Ferroli RMP series Technical Manual

RMP
AIR-WATER CHILLERS AND HEAT PUMPS FOR INDOOR INSTALLATION
TECHNICAL MANUAL
R
E
F
I
G
E
R
A
N
T
G
A
S
E
C
O
-
F
R
I
E
N
D
L
Y
2
The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing mi-
stakes. The manufacturer reserves the right to apply changes and improvements to the products at any time without notice.
3
TABLE OF CONTENTS
GENERAL FEATURES                                                                           5
Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
TECHNICAL DATA AND PERFORMANCES                                                          10
Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
NOMINAL performances - Base setting up (VB) - Standard plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
NOMINAL performances - Base setting up (VB) - Radiant plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
NOMINAL performances - Low noise setting up (AS) - Standard plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
NOMINAL performances - Low noise setting up (AS) - Radiant plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
COOLING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
HEATING performances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Plant side hydraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Source side aeraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Operating limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Noise levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Minimum operating area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4
5
IP 261 VB AB 0M5
GENERAL FEATURES
Unit description
This series of air-water chillers and heat pumps satises the co­oling and heating requirements of residential plants of small and medium size.
All the units are suitable for indoor installation and can be ap­plied to fan coil plants, radiant oor plants and high efciency radiators plants.
The refrigerant circuit, contained in a compartment protected from the air ow to simplify the maintenance operations, is equipped with scroll compressor mounted on damper supports, brazed plate heat exchanger, thermostatic expansion valve, re­verse cycle valve, centrifugal fans (plug fan), nned coil made of copper pipes and aluminium louvered ns. The circuit is protec­ted by high and low pressure switches and differential pressure switch on the plate heat exchanger.
The plate heat exchanger and all the hydraulic pipes are ther­mally insulated in order to avoid condensate generation and to reduce thermal losses.
All the units are equipped with variable speed fans control that allows the units to operate with low outdoor temperatures in co­oling and high outdoor temperature in heating and permits to reduce noise emissions in such operating conditions.
The low noise acoustic setting up (AS) is obtained, starting from the base setting up (AB), reducing the rotational speed of the fans and mounting sound jackets on the compressors.
All the units are supplied with an outdoor temperature sensor, al­ready installed on the unit, in order to realize the climatic control.
All the units are provided with a phase presence and correct sequence controller device.
All the units are accurately built and individually tested in the factory. Only electric and hydraulic connections are required for installation.
Unit identification code
The codes that identify the units and the meaning of the letters used are described below.
Unit type
IR - Unit suitable for hydronic plant in­stallation operating as chiller IP - Unit suitable for hydronic plant in­stallation operating as reversible heat pump BR - Unit suitable for hydronic plant in­stallation with brine solutions operating as chiller BP - Unit suitable for hydronic plant in­stallation with brine solutions operating as reversible heat pump
Power supply
5 - 400 V - 3N - 50 Hz
Operating range
M - Medium temperature. The unit is suitable to be instal­led in temperate climates.
Refrigerant type
0 - R410A
Acoustic setting up
AB - Base setting up AS - Low noise setting up
Unit version
VB - Base version VP - Pump version VA - Tank version
N° compressors
Unit model
RMP
6
GENERAL FEATURES
Description of components
External structure. Basement, supporting structure and lateral
panels are made of galvanized and painted sheet-steel (colour RAL 7035) to guarantee good resistance to atmospheric agents. Accessibility to internal parts is possible removing the frontal panel. For extraordinary manteinances also the rear panel can be removed.
Refrigerant circuit. It is contained inside a compartment separated from the air flow to simplify maintenance and control operations.
The hermetic scroll compressor (1) is mounted on damper supports and is protected against overtemperatures and overcurrents. It is equipped with an electrcal heater, that is activated when the compressor turns off, to keep the compressor crankcase oil temperature high enough to prevent migration of the refrigerant during winter stops and to evaporate any liquid present in the crankcase, in order to prevent possible liquid rushes on starting (only heat pump models).
The plant side heat exchanger (2) is a brazed stainless steel plate heat exchanger, properly insulated to avoid condensate generation and to minimize thermal losses, and protected by a differential pressure switch that detects whatever water flow lack. It is moreover protected against freeze danger by an antifreeze electrical heater.
The source side heat exchanger (3) is a finned coil realized with grooved copper pipes and aluminium fins with notched profile to increase the heat exchange coefficient. A tray is obtained in the basement to collect the condensate generated in heating mode.
The expansion device (4), a thermostatic expansion valve with external equalizer, allows the unit to adjust itself to the different operating conditions keeping steady the set superheating.
The refrigerant circuit of each unit contains moreover solid core hermetic filter dryer (5) to restrain impurity and moisture residuals that could be present in the circuit, high and low pressure switches in order to assure the compressor to
operate inside the permitted limits, 4 way reverse cycle valve (6) to allow operating mode change reversing the refrigerant flow (only heat pump models), liquid receiver (7) to compensate the different refrigerant charge required in heating and in cooling mode (only heat pump models) and pressure connections SAE 5/16” - UNF 1/2” - 20 equipped with pin, gasket and blind nut, as required for the use of R410A refrigerant (they allow the complete check of the refrigerant circuit: compressor inlet pressure, compressor outlet pressure and thermostatic expansion valve upstream pressure).
