Festo CPX-CP-4-FB Installing And Commissioning Instructions

CPX-terminal
Electrical interface CPX-CP-4-FB
CPI System Desciription
Installing and commissioning CPI systems
Electronics Description
CPX-CP interface
en 1211b
[761481]
Contents and general instructions
Original de.......................................
Edition en 1211b..................................
Designation P.BE-CPX-CP-EN.........................
Order no. 539294..................................
© (Festo AG & Co. KG, D-73726 Esslingen, Federal Republic of Germany, 2012) Internet: http://www.festo.com E-Mail: service_international@festo.com
The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility module or design.
Festo P.BE-CPX-CP-EN en 1211b
I
Contents and general instructions
PROFIBUS®,PROFIBUS-DP®,INTERBUS®, DeviceNet®, CC-Link®,TORX®are registered trademarks of the respective trademark owners in certain countries.
II
Festo P.BE-CPX-CP-EN en 1211b
Contents and general instructions
Contents
Designated use VI........................................................
Target group VII..........................................................
Service VII...............................................................
Important user instructions VIII..............................................
Notesontheuseofthismanual X...........................................
1. System summary – CPI system 1-1...................................
1.1 Overview of the CPI system 1-3.......................................
1.1.1 Method of operation of the CPI/CP system 1-6...................
1.1.2 Variants and extension rules for the CPI-/CP system 1-9...........
1.1.3 Assigned I/Os of the CPI/CP modules 1-12.......................
1.2 CPI system with the CPX-CP interface 1-13...............................
1.2.1 Address range of the CPI system with the CPX-CP interface 1-14......
1.2.2 Address assignment 1-15.....................................
2. Installation 2-1...................................................
2.1 General instructions on installation 2-3................................
2.2 CPI connections 2-6................................................
2.2.1 Permissible CPI/CP modules and string lengths dependent
on the CPI cables 2-7........................................
2.2.2 Connecting CP strings 2-9....................................
2.3 Connecting the power supply 2-10.....................................
2.3.1 Power supply 2-11...........................................
2.3.2 Ascertaining the current consumption 2-12.......................
2.3.3 Power supply arrangement – formation of power zones 2-16........
2.4 Complying with protection class IP65/IP67 2-19..........................
Festo P.BE-CPX-CP-EN en 1211b
III
Contents and general instructions
3. Commissioning 3-1................................................
3.1 Procedure for commissioning 3-3.....................................
3.2 Prepare the CPI system for commissioning 3-4..........................
3.2.1 Checking the CP strings 3-4..................................
3.2.2 Saving the string assignment 3-5..............................
3.3 Switching-on reaction of the CPI system 3-8.............................
3.4 Reaction of the CPI system to faults in operation 3-10......................
3.4.1 Eliminating assignment faults 3-10..............................
3.4.2 Replacing CPI/CP modules 3-11................................
3.4.3 Replacing CPI/CP modules during operation 3-12.................
3.5 Notes on operation 3-15..............................................
3.5.1 Factory default mark from version 22 3-16.......................
3.6 Parametrizing 3-17..................................................
3.7 Commissioning functions with the handheld 3-27.........................
3.7.1 Menu commands of the CPX-CP interface on the Handheld 3-28......
3.7.2 Representation of the CPI/CP modules 3-29......................
3.7.3 Displaying the string assignment 3-30...........................
3.7.4 Observing signal states (monitoring) 3-31........................
3.7.5 Parametrizing with the Handheld 3-33...........................
4. Diagnosis and error treatment 4-1....................................
4.1 Overview of diagnostic possibilities 4-3................................
4.2 Diagnosis via LEDs 4-4..............................................
4.2.1 Normal operating status 4-6..................................
4.2.2 CPI system-specific LEDs 4-7..................................
4.2.3 CP string-specific LEDs 4-9...................................
4.3 Error messages of the CPX-CP interface 4-12.............................
4.4 Diagnostics via the CPX-FEC or CPX bus node 4-16........................
4.4.1 Status bits of the CPX terminal 4-16.............................
4.4.2 I/O diagnostic interface and diagnostic memory 4-17..............
4.5 Diagnostic functions with the Handheld 4-21.............................
4.6 Error handling and parameterisation 4-22...............................
IV
Festo P.BE-CPX-CP-EN en 1211b
Contents and general instructions
A. Technical appendix A-1.............................................
A.1 Technical specifications of CPX-CP interface, type CPX-CP-4-FB A-3..........
A.2 Accessories A-4....................................................
A.3 Displaying CPI/CP module-specific information with the Handheld A-5.......
A.4 Address assignment of the CP valve terminals and CPI/CP modules A-6......
A.5 Parametrizing with the FST software (CPX-FEC) A-8.......................
A.6 Permissible CPI/CP modules and string lengths dependent on the
CPI cables A-10.....................................................
B. CPX-CP interface with Interbus field bus node B-1.......................
B.1 Addressing with Interbus B-3.........................................
B.1.1 Address range with Interbus field bus nodes B-3.................
B.1.2 Address assignment with Interbus field bus nodes B-3............
B.2 Diagnosing with Interbus B-7.........................................
C. Appendix C-1.....................................................
Festo P.BE-CPX-CP-EN en 1211b
V
Contents and general instructions
VI
Festo P.BE-CPX-CP-EN en 1211b
Contents and general instructions
Designated use
The CPX-CP interface described in this description has been designed exclusively for use in combination with CPX terminals from Festo. The designated CP modules from Festo (CP valve terminals and CPI I/O modules) can be connected to the CPX-CP interface. The CPX terminal and the connected CPI modules are only to be used as follows:
–asintended
without unauthorised modifications
in excellent technical condition.
If standard ancillary components, such as sensors and actuat­ors, are connected, the specified limits for pressures, temper­atures, electrical data, torques, etc. must be complied with.
Comply with the legal rules and regulations and standards, rules of the testing organisations and insurance companies and national specifications applicable for the location.
Warning
Only use PELV circuits in accordance with IEC/EN 60204-1 (protective extra-low voltage, PELV) for the electrical power supply.
Also observe the general requirements for PELV circuits in accordance with IEC EN 60204-1.
Use only voltage sources that guarantee reliable electrical isolation of the operating voltage according to IEC DIN EN 60204-1.
Festo P.BE-CPX-CP-EN en 1211b
VII
Contents and general instructions
Ranges of application and certifications
The products fulfil the requirements of EU directives and bear the CE certification.
Standards and test values, which the products must comply with and fulfil, can be found in the technical appendix section. The product-relevant EU directives can be found in the declar­ation of conformity.
Certificates and declarations of conformity for these products can be found at www.festo.com.
Target group
Service
This description is intended exclusively for technicians trained in control and automation technology, who have experience in installation, commissioning, programming and diagnostics of programmable logic controllers (PLC) and fieldbus systems/networks.
Please consult your local Festo repair service if you have any technical problems.
VIII
Festo P.BE-CPX-CP-EN en 1211b
Contents and general instructions
Important user instructions
Danger categories
This manual contains instructions on the possible dangers which may occur if the product is not used correctly. These instructions are marked (Warning, Caution, etc.), printed on a shaded background and marked additionally with a picto­gram. A distinction is made between the followi ng danger warnings:
Warning
This means that failure to observe this instruction may result in serious personal injury or damage to property.
Caution
This means that failure to observe this instruction may result in personal injury or damage to property.
Note
This means that failure to observe this instruction may result in damage to property.
The following pictogram marks passages in the text which describe activities with electrostatically sensitive compo­nents.
Festo P.BE-CPX-CP-EN en 1211b
Electrostatically sensitive components may be damaged if they are not handled correctly.
IX
Contents and general instructions
Marking special information
The following pictograms mark passages in the text containing special information.
Pictograms
Information: Recommendations, tips and references to other sources of information.
Accessories: Information on necessary or sensible accessories for the Festo product.
Environment: Information on environment-friendly use of Festo products.
Text markings
Bullet points denote activities that may be carried out in any sequence desired.
1. Figures denote activities which must be carried out in the numerical order specified.
Hyphens indicate general activities.
X
Festo P.BE-CPX-CP-EN en 1211b
Contents and general instructions
Notes on the use of this manual
This manual contains specific information on the method of operation, and on fitting, installing and commissioning the CPX-CP interface.
Special information on commissioning, programming and diagnostics of a CPX terminal with the CPX fieldbus node or CPX-FEC used can be found in the relevant description.
General basic information on the method of operation, on fitting, installing and commissioning CPX terminals can be found in the CPX system manual.
An overview of the structure of the CPX terminal user documentation is contained in the CPX system description. www.festo.com Support portal: search term “CPX system description”
Festo P.BE-CPX-CP-EN en 1211b
XI
Contents and general instructions
Information on the CPI modules and the valve terminals with a CPI connection can be found in the manual for the relevant module. An overview is shown in Tab. 0/1.
Version
CP modules, Electronics description
Modules with CP connection, Electronics description
Description Pneumatics
Title Contents
“CPI-CL modules, CPI-EL modules” Type P.BE-CPX-EA-CL...
“CPV Direct” Type P.BE-CP-DI...
“CDVI ...” Type P.BE-CDVI-DN-...
“CPA-SC / CPV-SC ...” Type P.BE-CPASC­CPVSC-...
“CPV valve terminal” Type P.BE-CPV-...
“CPA valve terminals” Type P.BE-CPA-...
Mounting, installation and commissioning of CP input and output modules, type CP-...-CL and CPI-…-EL
Instructions on mounting, installation, commissioning and diagnostics for the corresponding CPV valve terminal with direct link
Instructions on mounting, installation, commissioning and diagnostics of the CDVI with fieldbus direct link “DeviceNet”
Instructions on mounting, installation, commissioning and diagnostics of the CPV-SC or CPA-SC valve terminal with fieldbus direct link for PROFIBUS DP or DeviceNet.
Mounting, installation, c ommissioning, servicing and conversion of the CPV pneumatics (type 10)
Mounting, installation, c ommissioning, servicing and conversion of the CPA pneumatics (type 12)
“MPA valve terminal” Type P.BE-MPA-...
Tab. 0/1: Descriptions for CP I/O modules and CP valve terminals from Festo
XII
Mounting, installation, c ommissioning, servicing and conversion of the CPA pneumatics (type 32)
Festo P.BE-CPX-CP-EN en 1211b
Contents and general instructions
The following product-specific terms and abbreviations are used in this manual:
Term/abbreviation
CP cable Special cable for connecting the various CPI/CP modules in a CP string.
CP functionality Supports the CP protocol without extended functions
CP module Collective term for modules without extended functions which can be in-
CP string CPI or CP modules which are connected by CPI/CP cable to the CPX-CP
CP valve terminal CPV valve terminal (type 10) or CPA valve terminal ( type 12), each with CP
CP system Complete electrical installation system consisting of a CP master with one
CPI cable Special cable for connecting the various CPI/CP modules in a CP string.
CPI connection Socket or plug on the CPI modules which allows the modules to be connec-
Meaning
Colour: black, type KVI-CP1-... and type KVI-CP2-...
tegrated into a CPI/CP system.
interface. For reasons of simplicity, only the term “CP string” is used, even if it has CPI functions.
connection (also regarded as CP modules). Basic electric unit, black.
or more CP strings. The system consists of CP modules (without extended functions).
Colour: white, type KVI-CP3-. ..
ted using the CPI or CP cable.
CPI field bus interface Term for a CPI capable interface with field bus connection (e.g.
CPI field bus module Defined combination of a CPX field bus node and a CPX-CP interface.
CPI functionality Supports the CPI protocol with extended functions
CPI module Collective term for modules with extended functions which can be integ-
CPI system Also: “CPI installation system”
Tab. 0/2: Specific terms and abbreviations
Festo P.BE-CPX-CP-EN en 1211b
combination of CPX field bus node and CPX-CP interface (CPI field bus module) or CPV with CPI string extension (CPV Direct)).
connects a CPI system with a field bus.
rated into a CPI/CP system.
Complete electrical installation system consisting of a CP master with one or more CP strings. The system consists of CPI/CP modules with and without extended functions. The system need not consist exc lusively of CPI modules.
XIII
Contents and general instructions
Term/abbreviation Meaning
CPX-CP interface CPX module with 4 CP strings for connecting CPI/CP modules and CP valve
terminalstotheCPXterminal.
CPX modules Collective term for the various modules which can be integrated into a CPX
terminal.
CPX terminal Complete system comprising CPX modules with or without pneumatics
Extended functions – Additional options in string assignment:
Up to 4 modules per string with a maximum of 32 inputs and 32 outputs. Without extended functions, only 1 output and 1 input module is pos­sible.
– Revised data communication:
Inputs report change in status when data arrive or a diagnostic message is present. Message is queried specifically. Additionally, the system monitors the participants for TimeOut. Without extended functions, the system, queries information from the stations cyclically (so-called polling).
Fieldbus node s Provide the connection to spe cific fieldbuses. Tra nsmit control signals to
the connected modules and monitor their operational ability.
I Digital input
I/O modules Collective term for the modules which provide digital inputs and outputs
(e.g., CPX I/O modules, CPI input modules and CPI output modules)
I/Os Digital inputs and outputs
Input module Input module
O Digital output
Output module Output module
String allocation Type and sequence of the CPI/CP modules connected to one or mo r e CP
strings.
Tab. 0/3: Specific terms and abbreviations
XIV
Festo P.BE-CPX-CP-EN en 1211b
System summary – CPI system
Chapter 1
System summary – CPI system
Festo P.BE-CPX-CP-EN en 1211b
1-1
1. System summary – CPI system
Contents
1. System summary – CPI system 1-1...................................
1.1 Overview of the CPI system 1-3.......................................
1.1.1 Method of operation of the CPI/CP system 1-6...................
1.1.2 Variants and extension rules for the CPI-/CP system 1-9...........
1.1.3 Assigned I/Os of the CPI/CP modules 1-12.......................
1.2 CPI system with the CPX-CP interface 1-13...............................
1.2.1 Address range of the CPI system with the CPX-CP interface 1-14......
1.2.2 Address assignment 1-15.....................................
1-2
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
1.1 Overview of the CPI system
Festo can assist you in solving your automation task at the machine level with the aid of valve terminals. Due to its modular structure, the CPI system from Festo enables you to integrate valve terminals and I/O modules optimally in your machines and systems.
1
CPX terminal with CP interface as CP master
2
CP modules
3
CP string
12
3
4
4
CP input module
5
CPV valve terminal
6
CPA valve terminal
7
CP string exclusively with CPI modules (modules with exten­ded functions)
Fig. 1/1: Example 1 for design of a CPI system
Note
Observe that only products from Festo can be connected.
5
4
6
7
Festo P.BE-CPX-CP-EN en 1211b
1-3
1. System summary – CPI system
3
2
1
CPI fieldbus node
1
2
MPA-CPI valve terminal
3
CPV-CPI valve terminal
4
CP-CL module
5
CP-EL module
Fig. 1/2: Example 2 for design of a CPI system
45
1-4
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
A CPI system consists of individual modules which are con­nected to each other by means of CPI cables. In this way it is possible to decentralise the configuration of the CPI modules. The compact CP valve terminals and I/O modules can be mounted very close to the cylinders to be controlled. This enables short compressed air lines to be used.
System losses can be minimized if short compressed air tubing is used and the times required for pressurising and exhausting the tubing can be reduced.
This enables smaller valves with sufficient flow to be used, thereby helping to reduce costs.
Festo P.BE-CPX-CP-EN en 1211b
1-5
1. System summary – CPI system
1.1.1 Method of operation of the CPI/CP system
CPI/CP systems are composed of the following modules:
Modules
CPI/CP master Special CP fieldbus nodes and CP
Function
interfaces are available for the vari­ous fieldbuses. – As electrical modules are an in-
tegral part of a CPX terminal or a modular valve terminal (CPX-CP interface/CPI interface).
– Provide the connection to specif-
ic fieldbuses (CPI node, CPV dir­ect)
– These offer connections for up to
four strings to which I/O mod­ules and CP valve terminals are connected.
– They transmit control signals to
the c onnected modules and monitor their functioning
1-6
CPV/CPV-SC valve terminals with CPI connection
– These provide different valve
functions via valve sub-bases for controlling pneumatic actuators
– Relay plates, pressure zone sep-
aration plates and blanking plates can also be integrated
Tab. 1/1: Overview of the CPI modules - Part 1
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
Modules Function
MPA valve terminals with CPI connection
CP-/CPI input mod­ules (type CL, EL, RL)
CP-/CPI output modules (type CL, EL, RL)
– These provide different valve functions
via valves for controlling pneumatic ac­tuators.
– Provide inputs for connecting sensors
and thus enable, for example, cylinder positions to be interrogated
– These provide universally effective elec-
tric outputs for controlling low-current consuming devices (in addition, valves, lamps, etc.)
Festo P.BE-CPX-CP-EN en 1211b
Tab. 1/2: Overview of CPI modules - part 2
1-7
1. System summary – CPI system
123
In the capacity of CPI master, each CPX-CP interface controls data transfer to a wide variety of controller systems in a CPX terminal. In principle, several CPX-CP interfaces can be used in a CPX terminal.
1
Field bus (incoming)
2
Field bus (continuing)
3
CPI master (CPX-CP interface)
4
CP string
5
CP input module
6
CP valve terminal
7
Sensor
8
Cylinder
9
CP output module
Fig. 1/3: Method of operation of the CPI system
4
5
6
7
8
9
Cable lengths The complete length of cable on a string must not exceed
1-8
I/O data exchange between the CPX terminal and the modules connected to the CPX-CP interface takes place constantly via the CPX-CP interface.
10 m.
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
1.1.2 Variants and extension rules for the CPI-/CP system
Modules can be divided into two groups:
CPI modules (extended functions) – CP modules (no extended functions)
Tab. 1/3 shows the number of supported modules and rules dependent on the type of the master and the CPI/CP mod­ules.
Rules and properties
CPI system – Max. 4 modules on the CP string
– Max. 32 inputs and 32 outputs per CP string
CPI modules – There is an incoming and continuing interface on all CPI modules and valve
terminals
– Any sequence of the CPI modules/valve terminals within the CP string
CP modules – There is an incoming and continuing interface on CP output modules and CP
valve terminals
– Only incoming interface at CP input modules. They can therefore only be
placed at the end of a CP string.
CPI/CP master The CPX-CP interface and the CPV Direct are CPI masters.
A mixture of CPI/CP modules is possible on CPI masters: – Only one CP input module is possible at the end of a string – Per CP string, only one CP valve terminal – “Unused” locations on the CP string can be “filled” with CPI modules2).
1)
Without extended functions2)With extended functions
1)
or one CP output module
1)
Tab. 1/3: Rules for extending the CPI system
Festo P.BE-CPX-CP-EN en 1211b
Note
Independent of the type of CPI/CP modules, not more than 32 inputs and 32 outputs may be connected (sum of all modules on a CP string).
That is, a CP string can be extended with a maximum of 2 CP valve terminals with extended functions, since they always occupy 16 output addresses.
1-9
1. System summary – CPI system
CP master
VT / O I
VT / O
I
VT / O: CP valve terminal or
CP output module
I: CP input module
Fig. 1/4: Example: Setting up a CP system
(without extended functions)
All CPI modules (with extended functions) can also be con­nected to CP masters (without extended functions) as shown in Fig. 1/4.
1-10
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
CPI master
CPI master
CP (O) CPI (I/O)
CPI (I/O)
CPI (I/O)
CPI (I/O)
CP (O)
CPI (I/O)
CPI (I/O)
CPI (I/O)
CPI (I/O) CPI (I/O)
CPI (I/O)
CP (O)
CPI (I/O)CPI (I/O)
CPI (I/O)
CPI (I/O)
CPI (I/O)
CPI (I/O)
CP (O)
CP (I)
CP (I)CP (O) CPI (I/O)
Grey: CPI (with extended functions) CP (I): CP input module CP (O): CP output module or CP valve terminal CPI (I/O): CPI input or output module (with extended functions) or CP valve terminal
with CPI ability (for valve terminals: max. 2 possible)
Rules: CP: For the CP master, the rules remain valid. CPI: Max. 32 inputs and 32 outputs per string, max. 4 modules per string
Max. 1 CP output module or 1 CP valve terminal Max. 1 CP input module always at the end of the string Max. 2 valve terminals with CPI functions per string
Fig. 1/5: Example: expansion of a CPI/CP system
Festo P.BE-CPX-CP-EN en 1211b
CPI (I/O) CPI (I/O)
CPI (I/O)
CP (O)
CPI (I/O)
CP (O)
CP (I)
CP (I)
1-11
1. System summary – CPI system
1.1.3 Assigned I/Os of the CPI/CP modules
Tab. 1/4 provides an overview of the assigned addresses for the various CPI/CP modules (status at November 2012).
CPI modules
Kind Type Extended
functions
CPI/CP valve terminals
CPI/CP input modules
CPV..-GE-FB-4 CPV..-GE-FB-4/6/6 CPV..-GE-FB-6 CPV..-GE-FB-8 CPA10/14-IFB-CP CPI-MPA-S
CP-E08-M8-CL CP-E08-M12-CL CP-E16-KL-CL CP-E16-M12-EL CP-E16-M8-EL CP-E32-M8-EL CP-E16-M8 CP-E16N-M8 CP-E16-M8-Z CP-E16-M12x2-5POL CP-E16N-M12x2 CP-E16-KL-IP20-Z
No Yes No No No Yes
Yes Yes Yes Yes Yes Yes No No No No No No
Assigned I/Os
at CPI masters
(with extended functions)
16 O
8I 8I 16 I 16 I 16 I 32 I 16 I 16 I 16 I 16 I 16 I 16 I
1)
16 O 16 O 16 O
2)
– – – – – – – – – – – –
at CP masters
(without exten­ded functions)
16 O
16 O 16 O 16 O 16 O
2)
16 I 16 I 16 I 16 I 16 I
3
– 16 I 16 I 16 I 16 I 16 I 16 I
)
– – – – –
3)
– – – – – – –
CPI/CP output modules
CP-A04-M12-CL CP-A08-M12-EL-Z CP-A08-M12-5POL CP-A08N-M12
1)
Assignment dependent on equipment. CPV..-GE-FB-4/6/6 dynamically occupies 8 or 16 outputs
2)
Assignment depe ndent on equipment. CPI-MPA dynamically occupies 8, 16, 24 or 32 outputs
3)
No function on CP master
Tab. 1/4: Assigned I/Os of the CPI/CP modules
1-12
Yes Yes No No
– – – –
8O 8O 16 O 16 O
Festo P.BE-CPX-CP-EN en 1211b
– – – –
16 O 16 O 16 O 16 O
1. System summary – CPI system
1.2 CPI system with the CPX-CP interface
The CPX-CP interface supports CPI systems with extended functions. CPI systems with CP modules with extended functions are distinguished by the following features:
moreI/Osperstringarepossible(max.32I/32O)
up to 4 CPI/CP modules are possible
modules can be in any order.
