Ferroli ECONCEPT 51, ECONCEPT 51i, ECONCEPT 101, ECONCEPT 101i Instructions For Use, Installation And Maintenance

Page 1
6
cod. 3540S572 — 11/2010 (Rev. 00)
ECONCEPT 51 - 101 ECONCEPT 51i - 101i
ISTRUZIONE PER L’USO L'INSTALLAZIONE E LA MANUTENZIONE INSTRUCCIONES DE USO, INSTALACIÓN Y MANTENIMIENTO
KULLANMA, KURULUM VE BAKøM TALIMATLAR
INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE INSTRUCTIONS D'UTILISATION, D'INSTALLATION ET D'ENTRETIEN
INSTRUCğIUNI DE UTILIZARE, INSTALARE ùI ÎNTRETINERE
ɊɍɄɈȼɈȾɋɌȼɈɉɈɗɄɋɉɅɍȺɌȺɐɂɂ, ɆɈɇɌȺɀɍɂɌȿɏɈȻɋɅɍɀɂȼȺɇɂɘ
ȱɇɋɌɊɍɄɐȱəɁȿɄɋɉɅɍȺɌȺɐȱȲ, ɆɈɇɌȺɀɍɌȺɈȻɋɅɍȽɈȼɍȼȺɇɇə
Page 2
ECONCEPT 51/51i - 101/101i
47
EN
cod. 3540S572 - 11/2010 (Rev. 00)
EN
1. GENERAL INSTRUCTIONS
Carefully read the instructions contained in this instruction booklet.
After boiler installation, inform the user regarding its operation and give him this manual, which is an integral and essential part of the product and must be kept with care for future reference.
Installation and maintenance must be carried out by professionally qualified personnel, according to current regulations and the manufacturer's instructions. Do not carry out any operation on the sealed control parts.
Incorrect installation or inadequate maintenance can result in damage or injury. The Manufacturer declines any liability for damage due to errors in installation and use or failure to follow the instructions.
Before carrying out any cleaning or maintenance operation, disconnect the unit from the power supply using the system switch and/or the special cut-off devices.
In case of a fault and/or poor operation, deactivate the unit and do not attempt to repair it or directly intervene. Contact professionally qualified personnel. Repair/replacement of the products must only be carried out by professionally qualified using original spare parts. Failure to comply with the above could affect the safety of the unit.
This unit must only be used for its intended purpose. Any other use is considered improper and therefore dangerous.
The packing materials are potentially hazardous and must not be left within the reach of children.
The images given in this manual are a simplified representation of the product. In this representation there may be slight and insignificant differences with respect to the product supplied.
2. OPERATING INSTRUCTIONS
2.1 Introduction
Dear Customer, Thank you for choosing ECONCEPT 51/51i - 101/101i, heat generator of the latest gen-
eration FERROLIfeaturing advanced design and cutting-edge technology. Please read this manual carefully since it provides important information on safe installation, use and maintenance.
ECONCEPT 51/51i - 101/101i is a high-efficiency modular premix condensing heat generator for heating with very low emissions, running on natural gas or LPG and ar­ranged for installation in cascade.
Each ECONCEPT 51/51i - 101/101i module is equipped with a double aluminium lamel­lar exchanger and double ceramic premix burner housed in a vertical cabinet in AISI 316 stainless steel (version ECONCEPT 51i - 101i) or in epoxy powder coated steel resistant to atmospheric agents (version ECONCEPT 51 - 101).
The plumbing circuits of the exchangers, each equipped with its own local circulating pump, run into system delivery and return manifolds inside the module. The control sys­tem has a microprocessor and user interface with a large display.
A cascade control unit, available by request, enables effective and economical manage­ment of the modules ECONCEPT 51/51i - 101/101i connected in cascade.
The generators ECONCEPT 51/51i - 101/101i are designed for installation even outside. The versions ECONCEPT 51i - 101i with stainless steel cabinet are particularly recom­mended for places where the climatic and environmental conditions are unfavourable.
2.2 Control panel
fig. 1 - Control panel
The control panel is located inside the cabinet. To access it, open the front door with the special key supplied.
Key 1 = DHW temperature setting decrease button (with optional hot water tank in-
stalled)
2 = DHW temperature setting increase button (with optional hot water tank in-
stalled)
3 = Heating system temperature setting decrease button 4 = Heating system temperature setting increase button 5 = Display 6 = Summer/Winter mode selection button 7 = Economy/Comfort mode selection (with optional hot water tank installed) and
unit On/Off button
8 = Reset button 9 = DHW operation (with optional hot water tank installed) 10 = Summer mode 11 = Multifunction
12 = Eco (Economy) mode (with optional hot water tank installed) 13 = Heating mode 14 = Unit On / Off button 15 = Burner On 16 = Appears on connecting the Remote Timer Control (optional) 17 = Information symbol 18 = Top boiler shell 19 = Top boiler shell system fault reset request 20 = Fault 21 = Circulating pump On 22 = Appears on connecting the external probe (optional) 23 = Boiler Off 24 = Bottom boiler shell 25 = Bottom boiler shell system fault reset request (model ECONCEPT 101/
101ionly)
Indication during operation
Heating
A heating demand (generated by the Room Thermostat or Remote Timer Control or 0­10 Vdc signal) is indicated by activation of the circulating pump and the radiator (details 13 and 21 - fig. 1).
The display (detail 11 - fig. 1) shows the actual heating delivery temperature and, during heating standby time, the message "d". Activation of the arrows (details 18 and 24 ­fig. 1) indicates which boiler shell is on.
fig. 2
DHW (with optional hot water tank installed)
A hot water tank heating demand is indicated by activation of the circulating pump and the tap (details 9 and 21 - fig. 1). The display (detail 11 - fig. 1) shows the actual hot water tank sensor temperature and, during heating standby time, the message "d". Activation of the arrows (details 18 and 24 - fig. 1) indicates which boiler shell is on.
fig. 3 -
Exclude hot water storage tank (economy)
Hot water tank temperature maintaining/heating can be excluded by the user. If exclud­ed, domestic hot water will not be delivered. The hot water tank can be deactivated by the user (ECO mode) by pressing the eco/comfort button (detail 7 - fig. 1). In ECO mode the display activates the symbol (detail 12 - fig. 1). To activate the COMFORT mode, press the eco/comfort button (detail 7 - fig. 1) again.
2.3 Lighting and turning off
Boiler lighting
Press the On/Off button (detail 14 fig. 1).
fig. 4 - Boiler lighting
For the following 120 seconds the display will show FH which identifies the heating system air venting cycle.
During the first 10 seconds the display will also show the software version of the cards:
A = Display card software version B = Top boiler shell control unit software version C = Bottom boiler shell control unit software version (model ECONCEPT 101/ 101ionly)
Open the gas cock ahead of the boiler.
When the message FH disappears, the boiler is ready to operate automatically in case of a room thermostat demand.
17 18 2320
4
16
22
2
1 9 12
21
3
13
10
6 8 14
11
5
7
15 25
reset
eco
comfort
19
24
reset
eco
comfort
reset
eco
comfort
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
reset
eco
comfort
reset
eco
comfort
reset
eco
comfort
reset
eco
comfort
reset
eco
comfort
reset
eco
comfort
A
B C
Page 3
ECONCEPT 51/51i - 101/101i
48
EN
cod. 3540S572 - 11/2010 (Rev. 00)
Turning the boiler off
Press the button (detail 7 - fig. 1) for 5 seconds.
fig. 5 - Turning the boiler off
When the boiler is turned off, the PCB is still powered. Domestic hot water (with optional hot water tank installed) and heating operation are dis-
abled. The antifreeze system remains activated. To relight the boiler, press the button (detail 7 fig. 1) again for 5 seconds.
fig. 6
The boiler will be immediately ready to operate whenever domestic hot water is drawn (with optional hot water tank installed) or in case of a room thermostat demand.
To completely disconnect the power to the unit, press the button detail 14 fig. 1.
B
The antifreeze system does not work when the power and/or gas to the unit are turned off. To avoid damage caused by freezing during long idle periods in win­ter, it is advisable to drain all water from the boiler, DHW circuit and system; or drain just the DHW circuit and add a suitable antifreeze to the heating system, complying with that prescribed in sec. 3.3.
2.4 Adjustments
Summer/Winter Switchover
Press the button detail 6 - fig. 1 for 1 second.
fig. 7
The display activates the Summer symbol detail 10 - fig. 1. The heating function is deac­tivated, whereas the possible production of domestic hot water (with optional external hot water tank) remains activated. The antifreeze system remains activated.
To deactivate Summer mode, press the button (detail 6 - fig. 1) again for 1 sec­ond.
Heating temperature adjustment
Use the heating buttons (details 3 and 4 - fig. 1) to adjust the tempera­ture from a min. of 20°C to a max. of 90°C.
fig. 8
DHW temperature adjustment (with optional hot water tank installed)
Use the DHW buttons (details 1 and 2 - fig. 1) to adjust the temperature from a min. of 10°C to a max. of 65°C.
fig. 9
Room temperature adjustment (with optional room thermostat)
Using the room thermostat, set the temperature required in the rooms.
Room temperature adjustment (with optional remote timer control)
Using the remote timer control, set the temperature desired in the rooms. The boiler unit will set the system water according to the required room temperature. For information on the remote timer control, please refer to its user's manual.
Sliding temperature
When the optional external probe is installed the corresponding symbol (detailfig. 122 ­) is activated on the control panel display (detail 5 - fig. 1). The boiler control system op­erates with "Sliding Temperature". In this mode, the heating system temperature is ad­justed according to the outside weather conditions, to ensure high comfort and energy saving throughout the year. In particular, as the outside temperature increases, the sys­tem delivery temperature is decreased according to a specific "compensation curve".
With Sliding Temperature adjustment, the temperature set with the heating buttons
(details 3 and 4 - fig. 1) becomes the maximum system delivery temper­ature. It is advisable to set a maximum value to allow system adjustment throughout its useful operating range.
The boiler must be regulated at the time of installation by qualified personnel. Adjust­ments can in any case be made by the user to improve comfort .
Compensation curve and curve offset Press the button (detail 8 - fig. 1) for 5 seconds, to display the actual com-
pensation curve (fig. 10) which can be modified with the DHW buttons (details 1 and 2 - fig. 1).
Adjust the required curve from 1 to 10 according to the characteristic (fig. 12). By setting the curve to 0, sliding temperature adjustment is disabled.
fig. 10 - Compensation curve
Press the heating buttons (details 3 and 4 - fig. 1) to access parallel curve offset (fig. 13), modifiable with the DHW buttons (details 1 and 2
- fig. 1).
fig. 11 - Curve parallel offset
Press the button (detail 8 - fig. 1) again for 5 seconds to exit parallel curve adjustment mode.
If the room temperature is lower than the required value, it is advisable to set a higher order curve and vice versa. . Proceed by increasing or decreasing in steps of one and check the result in the room.
fig. 12 - Compensation curves
fig. 13 - Example of compensation parallel curve offset
reset
eco
comfort
reset
eco
comfort
reset
eco
comfort
reset
eco
comfort
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
reset
eco
comfort
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
reset
reset
eco
comfort
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
reset
eco
comfort
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
reset
20
30
40
50
60
70
80
90 85
20 10 0 -10 -20
1
2
3
4
5
68910 7
20
30
40
50
60
70
80
90 85
20 10 0 -10 -20
1
2
3
4
5
6
8910
7
20 10 0 -10 -20
20
30
40
50
60
70
80
90 85
1
2
3
4
568910 7
OFFSET = 20 OFFSET = 40
Page 4
ECONCEPT 51/51i - 101/101i
49
EN
cod. 3540S572 - 11/2010 (Rev. 00)
A
If the Remote Timer Control (optional) is connected to the boiler, the above ad­justments are managed according to that given in table 1.
Table. 1
System water pressure adjustment
The filling pressure with the system cold must be approx. 1.0 bar. If the system pressure falls to values below minimum, the boiler card will activate fault F37 (fig. 14). Flashing of the arrows (details 18 and 24 - fig. 1) together with the error code indicates which boiler shell is in fault status.
fig. 14 - Low system pressure fault
A
Once the system pressure is restored, the boiler will activate the 120-second air venting cycle indicated on the display by FH.
3. INSTALLATION
3.1 General Instructions
THE BOILER MUST ONLY BE INSTALLED BY QUALIFIED PERSONNEL, IN COMPLI­ANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE NATIONAL AND LOCAL REGULATIONS, AND THE RULES OF PROPER WORKMANSHIP.
ECONCEPT 51/51i - 101/101i is a high-efficiency heat generator arranged to operate alone or in cascade (bank). When two or more generators ECONCEPT 51/51i - 101/101i are installed in cascade with the original kits FERROLI, respecting the prescriptions of this manual, they can be considered as a single heat generator of total power equal to the sum of the powers of all the units connected in cascade.
All the requirements of the current standards and regulations applicable to this “equiva­lent” generator with total heating capacity must be met. In particular the place of instal­lation, safety devices and fume exhaust system must be adequate for the total heating capacity of the bank of units.
In fact, each ECONCEPT 51/51i - 101/101i is a complete and independent heat gener­ator, equipped with its own safety devices. In case of overtemperature, a lack of water or no circulation in the unit, the protection devices cause the unit to switch off or shut down, preventing it from working.
The installation instructions given in the following paragraphs concern both single units and connection in cascade.
3.2 Place of installation
The generator can be installed directly outside or in a suitable room with ventilation open­ings to the outside as prescribed by the current regulations. If there are several burners or extraction units that can work together in the same room, the ventilation openings must be sized for simultaneous operation of all the units. The place of installation must be free of flammable objects or materials, corrosive gases, volatile substances or dusts. For positioning, leave enough space around the modules for normal maintenance oper­ations. Make sure the front door opens without hindrance.
B
The air necessary for combustion enters through special openings in the bot­tom and top part of the unit. Make sure these air passages are not obstructed in any way.
fig. 15 - Air inlet
3.3 Gas and water connections
Plumbing connections
Make the relevant connections according to the instructions given below. Make the gen­erator connection in such a way that its internal pipes are free of stress. For proper op­eration and long life of the generator, the plumbing system must be of suitable size and complete with all the accessories that guarantee regular operation and running.
In particular, provide for all the protection and safety devices prescribed by current reg­ulations for the complete modular generator. They must be installed on the hot water cir­cuit delivery piping, immediately downstream of the last module, within a distance of 0.5 m, with no shut-off devices in between. A "Safety Device and Circuit Breaker module” equipped with internal hydraulic circuit breaker and safety units with ISPESL certification is available by request. Refer to the price-list or contact our sales network. The unit is not supplied with an expansion tank; its connection must therefore be made by the Installer.
B
A filter must also be installed on the system return piping to prevent impurities or sludge from the system clogging and damaging the heat generators.
