Ferroli RXA 6.1, RXA 9.1, RXA 14.1, RXA 7.1, RXA 11.1 Installation And Operation Manual

...
1
RXA
AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION
INSTALLATION AND OPERATION MANUAL
R
F
R
I
G
E
R
A
N
T
G
A
S
E
C
O
-
F
R
I
E
N
D
L
Y
FERROLI adheres to
EUROVENT
certication programme.
The products appear in the directory of certied products at www.eurovent-certication.com
2
The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing
mistakes. The manufacturer reserves the right to apply changes and improvements to the products at any time without notice.
Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years of experiences and of particular research stu­dies and has been made with top quality materials and advanced technologies. The CE mark guarantees that the products satisfy all the applicable European Directives. The qualitative level is kept under constant control and FERROLI products therefore offer SAFETY, QUALITY and RELIABILITY. Due to the continuous improvements in technologies and materials, the product specication as well as performances are subject to variations without prior notice.
Thank you once again for your preference FERROLI S.p.A
3
TABLE OF CONTENTS
GENERAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit dataplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
TECHNICAL DATA AND PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
NOMINAL performances - Standard plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
NOMINAL performances - Standard plants - EUROVENT certified data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
NOMINAL performances - Radiant plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
COOLING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
HEATING performances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Plant side hydraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Operating limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Noise levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Minimum operating area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Hydraulic connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
RECEIVING AND POSITIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
START UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Messa in funzione. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
CONTROL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Controller technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Alarms table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Functions available for the user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Serial communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Probes characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
SAFETY AND POLLUTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
General considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Refrigerant safety card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4
GENERAL FEATURES
General instructions
Declaration of conformity
Unit dataplate
The figure shows the fields reported on the unit dataplate :
This manual and the wiring diagram supplied with the unit must be kept in a dry place for possible future consultation. The manual provides information on installation and correct use and maintenance of the unit. Before carrying out installation,
please carefully read all the information contained in this manual, which describes the procedures necessary for correct installation and use of the unit.
Follow carefully the instructions contained in this manual and respect the safety regulations in force. The unit must be installed in conformity with the laws in force in the country of use. Unauthorized tampering with the electrical and mechanical equipment INVALIDATES THE WARRANTY. Check the electrical specifications given on the dataplate before making the electrical connections. Read the instructions given in the specific section on electrical connections. Deactivate the equipment in case of fault or poor operation. If the unit requires fixing, contact only specialized service centers recognized by the manufacturer and use original spare parts. The unit must be installed outdoor and connected to a hydronic cooling and/or heating system. Any use different from that permitted or outside the operating limits indicated in this manual is prohibited (unless previously agreed with the firm).
The manufacturer declines any responsability for damage or injury due to non-compliance with the information given in this manual.
The firm declares that the present unit complies with the requirements of the following directives :
• Machinery directive (MD) 2006/42/EC
• Pressure equipment directive (PED) 97/23/EC
• Electromagnetic compatibility directive (EMC) 2004/108/EC
• Low voltage directive (LVD) 2006/95/EC
Codice Code
B1
Rev
Ferroli Spa Via Ritonda 78/A
(VR) Italy
A - Trademark B - Model B1 - Code C - Serial number D - Capacity in cooling E - Capacity in heating (heat pump) F - Power input in cooling G - Power input in heating (heat pump) H - Reference standard I - Power supply L - Maximum absorbed current M - Refrigerant type and charge weight N - Unit weight O - Sound pressure level at 1 metre P - IP protection level Q - Maximum pressure - high pressure side R - Maximum pressure - low pressure side S - PED certification body
5
GENERAL FEATURES
Unit identification code
The codes that identify the units and the meaning of the letters used are described below.
RXA IP 14.1 VB AB 0M5
Unit type
IR - Unit suitable for hydronic plant installation operating as chiller IP - Unit suitable for hydronic plant installation operating as reversible heat pump
Power supply
Operating range
Refrigerant type
Acoustic setting up
Unit version
N° compressors
Unit model
VB - Base version VP - Pump version VA - Tank version
1 - 230 V - 1 - 50 Hz 5 - 400 V - 3N - 50 Hz
M - Medium temperature.
The unit is suitable to be instal­led in temperate climates.
0 - R410A
AB - Base setting up
Unit description
This series of air-water chillers and heat pumps satisfies the cooling and heating requirements of residential plants of small and medium size.
All the units are suitable for outdoor installation and can be applied to fan coil plants, radiant floor plants and high efficiency radiators plants.
The refrigerant circuit, contained in a compartment protected from the air flow to simplify the maintenance operations, is equipped with rotary or scroll compressor (according to the model) mounted on damper supports, brazed plate heat exchanger, thermostatic expansion valve, reverse cycle valve, axial fans with safety protection grilles, finned coil made of copper pipes and aluminium louvered fins. The circuit is protected by high and low pressure switches and differential pressure switch on the plate heat exchanger.
The plate heat exchanger and all the hydraulic pipes are thermally insulated in order to avoid condensate generation and to reduce thermal losses.
All the units are equipped with variable speed fans control that allows the units to operate with low outdoor temperatures in cooling and high outdoor temperature in heating and permits to reduce noise emissions in such operating conditions.
All three-phase power supply units are provided with a phase presence and correct sequence controller device.
All the units are accurately built and individually tested in the factory. Only electric and hydraulic connections are required for installation.
6
GENERAL FEATURES
Description of components
External structure. Basement, supporting structure and
lateral panels are made of galvanized and painted sheet-steel (colour RAL 7035) to guarantee good resistance to atmospheric agents. Accessibility to internal parts is possible removing the frontal panel. For extraordinary manteinances also the rear panel can be removed.
Refrigerant circuit. It is contained inside a compartment separated from the air flow to simplify maintenance and control operations.
The hermetic rotary or scroll (according to the model) compressor (1) is mounted on damper supports and is protected against overtemperatures and overcurrents. It is equipped with an electrcal heater, that is activated when the compressor turns off, to keep the compressor crankcase oil temperature high enough to prevent migration of the refrigerant during winter stops and to evaporate any liquid present in the crankcase, in order to prevent possible liquid rushes on starting (only heat pump models).
The plant side heat exchanger (2) is a brazed stainless steel plate heat exchanger, properly insulated to avoid condensate generation and to minimize thermal losses, and protected by a differential pressure switch that detects whatever water flow lack. It is moreover protected against freeze danger by an antifreeze electrical heater.
The source side heat exchanger (3) is a finned coil realized with grooved copper pipes and aluminium fins with notched profile to increase the heat exchange coefficient. A tray is obtained in the basement to collect the condensate generated in heating mode.
The expansion device (4), a thermostatic expansion valve with external equalizer, allows the unit to adjust itself to the different operating conditions keeping steady the set superheating.
The refrigerant circuit of each unit contains moreover solid core hermetic filter dryer (5) to restrain impurity and moisture residuals that could be present in the circuit, high and low
pressure switches in order to assure the compressor to operate inside the permitted limits, 4 way reverse cycle valve (6) to allow operating mode change reversing the refrigerant flow (only heat pump models), liquid receiver (7) to compensate the different refrigerant charge required in heating and in cooling mode (only heat pump models) and pressure connections SAE 5/16” - UNF 1/2” - 20 equipped with pin, gasket and blind nut, as required for the use of R410A refrigerant (they allow the complete check of the refrigerant circuit: compressor inlet pressure, compressor outlet pressure and thermostatic expansion valve upstream pressure).
The axial fans (8) are contained in a sheet nozzle and are equipped with a safety grille. The fans rotational speed is modulated continuosly by a phase cut device to control the condensation pressure (in cooling) and the evaporation pressure (in heating) in order to extend the operating limits of the unit and to reduce noise emissions.
Hydraulic circuit. All the pipes are thermally insulated to avoid condensate generation and minimize thermal losses. The circuit can be equipped with different kind of circulation pump (option). In that case the circuit is also equipped with expansion vessel and air vents. It is also possible to integrate inside the unit a buffer tank arranged as buffer on the flow towards the plant (option). In that case the circuit is equipped not only with expansion vessel and air vents, but also with safety valve, automatic air vent and drain cock.
Electrical panel. It contains all the power, control and security components necessary to guarantee the unit to work properly. The unit is managed by a microprocessor controller to which all the electrical loads and the control devices are connected. The user interface, placed on the frontal panel, allows to view and to modify, if necessary, all the parameters of the unit.
All the units are supplied with an outdoor temperature sensor, already installed on the unit, in order to realize the climatic control.
3
7
2
6
4
5
1
8
7
GENERAL FEATURES
Control system
The unit is managed by a microprocessor controller to which, through a wiring board, all the electrical loads and the control devices are connected. The user interface is realized by a display and four buttons that allow to view and, if necessary, modify all the operating parameters of the unit. It's available, as an accessory, a remote control that reports all the functionalities of the user interface placed on the unit.
The main functions available are :
- water temperature management (through set point adjustment)
- climatic control in heating and in cooling mode (automatic set point adjustment according to outdoor air temperature)
- dynamic defrost cycle management according to outdoor air temperature
- alarm memory management and diagnostic
- fans management by means of continuous rotational speed control
- pump management
- integrative electrical heaters management in heating mode (2 step logic)
- compressor and pump operating hours recording
- serial communication through Modbus protocol
- remote stand by
- remote cooling-heating
- general alarm digital output
Versions
Each model can be supplied in three different versions to satisfy the application requirements of the plants. The unit is always supplied assembled, wired and factory tested.
The version is automatically identified by the option "Storing and pumping module" selected.
Base Version - VB
The unit does not contain neither circulating pump nor tank. Therefore a proper water flow through the plate heat exchanger must be guaranteed to prevent internal safety devices activation. In any case the pump, if properly sized, can be connected to the electrical panel of the unit and managed by the controller of the unit.
Pump Version - VP
The unit contains a circulating pump, air vents, expansion vessel and drain cock.
Tank Version - VA
The unit contains a tank (arranged as buffer on the flow towards the plant), safety valve, circulating pump, air vents, expansion vessel and drain cock. The tank is also arranged for the installation of antifreeze or integrative electrical heaters.
°C
1
2
1 2
mode
disp
8
GENERAL FEATURES
Options
Storing and pumping module
Standard pump Allows the circulation of the water on the plant side.
High head pump
Allows the circulation of the water on the plant side and guarantees a higher available static head, suitable for high pressure drop plants.
Modulating pump
Allows the circulation of the water on the plant side with the possibility to set the rotational speed of the pump in order to get the requested flow rate without the necessity to install other setting devices.
Tank and standard pump
Allows the circulation of the water on the plant side. The thermal inertia of the buffer tank allows to reduce the number of compres­sor starts and to guarantee a more stable flow temperature.
Tank and high head pump
Allows the circulation of the water on the plant side and guarantees a higher available static head, suitable for high pressure drop plants. The thermal inertia of the buffer tank allows to reduce the number of compres­sor starts and to guarantee a more stable flow temperature.
Tank and modulating pump
Allows the circulation of the water on the plant side with the possibility to set the rotational speed of the pump in order to get the requested flow rate without the necessity to install other setting devices. The thermal inertia of the buffer tank allows to reduce the number of compres­sor starts and to guarantee a more stable flow temperature.
Integrative electrical heaters
Standard in the flow
Integrate or replace the heating power supplied by the heat pump and are ma­naged by the unit controller with a 2 step logic. They are also activated as antifreeze electrical heaters. Available only for the VB and VP versions.
Standard in the tank
Integrate or replace the heating power supplied by the heat pump and are ma­naged by the unit controller with a 2 step logic. They are also activated as antifreeze electrical heaters. Available only for the VA version.
Upsized in the tank
Soft starter Reduces the compressor start current.
Chiller (IR) without options (VB) Heat pump (IP) without options (VB)
9
GENERAL FEATURES
Accessories
Rubber vibration dampers
Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the com­pressor and by the fans in their normal operating mode.
Coil protection grille Protects the external surface of the finned coil..
Tank antifreeze electrical heater
Activated together with the antifreeze electrical heater of the plate heat exchanger, it has the task to keep the water in the buffer tank at a temperature high enough to avoid ice generation during winter.
Remote control
It is suitable for wall mounting and reports all the control and visualization functions available on the user inter­face placed on the unit. It therefore allows the complete remote control of the unit.
Modbus serial interface on RS485
It allows to communicate with the unit controller and to view the operating conditions of the unit through Modbus communication protocol. The RS485 serial line ensures the signal quality up to distances of about 1200 meters (that can be extended by means of proper repeaters).
Programmer clock
It allows the unit to be turned on and off according to a set program, through the digital input available on the unit wiring board (remote stand by).
Phase sequence and voltage controller
It checks not only the presence and correct order of the power supply phases but also the voltage level on each phase and avoid the unit to operate with voltage levels outside the permitted limits.
