Ferroli TEMPRA 24 Installation, Service And User Instructions Manual

Appr. nr. B99.04 A - CE 0461 bl 0520
TEMPRA 24
INSTALLATION, SERVICE AND USER
INSTRUCTIONS
Copper Wall-Mounted System,
Gas Fired Boiler for Central Heating ,
Fan Assisted, Room Sealed Compartment,
cod. 3543821/1 - 03/2004
TEMPRA 24
2
CE MARK
CE mark documents that the Ferroli gas appliances comply with the requirement contained in European directives applicable to them.
In particular, the appliances comply with the following CEE directives and the technical specifications provided from them:
• Gas appliances directive 90/396
• Efficiencies directive 92/42
• Low tension directive 73/23 (modified from the 93/68)
• Electromagnetic compatibility directive 89/396 (modified from the 93/68)
IMPORTANT
Your "benchmark" Installation, Commissioning and Service Record Log Book will be enclosed in your customer information pack.
"This record must be completed and left with the end user" "All CORGI Registered Installers carry a CORGI ID card and have a registration number. Both
should be recorded in your central heating log book. You can check with the CORGI register by calling CORGI on 01256 372300".
Ferroli is a member of the Benchmark initiative and fully supports the aims of the programme. Benchmark has been introduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency. Please see installation and servicing guidelines.
INDEX
1. DESCRIPTION....................................................................................................................................................... 3
2. TECHNICAL AND DIMENSIONAL CHARACTERISTICS......................................................................................4
3. INSTALLATION DETAILS ...................................................................................................................................... 9
4. COMMISSIONING AND TESTING..................................................................................................................... 28
5. ADJUSTMENT AND GAS CONVERSION .......................................................................................................... 29
6. MAINTENANCE AND CLEANING .................................................................................................................... 31
7. REPLACEMENT OF PARTS................................................................................................................................. 33
8. FAULT FINDING.................................................................................................................................................. 37
9. ELECTRICAL AND FUNCTIONAL SCHEME ...................................................................................................... 39
10. USER INSTRUCTIONS ...................................................................................................................................... 41
TEMPRA 24
3
1. DESCRIPTION
1.01 Introduction
The Tempra 24 is defi ned as a “room sealed” boiler, all air required for combustion is taken from outside the room in which it is installed. It is a new high performance gas fi red heat generator for central heating. A special feature of this boiler is its built-in electronic fl ame ignition and control unit making burner operation completely automatic and safe. The main components are as follows:
• Copper heat exchanger consisting of four fi nned tubes specifi cally shaped for high effi ciency.
• Ceramic fi bre insulated combustion chamber
• 12 stainless steel bladed burners specifi cally designed for this boiler.
• Fan for discharge of combustion products and intake of combustion air.
• Differential air pressure switch. For safety reasons, this ensures the burner ignites only when the fan is functioning correctly.
• Hermetically sealed compartment made from corrosion-resistant steel enclosing the above components.
• Combination gas safety valve with modulator, complete with pressure stabiliser.
• Pressure relief valve for the central heating circuit set to open at 3 bar.
• Built-in Expansion vessel.
• Variable speed pump.
• Central heating fl ow temperature adjustment thermostat.
• Central heating limit thermostat.
• Overheat safety thermostat.
• Electronic control unit for automatic fl ame ignition and control.
• Central heating fl ow temperature sensor.
1.02 Instructions and regulations
Assembly, installation, fi rst start up and maintenance must be carried out by competent persons only, in accordance with all current technical regulations and directives.
c.o.s.h.h.
Materials used in the manufacture of this appliance are non hazardous and no special precautions are required when servicing. 3Related Documents
Related documents This appliance must be installed strictly in accordance with these instructions.