The filter must necessarily be installed when replacing generators in existing systems. The manufacturer declines any liability for damage caused to the gen­erator by failure to install or inadequate installation of this filter.
Water system characteristics
In the presence of water harder than 25° Fr, it is advisable to use suitably treated water, in order to avoid possible scaling in the boiler caused by hard water, or corrosion pro­duced by aggressive water. Due to its low thermal conductivity, scaling even just a few mm thick causes significant overheating of the generator walls, with consequent serious problems.
Water treatment is indispensable in case of very large systems (containing large amounts of water) or with frequent introduction of replenishing water in the system. If par­tial or total emptying of the system becomes necessary in these cases, it is advisable to refill with treated water.
Gas connection
The gas must be connected to the corresponding union with a rigid metal pipe. The gas meter must be adequate for the simultaneous use of all units connected to it.
Carry out the generator gas connection in accordance with current regulations. The di­ameter of the gas pipe leaving the generator does not determine the diameter of the pipe between the unit and the meter; it must be chosen according to its length and pressure loss.
B
Make sure to install a fuel shutoff valve externally with respect to the modules, enabling the gas to be turned off even without opening the single modules equipped with key closing.
Connection instructions ECONCEPT 51/51i - 101/101i is equipped inside with 3 manifolds (gas, system delivery
and return) and a condensate drain pipe that facilitate cascade connection and also con­nection of a single module to the system. The manifolds are sized for connecting up to 5 modules in series. The cabinet contains a set of flanges, seals and screws for the con­nection.
To connect a single module - fig. 16
After determining on which side of the module to make the water and gas connec-
tions, connect the flanges with the joining section contained in the kit on that side after suitably welding them to the system pipes. Make sure to correctly to fit the seals contained in the kit.
Connect a Ø40 pipe to the condensate drain pipe for removing the condensate pro-
duced during operation (see fig. 37).
Fit the blind flanges contained in the kit on the opposite side of the module, inserting
the special seals.
To connect several modules in cascade - fig. 17
Connect the first module to the system and gas pipes, as described above, but with-
out fitting the blind flanges on the opposite side to that of the connection.
Place the second module on this side, making sure to align the connection flanges
and the condensate drain pipe. Insert the seals contained in the kit between the flanges of the two modules.
Fit the bolts contained in the kit on the flanges from inside the first module, making
them come out of the flanges inside the second module. Partially tighten the nuts on the bolts from inside the second module.
Before tightening the nuts, make sure all the seals are correctly positioned and join
the condensate drain pipes of the two modules (see fig. 38).
Tighten the nuts and repeat the connection operations for the following modules
(max.5).
If using a water trap
At the end, fit the blind flanges on the last module, inserting the special seals (fig. 16
and fig. 17).
If using a direct pump
Connect the delivery to the return on the last module (see fig. 18).
Heating temperature adjustment
Adjustment can be made from the Remote Timer Control menu and the boiler control panel.
DHW temperature adjustment (with optional hot water tank installed)
Adjustment can be made from the Remote Timer Control menu and the boiler control panel.
Summer/Winter Switchover
Summer mode has priority over a possible Remote Timer Control heating demand.
Eco/Comfort selection
(with optional
hot water tank installed)
On disabling DHW from the Remote Timer Control menu, the boiler selects the Econ­omy mode. In this condition, the button
fig. 1
detail 7 - on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the boiler selects the Com­fort mode. In this condition it is possible select one of the two modes with the button detail 7 -
fig. 1
.
Sliding Temperature
Both the Remote Timer Control and the boiler card manage Sliding Temperature adjustment: of the two, the Sliding Temperature of the boiler card has priority.
reset
eco
comfort
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Page 5
ECONCEPT 51/51i - 101/101i
50
EN
cod. 3540S572 - 11/2010 (Rev. 00)
Plumbing connection using one generator with water trap
fig. 16
1 Gas inlet 2 System delivery 3 System return 4 Condensate drain 5 Blind flanges 6 Connection side 7 Flanges with joining section
Plumbing connection using two or more generators with hydraulic separator
fig. 17
1 Gas inlet 2 System delivery 3 System return 4 Condensate drain 5 Blind flanges 6 Connection side 7 Flanges with joining section 8 Seals
Plumbing connection using one or more generators with direct pump
fig. 18
1 Gas inlet 2 System delivery 3 System return 4 Condensate drain 5 Blind flanges 6 Connection side 7 Flanges with joining section 8 Seals 9 Delivery/return connection
Water circuit examples
Key of examples
I ISPESL safety devices D Hydraulic separator 42 DHW temperature sensor (not supplied) 72 Room thermostat (not supplied) 72b Room thermostat (not supplied) 95 3-way valve - with spring return: at rest on DHW side (not supplied) 130 Hot water tank circulating pump (not supplied) 138 External probe (not supplied) 139 Remote control (not supplied) 298 Cascade temperature sensor (not supplied) 306 Heating system circulating pump (not supplied) 307 Heating system second circulating pump (not supplied) SM Delivery probe (supplied with kit FZ4) TS Safety thermostat (not supplied) PZ Zone pump (not supplied) FZ4 Zone regulator
Parameters Each system requires a different parametrisation.Follow the procedure for accessing the
two menus, given below; for the parameters to be modified, refer to the tables given next to the plumbing diagrams.
"Service Menu" Press the Reset button for 10 seconds to access the card Service Menu. Press the Heating buttons to select "tS", "In", "Hi" or "rE"”. “tS” means Transparent Pa-
rameters Menu, “In” Information Menu, “Hi” History Menu, and “rE” History Menu Reset. Select "tS" and press the Reset button.
The card has 29 transparent parameters also modifiable from Remote Control (Service Menu).
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or­der. Press the DHW buttons to modify the value of a parameter: the change will be au­tomatically saved.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec­onds to exit the card Service Menu.
"System Type Menu" Press the Summer/Winter button for 10 seconds to access the card System Type Menu. The card has 21 transparent parameters. Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au­tomatically saved.
Press the Summer/Winter button for 10 seconds to exit the card System Type Menu. One direct heating circuit Check/Change parameter P02 of the "Transparent Parameters Menu" to 1. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1.
fig. 19
One direct heating circuit and one DHW circuit with pump Check/Change parameter P02 of the "Transparent Parameters Menu" to 2. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1.
fig. 20
1
2
3
1
2
3
4765
1
2
3
1
2
3
6
5 7 7 7 4
1
2
3
1
2
3
9
6
8 8 7 4
A
I
D
138
298
72/139
306
B
I
D
138
298
306
42
130
72/139
Page 6
ECONCEPT 51/51i - 101/101i
51
EN
cod. 3540S572 - 11/2010 (Rev. 00)
One direct heating circuit and one DHW circuit with diverter valve Check/Change parameter P02 of the "Transparent Parameters Menu" to 3. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1. Change parameter P.11 of the "System Type Menu" to 1.
fig. 21
Two direct heating circuits Check/Change parameter P02 of the "Transparent Parameters Menu" to 1. Change parameter P.01 of the "System Type Menu" to 4. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1.
fig. 22
Two mixed heating circuits and one direct heating circuit Check/Change parameter P02 of the "Transparent Parameters Menu" to 1. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1. For the electrical connection and the zone system settings, refer to the "FZ4 zone reg-
ulator" handbook
fig. 23
Two mixed heating circuits, one direct heating circuit and one DHW circuit with pump Check/Change parameter P02 of the "Transparent Parameters Menu" to 2. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1. For the electrical connection and the zone system settings, refer to the "FZ4 zone reg-
ulator" handbook
fig. 24
3.4 Electrical connections
Connection to the electrical grid
B
The unit's electrical safety is only guaranteed when correctly connected to an efficient earthing system executed according to current safety standards. Have the efficiency and suitability of the earthing system checked by professionally qualified personnel. The manufacturer is not responsible for any damage caused by failure to earth the system. Also make sure that the electrical system is adequate for the maximum power absorbed by the unit, as specified on the boiler dataplate.