The fans (8) are plug fan type fans equipped with EC direct current motor and embedded inverter. The fans rotational speed is modulated continuosly to control the condensation pressure (in cooling) and the evaporation pressure (in heating) in order to optimize the operating conditions of the unit and to reduce noise emissions. The maximum rotational speed can be modified by parameter in order to set the available static head of the fan to the plant requirements.
Hydraulic circuit. All the pipes are thermally insulated to avoid condensate generation and minimize thermal losses. The circuit can be equipped with different kind of circulation pump (option). In that case the circuit is also equipped with expansion vessel and air vents. It is also possible to integrate inside the unit a buffer tank arranged as buffer on the flow towards the plant (option). In that case the circuit is equipped not only with expansion vessel and air vents, but also with safety valve, automatic air vent and drain cock.
Electrical panel. It contains all the power, control and security components necessary to guarantee the unit to work properly. The unit is managed by a microprocessor controller to which all the electrical loads and the control devices are connected. The user interface, placed on the frontal panel, allows to view and to modify, if necessary, all the parameters of the unit.
All the units are supplied with an outdoor temperature sensor, already installed on the unit, in order to realize the climatic control.
3
7
2
6
4
5
1
8
3
7
2
6
4
5
1
8
7
GENERAL FEATURES
Control system
The unit is managed by a microprocessor controller to which, through a wiring board, all the electrical loads and the control devices are connected. The user interface is realized by a display and four buttons that allow to view and, if necessary, modify all the operating parameters of the unit. It's available, as an accessory, a remote control that reports all the functionalities of the user interface placed on the unit.
The main functions available are :
- water temperature management (through set point adjustment)
- adaptive function
- climatic control in heating and in cooling mode (automatic set point adjustment according to outdoor air temperature)
- dynamic defrost cycle management according to outdoor air temperature
- alarm memory management and diagnostic
- fans management by means of continuous rotational speed control
- pump management
- integrative electrical heaters management in heating mode (2 step logic)
- compressor and pump operating hours recording
- serial communication through Modbus protocol
- remote stand by
- remote cooling-heating
- general alarm digital output
Versions
Each model can be supplied in three different versions to satisfy the application requirements of the plants. The unit is always supplied assembled, wired and factory tested.
The version is automatically identified by the option "Storing and pumping module" selected.
Base Version - VB
The unit does not contain neither circulating pump nor tank. Therefore a proper water flow through the plate heat exchanger must be guaranteed to prevent internal safety devices activation. In any case the pump, if properly sized, can be connected to the electrical panel of the unit and managed by the controller of the unit.
Pump Version - VP
The unit contains a circulating pump, air vents, expansion vessel and drain cock.
Tank Version - VA
The unit contains a tank (arranged as buffer on the flow towards the plant), safety valve, circulating pump, air vents, expansion vessel and drain cock. The tank is also arranged for the installation of antifreeze or integrative electrical heaters.
°C
1
2
1 2
mode
disp
8
GENERAL FEATURES
Options
Storing and pumping module
Standard pump Allows the circulation of the water on the plant side.
High head pump
Allows the circulation of the water on the plant side and guarantees a higher avai­lable static head, suitable for high pressure drop plants.
Modulating pump
Allows the circulation of the water on the plant side with the possibility to set the rotational speed of the pump in order to get the requested flow rate without the necessity to install other setting devices.
Tank and standard pump
Allows the circulation of the water on the plant side. The thermal inertia of the buffer tank allows to reduce the number of compressor starts and to guarantee a more stable flow temperature.
Tank and high head pump
Allows the circulation of the water on the plant side and guarantees a higher avai­lable static head, suitable for high pressure drop plants. The thermal inertia of the buffer tank allows to reduce the number of compressor starts and to guarantee a more stable flow temperature.
Tank and modulating pump
Allows the circulation of the water on the plant side with the possibility to set the rotational speed of the pump in order to get the requested flow rate without the necessity to install other setting devices. The thermal inertia of the buffer tank allows to reduce the number of compressor starts and to guarantee a more stable flow temperature.
Integrative electrical heaters
Standard in the tank
Integrate or replace the heating power supplied by the heat pump and are managed by the unit controller with a 2 step logic. They are also activated as antifreeze electrical heaters. Available only for the VA version.
Soft starter Reduces the compressor start current.
Compressor power factor correction
Allows to reduce the phase shift between the absorbed current and the power sup­ply voltage keeping it above the value of 0,9.
Electrical loads protection
Fuses Allows to protect the electrical loads with fuses.
Thermal magnetic circuit breakers
Allows to protect the electrical loads with thermal magnetic circuit breakers simpli­fying the maintenance operations.
Chiller (IR) without options (VB) Heat pump (IP) without options (VB)
Loading...
+ 16 hidden pages