The Gas Safety Regulations (Installations & Use). The Local Building Regulations. The Building Regulations. The Buildings Standards (Scotland - Consolidated) Regulations. British Standards Codes of Practice:
B.S. 7593 TREATMENT OF WATER IN DOMESTIC HOT WATER CENTRAL HEATING SYSTEMS B.S. 5546 INSTALLATION OF HOT WATER SUPPLIES FOR DOMESTIC PURPOSES B.S. 5440 Part 1 FLUES B.S. 5440 Part 2 AIR SUPPLY B.S. 5449 FORCED CIRCULATION HOT WATER SYSTEMS B.S. 6798 INSTALLATION OF GAS FIRED HOT WATER BOILERS B.S. 6891 GAS INSTALLATIONS B.S. 7671 IEE WIRING REGULATIONS B.S. 4814 SPECIFICATION FOR EXPANSION VESSELS B.S. 5482 INSTALLATION OF LPG
Model Water Bye Laws For Northern Ireland the rules in force apply
TEMPRA 24
4
Fig. 1
2. TECHNICAL AND DIMENSIONAL CHARACTERISTICS
2.01 Technical information
Tempra 24 boilers are central heating generators and are produced as standard to function with natural gas or Liquid Petrolium Gas converted appliances.
98
15536 155
460
100 25 150
272
25 160
9836 155 114
760
706
965
175
190
155
70 120 120 150
110
Ø80Ø80 Ø80
114
3
2
1
Key
1. Central Heating flow
2. Gas supply
3. Central Heating return
TEMPRA 24
5
N.B. - The gas pressures at the burner and gas fl ows during the central heating phase given in the table refer to nominal boiler output. To reduce this output (where necessary), gas pressure must be reduced until the required output level is reached (see fi gures 4 and 5).
Maximum working temperature for central heating ow: 85°C
Technical Data
Gas supply
Pmax Pmin
Nominal Heat Input (Net)
Nominal Heat Output
Output
Pmax Pmin
kW 23,3 9,7
kW 25,8 11,2
Dimensions, weights, fittings
Depth mm 272
Width mm 460
Height mm 760
Hot water capacity litres 1,5
Expansion vessel pre-fill pressure bar 1
Expansion vessel capacity litres 8
Minimum central heating operating pressure bar 0,8
Maximum central heating operating pressure bar 3
Maximum central heating operating temperature °C90
Index of protection IP 44
Power supply
Power supply voltage/frequency V/Hz 230/50
Max Power Absorbed W 125
C.H. return (with isolation valve fitted)
mm 22
C.H. flow (with isolation valve fitted) mm 22
Gas system fittings (with isolation valve fitted) mm 22
Weight with packaging kg 35
Central heating
Natural gas rate (G20) nm3/h 2,73 1,19
Main injectors, Natural Gas (G20) mm 12 x 1.3
Burner pressure, Natural Gas (G20) mbar 11,8 2,5
Supply pressure, Natural Gas (G20) mbar 20,0
LPG gas rate (G31) kg/h 2,00 0,87
Main injectors, LPG (G31) mm 12 x 0.77
Burner pressure, LPG (G31) mbar 36,0 7,0
Supply pressure, LPG (G31) mbar 36,0
Safety valve bar 3
TEMPRA 24
6
2.03 Boiler water flow diagram
Fig. 3
2.02 Boiler main components
Fig. 2
+
-
43
49
50
56
81
44
32
20
82
5
29-187
16
10 7 11
14
34
Key 5 Room sealed compartment 7 Gas inlet 10 Central heating flow 11 Central heating return 14 Safety valve 16 Fan 19 Combustion chamber 20 Burner assembly 21 Main injector 22 Burner 26 Combustion chamber insulation 27 Copper heat exchanger 28 Flue collector from heat exchanger 29 Internal flue exit 32 Central heating pump 34 Central heating flow temperature sensor 36 Automatic air vent valve 43 Air pressure switch
44 Gas valve 49 Safety overheat thermostat 50 Central heating flow limit thermostat 56 Expansion vessel 62 Time clock (option) 63 Central heating temperature adjustment 81 Ignition electrode 82 Sensor electrode 84 Primary gas valve solenoid 85 Secondary gas valve solenoid 98 On/Off/Reset switch 145 Central heating pressure gauge 187 Flue restrictor
R ES
E T
O
FF
ON
0
5
1
2
3
4
6
bar
98 63 145
117 4485841410
34
20 21
22 82 81
49
28
5
29 187 43
56
16
27
50
19
26
36
32
62
°C
TEMPRA 24
7
2.04 Central heating adjustment (not normally required)
To adjust boiler heat input (thus also regulating heat output to the central heating water) simply adjust the main burner via the electronic control board (fi g. 4 and see paragraph 5.04). The diagrams indicate the variation in heat output to the water as burner working pressure is varied. Adjusting boiler output to the actual requirements of the central heating system will minimise boiler cycling thus saving fuel, varying the output has virtually no effect on the efficiency and combustion characteristics of the boiler.
Diagram of pressures and outputs with Natural gas and with LPG (Propane)
Fig. 4
kW kcal/h
X 1000
m
b
ar
18 19 20 21 22 23
5
10
15
20
25
30
35
9 1011121314151617
91011121314 18192015 16 178
G31
G20
TEMPRA 24
8
Fig. 6
Pressure loss diagram
SIZING OF ADDITIONAL EXPANSION VESSELS: Deduct from the value given in the table the 8 litre vessel supplied.
Note:
1. Fill C.H. installation to min. 1.5 bar.
2. Expansion vessel must be tted to central
heating return pipe.
3. The standard 7 litre expansion vessel is charged to 1 bar.
4. The additional expansion vessel should be charged to 1 bar.
SAFETY VALVE SETTING (bar)
VESSEL CHARGE PRESSURE (bar)
INITIAL SYSTEM PRESSURE (bar)
TOTAL WATER CONTENT of SYSTEM
3.0
0.5 1.0 1.5
1.0 1.5 2.0 1.5 2.0 2.0
EXPANSION VESSEL VOLUME (litres)
LITRES 25 3.5 6.5 13.7 4.7 10.3 8.3 50 7.0 12.9 27.5 9.5 20.6 16.5 75 10.5 19.4 41.3 14.2 30.9 24.8 100 14.0 25.9 55.1 19.0 41.2 33.1 125 17.5 32.4 68.9 23.7 51.5 41.3 150 21.0 38.8 82.6 28.5 61.8 49.6 175 24.5 45.3 96.4 33.2 72.1 57.9 200 28.0 51.8 110.2 38.0 82.4 66.2
0.140 0.259 0.551 0.190 0.412 0.33
For syst. volumes other than those given above, mult. the syst. volume by the factor across
m |h
3
Q
8
7
6
5
4
3
2
1
0
0.5 1.5 2.512
H
mbar x 100
2.05 Pump characteristics
The pump head available for circulating the water is given in fi g. 5.
N.B. - The pump is factory set at position 3. The pump is a Grundfos type 15-50 UPS series.
Grundfos Pump per formance graph Note - Minimum fl ow through boiler heat exchanger at any time should not fall below 6 litres per minute. If the total volume of water in the system exceeds 40 litres an additional expansion vessel must be fi tted to the central heating return pipe.
Fig. 5
1 2 3 Speed settings A Boilers pressure drop B Available pump head C.H.
TEMPRA 24
9
3. INSTALLATION DETAILS
Gas Safety (Installation & Use) Regulations
In the interest of safety, it is the law that all gas appliances are installed by a competent person in accordance with the above Regulations, Building Regulations/Building Standards Scotland, Codes of Practice, current I.E.E. Regulations and the byelaws of the Local Water Undertaking. Failure to comply with the Regulations may lead to
prosecution; it is your responsibility to ensure that the law is complied with.
N.B. For Northern Ireland the rules in force apply.
Important - If the boiler is to be tted in a timber framed building it should be tted in accordance with the Institute
of Gas Engineers document IGE/UP/7. If in doubt advice should be sought from the Local Supplier.
Location of Boiler
The installation of the Tempra 24 must be on a suitable non-combustible load bearing wall which will provide an adequate fi xing for the boiler mounting bracket assembly. The location should be in an area where the water pipes will not be subjected to frost conditions. In siting the combination boiler the following limitations must be observed: The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. wiring regulations and in Scotland the electrical provisions of the building regulations applicable in Scotland, with respect to the installation of the combination boiler in a room or internal space containing a bath or shower. Where a room sealed appliance is installed in a room containing a bath or shower any electrical switch or appliance control utilising mains electricity must be situated so that it cannot be touched by a person using the bath or shower.