The boiler is prewired and provided with a Y-cable and plug for connection to the elec­tricity line. The connections to the grid must be made with a permanent connection and equipped with a bipolar switch whose contacts have a minimum opening of at least 3 mm, interposing fuses of max. 3A between the boiler and the line. It is important to re­spect the polarities (LINE: brown wire / NEUTRAL: blue wire / EARTH: yellow-green wire) in making connections to the electrical line. During installation or when changing the power cable, the earth wire must be left 2 cm longer than the others.
B
The user must never change the unit's power cable. If the cable gets damaged, switch off the unit and have it changed solely by professionally qualified person­nel. If changing the electric power cable, use solely “HAR H05 VV-F” 3x0.75 mm2 cable with a maximum outside diameter of 8 mm.
Room thermostat (optional)
B
CAUTION: The room thermostat must have clean contacts. CONNECTING 230 V. TO THE TERMINALS OF THE ROOM THERMOSTAT WILL IRREPA­RABLY DAMAGE THE ELECTRONIC CARD.
When connecting a remote timer control or a timer switch, do not take the pow­er supply for these devices from their cut-out contacts. Their power supply must be taken with a direct connection from the mains or with batteries, depending on the kind of device.
External probe (optional)
Connect the probe to its respective terminals. The maximum permissible length for the boiler - external probe connection electrical cable is 50 m. A normal 2-wire cable can be used. The external probe should preferably be installed on the North, North-West wall or that facing the largest area of living room. The probe must never be exposed to the early morning sun or, insofar as possible, direct sunlight; protect it if necessary. In any case, the probe must not be installed near windows, doors, ventilation openings, flues or heat sources that could affect the reading.
fig. 25 - External probe positioning not recommended
C
I
D
138
298
306
95
42
72/139
D
I
D
138
307 306
298
72b
72/139
E
Zona 1 Zona 2 Zona 3
M M
I
D
SM
298
138
PZ
TS
SM
PZ
TS
PR
FZ4
72/139 72/139 72/139
F
Zona 1 Zona 2 Zona 3
M M
I
D
SM
298
SM
PR
PZ
130
42
138
PZ
TS TS
72/139
FZ4
72/139 72/139
Page 7
ECONCEPT 51/51i - 101/101i
52
EN
cod. 3540S572 - 11/2010 (Rev. 00)
Accessing the electrical terminal block
The electrical terminal block is located inside a sealed box at the bottom left of the cab­inet. Make the electrical connections as shown in the wiring diagram on sec. 47 and run the cables through the special cable glands.
fig. 26 - Electrical terminal block
42 DHW temperature sensor (not supplied) 72 Room thermostat (not supplied) 72b Room thermostat (not supplied) 95 Diverter valve (not supplied)
A = Heating phase B = DHW phase C = Neutral
NOTE: For valves with 2 wires and spring return, use the connections B and C 130 DHW circulating pump (not supplied) 138 External probe (not supplied) 139 Remote timer control (not supplied) 298 Cascade temperature sensor (not supplied) 299 Input 0-10 Vdc 300 Burner lit contact (voltage-free contact) 301 Fault contact (voltage-free contact) 302 Remote reset input (230 Volt) 306 Heating system circulating pump (not supplied) 307 Heating system second circulating pump (not supplied)
For connection in cascade (MAX. 5 MODULES)
1. Connect the modules as shown in fig. 27 (example with 4 modules)
fig. 27 - Connection in cascade
A 1st Module B 2nd Module C 3rd Module D 4th Module
2. Carry out all the electrical connections (terminals 4 to 24) on module no. 1
3. On the remaining modules only connect the power supply and possible contacts for:
burner lit (300), fault contact (301) and remote reset input (302).
4. Switch on the power to the entire cascade
5. After the "FH" procedure, check correct operation of the cascade:
Module 1: arrow symbol at top left of the display
Module 2: arrow symbol at bottom right of the display
Module 3: arrow symbol at bottom right of the display
Module 4: arrow symbol at top right of the display
If this does not occur, disconnect the power and check the wiring in fig. 27.
Settings
All adjustments must be made on all the modules.
Possible faults
If the electrical connection of a module is disconnected for any reason, module 1 will ac­tivate fault F70.
If the electrical connection of a module is disconnected for any reason, the next module will activate fault F71.
3.5 Flue connection
Important
The unit is a B23 type with combustion air drawn from the installation room and fume ex­haust by means of a fan (operation with flue pressurised) and must be connected to one of the discharge systems indicated below. Before proceeding with installation, check and carefully comply with the local regulations and provisions. Also comply with the provi­sions concerning the positioning of wall and/or roof terminals and minimum distances from windows, walls, ventilation openings, etc.
Manifold, ducts and flue must be suitably sized, designed and made in compliance with current regulations. These must be made of suitable materials, i.e. resistant to heat and corrosion, smooth on the inside and hermetic. In particular, joints must be condensate tight. Also provide for suitable condensate drain points, connected to a trap to prevent the condensate formed in the flues from running into the generators.
B
The unit is equipped with two separate Ø80 flue connections for the two burner
- exchanger units (fig. 28) located inside the cabinet. The combustion circuits of the two units are completely independent. When
joining the two fume outlets to a single flue or manifold (in case of a single mod­ule or connection in cascade) it is necessary to install a fume anti-backflow valve on each outlet to prevent operation anomalies or to creation of hazard­ous conditions. Make sure to use the optional kits FERROLI, provided with spe­cial anti-backflow valves for installing inside the cabinets, in a position protected against the atmospheric agents.
A
Before carrying out the flue connection, make sure to fill the condensate tank as indicated incap. 3.6.
fig. 28
4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
(((
(
300
301
95
302
299
139
72
138 298 42
25 26 27 28 29 30
72B
130/307
306
A
B C
25 26 27 28 29 30 25 26 27 28 29 30 25 26 27 28 29 30 25 26 27 28 29 30
A B C D
250 250200
700
1650
Ø80 Ø80
Page 8
ECONCEPT 51/51i - 101/101i
53
EN
cod. 3540S572 - 11/2010 (Rev. 00)
Connection with separate pipes
Separate Ø80 ducts can be connected directly to the unit. Insert the seal 1KWMA84A on the Ø80 pipes leaving the unit and make it adhere to the upper wall of the cabinet.
Before proceeding with installation, make sure the maximum permissible length has not been exceeded, by means of a simple calculation:
1. Establish the layout of the system of split flues, including accessories and outlet ter-
minals for each of the two burner/exchanger bodies.
2. Consult the table 3 and identify the losses in meq (equivalent metres) of every com-
ponent, according to the installation position.
3. Check that the sum total of losses is less than or equal to the maximum permissible
length in table 2.
Table. 2 - Max. length separate ducts
Table. 3 - Accessories
Direct connection of terminals Ø 80 code 041013X0
Each single module can be connected directly to the terminal kits 041013X0 as given in , even with connection in bank fig. 29.
Each kit comprises a Ø80 terminal with grille (ref. 3), a seal (ref. 1) and a centering ring (ref. 2). For models ECONCEPT 101/101i use 2 kits per module, and 1 kit for models
ECONCEPT 51/51i.
fig. 29
B
Before installing the flues, open the cabinet and fill the trap with approx. 0.5 l.
of water through the flue connections (see fig. 30) A and B for the model and
ECONCEPT 101/101ionly A the model ECONCEPT 51/51i.
fig. 30 - Filling the trap
B
For outside installations make the seal 1 adhere perfectly to the top part of the
cabinet, to prevent possible infiltration of rain and atmospheric agents.
Connection with manifolds
To connect one or more modules in bank to a single flue, it is advisable to use the special manifolds (optionals) indicated in the table. The choice of diameter must be made ac­cording to the total power of the bank of units, respecting that given in the table. Use a starting kit for each bank and a suitable number of extension kits.
The starting kits have a special accessory inside them for connection also to modules ECONCEPT 51/51i. 90° bends and manifold extensions are also available for the flue connection.
Installation examples
fig. 31 - Installation of one module
fig. 32 - Installation of 5 modules
For installation:
fig. 33
A Insert the diameter 100 M-F pipe sections with fume inspection “1” and the re-
spective seals “2” from the outside of the modules for each flue connection.
B Respect the distance given in the box “B“ of fig. 33. This distance must be in-
creased by 5 mm with each additional module.
C Open the cabinets and install the anti-backflow valve “3” on eachflue connec-
tion D=80mm
Separate ducts
For each single Exchanger/Burner Body
Max. permissible length
20 m
eq
Losses in m
eq
Fume exhaust
Vertical Horizontal
Ø 80 PIPE
1 m M/F 1KWMA83W 1.6 2.0
BEND
45° M/F 1KWMA65W 1.8 90° M/F 1KWMA01W 2.0
PIPE SECTION
with test point 1KWMA70W 0.3
TERMINAL
fumes, wall with antiwind 1KWMA86A 5.0
FLUE
Split air/fumes 80/80 1KWMA84U 5.0
1
2
3
Bank heating capacity Manifold diameter Starting kit Extension kit
Manifold extension
Male-female
1000 mm
90° bend
for manifold
Up to 150 kW
125 mm 041008X0 041020X0 041017X0 041014X0
150 - 300 kW
160 mm 041009X0 041011X0 041018X0 041015X0
300 - 500 kW
200 mm 041010X0 041012X0 041019X0 041016X0
041008X0
Ø 125
041014X0
041017X0
A A+5 A+10 A+15 A+20
A+25
041010X0
Ø 200
041012X0 041012X0 041012X0 041012X0
041016X0
Page 9
ECONCEPT 51/51i - 101/101i
54
EN
cod. 3540S572 - 11/2010 (Rev. 00)
fig. 34
D Make sure to correctly fit the seals. E Lengthen the diameter 100mm extensible part of each valve until it rests
on the inner part of the casing. Fix with the screw “4”.
F Pour 1/2 litre of water on each flue in order to fill the respective traps and
anti-backflow valves. Repeat the above steps for all the flue connections of the modules.
fig. 35
G Fit the manifold support flanges “5“ using the special holes provided on
the top of the modules. The starting bracket on the first module must re­spect the distance of 45 mm. (see box “G” fig. 35). This distance must be increased by 5 at a time in the following modules, in order to obtain the fume manifold angle as indicated in fig. 32. Fit the condensate trap “6” support bracket on the flange of the first module.
H Insert the 90° M-F bends “8” on the pipe sections “7”, positioning them at
45° with respect to the module (see box “H” fig. 35). When installing a module ECONCEPT 51/51i use only one 90° bend and the cap contained in the starting kit.
fig. 36
L Fit the flue pipes together (operation to be carried out on the ground) , en-
suring the alignment of the various connections “9” and respecting the coupling measurement of 705 mm (see box “L” fig. 36).
M Place the manifolds connected together on the support flanges and grad-
ually insert all the bends on the previously fitted diameter 100 pipe sec­tions.
Check the correct angle of the manifold (see fig. 32) and the correct fitting of all the pipe sections, bends and valves, making sure the seals are prop­erly fitted (see box “M” fig. 36). Make the external seals adhere to the top of the modules. Tighten and fix the support flanges.
N Fit the manifold closing cap “10”. Insert the condensate trap “11” and fix
it to the special bracket “6” fitted in point “G”. Connect the trap outlet to a condensate collection point (e.g. the condensate manifold of the modules).
A
Use a special lubricant to facilitate the manifold connections.
3.6 Condensate drain
B
The boiler has an internal condensate drain trap connected to an internal con­densate outlet manifold.
Condensate drain connection using one generator
fig. 37 - Condensate drain connection with one generator
A Place the Ø40 pipe 1 (not supplied) on the side of the generator. B Slide the pipe 2 towards the side of the arrow for at least 2-3 cm in order to in-
sert it in the pipe 1.
Condensate drain connection using two or more generators
fig. 38 - Condensate drain connection with several generators
A Place the Ø40 pipe 1 (not supplied) on the side of the generator B Slide the pipe 2 (of each generator) towards the side of the arrow for at least 2-
3 cm in order to insert it in the pipe 1.
4. SERVICE AND MAINTENANCE
All adjustment, conversion, commissioning and maintenance operations described be­low must only be carried out by Qualified Personnel (meeting the professional technical requirements prescribed by current regulations) such as those of the Local After-Sales Technical Service.
FERROLI declines any liability for damage and/or injury caused by unqualified and un­authorised persons tampering with the unit.
4.1 Adjustments
Gas conversion
The unit can operate on natural gas or LPG and is factory-set for use with one of these two gases, as clearly shown on the packing and on the dataplate. Whenever a gas dif­ferent from that for which the unit is arranged has to be used, a conversion kit will be re­quired, proceeding as follows:
1. Open the cabinet of the upper exchange body using the special key supplied.
2. Loosen the gas valve fixing ring"A” .
3. Undo the three fixing screws "B" and remove the gas valve "C".
4. Replace the gas valve "D" with the one contained in the conversion kit, positioning itinside the seal"E” . Refit the parts and check their tightness.
5. Repeat steps 2, 3 and 4 for the lower exchanger body (model ECONCEPT 101/ 101ionly)
6. Modify the parameter on the control system.
put the boiler in standby mode
press the DHW buttons (details 1 and 2 - fig. 1) for 10 seconds. the display
shows "P01" flashing.
press the DHW buttons fig. 1 (details 1 and 2 - ) to set parameter 00 (for use
with natural gas) or 01 (for use with LPG ).
press the DHW buttons (details 1 and 2 - fig. 1) for 10 seconds.
the boiler will return to standby mode
7. Apply the label, contained in the conversion kit, near the dataplate.
8. Using a combustion analyser connected to the boiler fume outlet, make sure the CO
2
content in the fumes, with the boiler operating at max. and min. output, com-
plies with that given in the technical data table for the corresponding type of gas.
2
B
1
A
2 2
B
A
1
Page 10
ECONCEPT 51/51i - 101/101i
55
EN
cod. 3540S572 - 11/2010 (Rev. 00)
fig. 39 - Gas conversion
Activating TEST mode
Press the heating buttons (details 3 and 4 - fig. 1) at the same time for 5 seconds to activate TEST mode. The boiler lights at the maximum heating power set as described in the following section.
The heating symbol (detail 13 - fig. 1) and DHW symbol (detail 9 - fig. 1) flash on the dis­play; the heating power will be displayed alongside.
fig. 40 - TEST mode (heating power = 100%)
To deactivate TEST mode, repeat the activation sequence. TEST mode is automatically disabled in any case after 15 minutes.