Option "Storing and pumping module"
Pump (VP)
(standard, high head or modulating)
Option "Integrative electrical heaters"
Tank and pump (VA)
(standard, high head or modulating)
Standard in the flow
(only for VB and VP versions)
In the tank (standard or upsized)
(only for VA version)
10
TECHNICAL DATA AND PERFORMANCES
Frame
1 2 3
Model
6.1 7.1 9.1 11.1 14.1 17.1
U.M.
Power supply
230 - 1 - 50 230 - 1 - 50
230 - 1 - 50
400 - 3N - 50
230 - 1 - 50
400 - 3N - 50
400 - 3N - 50 400 - 3N - 50 V-ph-Hz
Technical data
Refrigerant
Type
R410A R410A R410A R410A R410A R410A -
Compressor
Type
rotary rotary scroll scroll scroll scroll -
Quantity
1 1 1 1 1 1
Power steps
0 - 100 0 - 100 0 - 100 0 - 100 0 - 100 0 - 100 %
Oil charge
1,13 1,13 1,20 1,80 1,80 1,80 kg
Plant side heat exchanger
Type
stainless steel
brazed plates
stainless steel
brazed plates
stainless steel brazed plates
stainless steel
brazed plates
stainless steel
brazed plates
stainless steel
brazed plates
-
Quantity
1 1 1 1 1 1
Water volume
0,53 0,53 0,53 0,53 0,67 0,84 l
Source side heat exchanger
Type
finned
coil
finned
coil
finned
coil
finned
coil
finned
coil
finned
coil
-
Quantity
1 1 1 1 1 1
Frontal surface
0,60 0,60 0,77 0,77 0,98 0,98 m
2
Fans
Type
axial axial axial axial axial axial -
Quantity
1 1 1 1 2 2
Diameter
450 450 500 500 500 500 mm
Maximum rotational speed
900 900 900 900 900 900 rpm
Total installed power
0,15 0,15 0,21 0,21 0,42 0,42 kW
Plant side hydraulic circuit
Expansion vessel volume - VP
10 10 10 10 10 10 l
Expansion vessel volume - VA
5 5 5 5 5 5 l
Tank volume - VA
33 33 50 50 71 71 l
Safety valve set - VA
6 6 6 6 6 6 bar
Standard pump (option)
Type
3 speed
glandless pump
3 speed
glandless pump
3 speed
glandless pump
3 speed
glandless pump
multi stage
pump
multi stage
pump
-
Installed power
0,15 0,15 0,15 0,15 0,25 0,25 kW
High head pump (option)
Type
3 speed
glandless pump
3 speed
glandless pump
multi stage
pump
multi stage
pump
multi stage
pump
multi stage
pump
-
Installed power
0,20 0,20 0,25 0,25 0,35 0,35 kW
Modulating pump (option)
Type
inverter
glandless pump
inverter
glandless pump
inverter
glandless pump
inverter
glandless pump
inverter
glandless pump
inverter
glandless pump
-
Installed power
0,07 0,07 0,14 0,14 0,14 0,14 kW
Integrative electrical heaters standard in the flow (option)
Installed power
6,6 6,6 6,6 6,6 6,6 6,6 kW
Power steps
2 2 2 2 2 2
Integrative electrical heaters in the tank (option)
Installed power - standard
3,3 3,3 3,3 3,3 3,3 3,3 kW
Installed power - upsized
- - 6,6 6,6 6,6 6,6 kW
Power steps
2 2 2 2 2 2
11
TECHNICAL DATA AND PERFORMANCES
Frame
1 2 3
Model
6.1 7.1 9.1 11.1 14.1 17.1
U.M.