The CPX-CP interface, in the capacity of technology module (also termed function module), assigns I/O addresses in the CPX terminal. The number of addresses assigned depends on:
the field bus node or FEC used and the operating mode of
the CPX terminal,
the saved configuration (string assignment).
Address assignment is carried out as follows:
Field bus node/FEC
CPX field bus node with Remote I/O operating mode, e.g.:
CPX-FB11, DeviceNet
CPX-FB13, PROFIBUS
CPX-FB14, CANopen
CPX-FB23, CC-Link
CPX front end controller with Stand Alone or Remote Controller operating mode:
CPX-FEC
CPX field bus node for Interbus with operating mode Remote I/O, e.g.:
CPX-FB6
Addressing see
Section 1.2.2
Section B.1.1
Festo P.BE-CPX-CP-EN en 1211b
Tab. 1/5: Addressing
1-13
1. System summary – CPI system
1.2.1 Address range of the CPI system with the CPX-CP interface
Size of the assigned ad­dress range
The following rules apply to the address range occupied by the CPX-CP interface (Tab. 1/6):
The size of the assigned address range depends on the
number of the last string used.
The assignment for inputs is independent of the assign-
ment for outputs.
Each string on the CP interface has an address range of
32 bits for inputs and 32 bits for outputs at its disposal.
Unused address range Unused address range is reserved for extensions.
Last string used
No string assigned 0I No module with inputs
String 1
1 2 3 4
Assigned address range Assigned address range
Inputs Description Outputs Description
0O No module with
connected.
32 I At least one input
module on string 1. No input modules on strings 2 to 4.
32 O At least one output
outputs connected.
module on string 1. No output modules on strings 2 to 4.
String 2
String 3
String 4
1 2 3 4
1 2 3 4
1 2 3 4
64 I At least one input
96 I At least one input
128 I At least one input
Tab. 1/6: Assigned address range
1-14
module on string 2. No input modules on strings 3 and 4.
module on string 3. No input modules on string 4.
module on string 4.
64 O At least one output
module on string 2. No output modules on strings 3 and 4.
96 O At least one output
module on string 3. No output modules on string 4.
128 O At least one output
module on string 4.
Festo P.BE-CPX-CP-EN en 1211b
1. System summary – CPI system
1.2.2 Address assignment
The assignment of the addresses of the CPI/CP modules depends on the CPX field bus node or CPX-FEC used. The following representation applies to the field bus nodes (e.g. CPX-FB13) as well as for the Front End Controller CPX-FEC, but not for Interbus field bus nodes. The assignment for Interbus field bus nodes (e.g. CPX-FB6) can be found in appendix B.1.
Address assignment of the individual modules takes places according to the following rules:
A CP interface provides four strings with a total of
128 input addresses and 128 output addresses.
A used string occupies 32 input addresses and 32 output
addresses.
The addresses are assigned fixed to the individual CP
strings and CPI modules in ascending order.
String
Input addresses Output addresses
number
1 I0 ... I31 O0 ... O31
2 I32 ... I63 O32 ... O63
3 I64 ... I95 O64 ... O95
4 I96 ... I127 O96 ... O127
Address assignment of the individual modules is there-
fore determined by the string to which they are connected and by the number of I/Os the existing modules occupy on the string.
Festo P.BE-CPX-CP-EN en 1211b
Unused address range (due to modules not being
available) remains reserved for later CPI extensions.
The diagram below shows as an example the address assignment of a CPI system.
1-15
1. System summary – CPI system
PROFIBUS addresses starting at input/output word 45 are used. The CPX-CP interface thus occupies 12 bytes of input addresses and 16 bytes of output addresses.
I/O mapping
Idata Odata
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9
Byte 10
Byte 11
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9
Byte 10
Byte 11
Byte 12
Byte 13
Byte 14
Byte 15
Module 0
L1
8I
Module 0
I45.0 ... I45.7 O45.0 ... O45.7 O46.0 ... O46.7 O47.0 ... O47.7
L2
16O
Module 4
Obyte4
Obyte5
O49.0 ... O49.7 O50.0 ... O50.7 ...
L3
16O
Module 8
Obyte8 Ibyte8
Obyte9
O53.0 ... O53.7 O54.0 ... O54.7
L4
8O
Module 12
Obyte12
O57.0 ... O57.7
Module 1 Module 2 Module 3String
8O
Module 1
Obyte0Ibyte0
8O
Module 2
Obyte1
16I
Module 5
Ibyte4
Ibyte5
I49.0 ... I49.7 I50.0 ... I50.7
8I
Module 9
I53.0 ... I53.7
8O
Module 13
Obyte13 Obyte14 Obyte15
O58.0 ... O58.7 O59.0 ... O59.7
(Module 6) (Module7)
16O
Module 10
Obyte10 Ibyte9
Obyte11
O55.0 ... O55.7 O56.0 ... O56.7
8O
Module 14
8O
Module 3
Obyte2
16I
Module 11
Ibyte10
I54.0 ... I54.7 I55.0 ... I55.7
8O
Module 15
O60.0 ... O60.7
used reserved
Fig. 1/6: Address assignment of a CPI system, example
1-16
The address assignment (method of counting, sequence of the I/Os) within the individual CP valve terminals and CPI/CP modules can be found in the relevant description for the module. Overview of the address assignments Appendix A.4.
Festo P.BE-CPX-CP-EN en 1211b
Installation
Chapter 2
Installation
Festo P.BE-CPX-CP-EN en 1211b
2-1
2. Installation
Contents
2. Installation 2-1...................................................
2.1 General instructions on installation 2-3................................
2.2 CPI connections 2-6................................................
2.2.1 Permissible CPI/CP modules and string lengths dependent
on the CPI cables 2-7........................................
2.2.2 Connecting CP strings 2-9....................................
2.3 Connecting the power supply 2-10.....................................
2.3.1 Power supply 2-11...........................................
2.3.2 Ascertaining the current consumption 2-12.......................
2.3.3 Power supply arrangement – formation of power zones 2-16........
2.4 Complying with protection class IP65/IP67 2-19..........................
2-2
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
2.1 General instructions on installation
Warning
Accidental movements of the connected actuators and loose tubing can cause injury to persons and/or damage to property.
Before carrying out mounting, installation and mainten­ance work, switch off the following:
– Compressed air supply – Operating voltage supply for the electronics/sensors – Load voltage supply for the outputs/valves.
Caution
Electrostatically sensitive components!
• D o not therefore touch the contacts of the components.
• Observe the regulations for handling electrostatically sensitive components.
You will then prevent the electronics from being damaged.
Note
Handle all modules and components with great care. Pay particular attention to the following:
– The specified torques must be complied with.
For information on mounting the CPX terminal CPX system description (P.BE-CPX-SYS-..).
Festo P.BE-CPX-CP-EN en 1211b
2-3
2. Installation
1
CPI system and CP string-specific status LEDs
2
CPI connections X1 … X4
3
Identification plates (accessories)
Electrical connecting and display elements
The following connecting and display elements can be found on the CPX-CP interface:
4
L1
PS
L2
PL
L3
RN
L4
X1
X2
1
2
4
Save key
X3
X4
3
Fig. 2/1: Connecting and display elements on the CPX-CP interface
Dismantling and fitting
The CPX-CP interface is mounted in an interlinking block of the CPX terminal (Fig. 2/2).
Dismantling Dismantle the CPX-CP interface as follows:
1. Loosen the four screws with a Torx screwdriver size T10.
2. Pull the CPX-CP interface carefully and without tilting away from the contact rails of the manifold block.
2-4
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
1
Screws, tightening torque 0.9 … 1.1 Nm
2
CPX-CP interface
1
3
Contact rails
4
Interlinking block (any, here with addi­tional power supply as an example)
3
Fig. 2/2: Dismantling/fitting the CPX-CP interface
Fitting Fit the CPX-CP interface as follows:
1. Place the CPX-CP interface in the manifold block. Make sure that the grooves with the terminals for electrical contact on the bottom of the CPX-CP interface lie directly above the contact rails.
2. Press the CPX-CP interface carefully and without tilting as far as possible into the manifold block.
2
4
Festo P.BE-CPX-CP-EN en 1211b
3. Tighten the screws at first only by hand. Place the screws so that the self-cutting threads can be used.
4. Tighten the screws with a Torx screwdriver size T10 with torque 0.9 ... 1.1 Nm.
2-5
2. Installation
2.2 CPI connections
Note
Operative malfunction due to impermissible cabling.
For connecting the CPI/CP modules to the CP string, use only the special CPI/CP cables from Festo (www.festo.com/catalogue).
Observe that the total cable length on a string must not exceed 10 m.
Dependent on the CPI/CP modules and CPI/CP cables used as well as the current consumption, the permissible modules and string length per CP st ring may be limited (section 2.2.1).
Observe the maximum permissible current consumption
per CP string, (section 2.3.2). In this way, you can avoid: – Errors in data exchange between the CPX-CP interface
and the connected modules.
2-6
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
2.2.1 Permissible CPI/CP modules and string lengths dependent on the CPI cables
Use for CPI systems the special CPI cables type KVI-CP-3-... (colour white).
Note
When using the CPI cable type KVI-CP-3-… (colour white) the following restriction applies, dependent on the mod­ules used and the current consumption:
– The maximum permissible string length of 10 m may be
limited further. An overview shows Tab. 2/1 and Tab. 2/2.
Note When using the CPI cable Type KVI-CP-1-… or KVI-CP-2-... (colour black) additional restrictions apply
for the string length and max. current consumption (Appendix A.6). Festo recommends the use of CP cable type KVI-CP-3-… (colour white).
Tip: PlaceCPvalveterminalsorCPoutputmodulesasthefirst module on the string if possible.
Festo P.BE-CPX-CP-EN en 1211b
2-7
2. Installation
CP string without CPI output module with maximum one CP valve terminal type
CPV10-.../CPA10-... 0.5 A . .. 1.5 A 10 m 10 m 10 m
CPV14-.../CPA14-... 0.5 A ... 1.5 A 10 m 10 m 10 m
CPV18-...
1)
Maximum sensor supply current used section 2.3.2, Tab. 2/5
2)
Nominal voltage or undervoltage of -10 %, 16 valve solenoid coils s witched simultaneously (high current phase)
3)
Maximum undervoltage of -15 %, 8 valve solenoid coils switched simultan eously (high current phase)
4)
Maximum undervoltage of -15 %, 16 valve solenoid coils switched simultaneously (high current phase)
5)
Valve terminal installed at each string beginning
6)
Valve terminal installed at each string end
Maximum sensor current con-
Maximum string length with CP cable, type KVI-CP-3-...
sumption of the
U
CPI modules on the CP string
0.5 A 10 m 10 m 10 m
1.0 A 10 m 10 m 10 m
1.5 A 10 m 10 m 10 m
1)
= 21.6 ... 24 V;
VAL
16 valves
2)
U
= 20.4 V;
VAL
8 valves
U
3)
VAL
16 valves
8m
5m
= 20.4 V;
5)
6)
5)
6)
4)
Tab. 2/1: Permissible string lengths with CP cables, type KVI-CP-3- dependent on the CP
valve terminal used and the sensor current consumption
CP string without CP valve terminal with maximum of one CPI output module type
CP-A04-M12-CL 0,5 A 10 m
CP-A08...-M12-... 1,5 A 10 m
1)
Maximum sensor supply current used section 2.3.2, Tab. 2/5
Tab. 2/2: Permissible string lengths with CP cables, type KVI-CP-3- dependent on the CPI
output module used and the sensor current consumption
2-8
Maximum sensor current consumption of the CPI modules on the CP string
Maximum string length with CP cable, type KVI-
1)
CP3-...
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
2.2.2 Connecting CP strings
CP connections There are four CPI connections for the CP strings on the
CPX-CP interface (X1 ... X4).
