Ferroli Econcept 50 A Installation And Operating Instructions Manual

Supplied By www.heating spares.co Tel. 0161 620 6677
ECONCEPT 50 A
WALL-HUNG, PRE-MIX
GAS-FIRED CONDENSING BOILER
INSTALLATION
OPERATING INSTRUCTIONS
Appr. nr. B99.15 A - CE 0063 BL 3475
cod. 3544205/0 ediz. 11/2002
Supplied By www.heating spares.co Tel. 0161 620 6677
ECONCEPT 50 A
IMPORTANT
Your “benchmark” Installation, Commissioning and Service Record Log Book will be enclosed in your customer information pack. “This record must be completed and left with the end user”.
Ferroli is a member of the Benchmark initiative and fully supports the aims of the programme. Benchmark has been introduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency. Please see installation and servicing guidlines.
CE MARK
CE mark documents that the Ferroli gas appliances comply with the requirement contained in European directives applicable to them. In particular, the appliances comply with the following CEE directives and the technical specifications provided from them:
• Gas appliances directive 90/396
• Efficiencies directive 92/42
• Low tension directive 73/23 (modified from the 93/68)
• Electromagnetic compatibility directive 89/396 (modified from the 93/68)
INSTRUCTIONS AND REGULATIONS
Assembly, installation, first start up and maintenance must be carried out by competent persons only, in accordance with all current technical regulations and directives.
c.o.s.h.h. Materials used in the manufacture of this appliance are non hazardous and no special precautions are required when servicing.
Related Documents
This appliance must be installed strictly in accordance with these instructions. The Gas Safety Regulations (Installations & Use) 1996. The Local Building Regulations. The Building Regulations. The Buildings Standards (Scotland - Consolidated) Regulations.
British Standards Codes of Practice:
B.S. 7593 1992 TREATMENT OF WATER IN DOMESTIC HOT WATER CENTRAL HEATING SYSTEMS B.S. 5546 1990 INSTALLATION OF HOT WATER SUPPLIES FOR DOMESTIC PURPOSES B.S. 5440 Part 1 2000 FLUES B.S. 5440 Part 2 1989 AIR SUPPLY B.S. 5449 1990 FORCED CIRCULATION HOT WATER SYSTEMS B.S. 6798 1987 INSTALLATION OF GAS FIRED HOT WATER BOILERS B.S. 6891 1989 GAS INSTALLATIONS B.S. 7671 1992 IEE WIRING REGULATIONS B.S. 4814 1990 SPECIFICATION FOR EXPANSION VESSELS B.S. 5482 1994 INSTALLATION OF LPG
Model Water Bye Laws
For Northern Ireland the rules in force apply
2
Supplied By www.heating spares.co Tel. 0161 620 6677
Econcept 50 A
• Read the warnings given in this manual thoroughly. They provide important in­formation for safe installation, use and maintenance
• Keep the manual safe for future consul­tation.
• The instruction manual is an integral and essential part of the product and must be kept by the user.
• If the appliance is sold or transferred to another owner or if the owner moves, leaving the appliance behind, always ensure that the manual is kept with the appliance for consultation by the new owner and /or installer.
• Incorrect installation or poor mainte­nance absolves the manufacturer from all liability for damage to persons or property.
• Installation and maintenance must be carried out and conform with current legislation, according to the manufac­turer’s instructions and by qualified per­sonnel.
• Incorrect installation and use or failure to follow the instructions provided by the manufacturer absolve the manufac­turer from all liability for damage.
• After unpacking, check that the con­tents are complete and undamaged.
• Keep packing out of reach of children as it may be potentially hazardous.
• To clean external parts, use a damp cloth moistened with soapy water if nec­essary. Avoid using abrasive cleaning products and solvents.
• Before cleaning or maintenance, dis­connect the appliance from the mains via the switch on the appliance or a suitable isolating device.
• In the event of malfunction or faulty operation, isolate the appliance. Do not attempt to repair or carry out any other operation on the appliance directly. Contact qualified personnel only.
• Repairs or the replacement of compo­nents must be carried out exclusively by qualified personnel using original spare parts only. Failure to respect the above my compromise the safety of the appli­ance.
• To guarantee efficient operation, the appliance must be serviced once a year by an authorised service centre.
• The appliance may not be used for pur­poses other than those for which it was explicitly designed. Any other use is considered improper and therefore dan­gerous.
