules without load
supply connection) takes place within the CPX-CP interface
through a shared cable.
•
Observe that currents in a shared cable add up.
+ _____ A
+ _____ A
= _____ A
Festo P.BE-CPX-CP-EN en 1211b
2-15
2. Installation
2.3.3Power supply arrangement – formation of power zones
The modular power supply arrangement of the CPX terminal
facilitates the formation of power zones.
Please note the following:
The internal electronics of the CPI/CP I/O modules are supplied from the operating voltage supply for ele ctronics/
sensors (U
The CP valve terminals and the CPI/CP output modules are
provided with load supply by the load supply for the valves
(U
).
VAL
EL/SEN
).
Note
The CPX-CP interface connects the internal contact rails
0U
EL/SEN
and 0 U
of the CPX terminal.
VAL
– As a result, the electrical isolation of the operating
voltage supply for electronics/sensors (U
EL/SEN
)ofthe
CPX terminal and of the load voltage valves supplying
the CPX-CP interface (U
) CPX-CP interface cancel each
VAL
other out.
– Complete electrical isolation (all poles) o f the valve sup-
ply of the CP valve terminals, even in conjunction with
CPX valve supply of type CPX-EV-V, is therefore not possible.
Note
The CPX-CP interface must be supplied via the same
potential (common power unit) as the operating power
supply for the electronics/sensors (U
EL/SEN
)ofthe
CPX terminal (see also Fig. 2/3).
2-16
Basic information on the power supply arrangement of the
CPX terminal can be found in the CPX system description.
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
Example CPX terminal with CP interface + system
supply and 2 additional power supplies for valves
In the example ( Fig. 2/3) the CPX-CP interface and therefore the CP valve terminals and CPI/CP output modules
without load voltage connection are supplied via the valve
supply 2 . The CP valve terminals can only be switched off at
asinglepole!
The MPA pneumatics are supplied via the valve supply 3
(only permitted with MPA electronic modules type
VMPA..-FB-EMG-...). The MPA pneumatics can be switched off
at all poles.
Festo P.BE-CPX-CP-EN en 1211b
2-17
2. Installation
0V
24V
0V
24V
0V
24V
FE
VAL
VAL
OUT
OUT
EL/SEN
EL/SEN
1
8DI
12 3 412 3 412 3 4
2
3
4
8DI4DOCP-I
MPA
8O8O
3
1
Interlinking block with system supply
2
Interlinking block with additional power supply for valves (supplies CPX-CP
interface)
3
Interlinking block with CP interface; connects internally at module level the
rails 0 U
4
Interlinking block with additional power supply for valves (supplies MPA p neu-
EL/SEN
and 0 U
VAL
matics)
Fig. 2/3:Separate power supply for CPX-CP interface and MPA pneumatics (example)
2-18
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
2.4Complying with protection class IP65/IP67
Note
To comply with protection class IP65/IP67:
• Seal unused CPI/CP connections and the Save key with
the appropriate protective caps.
If CPI/CP connections are not used, seal them with a protective cap, type FLANSCHDOSE, S712 (included in delivery).
You will then comply with protection class IP65/IP67.
3.7Commissioning functions with the handheld3-27.........................
3.7.1Menu commands of the CPX-CP interface on the Handheld3-28......
3.7.2Representation of the CPI/CP modules3-29......................
3.7.3Displaying the string assignment3-30...........................
3.7.4Observing signal states (monitoring)3-31........................
3.7.5Parametrizing with the Handheld3-33...........................
3-2
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.1Procedure for commissioning
In order to avoid connecting and addressing errors, you
should carry out commissioning in steps as follows. Proceed
as follows:
1. Check the CP strings ( section 3.2.1).
2. Save the string assignment of the CPI system
( section 3.2.2).
3. Check the saved string assignment
( sections 3.3 and 3.4)
4. If required: Parameterise the CPX-CP interface and CPI
modules ( section 3.6).
5. Check the address assignment (if necessary, without any
connected actuators by LED) Description for the CPX
fieldbus node or CPX-FEC.
6. Commission the total system Description for the CPX
fieldbus node or CPX-FEC.
Festo P.BE-CPX-CP-EN en 1211b
3-3
3. Commissioning
3.2Prepare the CPI system for commissioning
Note
Do not yet connect the CPX terminal to a higher-order
controller for preparing commissioning.
You will thus avoid addressing faults which may occur in
various field bus systems when address ranges are
modified during operation.
3.2.1Checking the CP strings
PreparationsBefore commissioning a CPX terminal with CPX-CP interface,
you should first prepare each individual CPI system for commissioning.
Proceedasfollows:
1. Check the pneumatic tubing connections of the
connected CP valve terminals with the help of the manual
override ( pneumatics description).