Air Supply
The room or compartment in which the boiler is installed does not require a purpose provided vent when using the standard concentric fl ue.
Flue System
The boiler allows the flue outlet to be taken from the rear of the boiler, from either side or vertically.
A standard fl ue length of 0.75 metres is provided. Alternative lengths of two or three metres can be supplied (equivalent to wall thicknesses of up to 565, 1815 and 2815mm for rear fl ues, deduct 91mm plus distance from side wall for side outlet fl ues). It is absolutely essential, to ensure that products of combustion discharging from
the terminal cannot re-enter the building, or enter any adjacent building, through ventilations, windows, doors, natural air infi ltration or forced ventilation/air conditioning.
Gas Supply
If necessary the local Gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas. An existing service pipe must not be used without prior consultation with the Local Gas supplier. A gas meter can only be connected by the Local Gas supplier, or by a Local Gas suppliers Contractor. Installation pipes should be fi tted in accordance with BS6891-1988. Appliance inlet working pressure must be 20mbar MINIMUM, for NG and 37 mbar minimum for LPG. Pipework from the meter to the combination boiler must be of an adequate size. The boiler requires 2.73m3/h of natural gas, and 2,00 kg/h of LPG. Do not use pipes of a smaller size than the boiler inlet gas connection. The complete installation must be tested for gas soundness and purged as described in BS6981-1988. All pipework must be adequately supported. An isolating gas valve is provided and should be fi tted on the boiler gas inlet. Please wait 10 minutes when lighting from cold before checking gas rate. Gas pressures should be checked
after the boiler has operated for 10 minutes to reach thermal equilibrium.
TEMPRA 24
10
NOTE: A by-pass that will ensure a minimum fl ow rate of 6 l/min. at all all time must be fi tted as far as possible from the boiler if thermostatic radiator valves are fi tted thoughout.
Fig. 7
Central Heating
Detailed recommendations are given in BS6798, BS5449, BS6700 and CP342 Part 2. Pipework not forming part of the useful heating surface should be insulated to prevent any heat losses or possible freezing (i.e. in roof spaces or ventilated underfl oor spaces). Drain taps should be positioned at the lowest point of the system in accessible locations to permit the whole system to be drained down. The drain taps should be in accordance with BS2879. Copper tubing to BS2871, Part 1 is recommended for water carrying pipework. Pipework in horizontal runs should have a gradient where possible to facilitate the removal of air. Ensure that the boiler heat exchanger is not a natural point for air collection. A typical heating system with domestic hot water circuit is illustrated in fi g. 7.
Important - If thermostatic radiator vales are tted a automatic bypass must be fi tted to ensure a minimum fl ow rate through the boiler of 6 l/min. The bypass should be tted as far as possible from the boiler.
Make Up Water
Provision must be made for replacing water lost from the sealed system. Reference should be made to BS6798, for methods of fi lling and making up sealed systems. There must be no direct connection between the boiler's central heating system and the mains water supply. The use of mains water to charge and pressurise the system directly, is conditional upon the Local Water Byelaws. Again any such connection must be disconnected after use.
Attention - is drawn to the Model Water Byelaws.
Fittings manufactured from duplex (alpha-beta) brass are not acceptable for underground use and certain water undertakings will not accept their use above ground.
Ensure all pipework is adequately supported
Gas
Additional expansion vessel C.H. (if required)
By-pass
AUTOMATIC BY-PASS
The by-pass must be capable of passing 6 l/min of water when all the trvs are shut down
TEMPRA 24
11
CLEARANCES:
* 600mm minimum clearance for servicing access
Top clearance only applies to 100Ø concentric ue system
460 5 min.5 min.
100 min.900
200 min.
272 50 mm
600* min.
760
Fig. 8
Terminal Position
Fig. 9
P
D, E
Q
Q
l
B
C
A
G
F
L
J
H
H
K
N
N
MM
Q
Directly below an opening, air brick, opening windows, etc.
Above an opening, air brick, opening windows, etc.
Horizontally to an opening, air brick, opening windows, etc.