CPI/CP modules can be connected to each CPI connection according to the rules described in section 1.2 .
Connecting CP modules
1. Check which address range is intended for the CPI/CP module ( section 1.2).
2. Connect the modules with the CPI/CP cables to the string which makes this address range available.
3. Fasten the plug and socket of the CPI/CP cable with the union nut. In this way the electrical contact is guaranteed.
4. Use the identification labels (type IBS 6x10 or IBS 9x20) to indicate the string to which the module is connected. In this way you can avoid confusion during later repair and maintenance work.
Festo P.BE-CPX-CP-EN en 1211b
2-9
2. Installation
2.3 Connecting the power supply
Take the following aspects into consideration when installing a CPI system with the CPX-CP interface:
Power supply (section 2.3.1)
Current consumption (section 2.3.2)
Formation of power zones (section 2.3.3).
Note
It is imperative that you observe the notes in section 2.3.3 when forming power zones in the CPX terminal by means of several manifold blocks with power supply.
Recommendation:
Provide the load voltage for the valve coils and, if necess­ary, for the outputs separately if you wish to implem ent an EMERGENCY STOP function.
Note
Check whether pressure switch-off is also necessary for an EMERGENCY STOP function on your machine/system.
Note
Observe the notes on earthing the CPI/CP modules in the manual for the relevant module.
2-10
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
2.3.1 Power supply
The power supply for the CPI system with the CPX-CP interface is provided via the following connections on the CPX terminal (manifold blocks with power supply):
Manifold block type CPX-EV-S... (U
Manifold block type CPX-EV-V... or CPX-EV-S... (U
VAL
)
EL/SEN
The power supply for the following is provided via the oper-
)
ating voltage supply for the electronics/sensors (U
EL/SEN
the CPX terminal:
the internal electronics of the CPX- CP interface
the internal electronics of all the CPI modules connected
the 24 V sensor supply of the inputs of the CPI input
modules connected.
The power supply for the following is provided via the load supply for the valves (U
)oftheCPXterminal:
VAL
the 24 V supply for the CP valve terminals and CPI/CP
output modules (output modules without load supply connection).
Note
Malfunctioning due to power supply outside the tolerance The module with the lowest tolerance always determines
the permitted voltage tolerances.
)of
Festo P.BE-CPX-CP-EN en 1211b
If the CPX-CP interface is used, special tolerances accord­ing to Tab. 2/3 must be observed for the load supply for the valves (U
Load supply for valves (U
CPX-CP interface 20,4 ... 26.4 V
1)
If midi/maxi pneumatics are also supplied via the load supply for the valves: 21.6 ... 26.4 V
) of the CPX-CP interface.
VAL
) Tolerance
VAL
1)
Tab. 2/3: Permitted voltage tolerance
2-11
2. Installation
2.3.2 Ascertaining the current consumption
The current consumption of a CPÎ system depends on the number and type of the CPI modules connected.
Recommendation:
Use a closed-loop controlled power unit.
When selecting the power unit, check that it has sufficient output. Calculate the total current consumption, if necessary.
Calculation Tab. 2/5 and Tab. 2/7 show how to calculate the total current
consumption for a CPI system. Please refer to the relevant technical specifications for the current consumption of the CP valve terminals and the CPI/CP modules.
Note
Select a power unit which provides sufficient output for later extensions to the CPI system.
If you are using CP output modules with a separa te load voltage connection, take into account the appropriate current consumption when selecting a power unit.
Observe the notes on selecting the power unit in the CPX system manual.
2-12
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
Note
Operative malfunctions due to the maximum permitted current consumption on a CP string being exceeded.
Make sure that the current consumption of all the mod­ules in a CP string does not exceed the maximu m per­missible value of 1.6 A.
Observe that the sensor current consumption from U
EL/SEN
can be additionally restricted dependent on the string assignment, string length and the CPI/CP cables used  section 2.2.1.
Festo P.BE-CPX-CP-EN en 1211b
2-13
2. Installation
Current consumption on CP string x of U
EL/SEN
of the CPX terminal
Current consumption for internal electronics of all the CPI/CP modules connected (number of CPI/CP modules x 0.035 A)
Current consumption of all sensors connected to the CPI/CP input modules (max. 1.5 A)
2)
1)
+ _____ A
Internal current consumption per input channel of the CPI/CP input modules (number of all inputs x 0.01 A)
+ _____ A
Sum of current consumption on string x (max. 1.6 A)
= _____ A
1)
Refer to manufacturer's specifications
2)
Dependent on the string assignment, string length and the CPI/CP cables used, section 2.2.1
Tab. 2/4: Current consumption of U
Total current consumption of U
EL/SEN
EL/SEN
of the CPX terminal per CP string
of the CPX terminal
_____ A
Sum of current consumption on CP string 1 of Tab. 2/4
Sum of current consumption on CP string 2 of Tab. 2/4
Sum of current consumption on CP string 3 of Tab. 2/4
Sum of current consumption on CP string 4 of Tab. 2/4
Total current consumption of
Tab. 2/5: Total current consumption of U
U
EL/SEN
of the CPX terminal
EL/SEN
_____ A
+ _____ A
+ _____ A
+ _____ A
= _____ A
of the CPX terminal
2-14
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
Current consumption on CP string x of U
Current consumption of all simultaneously energized valve coils of the CP valve terminals
Load current of all simultaneously activated ouputs of the CPI output modules
without load voltage connection
Sum of current consumption on string x (max. 1.6 A)
1)
Current consumption dependent on valve type (Technical data of the valves)
1)
Tab. 2/6: Current consumption from U
Total current consumption of U
Sum of current consumption on CP string 1 as per Tab. 2/6
Sum of current consumption on CP string 2 as per Tab. 2/6
of the CPX terminal
VAL
of the CPX terminal
VAL
of the CPX terminal per CP string
VAL
_____ A
+ _____ A
= _____ A
_____ A
+ _____ A
Sum of current consumption on CP string 3 as per Tab. 2/6
Sum of current consumption on CP string 4 as per Tab. 2/6
Total current consumption of
Tab. 2/7: Current consumption of U
U
of the CPX terminal
VAL
of the CPX terminal
VAL
Note
The 24 V supply of the CP valve terminals and of the CPI/CP output modules (output modules without load supply connection) takes place within the CPX-CP interface through a shared cable.
Observe that currents in a shared cable add up.
+ _____ A
+ _____ A
= _____ A
Festo P.BE-CPX-CP-EN en 1211b
2-15
2. Installation
2.3.3 Power supply arrangement – formation of power zones
The modular power supply arrangement of the CPX terminal facilitates the formation of power zones.
Please note the following:
The internal electronics of the CPI/CP I/O modules are sup­plied from the operating voltage supply for ele ctronics/ sensors (U The CP valve terminals and the CPI/CP output modules are provided with load supply by the load supply for the valves (U
).
VAL
EL/SEN
).
Note
The CPX-CP interface connects the internal contact rails 0U
EL/SEN
and 0 U
of the CPX terminal.
VAL
– As a result, the electrical isolation of the operating
voltage supply for electronics/sensors (U
EL/SEN
)ofthe CPX terminal and of the load voltage valves supplying the CPX-CP interface (U
) CPX-CP interface cancel each
VAL
other out.
– Complete electrical isolation (all poles) o f the valve sup-
ply of the CP valve terminals, even in conjunction with CPX valve supply of type CPX-EV-V, is therefore not pos­sible.
Note
The CPX-CP interface must be supplied via the same potential (common power unit) as the operating power supply for the electronics/sensors (U
EL/SEN
)ofthe
CPX terminal (see also Fig. 2/3).
2-16
Basic information on the power supply arrangement of the CPX terminal can be found in the CPX system description.
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
Example CPX terminal with CP interface + system supply and 2 additional power supplies for valves
In the example (Fig. 2/3) the CPX-CP interface and there­fore the CP valve terminals and CPI/CP output modules without load voltage connection are supplied via the valve supply 2 . The CP valve terminals can only be switched off at asinglepole!
The MPA pneumatics are supplied via the valve supply 3 (only permitted with MPA electronic modules type VMPA..-FB-EMG-...). The MPA pneumatics can be switched off at all poles.
Festo P.BE-CPX-CP-EN en 1211b
2-17
2. Installation
0V 24V
0V 24V
0V 24V
FE
VAL
VAL
OUT
OUT
EL/SEN
EL/SEN
1
8DI
12 3 4 12 3 412 3 4
2
3
4
8DI4DO CP-I
MPA
8O 8O
3
1
Interlinking block with system supply
2
Interlinking block with additional power supply for valves (supplies CPX-CP interface)
3
Interlinking block with CP interface; connects internally at module level the rails 0 U
4
Interlinking block with additional power supply for valves (supplies MPA p neu-
EL/SEN
and 0 U
VAL
matics)
Fig. 2/3: Separate power supply for CPX-CP interface and MPA pneumatics (example)
2-18
Festo P.BE-CPX-CP-EN en 1211b
2. Installation
2.4 Complying with protection class IP65/IP67
Note
To comply with protection class IP65/IP67:
• Seal unused CPI/CP connections and the Save key with the appropriate protective caps.
If CPI/CP connections are not used, seal them with a protec­tive cap, type FLANSCHDOSE, S712 (included in delivery). You will then comply with protection class IP65/IP67.
Festo P.BE-CPX-CP-EN en 1211b
2-19
2. Installation
2-20
Festo P.BE-CPX-CP-EN en 1211b
Commissioning
Chapter 3
Commissioning
Festo P.BE-CPX-CP-EN en 1211b
3-1
3. Commissioning
Contents
3. Commissioning 3-1................................................
3.1 Procedure for commissioning 3-3.....................................
3.2 Prepare the CPI system for commissioning 3-4..........................
3.2.1 Checking the CP strings 3-4..................................
3.2.2 Saving the string assignment 3-5..............................
3.3 Switching-on reaction of the CPI system 3-8.............................
3.4 Reaction of the CPI system to faults in operation 3-10......................
3.4.1 Eliminating assignment faults 3-10..............................
3.4.2 Replacing CPI/CP modules 3-11................................
3.4.3 Replacing CPI/CP modules during operation 3-12.................
3.5 Notes on operation 3-15..............................................
3.5.1 Factory default mark from version 22 3-16.......................
3.6 Parametrizing 3-17..................................................
3.7 Commissioning functions with the handheld 3-27.........................
3.7.1 Menu commands of the CPX-CP interface on the Handheld 3-28......
3.7.2 Representation of the CPI/CP modules 3-29......................
3.7.3 Displaying the string assignment 3-30...........................
3.7.4 Observing signal states (monitoring) 3-31........................
3.7.5 Parametrizing with the Handheld 3-33...........................
3-2
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.1 Procedure for commissioning
In order to avoid connecting and addressing errors, you should carry out commissioning in steps as follows. Proceed as follows:
1. Check the CP strings (section 3.2.1).
2. Save the string assignment of the CPI system (section 3.2.2).
3. Check the saved string assignment (sections 3.3 and 3.4)
4. If required: Parameterise the CPX-CP interface and CPI modules ( section 3.6).
5. Check the address assignment (if necessary, without any connected actuators by LED) Description for the CPX fieldbus node or CPX-FEC.
6. Commission the total system Description for the CPX fieldbus node or CPX-FEC.
Festo P.BE-CPX-CP-EN en 1211b
3-3
3. Commissioning
3.2 Prepare the CPI system for commissioning
Note
Do not yet connect the CPX terminal to a higher-order controller for preparing commissioning.
You will thus avoid addressing faults which may occur in various field bus systems when address ranges are modified during operation.