2. Check the complete electric circuitry of the CP system.
3. Save the current string assignment of th e CPI system as
the set assignment, as described in section 3.2.2.
3-4
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.2.2Saving the string assignment
Warning
Undesired modification of input and output addresses.
Be very careful if the string assignment of your CPI system
is modified at a later stage:
• After saving the string assignment, check the address
assignments of your CPI system before starting user
programs.
You can thereby avoid:
– addressing faults with incorrectly fitted CPI modules.
String allocationThe CPX-CP interface saves the type and sequence of the
connected CPI modules for every string ( chapter 1). This
is also termed string assignment.
The saved string assignment allows the CPX-CP interface to
avoid errors in connecting, and thus addressing errors. It
checks automatically to see if the current string assignment
is the same as the saved assignment. A distinction is made
here between the following test phases:
–Testing during the start-up phase ( section 3.3)
–Testing during operation ( section 3.4).
After the switch on procedure, the status LEDs indicate the
operating status and correct function of the bus node and the
fieldbus communication. If the status LEDs on all the CPI/CP
modules light up, the CPI system is prepared for configuration.
You can find out which indicator displays the normal operating status in the user documentation of the respective CPI
module. Different procedures are necessary for configuration
of the various fieldbus nodes or the FEC.
Festo P.BE-CPX-CP-EN en 1211b
Explanations on this can be found in the manual for the CPX
field bus node or the CPX-FEC.
3-5
3. Commissioning
Saving the string
assignment
The desired string assignment is generated and saved for
commissioning. In this way the appropriate addresses are
assigned to the connected CPI modules.
Save the string assignments as follows:
1. Leave the power supply of the CPX terminal switched off
for the time being.
2. Check that each of the CPI/CP modules is connected to
the string which provides the address range intended
( chapter 1).
3. Check that the CPI cables are fastened properly with the
union nut.
4. Switch on the power supply of the CPX terminal and, if
necessary, of the CPI/CP modules with load voltage connection.
On the CPX-CP interface, the LEDs of strings (L1 ... L4), to
which CP modules have been connected or for which the
string assignment has been modified, will flash.
5. Use a small screwdriver or similar to press the Save key
for at least 1 s ( section 2.1).
This will save the current string assignment as the target
string assignment in the CPX-CP interface.
The LEDs of strings (L1 ... L4), with which the connected
CPI/CP modules have been recognised, no longer flash.
ThestatusLEDsofalltherecognizedCPI/CPmodules
light up. Wait some seconds before continuing with the
next step.
6. Switch off the power supply for the CPX terminal. Wait
some seconds. Then switch it back on again.
The current string assignment is now available in the
fieldbus node or the CPX-FEC.
7. Depending on the CPX field bus node or CPX-FEC being
used, the modified address range of the CPX-CP interface
must be accepted:
3-6
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
CPX field bus node /
CPX-FEC
CPX fieldbus node
or CPX-FEC with operating
mode Remote I/O
CPX-FEC with Stand Alone or
Remote Controller operating
mode
How to accept the address range
System parameter “System start” [System start]:
“System start with default p arameterisation and up-to-date CPX
expansion” [default parameters], (factory setting):
– The revised address range of the CPX-CP interface is automatic-
ally accepted.
“System start with saved param eterisation and saved CPX expansion” [saved parameters]:
1. Change “System start ...” system parameter to “... default
parameterisation ...” .
2. Switch off the power supply of the CPX terminal then switch it
on again. The address range of the CPX-CP interface will then
be accepted.
3. If necessary, you can restore the desired parameterisation.
•
To accept the address range of the CPX-CP interface, you must
save the actual configuration as the set configuration (actualsetpoint comparison). Information on this can be found in the
manual for the CPX-FEC or software package FST 4.1.
Tab. 3/1:Saving the string assignment and accepting the address range
Note
After saving the string assignment, check the address
assignments of your CPI system before starting user
programs.
Festo P.BE-CPX-CP-EN en 1211b
3-7
3. Commissioning
3.3Switching-on reaction of the CPI system
When the power supply is switched on, the CPX-CP interface
ascertains automatically the current string assignment. It
ascertains one after the other which CPI modules are connected to the relevant string.
If the current assignment is the same as the saved assignment, the CPX-CP interface will switch automatically to the
ready status.
The RN LED of the CPX-CP interface as well as the status LEDs
on the connected CPI/CP modules light up ( Fig. 3/1).
If the current assignment is not the same as the saved assignment, the string LEDs (L1 ... L4) of the relevant string will
flash on the CPX-CP interface. In this case the CPI system is
not ready to operate.
You then have the following possibilities of restoring the
readiness to operate:
–Eliminate assignment errors manually or replace
individual CPI modules ( section 3.4)
–Save the current assignment as the set assignment
( section 3.2.2).