Only for model ECONCEPT 101/101i
In TEST mode, press the button (detail 7 - fig. 1) to obtain the following operation:
Top boiler shell on; bottom boiler shell off.
Top boiler shell off; bottom boiler shell on.
Top boiler shell on; bottom boiler shell on.
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the heating buttons (details 3 and 4 - fig. 1) to increase or decrease the power
(min. = 00 - max. = 100). Press the reset button (detail 8 - fig. 1) within 5 seconds; the max. power will remain
that just set. Exit the TEST mode (see sec. 4.1).
4.2 Start-up
B
Checks to be made at first lighting, and after all maintenance operations that involved disconnection from the systems or an operation on safety devices or parts of the boiler:
Before lighting the boiler
Open any on-off valves between the boiler and the systems.
Check the tightness of the gas system, proceeding with caution and using a soap and water solution to detect any leaks in connections.
Check correct prefilling of the expansion tank (ref. sec. 5.4).
Fill the water system and make sure all air contained in the boiler and the system has been vented, by opening the air vent valve on the boiler and any vent valves on the system.
Fill the condensate trap and check correct connection of the condensate elimination system.
Make sure there are no water leaks in the system, DHW circuits, connections or boil­er.
Check correct connection of the electrical system and efficiency of the earthing sys­tem
Make sure the gas pressure value for heating is that required.
Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler
Checks during operation
Turn the unit on as described in sec. 2.3.
Make sure the fuel circuit and water systems are tight.
Check the efficiency of the flue and air-fume ducts while the boiler is working.
Check the correct tightness and functionality of the condensate elimination system and trap.
Make sure the water is circulating properly between the boiler and the systems.
Make sure the gas valve modulates correctly in the heating and domestic hot water production phases.
Check proper boiler lighting by doing several tests, turning it on and off with the room thermostat or remote control.
Using a combustion analyser connected to the boiler fume outlet, check that the CO
2
content in the fumes, with the boiler operating at max. and min. output, corre-
sponds to that given in the technical data table for the corresponding type of gas.
Make sure the fuel consumption indicated on the meter matches that given in the technical data table on sec. 5.4.
Check the correct programming of the parameters and carry out any necessary cus­tomization (compensation curve, power, temperatures, etc.).
4.3 Maintenance
Periodical check
To keep the unit working properly over time, it is necessary to have qualified personnel make an annual check that includes the following tests:
The control and safety devices (gas valve, flow meter, thermostats, etc.) must func­tion correctly.
The fume extraction circuit must be fully efficient.
The airtight chamber must be sealed
The air-fume end piece and ducts must be free of obstructions and leaks
The condensate evacuation system must be efficient with no leakage or obstruc­tions.
The burner and exchanger must be clean and free of scale. When cleaning, do not use chemical products or wire brushes.
The electrode must be free of scale and properly positioned.
The gas and water systems must be airtight.
The water pressure in the cold water system must be about 1 bar; otherwise, bring it to that value.
The circulation pump must not be blocked.
The expansion tank must be filled.
The gas flow and pressure must correspond to that given in the respective tables.
A
The boiler casing, panel and aesthetic parts can be cleaned with a soft damp cloth, possibly soaked in soapy water. Do not use any abrasive detergents and solvents.
reset
eco
comfort
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Page 11
ECONCEPT 51/51i - 101/101i
56
EN
cod. 3540S572 - 11/2010 (Rev. 00)
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the display will flash together with the fault symbol (detail 20 - fig. 1) indicating the fault code. Flashing of the arrows (details 18 and 24 - fig. 1) together with the error code indi­cates which boiler shell is in fault status.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore operation, just press the RESET button (detail 8 - fig. 1) for 1 second or RESET on the optional remote timer control if installed; if the boiler fails to start, it is necessary to firstly eliminate the fault.
Other faults (marked with the letter "F") cause temporary shutdowns which are automat­ically reset as soon as the value returns within the boiler's normal working range.
Table. 4 - Fault list
5. TECHNICAL DATA AND CHARACTERISTICS
5.1 Dimensions and connections
fig. 41 - Dimensions and connections
A Model ECONCEPT 51/51i B Model ECONCEPT 101/101i 1 = Gas inlet 2 = Heating system delivery 3 = Heating system return
Fault code Fault Possible cause Cure
A01
No burner ignition
No gas
Check the regular gas flow to the boiler and that the air has been eliminated from the pipes
Ignition/detection elec­trode fault
Check the wiring of the electrode and that it is correctly positioned and free of any deposits
Faulty gas valve
Check the gas valve and replace it if nec­essary
Insufficient gas supply pressure
Check the gas supply pressure
Trap blocked Check the trap and clean it if necessary
A02
Flame present signal with burner off
Electrode fault Check the ionisation electrode wiring Card fault Check the card
A03
Overtemperature protec­tion activation
Heating sensor damaged
Check the correct positioning and opera­tion of the heating sensor
No water circulation in the system
Check the circulating pump
Air in the system Vent the system
A04
Fume extraction duct safety device activation
Fault F07 generated 3 times in the last 24 hours
See fault F07
A05
Fan protection activation
Fault F15 generated for 1 hour (consecutive)
See fault F15
A06
No flame after ignition stage (6 times in 4 min­utes)
Ionisation electrode fault Check the position of the ionisation elec-
trode and replace it if necessary Flame unstable Check the burner Gas valve Offset fault Check the Offset adjustment at minimum
power
air/fume ducts obstructed
Remove the obstruction from the flue,
fume extraction ducts and air inlet and
terminals Trap blocked Check the trap and clean it if necessary
F07
High fume temperature
Flue partially obstructed or insufficient
Check the efficiency of the flue, fume
extraction ducts and outlet terminal
Fume sensor position
Check the correct positioning and opera-
tion of the fume sensor
F10
Delivery sensor 1 fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
F11
Return sensor fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
F12
DHW sensor fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
F13
Fume sensor fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
F15
Fan fault
No 230V power supply Check the wiring of the 3-pin connector Tachometric signal inter-
rupted
Check the wiring of the 5-pin connector
Fan damaged Check the fan
F34
Supply voltage under 170V
Electric mains trouble Check the electrical system
F35
Faulty mains frequency Electric mains trouble Check the electrical system
F37
Incorrect system water pressure
Pressure too low Fill the system Water pressure switch
damaged or not con­nected
Check the sensor
F39
External probe fault
Probe damaged or wiring shorted
Check the wiring or replace the sensor
Probe disconnected after activating the sliding tem­perature
Reconnect the external probe or disable the sliding temperature
A41
Sensor positioning
Delivery sensor detached from the pipe
Check the correct positioning and opera­tion of the heating sensor
A42
Heating sensor fault Sensor damaged Replace the sensor
F42
Heating sensor fault Sensor damaged Replace the sensor
F50
Cascade temperature sensor fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted
Wiring disconnected
A61
Controller DBM12 fault
Controller DBM12 inter­nal error
Check the earth connection and replace the controller if necessary.
A62
No communication between controller and gas valve
Controller not connected Connect the controller to the gas valve
Valve damaged Replace the valve
A63 A64 A65 F66
Controller DBM12 fault
Controller DBM12 inter­nal error
Check the earth connection and replace the controller if necessary.