3.2.1 Checking the CP strings
Preparations Before commissioning a CPX terminal with CPX-CP interface,
you should first prepare each individual CPI system for com­missioning.
Proceedasfollows:
1. Check the pneumatic tubing connections of the connected CP valve terminals with the help of the manual override (pneumatics description).
2. Check the complete electric circuitry of the CP system.
3. Save the current string assignment of th e CPI system as the set assignment, as described in section 3.2.2.
3-4
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.2.2 Saving the string assignment
Warning
Undesired modification of input and output addresses. Be very careful if the string assignment of your CPI system
is modified at a later stage:
• After saving the string assignment, check the address assignments of your CPI system before starting user programs.
You can thereby avoid: – addressing faults with incorrectly fitted CPI modules.
String allocation The CPX-CP interface saves the type and sequence of the
connected CPI modules for every string (chapter 1). This is also termed string assignment.
The saved string assignment allows the CPX-CP interface to avoid errors in connecting, and thus addressing errors. It checks automatically to see if the current string assignment is the same as the saved assignment. A distinction is made here between the following test phases:
Testing during the start-up phase (section 3.3)
Testing during operation (section 3.4).
After the switch on procedure, the status LEDs indicate the operating status and correct function of the bus node and the fieldbus communication. If the status LEDs on all the CPI/CP modules light up, the CPI system is prepared for configuration. You can find out which indicator displays the normal operat­ing status in the user documentation of the respective CPI module. Different procedures are necessary for configuration of the various fieldbus nodes or the FEC.
Festo P.BE-CPX-CP-EN en 1211b
Explanations on this can be found in the manual for the CPX field bus node or the CPX-FEC.
3-5
3. Commissioning
Saving the string assignment
The desired string assignment is generated and saved for commissioning. In this way the appropriate addresses are assigned to the connected CPI modules.
Save the string assignments as follows:
1. Leave the power supply of the CPX terminal switched off for the time being.
2. Check that each of the CPI/CP modules is connected to the string which provides the address range intended (chapter 1).
3. Check that the CPI cables are fastened properly with the union nut.
4. Switch on the power supply of the CPX terminal and, if necessary, of the CPI/CP modules with load voltage con­nection. On the CPX-CP interface, the LEDs of strings (L1 ... L4), to which CP modules have been connected or for which the string assignment has been modified, will flash.
5. Use a small screwdriver or similar to press the Save key for at least 1 s (section 2.1). This will save the current string assignment as the target string assignment in the CPX-CP interface. The LEDs of strings (L1 ... L4), with which the connected CPI/CP modules have been recognised, no longer flash. ThestatusLEDsofalltherecognizedCPI/CPmodules light up. Wait some seconds before continuing with the next step.
6. Switch off the power supply for the CPX terminal. Wait some seconds. Then switch it back on again. The current string assignment is now available in the fieldbus node or the CPX-FEC.
7. Depending on the CPX field bus node or CPX-FEC being used, the modified address range of the CPX-CP interface must be accepted:
3-6
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
CPX field bus node / CPX-FEC
CPX fieldbus node or CPX-FEC with operating mode Remote I/O
CPX-FEC with Stand Alone or Remote Controller operating mode
How to accept the address range
System parameter “System start” [System start]:
“System start with default p arameterisation and up-to-date CPX expansion” [default parameters], (factory setting): – The revised address range of the CPX-CP interface is automatic-
ally accepted.
“System start with saved param eterisation and saved CPX expan­sion” [saved parameters]:
1. Change “System start ...” system parameter to “... default parameterisation ...” .
2. Switch off the power supply of the CPX terminal then switch it on again. The address range of the CPX-CP interface will then be accepted.
3. If necessary, you can restore the desired parameterisation.
To accept the address range of the CPX-CP interface, you must save the actual configuration as the set configuration (actual­setpoint comparison). Information on this can be found in the manual for the CPX-FEC or software package FST 4.1.
Tab. 3/1: Saving the string assignment and accepting the address range
Note
After saving the string assignment, check the address assignments of your CPI system before starting user programs.
Festo P.BE-CPX-CP-EN en 1211b
3-7
3. Commissioning
3.3 Switching-on reaction of the CPI system
When the power supply is switched on, the CPX-CP interface ascertains automatically the current string assignment. It ascertains one after the other which CPI modules are con­nected to the relevant string.
If the current assignment is the same as the saved assign­ment, the CPX-CP interface will switch automatically to the ready status. The RN LED of the CPX-CP interface as well as the status LEDs on the connected CPI/CP modules light up (Fig. 3/1).
If the current assignment is not the same as the saved as­signment, the string LEDs (L1 ... L4) of the relevant string will flash on the CPX-CP interface. In this case the CPI system is not ready to operate.
You then have the following possibilities of restoring the readiness to operate:
Eliminate assignment errors manually or replace
individual CPI modules (section 3.4)
Save the current assignment as the set assignment
(section 3.2.2).
Detailed notes on diagnosing the CPX-CP interface using the LEDs can be found in section 4.2.
3-8
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
Switch on power supply
“CP configuration er­ror”; error LED flashes; string LED on
String 1 ... 4: Record module types
No
Save key pressed?
Ye s
Save string allocation
No
ment saved?
String allocation?
“CP configuration error”; error LED flashes; string LEDs on
String assign-
Yes
String 1 ... 4: Record module types
No
Module types:
Set = Actual?
Yes
“CP configuration error”; error LED flashes; string LEDs off
Switch power supply on/off
Initial start-up Modification/extension Normal operation
Fig. 3/1: Switching-on reaction of the CPI system
Festo P.BE-CPX-CP-EN en 1211b
CPI system ready to operate (permanent I/O update)
3-9
3. Commissioning
3.4 Reaction of the CPI system to faults in operation
If there is a fault on a CP string during operation, e.g. by cable fracture etc., this will be indicated by the relevant string LED (L1 ... L4) flashing or lighting up. on the CPX-CP interface. The status LED on the relevant module goes out. All modules working without faults remain ready to operate.
Detailed notes on diagnosing the CPX-CP interface using the LEDs can be found in section 4.2.
3.4.1 Eliminating assignment faults
In order to eliminate assignment or connection faults of the CP system:
1. Switch off the power supply for the CPX terminal.
2. Restore the saved assignment by connecting the appropriate CPI/CP modules with the CXP-CP interface again.
3. Switch on the power supply for the CPX term inal again.
3-10
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.4.2 Replacing CPI/CP modules
Replacement possibilities Only one defective CPI/CP module can be replaced with a
CPI/CP module of the sa me type without the need to save the string assignment again.
Note
Replacing a CPI/CP module with a CPI/CP module of a dif­ferent type or replacing several CPI/CP modules will re­quire a new commissioning and new saving of the string assignment (section 3.2).
In order to replace a single CP module, proceed as follows:
1. Stop the process controller P LC/Master
2. Switch off the power supply for the CPX terminal.
3. In the case of CPI/CP output modules and CP valve terminals on the CP string concerned: Switch off the following sources of energy: – the compressed air supply for the CP valve terminal – the o perating voltage supply for the CPI/CP output
module.
4. Disconnect all connecting cables and, if necessary, also the tubing.
5. Connect all connecting cables and, if necessary, the tubing with the identically constructed new module.
6. Now connect the new module ofthesametypeto the same string.
Festo P.BE-CPX-CP-EN en 1211b
7. In the case of CPI/CP output modules and CP valve terminals: Switch on the operating voltage supply or the compressed air supply again.
8. Switch on the power supply for the CPX term inal again.
9. Check the addresses of the CPI system.
3-11
3. Commissioning
3.4.3 Replacing CPI/CP modules during operation
In special cases, a single CPI/CP module can be replace d during operation with a CPI module of the same type.
In rare cases, the replacement can produce a short circuit report for the string. Restart the system if there is a short circuit report.
Warning
Undesired modification of I/O states.
• Check whether the design of your machine/system permits replacement of modules during operation.
Warning
Undesired modification of input and output addresses. Be very careful if the string assignment of your CPI system
is modified at a later stage:
• Make sure that modules are not sepa rated from a string and subsequently connected to another string during operation. Use the identification labels (type IBS 6x10 or IBS9x20) in order to identify modules clearly.
You can thereby avoid: – modified input and output addresses of the modules.
The CPX-CP interface will recognise replacement with a differ­ent type of module (e.g., O module replaced with a valve ter­minal or CP-E16-M8 replaced with CP-E16-M12x2) as a string assignment fault. In this case, therefore, readiness to operate is not restored to the relevant module during operation.
Recommendation: When replacing CPI/CP modules, always switch off the power supply if possible (section 3.4.2).
3-12
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
If the design of your machine/system makes it necessary to replace a CPI/CP module during operation, you should proceed as follows:
1. In the case of CPI/CP output modules and CP valve terminals on the CP string concerned: Switch off the following sources of energy where applicable: – the compressed air supply to the valve terminal – the o perating voltage supply to the output module.
2. Disconnect all connecting cables and, if necessary, also the tubing.
3. Connect all connecting cables and, if necessary, the tubing with the identically constructed new module.
4. Now connect the new module ofthesametypeto the same string.
5. In the case of CPI/CP output modules and CP valve terminals: Switch on the operating voltage supply or the compressed air supply again.
You can thus restore the defective connection during operation, or replace the defective module without impairing operation of the modules in the other strings. When the connection is restored again or replaced, the readiness to operate will be taken up with the appropriate module automatically.
Festo P.BE-CPX-CP-EN en 1211b
3-13
3. Commissioning
Restriction in recognising the string assignment
Specific modifications to the string assignment cannot be recognised during operation:
CPI/CP modules or entire strings which are connected to
the previously unassigned string 2 instead of string 1 or vice versa. This also applies to strings 3 and 4, respect­ively.
However, these modules will retain their previous addresses until the power supply is switched off and then on again.
Note
Modifications to the string assignment will be recognised reliably after the power has been switched on.
Recommendation:
• If possible, switch the power supply off and t hen on again after performing conversion work on the CP strings, provided that your system permits this.
Note
After saving the string assignment, check the address assignments of your CPI system before starting user programs.
You can thereby avoid:
addressing faults with incorrectly fitted CPI/CP modules.
3-14
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.5 Notes on operation
Warning
Undesired activation of actuators! An incorrect status of the valves and outputs can lead to
dangerous situations.
• M ake sure that valves and outputs are put into a safe state when faults occur.
Note
Please note the following if the outputs of a valve terminal are reset after master stop, field bus interruption or fault:
– Single-solenoid valves move to the basic position. – Double-solenoid valves remain in the current position. – Mid-position valves move to the mid-position (depend-
ing on valve type: pressurized, exhausted or blocked).
Warning
Undesired modification of input and output addresses. Be very careful if the string assignment of your CPI system
is modified at a later stage:
• Make sure that modules are not separated from one string and accidentally connected to another. Use the identification labels (type IBS 6x10 or IBS9x20) in order to identify modules clearly.
• After saving the string assignment, check the address assignments of your CPI system before starting user programs.
You can thereby avoid: – modified input and output addresses of the modules.
Festo P.BE-CPX-CP-EN en 1211b
3-15
3. Commissioning
3.5.1 Factory default mark from version 22
Note
If defective data segments are discovered on an EEPROM during switch on, they are overwritten with default values. The CPI will then cancel the switch-on procedure and dis­play the error through the LEDs. (chapter 4.2) The error number 205 is returned via the C-bus.
3-16
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.6 Parametrizing
The reaction of the CPI system with the CPX-CP interface can be parametrized.
Module parameter (Tab. 3/2):
Activates or deactivates error monitoring for the total CPX-CP interface (overview).