Detailed notes on diagnosing the CPX-CP interface using the
LEDs can be found in section 4.2.
3-8
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
Switch on power supply
“CP configuration error”; error LED flashes;
string LED on
String 1 ... 4:
Record module types
No
Save key
pressed?
Ye
s
Save string allocation
No
ment saved?
String allocation?
“CP configuration
error”; error LED
flashes; string LEDs on
String assign-
Yes
String 1 ... 4: Record
module types
No
Module types:
Set = Actual?
Yes
“CP configuration
error”; error LED
flashes; string LEDs off
CPI system ready to
operate (permanent
I/O update)
3-9
3. Commissioning
3.4Reaction of the CPI system to faults in operation
If there is a fault on a CP string during operation, e.g. by
cable fracture etc., this will be indicated by the relevant string
LED (L1 ... L4) flashing or lighting up. on the CPX-CP interface.
The status LED on the relevant module goes out. All modules
working without faults remain ready to operate.
Detailed notes on diagnosing the CPX-CP interface using the
LEDs can be found in section 4.2.
3.4.1Eliminating assignment faults
In order to eliminate assignment or connection faults of the
CP system:
1. Switch off the power supply for the CPX terminal.
2. Restore the saved assignment by connecting the
appropriate CPI/CP modules with the CXP-CP interface
again.
3. Switch on the power supply for the CPX term inal again.
3-10
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.4.2Replacing CPI/CP modules
Replacement possibilitiesOnly one defective CPI/CP module can be replaced with a
CPI/CP module of the sa me type without the need to save
the string assignment again.
Note
Replacing a CPI/CP module with a CPI/CP module of a different type or replacing several CPI/CP modules will require a new commissioning and new saving of the string
assignment ( section 3.2).
In order to replace a single CP module, proceed as follows:
1. Stop the process controller P LC/Master
2. Switch off the power supply for the CPX terminal.
3. In the case of CPI/CP output modules and CP valve
terminals on the CP string concerned:
Switch off the following sources of energy:
– the compressed air supply for the CP valve terminal
– the o perating voltage supply for the CPI/CP output
module.
4. Disconnect all connecting cables and, if necessary, also
the tubing.
5. Connect all connecting cables and, if necessary, the
tubing with the identically constructed new module.
6. Now connect the new module ofthesametypeto the
same string.
Festo P.BE-CPX-CP-EN en 1211b
7. In the case of CPI/CP output modules and CP valve
terminals:
Switch on the operating voltage supply or the
compressed air supply again.
8. Switch on the power supply for the CPX term inal again.
9. Check the addresses of the CPI system.
3-11
3. Commissioning
3.4.3Replacing CPI/CP modules during operation
In special cases, a single CPI/CP module can be replace d
during operation with a CPI module of the same type.
In rare cases, the replacement can produce a short circuit
report for the string. Restart the system if there is a short
circuit report.
Warning
Undesired modification of I/O states.
• Check whether the design of your machine/system
permits replacement of modules during operation.
Warning
Undesired modification of input and output addresses.
Be very careful if the string assignment of your CPI system
is modified at a later stage:
• Make sure that modules are not sepa rated from a string
and subsequently connected to another string during
operation. Use the identification labels (type IBS 6x10 or
IBS9x20) in order to identify modules clearly.
You can thereby avoid:
– modified input and output addresses of the modules.
The CPX-CP interface will recognise replacement with a different type of module (e.g., O module replaced with a valve terminal or CP-E16-M8 replaced with CP-E16-M12x2) as a string
assignment fault. In this case, therefore, readiness to operate
is not restored to the relevant module during operation.
Recommendation:
When replacing CPI/CP modules, always switch off the power
supply if possible ( section 3.4.2).
3-12
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
If the design of your machine/system makes it necessary to
replace a CPI/CP module during operation, you should
proceed as follows:
1. In the case of CPI/CP output modules and CP valve
terminals on the CP string concerned:
Switch off the following sources of energy where
applicable:
– the compressed air supply to the valve terminal
– the o perating voltage supply to the output module.
2. Disconnect all connecting cables and, if necessary, also
the tubing.
3. Connect all connecting cables and, if necessary, the
tubing with the identically constructed new module.
4. Now connect the new module ofthesametypeto the
same string.
5. In the case of CPI/CP output modules and CP valve
terminals:
Switch on the operating voltage supply or the
compressed air supply again.
You can thus restore the defective connection during
operation, or replace the defective module without impairing
operation of the modules in the other strings. When the
connection is restored again or replaced, the readiness to
operate will be taken up with the appropriate module
automatically.
Festo P.BE-CPX-CP-EN en 1211b
3-13
3. Commissioning
Restriction in recognising the string assignment
Specific modifications to the string assignment cannot be
recognised during operation:
–CPI/CP modules or entire strings which are connected to
the previously unassigned string 2 instead of string 1 or
vice versa. This also applies to strings 3 and 4, respectively.
However, these modules will retain their previous addresses
until the power supply is switched off and then on again.
Note
Modifications to the string assignment will be recognised
reliably after the power has been switched on.
Recommendation:
• If possible, switch the power supply off and t hen on
again after performing conversion work on the
CP strings, provided that your system permits this.
Note
After saving the string assignment, check the address
assignments of your CPI system before starting user
programs.
You can thereby avoid:
–addressing faults with incorrectly fitted CPI/CP modules.
3-14
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.5Notes on operation
Warning
Undesired activation of actuators!
An incorrect status of the valves and outputs can lead to
dangerous situations.
• M ake sure that valves and outputs are put into a safe
state when faults occur.
Note
Please note the following if the outputs of a valve terminal
are reset after master stop, field bus interruption or fault:
– Single-solenoid valves move to the basic position.
– Double-solenoid valves remain in the current position.
– Mid-position valves move to the mid-position (depend-
ing on valve type: pressurized, exhausted or blocked).
Warning
Undesired modification of input and output addresses.
Be very careful if the string assignment of your CPI system
is modified at a later stage:
• Make sure that modules are not separated from one
string and accidentally connected to another. Use the
identification labels (type IBS 6x10 or IBS9x20) in order
to identify modules clearly.
• After saving the string assignment, check the address
assignments of your CPI system before starting user
programs.
You can thereby avoid:
– modified input and output addresses of the modules.
Festo P.BE-CPX-CP-EN en 1211b
3-15
3. Commissioning
3.5.1Factory default mark from version 22
Note
If defective data segments are discovered on an EEPROM
during switch on, they are overwritten with default values.
The CPI will then cancel the switch-on procedure and display the error through the LEDs. ( chapter 4.2) The error
number 205 is returned via the C-bus.
3-16
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.6Parametrizing
The reaction of the CPI system with the CPX-CP interface can
be parametrized.
–Module parameter ( Tab. 3/2):
Activates or deactivates error monitoring for the total
CPX-CP interface (overview).
–Channel-specific module parameters ( Tab. 3/3):
Activates or deactivates error monitoring for individual
CPI modules.
Further information on parametrizing can be found in the
system manual and in the manual for the CPX field bus node
or the CPX-FEC.
Tab. 3/6:Monitoring CPX module – CPX-CP interface and CPI/CP modules
3-22
[Active]
[Inactive]
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
Description of the channel-specific module
parameters
The channel-specific module parameters are each permanently assigned to the individual CPI/CP modules on the CP
strings Tab. 3/7).
String
Modulex
1)
Function no.StringModulex
1)
Function no.
L1M084828 + m * 64 + 8L3M0164828 + m * 64 + 16
L1M194828 + m * 64 + 9L3M1174828 + m * 64 + 17
L1M2104828 + m * 64 + 10L3M2184828 + m * 64 + 18
L1M3114828 + m * 64 + 11L3M3194828 + m * 64 + 19
L2M0124828 + m * 64 + 12L4M0204828 + m * 64 + 20
L2M1134828 + m * 64 + 13L4M1214828 + m * 64 + 21
L2M2144828 + m * 64 + 14L4M2224828 + m * 64 + 22
L2M3154828 + m * 64 + 15L4M3234828 + m * 64 + 23
1) x = Parameter byte in the function number, Tab. 3/8
Tab. 3/7:Assignment of the channel-specific module parameters to the CPI/CP
modules
CPX-CP interface
Module 0
Module 1Module 2Module 3String
Parameter byte 0
Parameter byte 6
Fig. 3/5:Parameter assignment of the CPI system
Festo P.BE-CPX-CP-EN en 1211b
L1
L2
L3
L4
Module 0
[L1/M0]
Module 4
[L2/M0]
Parameter byte 12
Module 8
[L3/M0]
Parameter byte 16
Module 12
[L4/M0]
Parameter byte 20
Module 1
[L1/M1]
Parameter byte 9Parameter byte 8Parameter byte 11
Module 5
[L2/M1]
Parameter byte 13
Module 9
[L3/M1]
Parameter byte 17
Module 13
[L4/M1]
Parameter byte 21
Module 2
[L1/M2]
Parameter byte 10
Module 6
[L2/M2]
Parameter byte 14Parameter byte 15
Module 10
[L3/M2]
Parameter byte 18
Module 14
[L4/M2]
Parameter byte 22
Module 3
[L1/M3]
Module 7
[L2/M3]
Module 11
[L3/M3]
Parameter byte 19
Module 15
[L4/M3]
Parameter byte 23
3-23
3. Commissioning
Note
If you connect a module or valve t erminal to a string, the
remaining address space of the string is reserved until you
connect additional equipment. This also applies if the
parameterisation of the connected device takes up less
than 4 bytes.