3
Supplied By www.heating spares.co Tel. 0161 620 6677
ECONCEPT 50 A
1. CHARACTERISTICS AND TECHNICAL DATA .................................. 5
1.1 Introduction ................................................................................................. 5
1.2 Boiler control panel ..................................................................................... 5
1.3 Ignition and Shut-down ............................................................................... 6
1.4 Regulations .................................................................................................. 7
1.5 Maintenance ................................................................................................ 8
1.6 Fault codes .................................................................................................. 8
2. INSTALLATION ................................................................................ 9
2.1 General Instructions .................................................................................... 9
2.2 Positioning and wall mounting .................................................................... 9
2.3 Connection to the hydraulic system.......................................................... 10
2.4 Connection to the gas system................................................................... 11
2.5 Electrical connections ................................................................................ 12
2.6 Flues........................................................................................................... 14
2.7 Condensation discharge connection ......................................................... 19
2.8 Modular installation ................................................................................... 20
3. SERVICE AND MAINTENANCE .................................................... 22
3.1 Settings ...................................................................................................... 22
3.2 Commissioning and testing ....................................................................... 23
3.3 Maintenance .............................................................................................. 25
3.4 Troubleshooting......................................................................................... 26
4. OPERATING INSTRUCTIONS ........................................................ 28
4.1 Dimensions and connections ..................................................................... 28
4.2 General view and main components ......................................................... 29
4.3 Technical data table ................................................................................... 30
4.4 Diagrams .................................................................................................... 31
4.5 Wiring diagrams ........................................................................................ 32
4
Supplied By www.heating spares.co Tel. 0161 620 6677
Econcept 50 A
1. CHARACTERISTICS AND TECHNICAL DATA
1.1 Introduction
Dear Customer, Thank you for having chosen the Econcept 50 A, the latest generation of FERROLI wall-hung boiler, featuring
advanced design and cutting-edge technology. The Econcept 50 A is a pre-mix condensing thermal generator for heating , with very high thermal efficiency
and very low emissions, fired by natural gas or LPG. The boiler can be connected with external DHW storage. The boiler control and regulation system is microprocessor-based, with advanced self-diagnostics. The user
interface, made up of a keypad and display, is user-friendly, and shows the operating status of the appliance at all times. (The operating parameters and the data logs are saved internally and can be called up using the Personal Computer interface to simplify Service operations).
The heat output is regulated continuously across the entire operating range (also with DHW storage), with temperature-scrolling climate control, which automatically adapts the operating mode to the characteristics of the internal and external environment, of the building and its location, using external and internal sensors (optional extra).
1.2 Boiler control panel
Function of the buttons
MODE button - Use this button to scroll the parameters.
RESET button - Use this button to reset the operation of the boiler in the event of shut-
MODIFY button - Use these buttons to modify the regulation values.
CONFIRM button - Use this button to enable the set regulation value.
fig. 1
down.
Display D3
Display D2Display D1
Ignition switch
Display indications
D1
MODE display - Indicates the operating mode of the boiler or the selected parameter.
D2 D3
DATA display - Indicates value of the parameters
Led L1 - Indicates:Economy Operation
Led L2 - Indicates:Comfort Operation
5
Supplied By www.heating spares.co Tel. 0161 620 6677
Econcept 50 A
Operating indications on the display
During operation, without pressing any of the buttons the display shows the operating status of the appliance:
Operating mode
Display “D1” Display “D2/D3”
Standby
Heating
Domestic hot water
Standby following domestic hot water op.
Standby following heating op.
Waiting for DHW production
Central heating outlet temperature
Central heating outlet temperature
Domestic hot water temperature
Domestic hot water temperature
Central heating outlet temperature
Domestic hot water temperature
Note: when the burner fires a small. Will appear in display D1 after the letter.
Accessing the operating menu
Pressing the “ - mode” button once accesses the operating menu. Pressing the “ - mode” button again displays the following parameters and information in sequence:
DISPLAY D1 DISPLAY D2/D3
Summer/Winter Selection (00 = Summer - 11 = Winter) Economy/Comfort Selection (0 = Economy - 1 = Comfort) CH outlet temperature view and setting Display and setting DHW storage temperature Display system return temperature External temperature Flue gas temperature
-
­Boiler power Compensation curve setting
-
1.3 Ignition and Shut-down
Ignition
Check that any shut-off valves in the heating system and domestic hot water circuit outside of the boiler are open. Open the gas control upstream from boiler and press the main switch. The boiler will perform a self­test cycle lasting approximately one minute, at the end of which it is ready for operation. The ignition and shut-down of the burner assembly are completely automatic operations, which depend on the requirements of the heating system or domestic hot water circuit (display should read "FHI" during test).
6
Supplied By www.heating spares.co Tel. 0161 620 6677
Econcept 50 A
Shut-down
In the event of extended periods of inactivity close the gas control upstream from the boiler and disconnect the electrical power supply to the appliance. In this case, the boiler antifreeze protection function is also disabled; this function switches on the burner assembly when the heating system temperature falls below 5°C.
For extended periods of inactivity during the winter months, in order to avoid damage due to freezing, all the water should be drained from the boiler, both the domestic hot water and the heating system; alternatively, drain only the domestic hot water and introduce antifreeze into the heating system.