Below gutters, soil pipes or drain pipes
Below eaves
Below balconies or car port roof
From a vertical drain pipe or soil pipe
From an internal or external corner
Above ground roof or balcony level
From a surface facing the terminal (also see 6.1.2)
From a terminal facing the terminal
From an opening in the car port ( e.g. door, window) into the dwelling
Vertically from a terminal on the same wall
Horizontally from a terminal on the same wall
From the wall on which the terminal is mounted
From a vertical structure on the roof
Above intersection with roof
Dimensions Terminal position
(kW input expressed in net)
Balanced flues room
sealed
Fanned draught
300 mm
300 mm
300 mm
D 75 mm
E 200 mm
F 200 mm
G 150 mm
H 300 mm
I 300 mm
J 600 mm
K 1200 mm
L 1200 mm
M 1500 mm
N 300 mm
O N/A
P N/A
Q N/A
NOTE N/A = Not applicable
a
In addition, the terminal should not be nearer than 150 mm (fanned draucht) or 300 mm (natural draught) to an opening in the building fabric
formed for the purpose of accommodating a built-in element such as a window frame.
A
B
C
Minimum dimensions of fl ue terminal positions
TEMPRA 24
12
Ø3/4" Ø1/2" Ø3/4"
200
Ø118
165 min
65
21 min
5 min
183 min
295.5 min 200 min
932 min
269
110
125 min
280
123
3.01 Drilling Template (Top Flue Application) (Standard Top Flue Application)
Select suitable mounting position for boiler, using the template mark fl ue outlet and boiler mounting points. Drill two 10mm holes 70mm deep to accept the wall plugs. Fit standard wall plugs on the left and right side and the special wall plug in the middle (fi g. 10a). Fix the wall bracket to the wall using standard lock nut (M8) on both sides. Mount the boiler on the wall bracket as described in the fi g. 10a. Using a core drill cut a 118mm diameter hole for the fl ue.
1. CH flow
2. Gas supply
3. CH return
Fig. 10b
Fig. 10a
TEMPRA 24
13
Holes Ø : 45 47 50
Ø
3.02 Restrictor
For boiler operation, the restrictor supplied with the unit must be mounted following the instructions below. Determine the correct size of fl ue restrictor required. Before inserting the fl ue gas duct in the boiler, check that the restrictor fi tted is correct and that it is correctly positioned (see fi g. 11).
N.B.: the diameter of the hole is
stamped on the restrictor
Boiler is fitted with Ø45
restrictor as standard
Fig. 11
Choice of restrictor:
RESTRICTOR FOR TWO PIPE SYSTEM
Total flow resistance
of flue system
Use
restrictor
size
minimum maximum mm
0 m 10 m 45 10 m 20 m 47 20 m 35 m 50 35 m 45 m No restrictor
With concentric systems:
- Choose correct restrictor from table below.
With 2 pipe system:
- Calculate the total fl ow resistance of the air and fl ue pipes in metres (cap. 3.04.2)
- utilise the table shown below to choose the more suitable restrictor for the fl ow resistance calculated
RESTRICTOR FOR CONCENTRIC SYSTEM
Flue lenght up to:
Use
restrictor
size
Concentric
60/100
1 bend + 1 meter 50 mm
1 bend + 3 meters No restrictor
Concentric
80/125
1 bend + 3 meters 45 mm
1 bend + 4 meters 50 mm
1 bend + 5 meters No restrictor
TEMPRA 24
14
3.03 Top Outlet Concentric Flue Connection
3.03.1 Vertical concentric connection
DS
L
125
70
50*
30
95
80
80
-3 mm/m
Ø60 Ø80
70 min.
* = between 10 e 60 mm
190 270
Fig. 13
A vertical connector can be supplied for vertical discharge with concentric pipes. The simple mounting and use of double lip gaskets at the joints makes this an extremely easy and safe option. For fl ue length up to 1 m long the 50 mmØ restrictor is required. Longer than this no restrictor is required.
Fig. 12
Concentric Vertical Connector
3.03.2 Horizontal concentric connection
A 90° bend (fi g. 13) is supplied for the horizontal connection of air and fl ue gas pipes. This can be oriented towards the chosen wall in degrees of 45°.
L = S + D + 205
Loading...
+ 30 hidden pages