Module parameters: Monitoring CPX mo dule – CPI/CP modules
Function no.4828 + m * 64 + xm = module number (0 ... 47)
x = dependent on string no. and module no. of the CPI/CP module, Tab. 3/7
DescriptionMonitoring of the possible faults can be activated or deactivated (suppressed) for
CP each module independently. Active monitoring causes the following: The fault is:
–
sent to the CPX field bus node
–
displayed by the module common error LED.
Monitoring
Bit
Description
0
Power failure/undervoltage for:
–
CPI/CP input modules (Vsen): Power failure
(or short circuit) of the sensor supply for modules
with additional supply
–
CPI/CP output modules (Vout): Power failure of the
load supply for modules with additional supply
–
CP valve terminals (Vval): Power failure of the load
supply of the valves
Short circuit/overload on:
1
–
CPI/CP output modules Output
Values1 = active (presetting)
0=inactive
NoteMonitoring can also be set for the total CPX terminal
( system parameter monitoring).
[Monitor ...]
[Monitor Vsen/Vout/Vval]
[Monitor SC]
[Active]
[Inactive]
Tab. 3/8:Monitoring CPX module – CPI/CP modules
3-24
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
Module parameters: Fail safe channel x
Function no.These module parameters are accessed via protocol-specific functions
( description of fieldbus node).
DescriptionFaultmodechannelx:Holdlaststate
Fault state (presetting)
Fault state channel x:Set output
Reset output (presetting)
NoteWith the aid of the so-called Fa il Sa fe par ameter isation, the signal status which
the outputs are to assume in the event of fieldbus communication errors can be
specified ( CPX system description).
Tab. 3/9:Fail safe channel x (channel-specific)
Module parameters: Idle mode channel x
Function no.These module parameters are accessed via protocol-specific functions
( description of fieldbus node).
DescriptionOnly relevant for certain field bus protocols
Idlemodechannelx:Holdlaststate
Idle state (presetting)
Idle state channel x:Set output
Reset output (presetting)
NoteWith the aid of the so-called Idle mode parameterisation, the signal status which
the outputs/valves are to assume when changing into the Idle state can be specified ( CPX system description).
This parameter is not available with all fieldbus protocols.
Tab. 3/10:Idle mode channel x (channel-specific)
Festo P.BE-CPX-CP-EN en 1211b
3-25
3. Commissioning
Module parameters: Force channel x
Function no.These module parameters are accessed via protocol-specific functions
( description of fieldbus node).
DescriptionForce mode of inputs channel x:Blocked (presetting)
Force state
Force state of inputs channel x:Set signal
Reset signal (presetting)
Force mode of outputs channel x:Blocked (presetting)
Force state
Force state of outputs channel x:Set signal
Reset signal (presetting)
NoteThe Force function permits the manipulation of signal statuses independent of
actual operating statuses ( CPX system description).
Tab. 3/11:Force channel x (channel-specific)
3-26
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.7Commissioning functions with the handheld
The universal Handheld type CPX-MMI-1 offers user-friendy
and extended functions which will support you in commissioning the CPX-CP interface.
This section contains an overview of the specific
commissioning functions for the CPX-CP interface.
–General information on the representation,
sections 3.7.1 and 3.7.2
–Display of the string assignment, section 3.7.3
–Display of the signal statuses, section 3.7.4
–Parameterisation, section 3.7.5
General information on operating the Handheld and on commissioning the CPX terminal using the Handheld can be found
in the manual for the Handheld, type P.BE.CPX-MMI-1-... .
Festo P.BE-CPX-CP-EN en 1211b
3-27
3. Commissioning
3.7.1Menu commands of the CPX-CP interface on the Handheld
Fig. 3/6 shows as an example the special menu structure for
the CPX-CP interface. For reasons of clarity only the parameter name is shown for the parameters.
“Monitoring/Forcing” menu (also “Fail safe”, “Idle mode”), section 3.7.4
2
“Parameters” menu, section 3.7.5
3
“CP modules” menu, section 3.7.3
Fig. 3/6:Menus of the CPX-CP interface on the Handheld
3-28
3
2:CPI:C.
L1/M0: CPV10-GE-FB-...
L1/M0: CP-E16-M12 /..
L2/M1: ...
...
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.7.2Representation of the CPI/CP modules
In the various menus of the handheld ( section 3.7.1,
Fig. 3/6) the CPI/CP modules on the CPX interface are displayed with either a long name or a short name ( Tab. 3/12
status at January 2012).