Power supply
230 - 1 - 50 230 - 1 - 50
230 - 1 - 50
400 - 3N - 50
230 - 1 - 50
400 - 3N - 50
400 - 3N - 50 400 - 3N - 50 V-ph-Hz
NOMINAL performances - Standard plants
IR
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 6,24 7,24 9,12 10,6 14,1 16,7
kW
Power input 2,31 2,81 3,52 4,16 5,25 6,49
kW
EER 2,70 2,58 2,59 2,55 2,69 2,57
-
Water flow rate plant side 1074 1246 1573 1836 2437 2883
l/h
Pressure drops plant side 17 21 31 40 43 39
kPa
IP
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 6,12 7,10 8,95 10,4 13,8 16,4
kW
Power input 2,31 2,81 3,51 4,15 5,24 6,49
kW
EER 2,65 2,53 2,55 2,51 2,63 2,53
-
Water flow rate plant side 1054 1222 1543 1802 2385 2831
l/h
Pressure drops plant side 16 20 30 39 42 38
kPa
Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 6,78 7,87 9,95 11,7 15,4 18,2
kW
Power input 2,22 2,71 3,38 4,01 5,06 6,25
kW
COP 3,05 2,90 2,94 2,92 3,04 2,91
-
Water flow rate plant side 1154 1339 1690 1981 2612 3090
l/h
Pressure drops plant side 18 24 35 45 48 43
kPa
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 5,60 6,50 8,21 9,61 12,7 15,1
kW
Power input 2,19 2,68 3,33 3,94 4,97 6,16
kW
COP 2,56 2,43 2,47 2,44 2,56 2,45
-
Water flow rate plant side 954 1106 1397 1632 2151 2561
l/h
Pressure drops plant side 13 17 25 33 35 32
kPa
Frame
1 2 3
Model
6.1 7.1 9.1 11.1 14.1 17.1
U.M.
Power supply
230 - 1 - 50 230 - 1 - 50
230 - 1 - 50
400 - 3N - 50
230 - 1 - 50
400 - 3N - 50
400 - 3N - 50 400 - 3N - 50 V-ph-Hz
NOMINAL performances - Standard plants - EUROVENT certified data
IR
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 6,23 7,45 9,44 10,9 13,9 17,4
kW
EER 2,94 2,66 2,58 2,67 2,75 2,66
-
Pressure drops plant side 28 39 26 34 41 36
kPa
ESEER 3,33 3,01 2,92 3,02 3,11 3,01
-
IP
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 6,02 7,14 9,24 10,7 13,7 17,2
kW
EER 2,83 2,54 2,52 2,62 2,71 2,63
-
Pressure drops plant side 26 36 25 33 40 35
kPa
ESEER 3,21 2,88 2,85 2,97 3,07 2,98
-
Heating A7W45 (air 7 °C bs - 6 °C bu / water 40 - 45 °C )
Heating capacity 6,96 8,14 10,3 11,4 15,2 18,5
kW
COP 3,15 3,03 2,86 2,86 3,15 2,95
-
Pressure drops plant side 34 45 31 37 48 40
kPa
Data declared according to EN 14511. The values are referred to units without options and accessories.
12
TECHNICAL DATA AND PERFORMANCES
Frame
1 2 3
Model
6.1 7.1 9.1 11.1 14.1 17.1
U.M.
Power supply
230 - 1 - 50 230 - 1 - 50
230 - 1 - 50
400 - 3N - 50
230 - 1 - 50
400 - 3N - 50
400 - 3N - 50 400 - 3N - 50 V-ph-Hz
NOMINAL performances - Radiant plants
IR
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 7,48 8,67 10,9 12,7 16,8 20,0
kW
Power input 2,39 2,91 3,64 4,32 5,46 6,75
kW
EER 3,13 2,98 2,99 2,94 3,08 2,96
-
Water flow rate plant side 1290 1496 1889 2198 2920 3469
l/h
Pressure drops plant side 22 29 42 53 58 53
kPa
IP
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 7,34 8,50 10,7 12,5 16,6 19,6
kW
Power input 2,39 2,91 3,64 4,31 5,45 6,74
kW
EER 3,07 2,92 2,94 2,90 3,05 2,91
-
Water flow rate plant side 1266 1467 1855 2164 2868 3400
l/h
Pressure drops plant side 22 28 41 52 56 51
kPa
Heating A7W35 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 6,92 8,03 10,2 11,9 15,7 18,6
kW
Power input 1,87 2,28 2,86 3,39 4,27 5,28
kW
COP 3,70 3,52 3,57 3,51 3,68 3,52
-
Water flow rate plant side 1183 1371 1731 2023 2674 3171
l/h
Pressure drops plant side 19 25 36 47 50 46
kPa
Heating A2W35 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 5,74 6,66 8,42 9,84 13,0 15,5
kW
Power input 1,84 2,25 2,81 3,32 4,18 5,18
kW
COP 3,12 2,96 3,00 2,96 3,11 2,99
-
Water flow rate plant side 982 1138 1437 1678 2211 2640
l/h
Pressure drops plant side 14 18 27 34 36 34
kPa
Data declared according to EN 14511. The values are referred to units without options and accessories.