Fault code Fault Possible cause Cure
410
704
1650
575
390
225
145
35
115
245 270
252
Ø
104
73.5
252 200 252
Ø
104
73.5
A
B
1
2
3
Page 12
ECONCEPT 51/51i - 101/101i
57
EN
cod. 3540S572 - 11/2010 (Rev. 00)
5.2 General view and main components
fig. 42 - General view ECONCEPT 51/51i
fig. 43 - General view ECONCEPT 101/101i
7 Gas inlet 10 System delivery 11 System return 16 Fan 19 Combustion chamber 22 Burner 32 Heating circulating pump 36 Automatic air vent 44 Gas valve 82 Detection electrode 114 Water pressure switch 154 Condensate outlet pipe 161 Condensing heat exchanger 179 Non-return valve 186 Return sensor 188 Ignition electrode 193 Trap 196 Condensate tray 252 3-way drain and shutoff cock 253 Shutoff cock 278 Double sensor (Safety + Heating) C Cascade control unit and support bracket (optional)
16
186
81 82
32
253
252
154
7
10
11
19
161
22
196
278
36
193
179
114
44
C
16
16
44
44
186
186
81 82
81 82
193
193
32
253
252
154
7
10
11
161
19
19
161
22
22
196
196
278
278
36
179
114
C
Page 13
ECONCEPT 51/51i - 101/101i
58
EN
cod. 3540S572 - 11/2010 (Rev. 00)
5.3 Water circuit
fig. 44 - Water circuit ECONCEPT 51/51i
fig. 45 - Water circuit ECONCEPT 101/101i
10 System delivery 11 System return 32 Heating circulating pump 154 Condensate outlet pipe 161 Condensing heat exchanger 186 Return sensor 193 Trap 252 3-way drain and shutoff cock 253 Shutoff cock 278 Double sensor (Safety + Heating)
186
161
278
193
154
32
252
253
11
10
186
161
278
32
186
161
278
193
154
32
252 252
253 253
11
10
193
154
Page 14
ECONCEPT 51/51i - 101/101i
59
EN
cod. 3540S572 - 11/2010 (Rev. 00)
5.4 Technical data table
The column on the right gives the abbreviation used on the dataplate.
5.5 Diagrams
Circulating pump head / pressure losses
fig. 46
A Boiler pressure losses 1 - 2 - 3 Circulating pump speed
5.6 Wiring diagram
A
Important: Before connectingthe room thermostat or the remote timercontrol , remove the jumper on the terminal block
A Only model ECONCEPT 101/101i 16 Fan 32 Heating circulating pump 42 DHW temperature sensor (not supplied) 44 Gas valve 72 Room thermostat (not supplied) 72b Second room thermostat (not supplied) 81 Ignition electrode 82 Detection electrode 95 Diverter valve (not supplied)
A = Heating phase B = DHW phase C = Neutral
NOTE: For valves with 2 wires and spring return, use the connections B and C 98 Switch 114 Water pressure switch 130 DHW circulating pump (not supplied) 138 External probe (not supplied) 139 Remote timer control (not supplied) 186 Return sensor 191 Fume temperature sensor 278 Double sensor (Safety + Heating) 298 Cascade temperature sensor (not supplied) 299 Input 0-10 Vdc 300 Burner lit contact (voltage-free contact) 301 Fault contact (voltage-free contact) 302 Remote reset input (230 Volt) 306 Heating system circulating pump (not supplied) 307 Heating system second circulating pump (not supplied)
Data Unit
ECONCEPT 51/51i ECONCEPT 101/
101i
Max. heating capacity kW 49.8 99.6 (Q) Min. heating capacity kW 11.2 11.2 (Q) Max. Heat Output in heating (80/60 °C) kW 48.8 97.6 (P) Min. Heat Output in heating (80/60 °C) kW 11.0 11.0 (P) Min. Heat Output in heating (50/30 °C) kW 53.0 106.0 Min. Heat Output in heating (50/30 °C) kW 12.0 12.0 Gas supply pressure G20 mbar 20 20 Max. gas delivery G20
m
3
/h
5.27 10.54
Min. gas delivery G20
m
3
/h
1.19 1.19 Gas supply pressure G31 mbar 37 37 Max. gas delivery G31 kg/h 3.9 7.8 Min. gas delivery G31 kg/h 0.88 0.88
Efficiency class Directive 92/42 EEC -
NOx emission class - 5 5 (NOx) CO
2
max. (G20) %
9 9
CO
2
min. (G20) %
8.5 8.5
CO
2
max. (G31) %
10.5 10.5 CO
2
min. (G31) %
9.5 9.5
Max. working pressure in heating bar 6 6 (PMS) Min. working pressure in heating bar 0.8 0.8 Max. heating temperature °C 95 95 (tmax) Heating water content litres 10 12.8 Protection rating IP X5D X5D Power supply voltage V/Hz 230V/50Hz 230V/50Hz Electrical absorption W 190 380 Empty weight kg 124 150 Type of unit B
23
PIN CE 0461BS0878
0
1
2
3
4
5
6
7
0 500 1.000 1.500 2.000
Q [l/h]
H [m H
2
O]
3
1
2
A
8
2.500
Page 15
ECONCEPT 51/51i - 101/101i
60
EN
cod. 3540S572 - 11/2010 (Rev. 00)
fig. 47 - Wiring diagram
T°T°
230V 50Hz
16
278
191
186
114
16
32
82
81
V1
V2
44
X1
X3
X2
98
L
N
12345
6
789
10
11
12
123
456
12345
6
789
10
FUSE
3.15A
T°T°
DBM12KC
16
278
191
186
114
16
32
82
81
V1
V2
44
X1
X3
X2
A
25 26 27 28 29 30
1
2
3
4
123
456
DSP12C
X01 X04 X03
X05
13 14 15 16 17 18 19 20 21 22 23 24
299
139
72
138 298 42
4 5 6 7 8 9 10
11 12
(((
(
300
301
95
302
130/307
72B
A B C
DBM12KC
306
Page 16
Declaración de conformidad
El fabricante: FERROLI S.p.A. Dirección: Via Ritonda 78/a 37047 San Bonifacio (Verona) declara que este equipo satisface las siguientes directivas CEE:
• Directiva de Aparatos de Gas 2009/142
• Directiva de Rendimientos 92/42
• Directiva de Baja Tensión 73/23 (modificada por la 93/68)
• Directiva de Compatibilidad Electromagnética 89/336 (modificada por la 93/68)
Presidente y representante legal
Caballero del Trabajo
Dante Ferroli
ES
Dichiarazione di conformità
Il costruttore: FERROLI S.p.A. Indirizzo: Via Ritonda 78/a 37047 San Bonifacio VR dichiara che questo apparecchio è conforme alle seguenti direttive CEE:
• Direttiva Apparecchi a Gas 2009/142
• Direttiva Rendimenti 92/42
• Direttiva Bassa Tensione 73/23 (modificata dalla 93/68)
• Direttiva Compatibilità Elettromagnetica 89/336 (modificata dalla 93/68)
Presidente e Legale rappresentante
Cav. del Lavoro
Dante Ferroli
IT
Uygunluk beyani
ømalatçi: FERROLI S.p.A.
Adres: Via Ritonda 78/a 37047 San Bonifacio VR bu cihazin; asagida yer alan AET(EEC) yönergelerine uygunluk içinde oldugunu beyan etmektedir:
• 2009/142 Gazla çalistirilan üniteler için Yönetmelik
• 92/42 Randiman/Verimlilik Yönetmeligi
• Yönerge 73/23, Düsük Voltaj (93/68 nolu direktifle degisiklige ugratildi)
• 89/336 Elektromanyetik Uygunluk Yönetmeligi (93/68 ile degisiklik yapilmistir)
Baskan ve yasal temsilci
øú. Dep.