Tab. 3/12:Representation of the CPI/CP modules on the Handheld
Festo P.BE-CPX-CP-EN en 1211b
E16EL
E32EL
A08EL
3-29
3. Commissioning
3.7.3Displaying the string assignment
To display the string assignment currently recognised by the
CPX-CP interface, in the module submenu of the CPX-CP interface ( Fig. 3/6) select the entry for the CPI/CP modules
[CP modules (C)] and confirm with OK.
All the CPI/CP modules of the recognised string assignment
are now each displayed with string number (e.g. L1), module
number on the string (e.g. M0) and their long name.
If no modules are recognised on the strings, the message
“No CP modules” will be displayed.
The following CPI/CP modules are marked with “x”:
–Modules recognised after the power supply has been
switched on but not included in the saved string assignment.
–Modules contained in the saved string assignment but
no longer recognised.
In this case the CPX-CP interface will report a configuration error.
Malfunctioning CPI/CP modules (modules reporting an error, e.g. short circuit) are marked with “!”. Diagnostic information about each of these modules can be displayed.
___________________
Back OK
3-30
Note
Always watch for error messages of the CPX-CP interface
when the string assignment is displayed.
This will also provide you with information about CPI/CP
modules that are not recognised.
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
1
3.7.4Observing signal states (monitoring)
You can use the Handheld to observe the signal states of the
connected (and recognised) CPI/CP modules.
•To do this, select the entry [Monitoring/Forcing (M)] in the
module submenu of the CPX-CP interface ( Fig. 3/7).
All the special entries for the CPI/CP module selected are
available in this module submenu.
The display and function correspond basically to the module
submenu for normal CPX modules.
•In order to display the signal status for the selected CPI/
CP module, in the relevant module submenu select the
entry [Monitoring/Forcing (M)] Fig. 3/8.
Fig. 3/8:Module submenu – Observing the signal states of a specific CPI/CP module
“Forcing”, “Idle mode” and “Fail safe”
Warning
The actuators connected can move unexpectedly.
Modification to the signal states and parameters with the
Handheld can trigger dangerous movements of the connected actuators.
• Make sure that nobody is in the positioning range of the
connected actuators and be very careful with the
parametrizing and manipulation of signal states.
1
• It is imperative that you observe the notes on Forcing,
Idle mode and Fail safe in the CPX system manual and in
the manual for the Handheld.
You can also call up the “Forcing” function via the “Monitoring ...” menu. This function allows you to force signal statuses
during the commissioning phase for test purposes.
The same representation of the CPI/CP modules applies
accordingly to the functions “Idle mode” and “Fail safe”.
3-32
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
1
3.7.5Parametrizing with the Handheld
For test purposes in the commissioning phase, for
troubleshooting or for fieldbus protocols which do not support parameterisation via the fieldbus, you can use the Handheld for parameterisation ( Fig. 3/9 and Fig. 3/10).
Warning
The actuators connected can move unexpectedly.
Modification to the signal states and parameters with the
Handheld can trigger dangerous movements of the connected actuators.
• Make sure that nobody is in the positioning range of the
connected actuators and be very careful with the
parametrizing and manipulation of signal states.
• It is imperative that you observe the notes on parametrizing in the CPX system manual and in the manual for
the Handheld.
An overview of the LED functions is shown in Tab. 4/2.
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
LEDDescription
PSPower sensorsLights up if the sensor power supply
PLPower loadLights up if the load power supply on
RNRunLights up if data exchange is running
on the CP string is correct. Flashes if
there is a voltage fault.
1)
the CP string is correct for outputs
and valves. Flashes if there is a
voltage fault.
1)
on the CP strings.
Fault LEDFlashes or lights up if there are faults
on the CPX-CP interface. The flash
pulses indicat e the type of fault.
L1 ... L4String faultFlashes o r lights up if there are faults
on the assigned CP string. The flash
pulses indicat e the location of thefault on the CP string.
1)
The power supplies are monitored by the CPI/CP modules
Tab. 4/2:Function overview of the LEDs on the CPX-CP
interface
Festo P.BE-CPX-CP-EN en 1211b
4-5
4. Diagnosis and error treatment
4.2.1Normal operating status
In the normal operating status all green LEDs light up.
The red LEDs do not light up.
LED display
All green LEDs light up:
–
PS
–
L1
L2
L3
L4
PS
PL
RN
PL
–
RN
The red LEDs do not
light up:
–
Fault
–
L1 ... L4
Tab. 4/3:LED display – normal operating status
Operating
status
Standard
4-6
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
4.2.2CPI system-specific LEDs
PS (power system) – power sensor supply of CPI/CP modules
LED (green)SequenceStatusFault numberFault treatment
ON
OFF
No fault. Sensor power
supply applied
––
LED lights up
ON
OFF
LED flashes
Short circuit/undervoltage
in the sensor supply of a
CPI/CP input module
2
5
Error numbers in
section 4.3, Tab. 4/6
PL (Power l oad) – power load supply for CPI/CP modules
LED (green)SequenceStatusFault numberFault treatment
ON
OFF
LED lights up
ON
OFF
LED flashes
No fault.