Channel-specific module parameters (Tab. 3/3):
Activates or deactivates error monitoring for individual CPI modules.
Further information on parametrizing can be found in the system manual and in the manual for the CPX field bus node or the CPX-FEC.
Function number
4828 + m * 64 + 0 Monitoring CPX module – CPX-CP interface
4828 + m * 64 + 6 Monitoring CPX module – CPX-CP interface and CPI modules
1)
m = module number (counting from left to right, beginning with 0)
1)
Module parameter – CPX-CP interface and CPI/CP modules
Tab. 3/2: Overview – module parameters
Function number
4828 + m * 64 + 8 ... 11 Monitoring CPI module string 1, module 0 ... 3
4828 + m * 64 + 12 ... 15 Monitoring CPI module string 2, module 0 ... 3
4828 + m * 64 + 16 ... 19 Monitoring CPI module string 3, module 0 ... 3
4828 + m * 64 + 20 ... 23 Monitoring CPI module string 4, module 0 ... 3
2)
2)
2)
1)
Channel-specific module parameters – CPI/CP modules
Fail safe channel x
Idle mode channel x
Force channel x
1)
m = module number (counting from left to right, beginning with 0)
2)
Access is protocol-specific (description of fieldbus node or FEC)
Tab. 3/3: Overview – channel-specific module parameters (specific to strings and/or
modules)
Festo P.BE-CPX-CP-EN en 1211b
3-17
3. Commissioning
Parameter assignment
Parametrisation of the CPX-CP interface applies only to cer­tain CPI/CP modules. An overview shows Tab. 3/4.
CPI module type
Parameter SCS SCO CP diag. Vout Vval Vsen Vsen, Vout, Vval SCS; SCO
Bit no. 0 1 0 1 2 3 4 0 1
Valve terminals
CPV..-GE-FB-... CPA..-… MPA-…
CP input modules
CP-E16-M8 (-Z) CP-E16N-M8 CP-E16-12-5-POL CP-E16N-M12 CP-E16-KL-IP20
CP output modules
CP-A08-M12-5-POL CP-A08N-M12
CPX-CP module parameter (CPX-CP interface / CPI/CP modules)
Par. byte 0 Fig. 3/2
-
­x
-
-
-
-
-
-
-
-
­x
-
-
-
-
-
x x
Parameter byte 6 Fig. 3/3
x x x
x x x x x
x x
x
-
x
-
x
x
x
-
x
-
x
-
x
-
x
-
x
x
x
x
x x x
-
-
-
-
-
-
-
Channel-specific param. (CPI/CP modules)
Parameter byte 8 ... 23 Fig. 3/4
-
­x
x x x x x
-
-
x x x
x x x x x
x x
-
­x
-
-
-
-
-
x x
CL input modules
CP-E08-M12-CL CP-E08-M8-CL CP-E08-KL-CL
CL output module
CP-A04-M12-CL
EL input modules
CP-E16-M12-EL CP-E16-M8-EL CP-E32-M8-EL
EL output module
CP-A08-M12-EL-Z
x x x
- x x x x - - x x
- - x x - - x - x
- x x x x - - x x
-
-
-
Tab. 3/4: Module-related paramete r assignment
3-18
x x x
x
-
x
-
x
-
-
-
-
x x x
x x x
Festo P.BE-CPX-CP-EN en 1211b
x x x
3. Commissioning
Fig. 3/2: Parameterisation byte 0
Festo P.BE-CPX-CP-EN en 1211b
3-19
3. Commissioning
Fig. 3/3: Parameterisation byte 6
3-20
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
Fig. 3/4: Parameterisation bytes 8 … 32
Festo P.BE-CPX-CP-EN en 1211b
3-21
3. Commissioning
Description of the module parameters
Module parameters: Monitoring CPX mo dule – CPX-CP interface
Function no. 4828 + m * 64 + 0 m = module n umber (0 ... 47)
Description Monitoring of the possible faults can be activated or deactivated (suppressed)
for each module independently. Active monitoring causes the following: The fault is:
sent to the CPX field bus node
displayed by the module common error LED.
Monitoring
Bit
Description
0
Short circuit/overload in sensor supply (SCS)
1
Short circuit/overload at the outputs (SCO)
Values 1 = active (presetting)
0=inactive
Remark Monitoring can also be set for the complete CPX terminal
(see “System parameter monitoring”).
Note Monitoring can also be set for the complete CPX terminal (system parameter
monitoring).
1)
Only effective for CPI modules with extended functions
2)
Must be active at the CPX-CP if a connected module is also active
1) 2)
2)
[Monitor]
[Monitor SCS] [Monitor SCO]
[Active] [Inactive]
Tab. 3/5: Monitoring CPX module – CPX-CP interface
Module parameter: monitoring CPX module – CPX-CP interface
Function no. 4828 + m * 64 + 6 m = module n umber (0 ... 47)
Description Tab. 3/5
Monitoring Description
Bit
0
CP communication fault (fault 34, 36)
1
CP configuration fault (fault 35)
2
CPI/CP modules Load supply for outputs Vout
3
CPI/CP modules Load supply for valves Vval
4
CPI/CP modules Load supply for sensors Vsen
[Monitor]
[Monitor CAN comm.] [Monitor config] [Monitor Vout] [Monitor Vval] [Monitor Vsen]
Values 1 = active (presetting)
0=inactive
Note Tab. 3/5
Tab. 3/6: Monitoring CPX module – CPX-CP interface and CPI/CP modules
3-22
[Active] [Inactive]
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
Description of the channel-specific module parameters
The channel-specific module parameters are each perman­ently assigned to the individual CPI/CP modules on the CP strings Tab. 3/7).
String
Module x
1)
Function no. String Module x
1)
Function no.
L1 M0 8 4828 + m * 64 + 8 L3 M0 16 4828 + m * 64 + 16
L1 M1 9 4828 + m * 64 + 9 L3 M1 17 4828 + m * 64 + 17
L1 M2 10 4828 + m * 64 + 10 L3 M2 18 4828 + m * 64 + 18
L1 M3 11 4828 + m * 64 + 11 L3 M3 19 4828 + m * 64 + 19
L2 M0 12 4828 + m * 64 + 12 L4 M0 20 4828 + m * 64 + 20
L2 M1 13 4828 + m * 64 + 13 L4 M1 21 4828 + m * 64 + 21
L2 M2 14 4828 + m * 64 + 14 L4 M2 22 4828 + m * 64 + 22
L2 M3 15 4828 + m * 64 + 15 L4 M3 23 4828 + m * 64 + 23
1) x = Parameter byte in the function number,  Tab. 3/8
Tab. 3/7: Assignment of the channel-specific module parameters to the CPI/CP
modules
CPX-CP interface
Module 0
Module 1 Module 2 Module 3String
Parameter byte 0 Parameter byte 6
Fig. 3/5: Parameter assignment of the CPI system
Festo P.BE-CPX-CP-EN en 1211b
L1
L2
L3
L4
Module 0 [L1/M0]
Module 4 [L2/M0]
Parameter byte 12
Module 8 [L3/M0]
Parameter byte 16
Module 12 [L4/M0]
Parameter byte 20
Module 1 [L1/M1]
Parameter byte 9Parameter byte 8 Parameter byte 11
Module 5 [L2/M1]
Parameter byte 13
Module 9 [L3/M1]
Parameter byte 17
Module 13 [L4/M1]
Parameter byte 21
Module 2 [L1/M2]
Parameter byte 10
Module 6 [L2/M2]
Parameter byte 14 Parameter byte 15
Module 10 [L3/M2]
Parameter byte 18
Module 14 [L4/M2]
Parameter byte 22
Module 3 [L1/M3]
Module 7 [L2/M3]
Module 11 [L3/M3]
Parameter byte 19
Module 15 [L4/M3]
Parameter byte 23
3-23
3. Commissioning
Note
If you connect a module or valve t erminal to a string, the remaining address space of the string is reserved until you connect additional equipment. This also applies if the parameterisation of the connected device takes up less than 4 bytes.
Module parameters: Monitoring CPX mo dule – CPI/CP modules
Function no. 4828 + m * 64 + x m = module number (0 ... 47)
x = dependent on string no. and module no. of the CPI/CP module, Tab. 3/7
Description Monitoring of the possible faults can be activated or deactivated (suppressed) for
CP each module independently. Active monitoring causes the following: The fault is:
sent to the CPX field bus node
displayed by the module common error LED.
Monitoring
Bit
Description
0
Power failure/undervoltage for:
CPI/CP input modules (Vsen): Power failure (or short circuit) of the sensor supply for modules with additional supply
CPI/CP output modules (Vout): Power failure of the load supply for modules with additional supply
CP valve terminals (Vval): Power failure of the load supply of the valves
Short circuit/overload on:
1
CPI/CP output modules Output
Values 1 = active (presetting)
0=inactive
Note Monitoring can also be set for the total CPX terminal
(system parameter monitoring).
[Monitor ...]
[Monitor Vsen/Vout/Vval]
[Monitor SC]
[Active] [Inactive]
Tab. 3/8: Monitoring CPX module – CPI/CP modules
3-24
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
Module parameters: Fail safe channel x
Function no. These module parameters are accessed via protocol-specific functions
(description of fieldbus node).
Description Faultmodechannelx: Holdlaststate
Fault state (presetting)
Fault state channel x: Set output
Reset output (presetting)
Note With the aid of the so-called Fa il Sa fe par ameter isation, the signal status which
the outputs are to assume in the event of fieldbus communication errors can be specified (CPX system description).
Tab. 3/9: Fail safe channel x (channel-specific)
Module parameters: Idle mode channel x
Function no. These module parameters are accessed via protocol-specific functions
(description of fieldbus node).
Description Only relevant for certain field bus protocols
Idlemodechannelx: Holdlaststate
Idle state (presetting)
Idle state channel x: Set output
Reset output (presetting)
Note With the aid of the so-called Idle mode parameterisation, the signal status which
the outputs/valves are to assume when changing into the Idle state can be spe­cified (CPX system description). This parameter is not available with all fieldbus protocols.
Tab. 3/10: Idle mode channel x (channel-specific)
Festo P.BE-CPX-CP-EN en 1211b
3-25
3. Commissioning
Module parameters: Force channel x
Function no. These module parameters are accessed via protocol-specific functions
(description of fieldbus node).
Description Force mode of inputs channel x: Blocked (presetting)
Force state
Force state of inputs channel x: Set signal
Reset signal (presetting)
Force mode of outputs channel x: Blocked (presetting)
Force state
Force state of outputs channel x: Set signal
Reset signal (presetting)
Note The Force function permits the manipulation of signal statuses independent of
actual operating statuses (CPX system description).
Tab. 3/11: Force channel x (channel-specific)
3-26
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.7 Commissioning functions with the handheld
The universal Handheld type CPX-MMI-1 offers user-friendy and extended functions which will support you in commis­sioning the CPX-CP interface.
This section contains an overview of the specific commissioning functions for the CPX-CP interface.
General information on the representation,
sections 3.7.1 and 3.7.2
Display of the string assignment, section 3.7.3
Display of the signal statuses, section 3.7.4
Parameterisation, section 3.7.5
General information on operating the Handheld and on com­missioning the CPX terminal using the Handheld can be found
in the manual for the Handheld, type P.BE.CPX-MMI-1-... .
Festo P.BE-CPX-CP-EN en 1211b
3-27
3. Commissioning
3.7.1 Menu commands of the CPX-CP interface on the Handheld
Fig. 3/6 shows as an example the special menu structure for the CPX-CP interface. For reasons of clarity only the para­meter name is shown for the parameters.