Dante Ferroli
TR
Declaration of conformity
Manufacturer: FERROLI S.p.A. Address: Via Ritonda 78/a 37047 San Bonifacio VR Italy declares that this unit complies with the following EU directives:
• Gas Appliance Directive 2009/142
• Efficiency Directive 92/42
• Low Voltage Directive 73/23 (amended by 93/68)
• Electromagnetic Compatibility Directive 89/336 (amended by 93/68) President and Legal Representative
Cav. del Lavoro
Dante Ferroli
EN
Page 17
Ⱦɟɤɥɚɪɚɰɿɹɩɪɨɜɿɞɩɨɜɿɞɧɿɫɬɶ
ȼɢɪɨɛɧɢɤ: ɤɨɦɩɚɧiɹ FERROLI S.p.A.
ɡɚɚɞɪɟɫɨɸ: Via Ritonda 78/a 37047 San Bonifacio VR
ɡɚɹɜɥɹɽ, ɳɨɰɟɣɚɩɚɪɚɬɜɿɞɩɨɜɿɞɚɽɭɫɿɦɧɚɫɬɭɩɧɢɦȾɢɪɟɤɬɢɜɚɦȯɋ:
• Ⱦɢɪɟɤɬɢɜɚȯɋ 2009/142 (Ⱦɢɪɟɤɬɢɜɚɩɪɨɡɛɥɢɠɟɧɧɹɩɪɚɜɨɜɢɯɧɨɪɦɤɪɚʀɧ-ɱɥɟɧɿɜȯɋɞɥɹɝɚɡɨ-ɪɨɡɯɿɞɧɢɯ
ɭɫɬɚɧɨɜɨɤ)
Ⱦɢɪɟɤɬɢɜɚȯɋ 92/42 (ȾɢɪɟɤɬɢɜɚɩɪɨɜɢɦɨɝɢɄɉȾɞɥɹɧɨɜɢɯɜɨɞɨɝɪɿɣɧɢɯɤɨɬɥɿɜ, ɩɪɚɰɸɸɱɢɯɧɚɪɿɞɢɧɧɨɦɭ
ɿɝɚɡɨɩɨɞɿɛɧɨɦɭɩɚɥɢɜɿ)
• Ⱦɢɪɟɤɬɢɜɚȯɋ 73/23 (Ⱦɢɪɟɤɬɢɜɚɩɪɨɡɛɥɢɠɟɧɧɹɩɪɚɜɨɜɢɯɧɨɪɦɤɪɚʀɧ-ɱɥɟɧɿɜȯɋ, ɳɨɫɬɨɫɭɸɬɶɫɹ
ɟɥɟɤɬɪɨɨɛɥɚɞɧɚɧɧɹ, ɹɤɟɜɢɤɨɪɢɫɬɨɜɭɽɬɶɫɹɜɩɟɜɧɢɯɦɟɠɚɯɧɚɩɪɭɝɢ) (ɡɦɿɧɟɧɚȾɢɪɟɤɬɢɜɨɸȯɋ 93/68)
Ⱦɢɪɟɤɬɢɜɚȯɋ 89/336 (Ⱦɢɪɟɤɬɢɜɚɩɪɨɩɪɢɜɟɞɟɧɧɹɭɜɿɞɩɨɜɿɞɧɿɫɬɶɡɚɤɨɧɨɞɚɜɫɬɜɤɪɚʀɧ-ɱɥɟɧɿɜɜɨɛɥɚɫɬɿ
ɟɥɟɤɬɪɨɦɚɝɧɿɬɧɨʀɫɭɦɿɫɧɨɫɬɿ) (ɡɦɿɧɟɧɚȾɢɪɟɤɬɢɜɨɸȯɋ 93/68).
ɉɪɟɡɢɞɟɧɬɿɡɚɤɨɧɧɢɣɩɪɟɞɫɬɚɜɧɢɤ
Ʉɚɜɚɥɟɪɩɪɚɰɿ
Dante Ferroli
UK
Ⱦɟɤɥɚɪɚɰɢɹɫɨɨɬɜɟɬɫɬɜɢɹ
ɂɡɝɨɬɨɜɢɬɟɥɶ: FERROLI S.p.A.,
ɚɞɪɟɫ: Via Ritonda 78/a 37047 San Bonifacio VR,
ɡɚɹɜɥɹɟɬ, ɱɬɨɧɚɫɬɨɹɳɟɟɢɡɞɟɥɢɟɫɨɨɬɜɟɬɫɬɜɭɟɬɫɥɟɞɭɸɳɢɦɞɢɪɟɤɬɢɜɚɦ CEE:
Ⱦɢɪɟɤɬɢɜɚɩɨɝɚɡɨɜɵɦɩɪɢɛɨɪɚɦ 2009/142
ȾɢɪɟɤɬɢɜɚɩɨɄ.ɉ.Ⱦ. 92/42
Ⱦɢɪɟɤɬɢɜɚɩɨɧɢɡɤɨɦɭɧɚɩɪɹɠɟɧɢɸ 73/23 (ɫɢɡɦɟɧɟɧɢɹɦɢ, ɜɧɟɫɟɧɧɵɦɢɞɢɪɟɤɬɢɜɨɣ 93/68)
Ⱦɢɪɟɤɬɢɜɚɩɨɷɥɟɤɬɪɨɦɚɝɧɢɬɧɨɣɫɨɜɦɟɫɬɢɦɨɫɬɢ 89/336 (ɫɢɡɦɟɧɟɧɢɹɦɢ, ɜɧɟɫɟɧɧɵɦɢ
ɞɢɪɟɤɬɢɜɨɣ 93/68).
ɉɪɟɡɢɞɟɧɬɢɭɩɨɥɧɨɦɨɱɟɧɧɵɣɩɪɟɞɫɬɚɜɢɬɟɥɶ
Ʉɚɜɚɥɶɟɪɟɞɟɥɶɥɚɜɨɪɨ (ɩɨɱɟɬɧɵɣɬɢɬɭɥ, ɩɪɢɫɭɠɞɚɟɦɵɣ
ɝɨɫɭɞɚɪɫɬɜɨɦɡɚɡɚɫɥɭɝɢɜɪɭɤɨɜɨɞɫɬɜɟɩɪɨɦɵɲɥɟɧɧɨɫɬɶɸ)
Dante Ferroli
RU
DeclaraĠie de conformitate
Producător: FERROLI S.p.A.
Adresă: Via Ritonda 78/a 37047 San Bonifacio VR
declară că acest aparat este în conformitate cu următoarele directive CEE:
• Directiva Aparate cu Gaz 2009/142
• Directiva Randament 92/42
• Directiva Joasă Tensiune 73/23 (modificată de 93/68)
• Directiva Compatibilitate Electromagnetică 89/336 (modificată de 93/68)
Preúedinte úi reprezentant legal
Cavaler al Muncii
Dante Ferroli
RO
Déclaration de conformité
Le constructeur : FERROLI S.p.A. Adresse: Via Ritonda 78/a 37047 San Bonifacio VR déclare que cet appareil est conforme aux directives CEE ci-dessous:
• Directives appareils à gaz 2009/142
• Directive rendements 92/42
• Directive basse tension 73/23 (modifiée 93/68)
• Directive Compatibilité Electromagnétique 89/336 (modifiée 93/68) Président et fondé de pouvoirs
Cav. du travail
Dante Ferroli
FR
Page 18
Page 19
FERROLI S.p.A.
Via Ritonda 78/a
37047 San Bonifacio - Verona - ITALY
www.ferroli.it
Loading...