For short periods of inactiviti leave the power and gas turned on, the frost protection will activate if the appliance falls below 5°C, however, this will only protect the appliance. For system protection internal and external frost stat.
1.4 Regulations
Setting the heating system temperature
Set, using the room thermostat or remote control, the desired temperature inside the rooms. When acting on the room thermostat, the boiler is turned on and the heating system water is brought to the central heating outlet set temperature or calculated temperature (with temperature scrolling active). On reaching the required temperature inside the rooms, the boiler will switch off.
If no room thermostat or remote control is installed, the boiler will maintain the heating system temperature at the central heating outlet setpoint.
To set the central heating outlet temperature, access the operating menu, and using the button display parameter 1 – central heating outlet temperature. On pressing one of the buttons the display will start to flash, showing the outlet temperature setpoint. Use the buttons to set the required value. To activate the new value, press the button . To cancel the setting, do not press the button , and press
the button .
7
Supplied By www.heating spares.co Tel. 0161 620 6677
Econcept 50 A
Outside temperature compensation
When the (optional) external probe is installed, the boiler regulation system functions in “Outside temperature compensation” mode. In this mode, the temperature of the heating system is regulated according to the external climatic conditions, so as to guarantee a high degree of comfort and energy saving all year round. Specifically, when the external temperature falls, the central heating outlet temperature is increased, according to a pre-determined “compensation curve”.
In this mode, the temperature set in parameter 1 of the operating menu becomes the maximum central heating outlet temperature. This should be set to Maximum to allow the system to regulate over the entire working range.
The boiler must be set during installation by qualified personnel. Other minor modifications can be made by the user to improve the level of comfort: the compensation curve can in fact be modified by accessing the
operating menu with the button and scrolling the menu, again using the button, to parameter 9. The set compensation curve is displayed (refer to graph below). Pressing one of the buttons the display
starts to flash; use the buttons to set the required value. To activate the new curve, press the button
. To cancel the setting, do not press the button, and press the button .
If the ambient temperature is lower than the required value, it is suggested to set a higher curve, and vice­versa. Proceed with single unit increments or decreases, and check the results in the room.
Compensation curve
90
80
70
60
50
Temperatura
40
30
di mandata impianto C°
20
20 10 0 -10 -20
10
Temperatura esterna °C
9
8
7
6
5
4
3
2
1
1.5 Maintenance
This appliance must be serviced anually by an approved corgi engineer. The casing, the control panel and the aesthetic parts of the boiler can be cleaned using a soft and damp cloth.
Do not use abrasives or solvents.
1.6 Fault codes
In the event of operating problems, the display flashes and shows the code identifying the fault code. The display D1 is marked by the letter “F” and will temporary shut-down, this will reset automatically as soon
as the value returns within the boiler’s normal operating range. The display marked by the letter “A” causes a shut-down of the boiler which can be reset by the user. To reset operation, press the (reset) button.
If the problem persists, or for diagnosis if the fault codes (page 26), please refer to the “troubleshooting” chapter in this manual for more details.
8
Supplied By www.heating spares.co Tel. 0161 620 6677
Econcept 50 A
A A
B
D
C
2. INSTALLATION
2.1 General Instructions
Gas Safety (Installation & Use) Regulations: 1996 In the interest of safety, it is the law that all gas appliances are installed by a competent person in accordance
with the above Regulations, Building Regulations/Building Standards Scotland, Codes of Practice, current I.E.E. Regulations and the byelaws of the Local Water Undertaking. Failure to comply with the Regulations may lead to prosecution; it is your responsibility to ensure that the law is complied with.
N.B. For Northern Ireland the rules in force apply. IMPORTANT: If the boiler is to be fitted in a timber framed building it should be fitted in accordance with
the Institute of Gas Engineers document IGE/UP/7. If in doubt advice should be sought from the Local Supplier.
2.2 Positioning and wall mounting
The place of installation must be free of flammable objects or materials, corrosive gas, dust or volatile substances. The environment must be dry and not exposed to rain, snow or frost.
The installation of the ECONCEPT must be on a suitable non-combustible load bearing wall which will provide an adequate fixing for the boiler mounting bracket assembly. The location should be in an area where the water pipes will not be subjected to frost conditions. In siting the boiler the following limitations must be observed.
The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. wiring regulations and in Scotland the electrical provisions of the building regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower.
Where a room sealed appliance is installed in a room containing a bath or shower any electrical switch or appliance control utilising mains electricity must be situated so that it cannot be touched by a person using the bath or shower.
The boiler is supplied ready for wall-hung installation. The rear frame of the appliance has a series of slots for fastening it to the wall, using screws with metal wall plugs. The fastening to the wall must provide stable and effective support of the appliance.