System overview CPX terminal 0: ... Module ... 1: ... Module ... 2: CPI-CP interface 3: ... Module ... ...
2:CPI .
Monitoring/Forcing (M)
Diagnostics (D)
Parameters (P)
Fail safe (F) Idle mode (I) Moduledata(MD)
CP modules (C)
1
2
2:CPI:M .
L1/M0: V10
0........................7
O00..07
...
2:CPI:P . Monitor SCS: ... Monitor SCO: ... Monitor SCV: ... Monitor CAN comm.: ... Monitor config.: ... Monitor Vout: ... Monitor Vval: ... Monitor Vsen: ...
L1/M0: V10
Monitor Vsen/Vout/Vval: Monitor SC: ...
L1/M0: I16
Monitor Vsen/Vout/Vval: L2/M... ...
1
“Monitoring/Forcing” menu (also “Fail safe”, “Idle mode”), section 3.7.4
2
“Parameters” menu, section 3.7.5
3
“CP modules” menu, section 3.7.3
Fig. 3/6: Menus of the CPX-CP interface on the Handheld
3-28
3
2:CPI:C .
L1/M0: CPV10-GE-FB-...
L1/M0: CP-E16-M12 /..
L2/M1: ... ...
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
3.7.2 Representation of the CPI/CP modules
In the various menus of the handheld (section 3.7.1, Fig. 3/6) the CPI/CP modules on the CPX interface are dis­played with either a long name or a short name (Tab. 3/12 status at January 2012).
Long name / type
Valve terminals
CPV10-GE-FB-4, CPV10-GE-FB-6, CPV10-GE-FB-8 CPV14-GE-FB-4, CPV14-GE-F B-6, CPV14-GE-FB-8 CPV18-GE-FB-4, CPV18-GE-FB-6, CPV18-GE-FB-8 CPA10/14-IFB-CP MPA-CPI-VI
CP input modules
CP-E16-M8, CP-E16-M12x2 CP-E16-KL-IP20-Z, CP-E16-M12x2-Z, CP-E16-M8-Z CP-E16N-M8, CP-E16N-M12x2
CP output modules
CP-A8-M12 CP-A8N-M12
CL input modules
CP-E08-M8-CL, CP-E08-M12-CL CP-E16-KL-CL
CL output module
CP-A04-M12-CL
Short name
V10 V14 V18 V10/14 MPA-CPI
E16 E16Z E16N
A8 A8N
E08CL E16CL
A04CL
EL output modules
CP-E16-M12-EL, CP-E16-M8-EL CP-E32-M8-EL
EL output modules
CP-A08-M12-EL-Z
Tab. 3/12: Representation of the CPI/CP modules on the Handheld
Festo P.BE-CPX-CP-EN en 1211b
E16EL E32EL
A08EL
3-29
3. Commissioning
3.7.3 Displaying the string assignment
To display the string assignment currently recognised by the CPX-CP interface, in the module submenu of the CPX-CP inter­face (Fig. 3/6) select the entry for the CPI/CP modules [CP modules (C)] and confirm with OK.
______2:CPI:C_______
L1 /M0: CPV10-GE-FB> L1 /M 1 : CP-E16-M12 > L2/M0: CPV10-GE-FB> L4/M0: CPV10-GE-FB>
___________________ Back OK
______2:CPI:C_______ x L1 /M0: CPV10-GE-FB> x L1 /M 1 : CP-E16-M12 >
L2/M0: CPV10-GE-FB> L4/M0: CP-A8-M12
___________________ Back OK
______2:CPI:C_______
L1 /M0: CPV10-GE-FB> L1 /M 1 : CP-E16-M12 > L2/M0: CPV10-GE-FB>
! L4/M0: CP-A8-M12
All the CPI/CP modules of the recognised string assignment are now each displayed with string number (e.g. L1), module number on the string (e.g. M0) and their long name.
If no modules are recognised on the strings, the message “No CP modules” will be displayed.
The following CPI/CP modules are marked with “x”:
Modules recognised after the power supply has been
switched on but not included in the saved string assign­ment.
Modules contained in the saved string assignment but
no longer recognised. In this case the CPX-CP interface will report a configura­tion error.
Malfunctioning CPI/CP modules (modules reporting an er­ror, e.g. short circuit) are marked with “!”. Diagnostic in­formation about each of these modules can be displayed.
___________________ Back OK
3-30
Note
Always watch for error messages of the CPX-CP interface when the string assignment is displayed.
This will also provide you with information about CPI/CP modules that are not recognised.
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
1
3.7.4 Observing signal states (monitoring)
You can use the Handheld to observe the signal states of the connected (and recognised) CPI/CP modules.
To do this, select the entry [Monitoring/Forcing (M)] in the module submenu of the CPX-CP interface (Fig. 3/7).
2:CPI .
Monitoring/Forcing (M)
Diagnostics (D) Parameters (P) Fail safe (F) Idle mode (I) Moduledata(MD) CP modules (C)
1
Inputs and outputs of the first CPI/CP module
2
Inputs and outputs of further CPI/CP modules
O00..07 O08..15
I00..07
O00..07 O08..15
2:CPI:M .
L1/M0: V10
0........................7
L1/M1: E08CL
0........................7
L2/M0: V12
0........................7
...
Fig. 3/7: Module submenu – Observing the signal states of all CPI/CP modules
When you select one of the modules in the menu of the CPI/ CP modules and confirm with OK, a further module submenu is displayed.
2
___2:CPI(L1/M0):V10___ Monitoring/Forcing (M) Diagnostics (D) Parameters (P) Fail safe (F) Idle mode (I) ___________________ Back OK
Festo P.BE-CPX-CP-EN en 1211b
All the special entries for the CPI/CP module selected are available in this module submenu.
The display and function correspond basically to the module submenu for normal CPX modules.
In order to display the signal status for the selected CPI/ CP module, in the relevant module submenu select the entry [Monitoring/Forcing (M)] Fig. 3/8.
3-31
3. Commissioning
2:CPI:C .
L1/M0: CPV10-GE-FB-.. L1/M0: CP-E16-M12/. L2/M1: ...
...
1
Inputs and outputs of the selected CPI module
2:CPI(L1/M0):V10 .
Monitoring/Forcing (M)
Diagnostics (D) Parameters (P) Fail safe (F) ...
2:CPI(L1/M0):V10:M .
L1/M0: V10
0........................7
O00..07 O00..07
Fig. 3/8: Module submenu – Observing the signal states of a specific CPI/CP module
“Forcing”, “Idle mode” and “Fail safe”
Warning
The actuators connected can move unexpectedly. Modification to the signal states and parameters with the
Handheld can trigger dangerous movements of the con­nected actuators.
• Make sure that nobody is in the positioning range of the connected actuators and be very careful with the parametrizing and manipulation of signal states.
1
• It is imperative that you observe the notes on Forcing, Idle mode and Fail safe in the CPX system manual and in the manual for the Handheld.
You can also call up the “Forcing” function via the “Monitor­ing ...” menu. This function allows you to force signal statuses during the commissioning phase for test purposes.
The same representation of the CPI/CP modules applies accordingly to the functions “Idle mode” and “Fail safe”.
3-32
Festo P.BE-CPX-CP-EN en 1211b
3. Commissioning
1
3.7.5 Parametrizing with the Handheld
For test purposes in the commissioning phase, for troubleshooting or for fieldbus protocols which do not sup­port parameterisation via the fieldbus, you can use the Hand­held for parameterisation (Fig. 3/9 and Fig. 3/10).
Warning
The actuators connected can move unexpectedly. Modification to the signal states and parameters with the
Handheld can trigger dangerous movements of the con­nected actuators.
2:CPI . Monitoring/Forcing ( M) Diagnostics (D)
Parameters (P)
Fail safe (F) Idle mode (I) Moduledata(MD) CP modules (C)
• Make sure that nobody is in the positioning range of the connected actuators and be very careful with the parametrizing and manipulation of signal states.
• It is imperative that you observe the notes on parame­trizing in the CPX system manual and in the manual for the Handheld.
2:CPI:P . Monitor SCS: ... Monitor SCO: ... Monitor SCV: ... Monitor CAN comm.: ... Monitor config.: ... Monitor Vout: ... Monitor Vval: ... Monitor Vsen: ...
L1/M0: V10
Monitor Vsen/Vout/Vval: Monitor SC: ...
L1/M0: I16
Monitor Vsen/Vout/Vval: L2/M... ...
2
1
Module parameters (CPX-CP interface)
2
Parameters of the individual CPI/CP modules (channel-specific module parameters)
Fig. 3/9: Module submenu – Parameterisation in the “Parameters” menu
Festo P.BE-CPX-CP-EN en 1211b
3-33
3. Commissioning
2:CPI:C .
L1/M0: CPV10-GE-FB-... L1/M0: CP-E16-M12 /.. L2/M1: ...
...
1
Parameters of the CPI/CP modules selected (channel-specific module parameters)
2:CPI(L1/M0):V10 . Monitoring/Forcing ( M) Diagnostics (D)
Parameters (P)
Fail safe (F) ...
2:CPI(L1/M0):V10 .
Monitor Vsen/Vout/Vval: Monitor SC: ...
Fig. 3/10: Module submenu – Channel-specific parametrizing
1
3-34
Festo P.BE-CPX-CP-EN en 1211b
Diagnosis and error treatment
Chapter 4
Diagnosis and error treatment
Festo P.BE-CPX-CP-EN en 1211b
4-1
4. Diagnosis and error treatment
Contents
4. Diagnosis and error treatment 4-1....................................
4.1 Overview of diagnostic possibilities 4-3................................
4.2 Diagnosis via LEDs 4-4..............................................
4.2.1 Normal operating status 4-6..................................
4.2.2 CPI system-specific LEDs 4-7..................................
4.2.3 CP string-specific LEDs 4-9...................................
4.3 Error messages of the CPX-CP interface 4-12.............................
4.4 Diagnostics via the CPX-FEC or CPX bus node 4-16........................
4.4.1 Status bits of the CPX terminal 4-16.............................
4.4.2 I/O diagnostic interface and diagnostic memory 4-17..............
4.5 Diagnostic functions with the Handheld 4-21.............................
4.6 Error handling and parameterisation 4-22...............................
4-2
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
4.1 Overview of diagnostic possibilities
The CPX-CP interface supports the following diagnostic and error handling options in the CPX terminal (Tab. 4/1):
Diagnostic
Brief description Advantages Detailed
possibility
LED display The LEDs directly display config-
uration errors, hardware errors, bus errors, etc.
Error messages The CPX-CP interface reports spe-
cific malfunctions as error mes­sages (error numbers) to the CPX bus node or CPX-FEC.
Status bits, I/O diagnostic inter­face and specific diagnostic func­tions
Diagnostics via the Handheld
The errors recognised by the CPX­CP interface are reported in some cases to the CPX bus node or CPX­FEC wit h spe cial additional in­formation.
Diagnostic information can be shownontheCPXHandheldina user-friendly and menu-driven manner.
Fast “on-site” error de­tection
The error messages can be evaluated via the CPX bus node or CPX-FEC as well as with the Handheld
Fast access to error messages via the field­bus, etc.
Fast “on-site” error de­tection
description
Section 4.2
Section 4.3 and CPX system de­scription
Section 4.4, CPX system descrip­tion and descrip­tion for the CPX bus node or CPX­FEC
Section 4.5 and description for the Handheld
Tab. 4/1: Diagnostics options of the CPX-CP interface
Festo P.BE-CPX-CP-EN en 1211b
Note
Observe that the available diagnostic information may depend on the settings of the CPX bus node or CPX-FEC or on the parameterisation settings.