Load voltage applied
Undervoltage in the load
supply of a CPI/CP module
with additional power supply
–None
5 Error numbers in
section 4.3, Tab. 4/6
RN (Run) – CPI/CP communication active
LED (green)SequenceStatusFault numberFault treatment
ON
OFF
LED lights up
ON
OFF
LED not illuminated
Festo P.BE-CPX-CP-EN en 1211b
No error
Communication OK
Saved string assignment
corresponds to the recognised string assignment
Malfunction in the CPI system
– Communication error
– Configuration error
– String assignment error
–None
Error numbers in
36
section 4.3, Tab. 4/6
34, 35
34, 35
4-7
4. Diagnosis and error treatment
(Fault)– CPI system fault (location of the fault)
LED (red)SequenceStatusFault
number
ON
OFF
No fault.––
LED is out
LED flashes
ON
OFF
ON
OFF
Malfunction in the CPI/CP
communication
–
Short c ircuit/overload
–
Undervoltage
34
2
5
On one CP string or one
CPI/CP module:
34
35
36
34
35
36
ON
OFF
–
Module missing / faulty
–
CP configuration fault
–
Short circuit in CP string
On several CP strings or
several CPI/CP modules:
–
Module missing / faulty
–
CP configuration fault
–
Short circuit in CP string
Fault treatment
Error numbers in
section 4.3,
Tab. 4/6
LED illuminated
ON
OFF
ON
OFF
ON
OFF
–
Recognised string assign-
35
ment does not correspond
to saved string assignment; Save key was not
pressed
–
String assignment cannot
35
be saved (configuration
not capable of being
saved)
Unkown fault255
Internal CPX communication
–Switchonphase
– C-bus error
–
131
•
Switch power
supply off then
on again,
replace module
if necessary
None.
CPX system description
4-8
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
4.2.3CP string-specific LEDs
L1 ... L4 – CP string fault (type of fault)
LED (red)SequenceStatusFault
number
LED is out
ON
OFF
–
No fault
or
–
Save key pressed after
–
–
string assignment was
modified
LED flashes
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Error on module of the relevant assigned string L1,
L2, L3 or L4:
1)
Fault on module 0
Fault on module 1
Fault on module 2
Fault on module 3
2, 5,
34, 35
2, 5,
34, 35
Fault treatment
–
Switch power
supply off then on
again, replace
module if necessary
assigned error
numbers in section
4.3, Tab. 4/6
ON
OFF
ON
OFF
LED illuminated
1)
If there are faults on several modules, the lowest module number in each case is shown.
Festo P.BE-CPX-CP-EN en 1211b
During operation:
– Revised string assign-
ment, e.g. due to an additional module connected (at least 2 LEDs flash
– L1+L2 and/or L3+L4).
After switching on:
– Invalid string assign-
ment (only the LEDs of
the CP strings concerned
flash).
Short c ircuit on the relevent assigned CP string
35
• Check string
assignment. If
necessary, save
the new string
assignment,
Section 3.2.2.
• Check and correct
the string assignment, Section
1.2.
36 Section 4.3,
Tab. 4/6
4-9
4. Diagnosis and error treatment
4.2.4Special system error (starting with software version Rev. 22)
These special system errors occur in very rare cases. The CP
interface has detected an error that requires a software stop.
The error is displayed through flashing of all CPI-specific LEDs
(PS, PL, RN, P). In addition, an error message is shown encoded through flashing of the LEDs L1 … L4 ( Tab. 4/4 and
Tab. 4/5).
•
In the event of error, restart the CPX terminal with POWER
OFF/ON and observe the instructions in the tables
Tab. 4/4 and Tab. 4/5.
If the error still exists: service matter.
Special system errors
LED (red)Status/error handlingLED (red)Status/e rror handling
1
2
L1, L2
flash
L2, L3
flash
Malfunction of communication
on one CP string.
Error handling:
• Check CP c ables for damage
• Check earthing of the CPI/CP
system (EMC load)
Time-out when reading from EEPROM.
Error handling:
• S ave the string assignment
again with the SAVE button
(3.2.2)
3
L1, L2, L3
flash
4
L4
flashing
Time-out when writing from EEPROM.
Error handling:
• S ave the string assignment
again with the SAVE button
(3.2.2)
Unstable clock signal detected.
Error handling:
• Restart system
• Servicing required
Tab. 4/4: Special system errors - Part 1
4-10
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
Special system errors
LED (red)Status/error handlingLED (red)Status/error handling
5
L1, L4
6
L1, L2, L4
7
flash
flash
Critical timeouts in internal timing. Possibly to high bus load or
external diagnostic requests, or
similar
Error handling:
• Restart system
• Reduce bus load, if neces-
sary
Incorrect access lower boundary data exchange buffer.
Error handling:
• Restart system
Incorrect access upper boundary data exchange buffer.
8
L1, L3, L4
flash
9
L1, L2, L3, L4
flash
–
EEPROM defective.
Error handling:
• Restart system; if successful,
save the string assignment
again with the SAVE button
(3.2.2)
• Servicing required
Undefined error message.
Error handling:
• Restart system
• Servicing required
–
Error handling:
• Restart system
L1, L2
flash
Tab. 4/5: Special system errors – Part 2
Festo P.BE-CPX-CP-EN en 1211b
4-11
4. Diagnosis and error treatment
4.3Error messages of the CPX-CP interface
A CPX-CP interface can report the following errors (Tab. 4/6
and Tab. 4/7):
Error
DescriptionError handling
number
2Short circuit/overload
(Handheld: [Short circuit] )
– Short circuit/overload at output
or
– Short circuit/overload, sensor supply
(only for I/O modules with extended functions)
5Undervoltage in the power supply
(Handheld: [Undervoltage in power supply] )
– Load voltage of the valves (U
or too low.
or
– Load voltage supply (Vout) not applied or too
low (only for CPI/CP output modules with a
separate power supply)
or
– Power supply of the CPI/CP modules (Vsen/
Vout/Vval) via the CP string not applied or too
low (only for CPI/CP modules without a separate power supply)
or
– Short circuit/overload, sensor supply
(only for CP input modules without extended
functions)
VAL
) not applied
• Check the connected actuators,
eliminate short circuit/overload
and delete errors
• Check the connected sensors,
1)
eliminate short circuit/overload
and delete errors, if necessary
• Check the load voltage
• Check the load voltage
• Check the load voltage,
Check CPI/CP cables
• Eliminate short circuit/overload,
check connected sensors, delete
errors, if necessary
2)
2)
1)
Dependent on the CPI/ CP module: All the outputs of the module are switched off in the event of an
error. The error must be deleted by resetting all the outputs.
2)
Dependent on the CPI/ CP module: The error is automatically deleted or must be deleted by disconnecting the module from t he CP string or by switching the power supply off then on again.
Tab. 4/6: Error messages of the CPX-CP interface - Part 1
4-12
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
Error
DescriptionError handling
number
34CPI/CP module missing / faulty
(Handheld: [CP module lost / fault] )
– Incorrect string assignment discovered during
operation (e.g. CPI/CP module failed or CPI/
CP cables defective)
– More than one module failed during operation
– modules are no longer recognised.
35CP configuration error
(Handheld: [CP configuration failure] )
– When the power supply is switched on, the
string assignment does not match the saved
string assignment
or
– The wrong module is rec ognised during opera-
tion (different type, chapter 3)
• Check CP strings (CPI/CP modules
and cables), if necessary replace
modules or cables
• Switch power supply off then on
again, check cables and modules
if error occurs repeatedly, replace
if necessary
• Check CP strings ( modules and
cables), if necessary replace modules or cables
• With correct string assignment:
String assignment must be saved
( chapter 3)
• Check string assignment, if neces-
sary replace module
36Short circuit in CP string
(24 V
EL/SEN
(Handheld: [Short circuit CP-Line] )
– Communication on CP string malfunctioned
or 24 V
Val
)
Tab. 4/7: Error messages of the CPX-CP interface - Part 2
In addition, the following error can occur during the commissioning phase for the CPX bus node with the parameter “System start” = “saved parameterisation and CPX system expansion” or with the CPX-FEC:
• Check CP strings, if necessary re-
place cable
Festo P.BE-CPX-CP-EN en 1211b
4-13
4. Diagnosis and error treatment
Error
DescriptionError handling
number
16Module code not permitted or incorrect module
(Handheld: [Module code incorrect] )
– The saved string assignment of the CPX-CP
interfaceisnotthesameastheconfiguration
saved in the CPX bus node or in the CPX-FEC
205NVRAM reset to default values
(Handheld: [Module set to default values])
– EEPROM has valid content, but no valid con-
figuration.
Tab. 4/8: Additional error message of the CPX terminal
Specific monitoring of the CPX-CP interface can be activated
or deactivated by means of parameterisation.
Parameterisation of the CPX-CP interface applies only to certain CPI/CP modules. An overview shows Tab. 4/9 (status at
January 2012).
• For the CPX bus node:
Change parameter “System start
...” to “... default parameterisation and current CPX expansion”
• With the CPX-FEC:
Save the actual configuration as
setpoint configuration with FST
software
• No need for action. This is inform-
ation and not an error
4-14
Festo P.BE-CPX-CP-EN en 1211b
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.