If the appliance is enclosed in a cabinet or alongside another appliance, space must be allowed for normal maintenance operations. Fig. 2 shows the minimum and recommended space to be left free around the appliance.
WARNING!! This appliance must be installed in a room with sufficient ventilation, to avoid dangerous conditions arising in the event of, even minor, gas leaks. These safety standards are imposed by the EEC Directive no. 09/396 for all gas appliances, including the so-called sealed appliances.
For further instruction concerning devices installation in cascade, please refer to the related paragraph.
Minimum Recommended
5 cm
A B
5 cm
C 15 cm 20 cm
1,5 cm
D
(from any openable panel)
15 cm 30 cm
> 50 cm
Fig. 2
9
Supplied By www.heating spares.co Tel. 0161 620 6677
Econcept 50 A
2.3 Connection to the hydraulic system
Make the connections to the corresponding couplings, according to the positions indicated in Fig. 3. The discharge of the safety valve must be
connected to a funnel or collection pipe, to discarge against a wall approx 300mm from ground level.
Make the connections to the boiler so as its internal pipes are not subject to stress.
Note: Caution must be taken to ensure the discarge pipe cannot cause damage to persons en property in the event of discharge.
The appliance is not supplied with an expansion vessel, and therefore such device must be connected by the installer. Please note that the pressure in the system, when cold, must be between 0.5 and 1 bar.
Water treatment
If water treatment is used Ferroli Limited recommend only the use of Fernox or Sentinel water treatment products, which must be used in accordance with the manufacturers instructions. For further information contact:
50 120 145 145 120 50
1 2 3 4 5
1 CH flow 2 DHW flow 3 Gas inlet
4 DHW return 5 CH return 6 Safety valve
6
Fig. 3
Feronx Manufacturing Co. LTD. Sentinel Division Tandern house, Marlowe way Betz Dearborn LTD Croydon, surrey, CRO 4YS Widnes, Cheshire WA8 8ND Tel: 0870 5601 5000 Tel: 0151 424 5351
Note:
If the boiler is installed in an existing system any unsuitable additives must be removed by thorough cleasing. All systems should be cleansed according to B.S. 7593.
In hard water areas treatment to prevent lime scale may be necessary.
It is important that the correct concentration of the water treatment product is maintained in
accordance with the manufacturers instructions.
Water System
Note The boiler is designed for sealed systems only and must NOT be used on open vented systems.
Central Heating
Detailed recommendations are given in BS6798, BS5449, BS6700 and CP342 Part 2. Pipework not forming part of the useful heating surface should be insulated to prevent any heat losses or possible freezing (i.e. in roof spaces or ventilated underfloor spaces). Drain taps should be positioned at the lowest point of the system in accessible locations to permit the whole system to be drained down. The drain taps should be in accordance with BS2879. Copper tubing to BS2871, Part 1 is recommended for water carrying pipework. Pipework in horizontal runs should have a gradient where possible to facilitate the removal of air. Ensure that the boiler heat exchanger is not a natural point for air collection.
10
Supplied By www.heating spares.co Tel. 0161 620 6677
Econcept 50 A
aa
a
aaa
Kit 1KWMH17A
Cylinder not supplied
Make Up Water
Provision must be made for replacing water lost from the sealed system. Reference should be made to BS6798, for methods of filling and making up sealed systems. There must be no direct connection between the boiler's central heating system and the mains water supply. The use of mains water to charge and pressurise the system directly, is conditional upon the Local Water Byelaws. Again any such connection must be disconnected after use.
Always connect and filling device to the return pipework
DHW calorifier connection(Optional kit 1KWMH17A)
The optional kit 1KWMH17A is available for connection with an external cylinder. The kit, which includes circulator, cylinder feeler and hydraulic pipe fittings, has to be mounted inside the cylinder, according with instruction contained in the kit itself. Then the connections have to be joined to the cylinder.
2.4 Connection to the gas system
If necessary the local Gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas.
An existing service pipe must not be used without prior consultation with the Local Gas supplier.
A gas meter can only be connected by the Local Gas supplier, or by a Local Gas suppliers Contractor.
Installation pipes should be fitted in accordance with BS6891.
Appliance inlet working pressure must be 20mbar MINIMUM, for NG and 37 mbar minimum for LPG. Pipework from the meter to the boiler must be of an adequate size. Do not use pipes of a smaller size than the boiler inlet gas connection. The complete installation must be tested for gas soundness and purged as described in BS6981. All pipework
must be adequately supported. An isolating gas valve should be fitted on the boiler gas inlet. Please wait 10 minutes when lighting from cold before checking gas rate. Gas pressures should be checked after the boiler has operated for 10 minutes to ensure thermal equilibrium.
Fig. 4
11
Loading...
+ 23 hidden pages