4-3
4. Diagnosis and error treatment
4.2 Diagnosis via LEDs
LEDs for diagnosing the CPX terminal are available on the CPX-CP interface as well as on the individual CPI/CP modules.
The meaning of the LEDs on the CPI/CP modules can be found in the manual for the relevant module.
LEDs on the CPX-CP interface
The LEDs on the cover indicate the operating status of the CPX-CP interface.
1
CPI system­specific LEDs: – PS (green) – PL (green) – RN (green)
X1
– Fault (red)
X2
2
CP string­specific LEDs:
X3
– L1 ... L4 (red)
X4
Fig. 4/1: LEDs on the CPX-CP interface
PS
L1
L2
PL
RN
L3
L4
L1
L2
L3
L4
L1
L2
L3
L4
PS
PL
RN
PS
PL
RN
1
2
4-4
An overview of the LED functions is shown in Tab. 4/2.
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
LED Description
PS Power sensors Lights up if the sensor power supply
PL Power load Lights up if the load power supply on
RN Run Lights up if data exchange is running
on the CP string is correct. Flashes if there is a voltage fault.
1)
the CP string is correct for outputs and valves. Flashes if there is a voltage fault.
1)
on the CP strings.
Fault LED Flashes or lights up if there are faults
on the CPX-CP interface. The flash pulses indicat e the type of fault.
L1 ... L4 String fault Flashes o r lights up if there are faults
on the assigned CP string. The flash pulses indicat e the location of the fault on the CP string.
1)
The power supplies are monitored by the CPI/CP modules
Tab. 4/2: Function overview of the LEDs on the CPX-CP
interface
Festo P.BE-CPX-CP-EN en 1211b
4-5
4. Diagnosis and error treatment
4.2.1 Normal operating status
In the normal operating status all green LEDs light up. The red LEDs do not light up.
LED display
All green LEDs light up:
PS
L1
L2
L3
L4
PS
PL
RN
PL
RN
The red LEDs do not light up:
Fault
L1 ... L4
Tab. 4/3: LED display – normal operating status
Operating status
Standard
4-6
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
4.2.2 CPI system-specific LEDs
PS (power system) – power sensor supply of CPI/CP modules
LED (green) Sequence Status Fault number Fault treatment
ON
OFF
No fault. Sensor power supply applied
LED lights up
ON
OFF
LED flashes
Short circuit/undervoltage in the sensor supply of a CPI/CP input module
2 5
Error numbers in section 4.3, Tab. 4/6
PL (Power l oad) – power load supply for CPI/CP modules
LED (green) Sequence Status Fault number Fault treatment
ON
OFF
LED lights up
ON
OFF
LED flashes
No fault. Load voltage applied
Undervoltage in the load supply of a CPI/CP module with additional power sup­ply
None
5 Error numbers in
section 4.3, Tab. 4/6
RN (Run) – CPI/CP communication active
LED (green) Sequence Status Fault number Fault treatment
ON
OFF
LED lights up
ON
OFF
LED not illu­minated
Festo P.BE-CPX-CP-EN en 1211b
No error Communication OK Saved string assignment corresponds to the recog­nised string assignment
Malfunction in the CPI sys­tem – Communication error – Configuration error – String assignment error
None
Error numbers in
36
section 4.3, Tab. 4/6 34, 35 34, 35
4-7
4. Diagnosis and error treatment
(Fault) – CPI system fault (location of the fault)
LED (red) Sequence Status Fault
number
ON
OFF
No fault.
LED is out
LED flashes
ON
OFF
ON
OFF
Malfunction in the CPI/CP communication
Short c ircuit/overload
Undervoltage
34
2 5
On one CP string or one CPI/CP module:
34 35 36
34 35 36
ON
OFF
Module missing / faulty
CP configuration fault
Short circuit in CP string
On several CP strings or several CPI/CP modules:
Module missing / faulty
CP configuration fault
Short circuit in CP string
Fault treatment
Error numbers in section 4.3, Tab. 4/6
LED illuminated
ON
OFF
ON
OFF
ON
OFF
Recognised string assign-
35
ment does not correspond to saved string assign­ment; Save key was not pressed
String assignment cannot
35
be saved (configuration not capable of being saved)
Unkown fault 255
Internal CPX communication –Switchonphase – C-bus error
– 131
Switch power supply off then on again, replace module if necessary
None. CPX system de­scription
4-8
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
4.2.3 CP string-specific LEDs
L1 ... L4 – CP string fault (type of fault)
LED (red) Sequence Status Fault
number
LED is out
ON
OFF
No fault
or
Save key pressed after
string assignment was modified
LED flashes
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Error on module of the rel­evant assigned string L1, L2, L3 or L4:
1)
Fault on module 0
Fault on module 1
Fault on module 2
Fault on module 3
2, 5, 34, 35
2, 5, 34, 35
Fault treatment
Switch power
supply off then on
again, replace
module if necessary
assigned error
numbers in section
4.3, Tab. 4/6
ON
OFF
ON
OFF
LED illuminated
1)
If there are faults on several modules, the lowest module number in each case is shown.
Festo P.BE-CPX-CP-EN en 1211b
During operation: – Revised string assign-
ment, e.g. due to an ad­ditional module connec­ted (at least 2 LEDs flash
– L1+L2 and/or L3+L4). After switching on: – Invalid string assign-
ment (only the LEDs of
the CP strings concerned
flash).
Short c ircuit on the re­levent assigned CP string
35
Check string
assignment. If necessary, save the new string assignment, Section 3.2.2.
Check and correct
the string assign­ment, Section
1.2.
36 Section 4.3,
Tab. 4/6
4-9
4. Diagnosis and error treatment
4.2.4 Special system error (starting with software version Rev. 22)
These special system errors occur in very rare cases. The CP interface has detected an error that requires a software stop. The error is displayed through flashing of all CPI-specific LEDs (PS, PL, RN, P). In addition, an error message is shown en­coded through flashing of the LEDs L1 … L4 (Tab. 4/4 and Tab. 4/5).
In the event of error, restart the CPX terminal with POWER OFF/ON and observe the instructions in the tables Tab. 4/4 and Tab. 4/5. If the error still exists: service matter.
Special system errors
LED (red) Status/error handling LED (red) Status/e rror handling
1
2
L1, L2
flash
L2, L3
flash
Malfunction of communication on one CP string.
Error handling:
Check CP c ables for damage
Check earthing of the CPI/CP
system (EMC load)
Time-out when reading from EE­PROM.
Error handling:
S ave the string assignment
again with the SAVE button (3.2.2)
3
L1, L2, L3
flash
4
L4
flashing
Time-out when writing from EE­PROM.
Error handling:
S ave the string assignment
again with the SAVE button (3.2.2)
Unstable clock signal detected.
Error handling:
Restart system
Servicing required
Tab. 4/4: Special system errors - Part 1
4-10
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
Special system errors
LED (red) Status/error handling LED (red) Status/error handling
5
L1, L4
6
L1, L2, L4
7
flash
flash
Critical timeouts in internal tim­ing. Possibly to high bus load or external diagnostic requests, or similar
Error handling:
Restart system
Reduce bus load, if neces-
sary
Incorrect access lower bound­ary data exchange buffer.
Error handling:
Restart system
Incorrect access upper bound­ary data exchange buffer.
8
L1, L3, L4
flash
9
L1, L2, L3, L4
flash
EEPROM defective.
Error handling:
Restart system; if successful,
save the string assignment again with the SAVE button (3.2.2)
Servicing required
Undefined error message.
Error handling:
Restart system
Servicing required
Error handling:
Restart system
L1, L2
flash
Tab. 4/5: Special system errors – Part 2
Festo P.BE-CPX-CP-EN en 1211b
4-11
4. Diagnosis and error treatment
4.3 Error messages of the CPX-CP interface
A CPX-CP interface can report the following errors (Tab. 4/6 and Tab. 4/7):
Error
Description Error handling
number
2 Short circuit/overload
(Handheld: [Short circuit] ) – Short circuit/overload at output
or
– Short circuit/overload, sensor supply
(only for I/O modules with extended func­tions)
5 Undervoltage in the power supply
(Handheld: [Undervoltage in power supply] ) – Load voltage of the valves (U
or too low.
or
– Load voltage supply (Vout) not applied or too
low (only for CPI/CP output modules with a separate power supply)
or
– Power supply of the CPI/CP modules (Vsen/
Vout/Vval) via the CP string not applied or too low (only for CPI/CP modules without a separ­ate power supply)
or
– Short circuit/overload, sensor supply
(only for CP input modules without extended functions)
VAL
) not applied
Check the connected actuators,
eliminate short circuit/overload and delete errors
Check the connected sensors,
1)
eliminate short circuit/overload and delete errors, if necessary
Check the load voltage
Check the load voltage
Check the load voltage,
Check CPI/CP cables
Eliminate short circuit/overload,
check connected sensors, delete errors, if necessary
2)
2)
1)
Dependent on the CPI/ CP module: All the outputs of the module are switched off in the event of an error. The error must be deleted by resetting all the outputs.
2)
Dependent on the CPI/ CP module: The error is automatically deleted or must be deleted by discon­necting the module from t he CP string or by switching the power supply off then on again.
Tab. 4/6: Error messages of the CPX-CP interface - Part 1
4-12
Festo P.BE-CPX-CP-EN en 1211b
4. Diagnosis and error treatment
Error
Description Error handling
number
34 CPI/CP module missing / faulty
(Handheld: [CP module lost / fault] ) – Incorrect string assignment discovered during
operation (e.g. CPI/CP module failed or CPI/ CP cables defective)
– More than one module failed during operation
– modules are no longer recognised.
35 CP configuration error
(Handheld: [CP configuration failure] ) – When the power supply is switched on, the
string assignment does not match the saved string assignment
or
– The wrong module is rec ognised during opera-
tion (different type, chapter 3)
Check CP strings (CPI/CP modules
and cables), if necessary replace modules or cables
Switch power supply off then on
again, check cables and modules if error occurs repeatedly, replace if necessary
Check CP strings ( modules and
cables), if necessary replace mod­ules or cables
With correct string assignment:
String assignment must be saved (chapter 3)
Check string assignment, if neces-
sary replace module
36 Short circuit in CP string
(24 V
EL/SEN
(Handheld: [Short circuit CP-Line] ) – Communication on CP string malfunctioned
or 24 V
Val
)
Tab. 4/7: Error messages of the CPX-CP interface - Part 2
In addition, the following error can occur during the commis­sioning phase for the CPX bus node with the parameter “Sys­tem start” = “saved parameterisation and CPX system expan­sion” or with the CPX-FEC:
Check CP strings, if necessary re-
place cable
Festo P.BE-CPX-CP-EN en 1211b
4-13
4. Diagnosis and error treatment
Error
Description Error handling
number
16 Module code not permitted or incorrect module
(Handheld: [Module code incorrect] ) – The saved string assignment of the CPX-CP
interfaceisnotthesameastheconfiguration saved in the CPX bus node or in the CPX-FEC
205 NVRAM reset to default values
(Handheld: [Module set to default values]) – EEPROM has valid content, but no valid con-
figuration.
Tab. 4/8: Additional error message of the CPX terminal
Specific monitoring of the CPX-CP interface can be activated or deactivated by means of parameterisation. Parameterisation of the CPX-CP interface applies only to cer­tain CPI/CP modules. An overview shows Tab. 4/9 (status at January 2012).
For the CPX bus node:
Change parameter “System start ...” to “... default parameterisa­tion and current CPX expansion”
With the CPX-FEC:
Save the actual configuration as setpoint configuration with FST software
No need for action. This is inform-
ation and not an error
4-14
Festo P.BE-CPX-CP-EN en 1211b
Loading...