Important - If thermostatic radiator valves are fi tted throughout a bypass must be fi tted to ensure a minimum fl ow rate
through the boiler of 6 l/min. The bypass should be fi tted as far as possible from the boiler.
2.02.01 Safety valve
A safety valve complying with the requirements of BS 6750 Part 1 must be fi tted close to the boiler on the fl ow pipe by
means of a horizontal or vertically upward connection with no intervening valve or restrictions and should be positioned
to facilitate testing. The valve should be pre-set and nonadjustable to operate at a pressure of 3 bar (45 Ibf/in2). It must be
arranged to discharge any water or steam through a pipe to a safe outlet position.
2.02.02 Pressure gauge
A pressure gauge of minimum range 0-4 bar (0-60 Ibf/in2) with a fi ll pressure indicator must be fi tted to the system,
preferably at the same point as the expansion vessel in an easily visible position.
2.02.03 Venting
A method of venting the system during fi lling and commissioning must be provided by fi tting automatic air
vents or by venting manually.
2.02.04 Expansion vessel
In a sealed system an expansion vessel complying with the requirements of BS 4814 must be fi tted to the system
by means of a connection close to the inlet side of the circulating pump in accordance with the manufacturers
instructions, the connecting pipe being unrestricted and not less than 15 mm (1/2 in) nominal size. The volume
of the vessel should be suitable for the system water content and the nitrogen or air charge pressure should
not be less than the system static head.
Further details of sealed system design can be obtained from BS 5449: Part 1 and the British Gas publication entitled
Specifi cations for Domestic Wet Central Heating Systems.
2.02.05 Water treatment
If water treatment is used ferroli limited recommend only the
use of Fernox or Sentinel water treatment products, which must
be used in accordance with the manufacturers instructions. For
further information contact:
Fernox Manufacturing Co. LTD. Sentinel Division
Tandern house, Marlowe Way Betz Dearborn LTD
Croydon, surrey, CRO 4YS Widnes, Cheshire WA8 8ND
Tel: 0870 5601 5000 Tel: 0151 424 5351
Note - If the boiler is installed in an existing system any
unsuitable additives must be removed by thorough cleansing.
All systems should be cleansed according to B.S. 7593.
Note - In hard water areas treatment to prevent lime scale
may be necessary.
Note - It is important that the correct concentration of the
water treatment product is maintained in accordance with the manufacturers instructions.
2.03 Gas connection
Gas connection must be carried out using a rigid pipe.
The fl ow at the gas meter should be suffi cient for the simultaneous use of all appliances connected to it. Connect
the gas supply to the boiler according to current regulations. The diameter of the gas cock leaving the boiler is not
the determining factor in choosing the diameter of the pipe between the appliance and the meter. This must be
selected in relation to length and pressure drop.
The whole of the gas installation including the meter should be inspected and tested for soundness and purged
in accordance with BS6891-1988.
VESSEL CHARGE
PRESSURE (bar)
INITIAL SYSTEM
PRESSURE (bar)
TOTAL WATER
CONTENT of SYSTEM
Litres
25
50
75
100
125
150
175
200
0.33
For syst. volumes other than
those given above, mult. the syst.
volume by the factor across.
0.5 1.0
EXPANSION VESSEL VOLUME (litres)
8.3
16.5
24.8
33.1
41.3
49.6
57.9
66.2
1.5
2.0
10.3
20.6
30.9
41.2
51.5
61.8
72.1
82.4
0.412
2.0
4.7
9.5
14.2
19.0
23.7
28.5
33.2
38.0
0.190
1.5
13.7
27.5
41.3
55.1
68.9
82.6
96.4
110.2
0.551
2.0
6.5
12.9
19.4
25.9
32.4
38.8
45.3
51.8
0.259
1.5
3.5
7.0
10.5
14.0
17.5
21.0
24.5
28.0
0.140
1.0
Sizing of expansion vessels: