FBD FBD553D Installation, Operation And Service Manual

Page 1
Please refer to the FBD web site (www.fbdfrozen.com) for information relating to FBD Installation and Service Manuals, Instruction Sheets, Technical Bulletins, Service Bulletins, etc.
INSTALLATION, OPERATION, AND SERVICE MANUAL
FOR THE
MODEL FBD553D
FROZEN BEVERAGE DISPENSER
SPECIFICATIONS
DIMENSIONS
Width 20.25 inches (511 mm) Depth 33.5 inches (851 mm) Height (Countertop Unit With Door) 41.4 inches (1054 mm) Height (Optional Roll Around Unit/Stand) 68.0 inches (1727 mm)
WEIGHT
Shipping 415 pounds (188 kg) Empty 365 pounds (165 kg) Operational 390 pounds (177 kg)
WATER REQUIREMENTS
Minimum flowing pressure 30 PSIG (206.8 KPa) Maximum static pressure 70 PSIG (483.0 KPa)
CARBON DIOXIDE (CO
Minimum pressure 70 PSIG (483.0 KPa) Maximum pressure 75 PSIG (517.5 KPa)
2) REQUIREMENTS
NOTICE:
The information contained in this document is subject to change without notice.
FBD MAKES NO WARRANTY OFANY KIND WITH REGARD TO THIS MATERIAL, INCLUDING, BUT NOT LIMIT­ED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. FBD shall not be liable for errors contained her ein orfor incidental consequential damages in connection with the furnishings, performance, or use of this material.
This document contains proprietary information which is protected by copyright. All rights reserved.
© Copyright 2006 by FBD, all rights reserved.
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION
This manual must be read and understood before the installation and operation of this dispenser.
This manual supersedes and replaces 24-2116-0001 dated 06/27/05.
FBD Partnership, LP
P.O. BOX 18597. • SAN ANTONIO, TX 78218 USA •
210-637-2800 • FAX 210-637-2844 www.fbdfrozen.com •
FBD TECHNICAL SUPPORT • 1-866-323-2777 • TECHNICAL SUPPORT FAX 1-210-637-2832
REV: 10/25/06 FBD Part Number: 24-2116-0001
Page 2
TABLE OF CONTENTS
SPECIFICATIONS...................................................................................................................................COVER
TABLE OF CONTENTS......................................................................................................................................i
SAFETY PRECAUTIONS ..................................................................................................................................ii
1. PREPARING THE LOCATION ....................................................................................................................1
1.1 LOCATION REQUIREMENTS ...........................................................................................................1
1.2 ADDITIONAL REQUIREMENTS........................................................................................................1
2. RECEIVING AND UNPACKING UNIT.........................................................................................................1
2.1 RECEIVING........................................................................................................................................1
2.2 UNPACKING ......................................................................................................................................1
3. INSTALLING THE UNIT..............................................................................................................................1
3.1 FLUSH MOUNTING...........................................................................................................................1
3.2 ROLL AROUND CART .......................................................................................................................2
4. CONNECTING TO ELECTRICAL POWER ................................................................................................2
5. CONNECTING WATER, CO2, AND SYRUP SUPPLIES ............................................................................3
5.1 WATER SUPPLY................................................................................................................................3
5.2 CO2 SUPPLY......................................................................................................................................3
5.3 SYRUP SUPPLY................................................................................................................................4
6. STARTING THE UNIT .................................................................................................................................4
6.1 INITIAL POWER-UP...........................................................................................................................4
6.2 BRIXING.............................................................................................................................................5
6.3 FILLING THE CHAMBER...................................................................................................................6
CRITICAL REGULATOR AND FLOW CONTROL SETTINGS.........................................................................7
7. OPERATION OF THE DISPENSER ............................................................................................................7
7.1 OPERATING ELECTRONIC CONTROLS .........................................................................................7
7.2 MACHINE ACCESS .........................................................................................................................11
7.3 MACHINE SETTINGS ......................................................................................................................12
7.4 READOUTS......................................................................................................................................13
8. CLEANING AND SANITIZING THE UNIT ................................................................................................13
8.1 GENERAL INFORMATION..............................................................................................................13
8.2 REQUIRED CLEANING EQUIPMENT.............................................................................................14
8.3 DAILY CLEANING OF THE UNIT....................................................................................................14
8.4 SANITIZING THE SYRUP SYSTEMS .............................................................................................14
9. BASICS OF OPERATION .........................................................................................................................15
9.1 MAKING ADJUSTMENTS TO THE FBD553D .................................................................................15
10. CHANGING FACTORY SET “LEVEL CONTROL” ..................................................................................16
10.1 BEFORE CHANGING “LEVEL CONTROL” SETTINGS..................................................................16
10.2 DRINK TOO HARD AND COLD.......................................................................................................17
10.3 DRINK TOO LIQUID ........................................................................................................................17
10.4 CHANGING THE DEFAULT LEVEL CONTROL SETTING .............................................................18
11. CHANGING FACTORY THAW AND FREEZE SETTINGS.......................................................................18
11.1 BEFORE CHANGING THAW AND FREEZE SETTINGS................................................................18
11.2 CHANGING THAW AND FREEZE SETTINGS................................................................................19
12. BEVTRAK OPERATION ............................................................................................................................19
12.1 NAVIGATING THE BEVTRAK MENU ..............................................................................................19
12.2 NORMAL OPERATION....................................................................................................................20
13. CRITICAL INFORMATION........................................................................................................................20
13.1 DEFROST AND RUN TIME DELAY .................................................................................................20
13.2 CHAMBERS 90% FULL ON INITIAL SET UP .................................................................................20
13.3 LINE VOLTAGE DROP ....................................................................................................................21
13.4 LONG TUBING RUNS .....................................................................................................................21
14. TROUBLESHOOTING GUIDE..................................................................................................................21
MECHANICAL............................................................................................................................................21
ELECTRICAL.............................................................................................................................................23
ELECTRONIC CONTROLS.......................................................................................................................25
REFRIGERATION......................................................................................................................................25
DRINK QUALITY........................................................................................................................................27
LCD DISPLAY ERROR MESSAGES .........................................................................................................29
LCD DISPLAY MESSAGES.............................................................................................................................32
LCD DISPLAY ERROR MESSAGES ..............................................................................................................33
WARNING LIGHTS ..........................................................................................................................................33
i
Page 3
15. ILLUSTRATIONS, PARTS LISTINGS, AND DIAGRAMS.........................................................................34
15.1 MOUNTING DIAGRAM ..................................................................................................................34
15.2 FLOW DIAGRAM/SCHEMATIC ......................................................................................................35
15.3 ELECTRICAL/SCHEMATIC-01.......................................................................................................36
15.4 ELECTRICAL/SCHEMATIC-02.......................................................................................................37
15.5 FRAME SUB ASSEMBLY...............................................................................................................38
15.5 ELECTRICAL BOX ASSEMBLY.....................................................................................................39
15.7 FAN SHROUD ASSEMBLY............................................................................................................40
15.8 REFRIGERATION COMPONENTS ..........................................................................................41-42
15.9 FREEZE PACK/MANIFOLD ASSEMBLIES....................................................................................43
15.10 TEMPERATURE SENSOR REPLACEMENT.................................................................................44
15.11 MISCELLANEOUS COMPONENTS.........................................................................................45-46
15.12 EXPANSION TANK ASSEMBLIES.................................................................................................48
15.13 BEATER BAR ASSEMBLIES....................................................................................................49-50
15.14 CONTROLLER BOARD ASSEMBLY.............................................................................................52
15.15 HEADER SUB ASSEMBLIES ...................................................................................................53-54
15.16 HEADER ASSEMBLY................................................................................................................55-56
15.17 PRODUCT HEADER ASSEMBLIES ..............................................................................................57
15.18 FRONTASSEMBLIES....................................................................................................................58
15.19 OUTER COMPONENTS................................................................................................................59
15.20 DDV NOZZLE AND FACE PLATE ASSEMBLY..............................................................................60
15.21 RETRO MERCHANDISER DOOR, FBD553 (7-11) .......................................................................61
SAFETY PRECAUTIONS
We at FBD are concerned about your safety. Please carefully read the following precautions before working with the FBD553D unit. This will familiarize you with proper equipment handling techniques.
LIFTING
To avoid personal injury or damage, do not attempt to lift the unit without help. The empty unit weighs approximately 365 pounds (165 kg). The use of a mechanical lift is recommended.
Use gloves to protect hands from being injured by the edges of cross bracing if lifting by hand.
Use proper equipment and lifting techniques when lifting or moving equipment. The unit is top heavy. Maintain unit in a vertical, upright position when lifting and positioning the unit.
ELECTRICAL
This unit must be properly electrically grounded to avoid possible fatal electrical shock or serious injury to the operator. The power cord is provided with a three prong grounded plug. If a three-hole grounded electrical outlet is not available, use an approved method to ground the unit. Only qualified
electricians should perform this task and the work performed should meet all applicable codes.
Always disconnect electrical power to the unit to prevent personal injury before attempting any internal maintenance. Only qualified personnel should service internal components of electrical wiring.
CARBON DIOXIDE (CO
2)
•CO2 (carbon dioxide) displaces oxygen. Strict attention must be observed in the prevention of CO2 gas leaks in the entire CO2 and soft drink system. If a CO2 gas leak is suspected, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentrations of CO2 gas will experience tremors which are followed rapidly by loss of conscious­ness and suffocation.
To avoid personal injury and/or property damage, always secure CO
2 cylinders in an upright position
with a safety chain to prevent cylinders from falling over. Should the valve become accidentally damaged or broken off, a CO
2 cylinder can cause serious personal injury.
ii
Page 4
1. PREPARING THE LOCATION
2
INCHES
12 INCHES
2
INCHES
2
INCHES
1.1 LOCATION REQUIREMENTS
A. The operational FBD553D countertop unit
weighs 390 pounds (177 kg) and requires a sturdy, level surface for placement. When selecting a counter location, ensure the counter will support the unit weight plus the weight of any additional equipment placed near it.
B. Adequate space above and behind the unit
(See Figure 1.1) is required to allow:
1. Removal of side panels, if service is
Air Circulation
necessary.
2. Air circulation around vents on sides, back, and top of unit.
C. A well-ventilated room is required with a temperature of 50°F to 90°F (10°C to 32.5°C). The
environment, however, should be stable and not subject to abrupt changes in temperature.
D. The unit should not be exposed to direct sunlight or chemicals.
1.2 ADDITIONAL REQUIREMENTS (TO BE PROVIDED BY THE CUSTOMER)
A. CO
2 supply with a pressure of 70-72 PSIG (482.6 to 496.4 KPa). If a bulk CO2 supply is used,
the pressure should be set at 115 to 120 PSIG (793.5 to 828.0 KPa) and a secondary regulator installed at the unit to reduce the pressure to 70-72 PSIG (482.6 to 496.4 KPa).
B. Syrup supply - Bag-in-Box or five (5) gallon syrup tank (figal). C. Water supply with a minimum flowing pressure of 30 PSIG (206.8 KPa) and a maximum static
pressure of 70 PSIG (483.0 KPa).
2. RECEIVING AND UNPACKING UNIT
Figure 1.1
2.1 RECEIVING
Each unit is tested and thoroughly inspected before shipment. At the time of shipment, the carrier accepts the unit and any claim for damages must be made with the carrier. Upon receiving the unit from the delivering carrier,carefully inspect carton for visible indication of damage. If damage exists, have carrier note same on bill of lading and file a claim with the carrier.
2.2 UNPACKING
A. Cut banding from shipping carton and remove carton by lifting up. Remove protective side
panels and four corner protectors.
B. Remove drip tray assembly, accessory kit and manual from top packaging. Contact the dealer
if any parts are missing or damaged. C. Remove side panels from unit. D. Inspect unit for concealed damage. If evident, immediately notify delivering carrier and file a
claim against same. E. Lift unit up by the frame cross bracing and remove lower portion of carton. F. Remove shipping board from bottom of unit by accessing and removing the bolts located on the
underside of the shipping board.
3. INSTALLING THE UNIT
There are several ways to install the unit. Follow the appropriate directions for the method you are using. Insure that there is a minimum of twelve (12) inches (30.48 cm) ABOVE and two (2)
inches (5.08 cm) on the SIDES and BEHIND the unit for proper ventilation (see Figure 1.1).
3.1 FLUSH MOUNTING
Flush mounting is when the unit is mounted on a countertop. Follow the following guidelines to ensure a proper installation.
A. Be sure the counter will support 390 pounds (177 kg) the full length of the unit (including the drip
tray). If permanently mounting the unit to a countertop, use the information in Section 14.1 to
1
Page 5
240V
120V
120V
mark and drill the four (4) mounting holes in the countertop. B. With the side panels removed, lift unit by the frame cross bracing and place unit on the counter. C. If permanently mounting the unit to a countertop, install four (4) 3/8-16 UNC bolts (not included)
through the underside of the counter [through the four (4) mounting holes drilled in the step just
above], and into the frame. D. When the dispenser is to be permanently mounted to the counter top, seal dispenser base to
counter top with a bead of clear silicone caulk or sealant which provides a smooth and easily
cleaned bond to the counter.
3.2 ROLL AROUND CART
Aroll around cart is used when a suitable countertop is not available and allows the unit to be moved for cleaning. These can be purchased from the dealer.
A. Lock the wheels on the roll around cart. B. With the side panels removed, lift unit by the frame cross bracing and place the unit on the cart. C. Secure the unit to the cart by installing four (4) 3/8-16 UNC bolts (not included) through the cart
mounting holes and into the frame of the unit. D. When the dispenser is to be permanently mounted to the roll around cart, seal dispenser base
to cart with a bead of clear silicone caulk or sealant which provides a smooth and easily cleaned
bond to the counter.
4. CONNECTING TO ELECTRICAL POWER
Ground
Continuity
Figure 4.1
Figure 4.2
Use the following guidelines to connect electrical power to the machine for both 50 and 60 Hz service.
A. The machine requires single phase 230VAC. If line voltage is below 215VAC or above 245VAC,
a 10% buck and boost transformer must be used. If a buck and boost transformer is installed,
ensure that the boosted leg is on L1 of the contactor. Operation below 215VAC or above
245VAC may damage the unit and cause inconsistent performance. This also voids all
warranties.
B. If connected to a "delta" three phase electrical system, use the two low volt age legs (check each
leg to ground to insure the low voltage legs are used). Using the high voltage leg will cause
the machine to malfunction. In some locations, the power supply may have only one 230 volt
hot leg. If so, ensure the hot leg goes to the L1 contactor in the electrical box.
C. This unit will not work properly if there is more than a 10V voltage drop in the power supply line
between the power source and the machine. A drop of more than 10V indicates undersized
wiring or excessively long runs.
D. The unit must be installed on a "single branch" circuit (on a circuit by itself), protected by 30 Amp
service and a 30 Amp fuse (or circuit breaker).
E. It is recommended that a 3 conductor, 30 Amp receptacle (NEMA#L-630-R) be used. Using a
voltmeter, check voltage across both "hot legs" (240VAC) and between ground and each "hot
leg" (120VAC) to ensure proper wiring and voltage (see Figure 4.1).
F. Remove the plug from the power cord and feed the cord through the strain relief located at the
back of the unit. Tighten the strain relief securely. Reinstall the plug on the power cord and
check for continuity on the plug across both "hot legs" and no continuity between each "hot leg"
and ground (see Figure 4.2).
G. Do not connect the unit to power at this time.
2
Page 6
5. CONNECTING WATER, CO2, AND SYRUP SUPPLIES
5.1 WATER SUPPLY IMPORT
ANT
A W ATER PUMPAND WA TER REGULATOR ARE INSTALLED IN THE BASE OF THE MACHINE. A WATER FILTER SHOULD BE INSTALLED IN THE WATER LINE BEFORE BEING CONNECTED TO THE MACHINE. FLUSH THE FILTER WITH SEVERAL GALLONS (12-15 LITERS) OF WATER PRIOR TO USE TO INSURE BLACK CARBON "FINES" ARE NOT FED INTO THE FREEZING CHAMBER.
DRAIN
WATER
R SYRUP L SYRUP
SUPPLY
TO UNIT
Figure 5.1
CAUTION:
THE BACKFLOW PREVENTION DEVICE (FBD PN 12-2272-0001) MUST HAVE A DRAIN LINE CONNECTED TO THE VENT (SEE FIGURE 5.1). THIS IS REQUIRED TO DRAIN AWAY WATER IN THE EVENT OF A BACKFLOW SITUATION OR A FAILURE OF THE BACKFLOW DEVICE. FAILURE TO DO SO MAY RESULT IN FLOODING OF THE ESTABLISHMENT.
NOTE:
Water pipe connections and fixtures directly connected to a potable water supply shall be sized, installed, and maintained in accordance with federal, state and local codes.
A. Connect the backflow prevention assembly to the water inlet of the unit (see Figure 5.1). The
backflow prevention assembly is provided with the unit.
B. Fabricate a 3/8 inch supply line for connecting the unit to a potable water supply (a 3/8” barb by
1/4” flare nut fitting will be required).
C. Install a shutoff valve in the water line as close to the unit as practical and convenient. The use
of a water filter is recommended.
D. Clear the line by running a minimum of two (2) gallons (7.57 liters) of water through the line
before attaching the line to the unit.
E. Connect the line to the bulkhead fitting labeled "WATER IN" located at the rear of the unit (see
Figure 5.2).
F. Do not turn water on at this time.
5.2 CO
2 SUPPLY
NOTE:
The CO2 supply may come from either an independent tank/regulator or a bulk CO2 system. If connected to a bulk CO2 system, ensure the bulk regulator is set at 115 to 120 PSIG (793.5 to
828.0 KPa)] and install a shutoff valve and a secondary supply regulator [to be set at 70-72 PSIG (482.6-496.4 KPa)] in the line. Ensure that the CO
on the bulk supply and is not branched off down line. Failure to do so may starve the unit
2 flow and cause performance problems.
of CO
A. Fabricate a 3/8 inch supply line for connecting the unit to a CO B. Connect the supply line to the CO2bulkhead fitting labeled "CO2
unit (see Figure 5.2). A3/8” barb by 1/4” flare nut fitting will be required to make connection.
C SYRUP
WATER
CO2
Figure 5.2
2 line comes directly from the main branch
supply.
2
IN" located at the rear of the
3
Page 7
C. Splice a barb "cross" into the CO
2 supply line and run two (2) lines to the syrup pump CO2 inlets.
Or
If Figal tank will be utilized, splice a barb "cross" into the CO2 supply line and run three (3) lines to tank location and install CO2 tank couplers to end of lines.
D. Do not turn on the CO2 at this time.
5.3 SYRUP SUPPLY
The unit may be connected to either a BIB (Bag-in-Box) or a five-gallon syrup supply (figal). Use the appropriate connection method below.
NOTE
Installations requiring long runs of tubing [25 feet or more (7.62 meters)] may encounter pressure fluctuation problems. The machine's sensors may indicate that the machine is out of syrup, water, or CO2. To avoid pressure fluctuations, consider the following solutions.
A. Increase the tubing size to 3/8 inch diameter. B. Install booster pumps in the supply lines. Use a vacuum regulating valve with syrup booster
pumps.
C. Increase primary CO
2 regulator pressure from bulk or tank CO2 to 105 - 120 PSIG (723.9 to
828.0 KPa). A secondary regulator WILL be necessary for syrup pumps to avoid exceeding manufacturer’s recommended operating pressures. Set the secondary regualtor to 70-72 PSIG (482.6 to 496.4 KPa).
BIB SUPPLY
A. Fabricate three (3) 1/4 inch supply lines for connecting the unit to the syrup pumps. B. Connect the lines to the bulkhead fittings labeled "SYRUP LEFT", "SYRUP CENTER" and
"SYRUP RIGHT" located at the rear of the unit (see Figure 5.2).
C. Do not turn on the CO
2 at this time.
FIVE GALLON (FIGAL) TANK SUPPLY
A. Fabricate three (3) 1/4 inch supply lines for connecting the unit to the syrup tanks. B. Connect the lines to the bulkhead fittings labeled "SYRUP LEFT", "SYRUP CENTER" and
"SYRUP RIGHT" located at the rear of the unit (see Figure 5.2).
C. When using five gallon (figal) syrup tanks, a Syrup Restart Valve (SRV) and tank couplers
must be used on each line. Warranties will be void if an SRV is not installed.
1. The "OUT OF" devices in the machine will not function properly without the use of a Syrup Restart Valve. If the "OUT OF" devices do not function, the machine will supply only water to the product cylinder and it will freeze up.
2. When replacing a figal, insure that the syrup line to the dispenser is attached to the figal before the CO
2 line is attached to the figal. This will allow the SRV to work properly.
3. To operate the SRV, press the restart button after syrup tank is changed. The red light beside each chamber will then go out and product will refreeze.
D. Do not turn on the CO
2 at this time.
6. STARTING THE UNIT
6.1 INITIAL POWER-UP
A. Insure the electrical power is disconnected from the
unit.
B. Open front marquee door, if installed, by firmly
pulling back at the bottom and rotating up and over.
C. Using a Phillips head screwdriver, remove the
stainless steel access panel located below the keypad.
D. Remove the splash plate and electric box cover
(see Figure 6.1).
E. Plug unit in to the electrical power . Check for the display of information on the LCD control p anel
(this will read "COPYRIGHT" on bottom line of LCD display).
COVER
Figure 6.1
4
Page 8
F. With voltage meter, check voltage at contactor between L1 & L2 and record. Also check
between L1 and ground bar, and between L2 and ground bar, to ensure highest voltage leg is on L1 (see Figures 6.2, 6.3, and Section 14.3).
H. Access the “Line Voltage” readout in the "SERVICE MENU\READOUTS\COMMON
READOUTS" section of the LCD menu. If the “Readout” voltage is more than two (2) volts
different than the voltage across L1 and L2, the "Voltage Offset" must be changed.
Failure to do so will cause performance loss of the unit. To change the "voltage offset", go to "SERVICE MENU\MACHINE SETTINGS\COMMON SETTINGS" and enter the difference between the meter reading and the “Line Voltage” readout to make the LCD voltage reading match the L1 and L2 voltage. Reinstall the splash plate and electric box cover.
L1
L2
Figure 6.2
6.2 BRIXING
A. With the unit powered up, press both of the "OFF" buttons on the display to ensure the unit is
in the OFF state.
CAUTION
CHECK ALL SUPPLY LINES TO INSURE THAT THEY ARE CONNECTED TO THE CORRECT FITTINGS. IF LINES ARE NOTCONNECTED PROPERLY, COMPONENTS WILL BE DAMAGED.
B. Open the water supply valve and check all water line connections for leaks. C. Connect the BIB connectors, or the syrup and CO
supply connections at the rear of the machine for leaks
D. Open the CO2 tank valve and adjust the primary tank regulator until the "CO2 Pressure"
readout in the "SERVICE MENU\ READOUTS\ COMMON READOUTS" reads 70-72 PSIG (482.6 KPa to 496.4 KPa). Check all CO
E. Adjust the CO2 secondary regulator (located inside the machine) to read 28-32 PSIG (193.2 to
220.8 KPa) according to the LCD readout found in the "REGULATED CO2" readout in the "SERVICE MENU\ READOUTS\ COMMON READOUTS" section of the LCD menu.
IMPORT
SET ALL PRESSURES USING THE LCD READOUTS ON THE UNIT - NOT BY THE GAUGES ON THE REGULATORS!
F. Close Syrup flow controls by backing (counter-clockwise) controls all the way out (see Figure
6.4).
G. Using water only, check the flow rate (through the sample valve) and set water flow to provide
a flow of 15 ounces in 10 seconds using a graduated container. Do this for both left and right side flow controls. Turn control adjustment screw clockwise to increase flow or
counter-clockwise to decrease flow.
H. Pre-set Syrup flow by turning in Syrup flow controls four (4) turns (clockwise). I. Place a container under the sample tube and fully depress the sample valve until a good water
and syrup mixture is obtained. Sample tube is located inside unit. This sample should be
discarded.
J. Place a sixteen (16) ounce (0.473 l) cup under sample tube and fully depress the sample valve
until 9 - 12 ounces (0.266 - 0.355 liter) have been dispensed into cup.
2 line connections for leaks.
ANT!
2 couplers, to figal tanks. Check all syrup
Figure 6.3
5
Page 9
Figure 6.4
K. Measure the brix with a refractometer. Set brix to between 13.5 and 15.0 by adjusting the syrup
brix flow controller clockwise to increase brix level or counter-clockwise to decrease brix level.
If the brix requires adjustment, discard a sample before checking the brix again.
NOTE
Do not adjust the brix with the water flow control setting unless you are unable to obtain the desired brix with adjustments to the syrup flow control.
Brix reading is affected by temperature. Samples taken from the chamber should be at the same temperature as from the sample valve.
L. Repeat steps I, J, and K for other side and center.
6.3 FILLING THE CHAMBER
A. Access "CO
2 SOL" by going to the "SERVICE MENU\MANUAL ON/OFF" section of the service
menu.
by activating the CO2 solenoid.
B. Displace the air in the chamber with CO
2
1. Pull and hold the relief ring until the escaping, rushing air sound almost stops; then release
the ring. Allow the pressure to rebuild in the tank.
2. Repeat this procedure at least two more times until the air has been displaced by the CO
Remember to deactivate the CO2 solenoid upon completion.
C. Repeat steps Aand B above for the center and right side of unit. Remember to deactivate the
2 solenoid upon completion.
CO
D. With CO
2 in the chamber, press the left side "FILL" button to begin filling the chamber with prod-
uct. If the chamber does not fill, gently pull the Relief Ring until filling begins and then release. As the chamber fills, the pressure in the chamber will increase until it rises above the PSI fill point. At this point, the chamber will stop filling and the LCD will readout "Fill Hold". It will then be necessary to pull the relief ring to relieve the pressure and allow filling to continue. Slowly pull the relief ring until the pumps activate, then release. Repeat the venting process until the
chamber is 90% full (level with relief valve), then press Fill button to turn OFF. Fill one (1) chamber at a time.
E. Repeat steps A, B, C, and D for the center and right chambers. F. Press the "DEFROST" and then the "RUN" buttons for all barrels to begin the freezing process.
The beater motors will begin to run but the compressor will wait for two (2) minutes before starting. After the two (2) minute waiting period, the machine will defrost and then begin the freeze cycle.
G. After an initial freeze down [approximately ten (10) to twelve (12) minutes], the product will be
frozen and ready to dispense.
NOTE
On an initial freeze down, products must be given adequate time to absorb CO2. Until CO2 is properly and adequately absorbed, drinks could be too "wet" or too "heavy". If adjustments are necessary, refer to section 9.
H. Re-check CO
2, Water, and Syrup lines for leaks.
6
2.
Page 10
CRITICAL REGULATOR AND FLOW CONTROL SETTINGS
FBD
FWDBACK SELECTCANCEL
OFF
RIGHT SIDE
FILL BEATER
RUN
DEF.
LEFT SIDE
FILL BEATER
RUN
OFFDEF.
CENTER
FILL BEATER
RUN
OFFDEF.
SET ALL PRESSURES USING THE LCD READOUTS ON THE UNIT - NOT
BY THE GAUGES ON THE
REGULATORS!
2 PRIMARY REGULATOR The CO2 Primary Regulator MUST BE SET TO 70-72 PSIG (482.6
CO
TO 496.4 KPa) [bulk tank set at 115-120 PSIG (793.5 - 828.0 KPa)].
CO2 SECONDARY REGULATOR The CO2 Secondary Regulator SHOULD BE SET AT 28-32 PSI
(Secondary Regulator) (193.2 TO 220.8 KPa) STATIC PRESSURE. The CO2 Secondary Regulator is on the header assembly which is behind the access panel. This regulator is a “non-vent” regulator. This means that if you lower the regulator setting, you will need to dispense drinks (with “Fill” activated) until cylinder begins to refill before the new setting will register on the gauge.
FLOW CONTROLLERS WATER FLOW MUST BE SET TO PROVIDE A FLOW OF 15
OUNCES IN 10 SECONDS BEFORE ADJUSTING THE BRIX. BRIX MUST BE SET BETWEEN 13.5 -15. Flow controllers are on the
header assembly. A sample may be taken by fully depressing the sample valve while "FILL" is in the "OFF" position.
7. OPERATION OF THE DISPENSER
7.1 OPERATING ELECTRONIC CONTROLS
A. The electronic machine controls are designed to provide a logical sequence of operation with a
minimum of written instruction. System operating parameters are selected and set from a menu.
B. LEFT, CENTER, and RIGHT Buttons (see Figure 7.1).
1. Each barrel has five (5) active buttons. They are labeled FILL, BEATER, RUN, DEF (defrost), and OFF.
2. Each button operates a double acting switch. Pressing the button once activates the process. Pressing the button a second time deactivates the process. Take care not to double press the buttons when first activating a process.
The RUN button initiates the freeze process. After pressing this button, the
RUN
beater motors will run for two minutes before the compressor starts. This delay eliminates the possibility of "short cycle" damage to the compressor.
OFF
Run also maintains the flow of product into the chambers when needed.
The OFF button turns off all the machine's refrigeration and chamber refill systems. All of the electronic controls are still active.
Figure 7.1
7
Page 11
BEATER
The BEA TER button activates the beaters inside the freezing chambers. The beaters can be activated to mix the slurry.
NOTE:
The beaters start automatically when the RUN or DEF buttons are pressed.
The DEF button allows the user to manually defrost chamber. Because the unit automatically defrosts during the day, it is not necessary to defrost
DEF
manually. However, this button provides the option to do so if desired. If the defrost is manually activated, the unit will return to the previous mode (after completion of the defrost).
NOTE:
If the machine is in the "OFF" state when the DEF button is pushed, there will be a two (2) minute delay before the compressor starts.
The FILL button activates the solenoid valves that allow product to flow into
FILL
the freezing chambers (providing the pressure in the barrel is low enough to allow a fill). Each chamber should be filled to 90% of chamber capacity (level with the relief vent valves) prior to start-up.
C. Common Controls and Displays
1. The four (4) control buttons, located below the LCD display, allow access to the various menu levels for the machine (see Figure 7.1).
CANCEL
BACK
FWD
The CANCEL button cancels any current operation and steps the operator back one (1) level in the menu.
The BACK button steps the operator backwards within the current level. This button also allows the operator to decrease or lower values (numbers).
The FWD button steps the operator forward within the current level. This button also allows the operator to increase or raise values.
The SELECT button allows the operator to enter changes in the unit
SELECT
programming and it also allows the operator to move into different levels in the menu.
2. The LCD display screen in the center of the control panel allows the operator access to unit status, settings, and operational information (see Figure 7.2). The screen is divided into four (4) sections. The upper portions of the screen display the current status of each cham­ber. The lower half of the screen displays a mode that can be changed or monitored.
D. Explanation of the Menu Structure (See Figure 7.3)
1. Access to the control panel is separated into two (2) levels. These levels have been
established to make certain information available to the operators and other information available to service personnel.
Level One This CUSTOMER MENU level is designed for the machine operator at the
store level. The store operator should only access this level of information,
and should NOT access or make changes in the SERVICE MENU without prior authorization and approval.
Level Two The SERVICE MENU has been established for the use of authorized service
technicians ONLY. This level provides access to all setup values that will
8
Page 12
FBD
FWDBACK SELECTCANCEL
OFF
RIGHT SIDE
FILL BEATER
RUN
DEF.
LEFT SIDE
FILL BEATER
RUN
OFFDEF.
CENTER
FILL BEATER
RUN
OFFDEF.
SIDE 1 STATUS
MODE DISPLAY
SIDE 2 STATUS
optimize the operation of the machine. Incorrect settings at this level could prevent the machine from operating properly or cause damage to the unit. Included in this level are various accumulated totals and diagnostic tools that help the technician evaluate problems.
NOTE
To access the Service Menu, press the FWD button on the control panel until “SERVICE MENU” displays. Press the unmarked button on the right side of the panel. The service menu has been accessed when “MACHINE SETTINGS” displays. Press FWD to access other options.
E. How to Access and Change Values
The same procedure for changing values applies to all access levels. The following steps allow the parameters of the control system to be monitored and changed.
1. The current mode is displayed in the lower half of the LCD. Press the FWD button to step to the next mode. Continue pressing the FWD or BACK button until the desired mode is displayed. When the desired mode is displayed, press SELECT to enter the mode.
2. To make changes to the displayed mode, press the SELECT button. When a value in the lower half of the display begins to flash, this indicates that the value can be changed.
3. To change the value, press the FWD button to increase the value or the BACK button to decrease the value. Any on/off functions can be changed by pressing the SELECT button.
4. Once the desired value is displayed, press the SELECT button to enter the value into the computer. Pressing the SELECTbutton will stop the display from flashing. When the value stops flashing, it has been changed.
NOTE:
When entering TIME, WAKE, or SLEEP functions, both the hours and minutes must be selected before the computer will accept the change. For the Defrost Times, days in upper case (capitals) are selected. Days in lower case are NOT selected.
Figure 7.2
NOTES
9
Page 13
Baseline
Thaw Base
Freeze Base
FFreeze Base
Cutoff LO %
Current Thaw
Current Freeze
Current FFreeze
Base
Thaw/Freeze
Left Side Settings
Center Settings
Right Side Settings
Readouts
Machine
Settings >
Version
Copyright
Customer Menu
Fault Code
History >
Time
Date
Base
Liquid Level
Full Base PSI
Rfill Base PSI
PressConFac
Current Full
Current Rfill
Base
Refrigeration
H2O Reset 50
H20 Out 45
CO2 Reset 50
CO2 Out 45
L Side Sy.
Center Sy.
R Side Sy.
Def Min Time
Def Off Temp
Sold Out Delay
Serial Number
Sy. Reset 50
Sy. Out 45
Base Common
Settings
Right Side
Up to 12 Defrost
Times & Day
Day of Week
Wake
Sleep
DL Savings
Wake/Sleep
Time >
Service
Menu
Use these buttons on Keypad
to navigate the Menu:
Error History 0
thru 9
To enter "Service Menu"
press blank button on
"Center" of keypad
FBD553D MENU
Up to 12 Defrost
Times & Day
Center
BACK
SELECT
CANCEL
FORWARD
Service Menu
Level Control
Thaw/Freeze
Common
Settings
MaxDefTime
Volt. Offset
Beater %
Tan k Press
Syr Press
Return Temp
Inlet Temp
Liq Level
Common
Readouts
H2O Press
CO2 Press
CO2 Press R
Reg CO2 R
Reg CO2 Press
Line Volt
L CO2 Sol
L Solution Sol
L Beater Motor
L Defrost Sol
L Refrig Sol
L Prod Out
C CO2 Sol
C Solution Sol
C Beater Motor
C Defrost Sol
C Refrig Sol
C Prod Out
R CO2 Sol
R Solution Sol
R Beater Motor
R Defrost Sol
R Refrig Sol
R Prod Out
Compressor
Fan Motor
Manual
On/Off
One Side Min
One Side Thaw
One Side Max
Two Side Min
Two Side Thaw
Two Side Max
Full Freeze
Delta T Min
Delta T Max
Sy. Reset 50
Sy. Out 45
Left Side Readouts
Center Readouts
Right Side Readouts
Left Side Thaw/Freeze
Center Thaw/Freeze
Right Side Thaw/Freeze
Left Side Liquid Level
Center Liquid Level
Right Side Liquid Level
Left Side Duty Cycle
Center Duty Cycle
Right Side Duty Cycle
Sy. Reset 50
Sy. Out 45
Machine
Tot als
Load All
Defaults
Are You
Sure?
Comp Hrs
Comp Cycl
Power On Hrs
Sleep Hrs
Left Side Readouts
Center Readouts
Right Side Readouts
Defrost Cycl
Sold Out Hrs
Beater Hrs
Run On Hrs
Error Hrs
Syrup Mins
Common
Tot als
BEVTRAK
Phone #
Call
Hang Up
Reset Modem
Bevtrak Enable = 1
Retry Times = 50
Retry Inv m = 6
Timeout m = 3
BT Manual = 0
Call per m = 1440
Call delay m = 1
CT: MM/DD/YY
HH:MM:SS
Display Modbus Error = 1
Base
Changes
Up to 12 Defrost
Times & Day
Left Side
Defrost Times >
Figure 7.3
10
Page 14
7.2 MACHINE ACCESS (SEE FIGURE 7.2)
A. Machine Operator Display
Mode Display Description Preset Value
1. VERSION Shows current version of the software installed.
2. TIME Used to set the time of day. The machine uses a 24 hour format (military time) clock. The clock has a battery backup which maintains correct time even if not plugged into electrical power.
3. DATE Used to set the date and day of the week. mmm-dd dow
4. DAYLIGHT Sets Daylight Savings Time (DST) option. ON for SAVINGS use of DST; OFF for use of Standard time.
5. DEFROST TIMES Each side can defrost itself up to 12 times a day. 4 hours Set the defrost times so the machine does not defrost during periods of high demand.
Low demand, every 3 hours. High demand, every 4-5 hours. Offset Left Side, Right Side, and Center defrost times by 45 minutes.
6. WAKE/SLEEP TIME Sets the machine wake and sleep times. 00:00
o manually wake-up and operate the unit, press
T DEFROST, then RUN.
7. FAULT CODE This feature stores the last 10 error codes and helps
HISTORY the service agent to readily diagnose a problem.
The readout is formatted as shown in the two examples below.
0 : Out of syrup (first error is an out
of syrup error)
0S:04/03/00 12:31:05 (error started at
12:31 PM on 4/3/00)
0E:04/03/00 13:33:56 (error ended at
1:33 PM on 4/3/00)
1 : Out of CO
2 (second error is an
out of CO2 error)
1S:04/07/00 15:03:55 (error started at
3:03 PM on 4/7/00)
1E:04/08/00 10:26:01 (error ended at
10:26 AM on 4/8/00)
The same format continues on for errors 2 through 9.
8. SERVICE MENU Authorized technician access. N/A
Service Note: Press “DEF” and then “RUN” on the control panel to start a machine that
has been turned off manually. This allows the machine to automatically reset the baseline.
11
Page 15
7.3 MACHINE SETTINGS
These settings are preset by the machine. DO NOT change unless there is a problem with drink quality.
Mode
L Side Settings Level Control = 3 The higher the value, the higher the product level Center Settings in the chamber. R Side Settings The lower the value, the lower the product level in
the chamber. The lower the value, the harder and colder.
Thaw/Freeze = 3 The higher the value, the higher the drink
temperature. The lower the value, the lower the drink temperature. For more frozen, use lower values. For more liquid or less frozen, use higher values.
T est for proper drink temperature (24°F to 28°F) before adjusting.
Defrost Max Time Max Def Time = 420 Number of minutes “Defrost Cycle” will run unless
“Return Temperature” reaches 50°F first.
Common Settings Voltage Offset = 0 Use this offset to match the “Line Voltage” readout
(in “Common Readouts”) to the actual incoming voltage measured with a voltmeter at L1 and L2 of the contactor.
This must be completed prior to starting machine for operation.
1. Measure, with a voltmeter, incoming line voltage at L1 and L2 of contactor and record.
2. Read LCD “Line Voltage” reading under READOUTS - Common Readouts and compare with voltmeter reading. [If within two (2) volts, skip Steps 3 and 4.]
3. Using Voltage Offset, enter valve that will allow LCD Line Voltage readout to match the voltmeter reading.
4. Once this is set, the machine is ready to run.
NOTES
12
Page 16
7.4. Readouts
For information and diagnostics.
Mode
L Readouts Allows user to view Beater % = This percentage represents C Readouts information about frozen and thaw status. R Readouts each side individually
. Tank Pressure = This represents current pressure
in the chamber (tank).
Syrup Pressure = This represents current pressure
of the syrup at the header.
Return Temp. = This represents the current
temperature of the return refrigerant line to the compressor.
Inlet Temp. = This represents the current
temperature of the refrigerant line entering the cold pac.
Liquid Level = 3 “Display Only” This changing
value is controlled by the machine. Anumber above 3 means the chamber level is rising and a number below 3 means the chamber level is lowering.
Common Readouts Allows user to view H
information common incoming water pressure. to both sides.
8. CLEANING AND SANITIZING THE UNIT
8.1 GENERAL INFORMATION
The following cleaning and sanitizing procedures pertain to the FBD equipment identified by this manual. If other equipment is being cleaned, follow the guidelines established for that
equipment.
A. FBD equipment (new or reconditioned) is shipped from the factory, cleaned and sanitized in
accordance with NSF guidelines. After installation is complete, the operator of the equipment must provide continuous maintenance as required by this manual and/or state and local health department guidelines to ensure proper operation and sanitation requirements are maintained.
B. Cleaning and sanitizing should be accomplished only by trained personnel. Sanitary gloves are
to be used during cleaning and sanitizing operations. Applicable safety precautions must be observed. Instruction warnings on the product being used must be followed.
20 Pressure = This represents the current
CO2 Pressure = This represents the current
2 Pressure R incoming CO
CO Regulated CO
2 = This represents the current
2 pressure.
Regulated CO2 R internally REGULATED CO2
as set by the secondary CO2 regulator.
Line Voltage = This represents the current
incoming line voltage.
NOTE
13
Page 17
C. Water lines are not to be disconnected during the cleaning and sanitizing of syrup lines to avoid
contamination.
D. Do NOT use strong bleaches or detergents. They tend to discolor and corrode various
materials.
E. Do NOT use metal scrapers, sharp objects, steel wool, scouring pads, abrasives, solvents, etc.,
on the dispenser.
F. Do NOT use hot water above 140°F (60°C). This may damage certain materials.
8.2 REQUIRED CLEANING EQUIPMENT
A. A mild soap solution (for example, Ivory Liquid, Calgon, etc.) mixed with clean, potable water at
a temperature of 90 to 110°F (32 to 44°C) should be used to clean the external components of the equipment. Any equivalent mild soap solution may be used as long as it provides a caustic based, non-perfumed, easily rinsed mixture containing at least two (2) percent sodium hydroxide (NaOH). Rinsing must be thorough and use clean, potable water which is also at a temperature of 90 to 110°F (32 to 44°C).
B. Sanitizing solutions should be prepared in accordance with the manufacturer's written
recommendations and safety guidelines. Any sanitizing solution may be used as long as it is prepared in accordance with the manufacturer's written recommendations and safety guide­lines, and provides 200 parts per million (PPM) available chlorine. Sanitizing solution is to be purged from line(s) and equipment by flushing with product only until there is no after taste. Do
not rinse with water.
NOTE
Please note that a fresh water rinse cannot follow sanitization of equipment. Purge only with the end use product until there is no after taste in the product. This is an NSF requirement.
8.3 DAILY CLEANING OF THE UNIT CAUTION
DO NOT USE ABRASIVE TYPE CLEANERS. A. On a daily basis, or more often if necessary, wash all exterior surfaces of unit with a mild soap
solution. Rinse with clean water. Wipe dry with a clean soft cloth.
B. Remove and wash drip tray in mild soap solution. Rinse with clean water. Reinstall drip tray on
unit.
8.4 SANITIZING THE SYRUP SYSTEMS
The unit should be sanitized every 90 days. Prepare a chlorine solution (less than pH 7.0) containing 500 PPM available chlorine with clean, potable water at 90°F to 100°F (Note: 500 PPM is five (5) times
stronger than the usual recommended 100 PPM. This is required because the sanitizing solution will be diluted with four (4) parts water when it enters the barrel). Any sanitizing solution may be used as long as
it is prepared in accordance with the manufactures safety guidelines and provides 500 PPM available chlorine." The following procedure takes about one (1) hour.
A. Press the "OFF" button, followed by the "DEF" button, for all three chambers. Remember, there
will be a two (2) minute delay before the unit begins defrosting.
B. After defrost, activate the left, center and right CO
2 solenoids by going to the "SERVICE
MENU/MANUAL ON/OFF" section of the menu.
C. Place a container under the valve and empty the barrels. Activate the beaters to facilitate the
removal of product.
D. Disconnect the BIB connectors from the syrup boxes and install BIB adapters (FBD
PN 05-0249) onto the BIB connectors. Activate the right, center, and left solution solenoids at the "SERVICE MENU/MANUAL ON/OFF" section of the service menu until all syrup has been
evacuated from the lines. Purge barrel of product as necessary. E. Turn off the solution solenoids and drain the barrels again. F. Turn off the CO
2 solenoids and beaters after the barrels are empty.
G. Relieve pressure by opening valves. Remove the faceplate to drain out excess product.
Replace the faceplates. H. Prepare five (5) gallons of sanitizing solution BUT ADD FIVE (5) TIMES THE AMOUNT OF
SANITIZER CONCENTRATE THAT THE SANITIZER MANUFACTURER RECOMMENDS.
This is required because the solution will be diluted at about 4:1 in the barrel.
temperature should be 110 to 115°F (44 to 46°C). If using a powder, stir the solution until
the sanitizing agent has completely dissolved.
14
The water
Page 18
I. Drop the BIB connectors (with adapter) into the sanitizing solution. J. Activate the right, center, and left solution solenoids at the "SERVICE MENU/MANUAL
ON/OFF" section of the service menu.
K. Fill each chamber approximately 2/3 full with sanitizing solution/water mixture, then deactivate
the solution solenoids.
L. Activate the CO
Once the chambers are evacuated, deactivate the CO2 solenoids and purge the pressure from the cylinders by pulling the faceplate relief valve.
M. Activate the solution solenoids again and fill the chamber to fill to ½ full of sanitizing solution.
Deactivate the solution solenoids and turn on the beaters. Let solution agitate for three (3) minutes.
N. Activate the CO
beaters and CO2 solenoids, and purge pressure from the chambers. O. Remove sanitizing adapters from the BIB lines and reconnect the lines to the syrup supplies. P. Partially fill the chambers (1/2 full) with syrup and water by activating the solution solenoids.
Turn off the solenoids. Run the beaters for a few seconds. Q. Drain the product by activating the CO R. Partially refill the chambers again and test the product for off taste. Repeat the drain/fill process
until no off taste exists. S. When there is no more off taste, fill the unit following the procedure outline in section 6.3 and
restart.
REMOVE SANITIZING SOLUTION FROM DISPENSER AS INSTRUCTED. RESIDUAL SANITIZING SOLUTION LEFT IN THE SYSTEM COULD CREATE AHEALTH HAZARD.
9. BASICS OF OPERATION
2 solenoids and evacuate the solution from the chambers while running beaters.
2 solenoids and evacuate the sanitizing solution from the cylinders. Turn off
2 solenoids.
CAUTION
NOTE
On an initial freeze down, products must be given adequate time to stabilize. Making adjustments too quickly may negatively affect drink quality.
9.1 MAKING ADJUSTMENTS TO THE FBD553D
A. In order to produce a consistent, quality beverage with the FBD553D Frozen Beverage Machine,
there are a few critical settings that must be maintained. These settings are preset when you
receive the machine from the factory, but, due to variations that occur (e.g., in operating
environments, syrups, and individual machines, etc.), it may be necessary to make minor
adjustments to these critical settings. Adjustments are easily made using the keypad located
behind the door at the front of the machine, or by adjusting the CO
2 regulator located behind the
access panel below the keypad. B. The settings that control product quality and production rate are:
1. Beverage Syrup Content or Brix Level (Set on Volumetric Valve)
2. Chamber “Level Control”
3. Regulated CO
2 Injection Pressure
4. Freeze and Thaw Settings
C. In Sections 6 and 7 of this manual are instructions on machine installation and initial operation.
These instructions should be followed for initial setup of the machine. If the product quality is
not as desired after allowing time for stabilization, the critical settings should be checked and
adjusted as necessary . The following sections discuss the sequence and method to verify these
settings. These four (4) critical settings are explained here to help better your
understanding of how the machine operates so you can make adjustments, if necessary.
1. Adjusting the Brix Level a. Consistent, high quality beverages require adjusting and maintaining the syrup content
of the drink or brix level between 13.5 and 15. Abrix level lower than 13.0 may cause operational problems. A low brix level (lower than 13.0) will produce a weak tasting drink and tends to freeze product around the beater shaft. Ahigh brix level (higher than
15.0) causes freezedown times to be longer and produces a more liquid drink. The
water flow rate must be set to provide a flow of 15 ounces in 10 seconds prior to adjusting brix.
15
Page 19
2. “Level Control” a. The FBD553D frozen beverage dispenser utilizes a proprietary liquid level control
system (patented) to hold a constant liquid level. A constant liquid level assures a quality frozen product.
b. If a more “wet” product is desired, the numerical setting (0-6) should be increased. If a
“drier” and colder product is desired, the numerical setting should be decreased.
c. The default value set at the factory is 3. This setting should produce an excellent
quality product. (See Section 10 for instructions on changing settings.)
3. Regulated CO a. The CO
2 Injection Pressure
2 injection pressure is set by adjusting the secondary regulators, located behind
the access panel below the control panel in the front of the machine. The left regulator feeds the left and center barrels and the right regulator feeds the right barrel. The CO2 regulators should be set at 28-32 PSIG (193.0 to 220.8 KPa). The unit then automatically sets the chamber pressure between 25 and 30 PSIG (172.5 and
206.8 KPa).
Some "citrus based syrups" have been shown to produce a better quality drink with a lower chamber pressure. However, lowering the "Regulated CO2 regulator" will affect both left and center chambers. For adjusting individual chamber pressures, refer to Section 10.
4. Thaw and Freeze Settings a. The Thaw and Freeze settings signal the refrigeration system when to start freezing and
when to stop freezing. The liquid in the chamber freezes until it reaches the desired frozen consistency; then the refrigeration system shuts off and the chamber begins to thaw. The liquid continues to thaw until it reaches a consistency specified by the Thaw value. The Thaw value is the point at which the refrigeration system turns back on and refreezes the product. This assures the product is maintained in a good acceptable quality frozen drink range.
b. Prior to changing any Thaw or Freeze settings, make sure the brix and water flow rate
are correct and the liquid level control settings are properly set. Also assure the chambers stay filled to the proper levels with the proper amount of CO
frozen drink temperature is 24 to 28°F (-4.4 to -2.2°C) and should be checked prior to making any adjustments. (See Section 10 for instructions on changing settings.)
CAUTION
IF THE THAW - FREEZE IS SET AT A LOWER SETTING, COMPRESSOR “SHORT CYCLE” CAN OCCUR THAT WILL CAUSE THE COMPRESSOR TO OVERHEAT. IF A LOWER SETTING IS USED, THE DISPENSER OPERATION MUST BE MONITORED TO INSURE THE COMPRESSOR DOES NOT “SHORT CYCLE”.
c. The Thaw and Freeze settings may be raised or lowered to change the temperature of
the product. A default setting of 3 is set at the factory. To decrease the temperature, decrease the numerical setting to 2 or 1; to increase the temperature, increase the numerical setting to 4 or 5.
10. CHANGING FACTORY SET “LEVEL CONTROL”
NOTE
2. The optimum
Always check brix, Regulated CO2 setting, and water flow rates before adjusting “Level Control”. The factory setting of the liquid “Level Control” may be changed to alter the consistency of the product.
Adjusting the liquid “Level Control” will change a drink that is too liquid or one that is frozen too hard. A product that is frozen too hard will not allow the chamber to stay full and the drink will dispense with sudden releases of CO
2 (“spitting”). A“too full” chamber may cause a “too wet” drink.
10.1 BEFORE CHANGING “LEVEL CONTROL” SETTINGS
A. Each machine ships with preset level control values. These values should be correct for
normal operation of the machine and should not have to be modified.
NOTE
16
Page 20
B. Before making any changes to the level control settings, defrost all three chambers by
HIGHER LEVEL SETTING
HIGHER LEVEL SETTING
HIGHER LEVEL SETTING
FACTORY SETTING LOWER LEVEL SETTING LOWER LEVEL SETTING LOWER LEVEL SETTING
6 5
4 3 2 1 0
MORE LIQUID
"DRY" OR MORE
FROZEN
pressing the “DEF” buttons located on the control panel. The machine may automatically correct any problems with drink quality after going through a defrost cycle.
C. After the defrost cycle, the compressor may cycle on and off several times to ensure that the
product is uniformly frozen. Wait several minutes before judging the quality of the product.
D. If factory level control settings are correct, the product should freeze, thaw and then refreeze to
an acceptable consistency range. Remember, drinks poured directly after a freeze cycle will
appear more frozen than the last drink poured before the unit begins to refreeze the cylinder.
E. The level control settings of each drink chamber are preset to a default value of 3. If the
corresponding secondary regulator inside the unit is properly set to 28-32 PSIG (193.0 to
220.8 KPa), the chamber pressure will be “set” automatically.
F. After the machine is installed and each chamber is properly filled, press the “DEF” button on the
control panel to allow the machine to automatically “baseline”. Baselining indicates to the machine that the chamber contains liquid. As a result, the machine sensors determine how much to freeze the product.
G. The display will flash “DEFROSTING” until baselining is complete. The machine will
automatically start running if the machine was running when the defrost cycle was started. If the machine was not running before the defrost cycle started, the “RUN” button must be pressed. Note that there may be a delay of up to two (2) minutes before the machine turns on after the “RUN” button is pushed. This delay is normal. Do not press the “RUN” button again or press
any other buttons until the machine starts.
10.2 DRINK TOO HARD AND COLD
A. If the drink is too hard and cold or the chamber is not full, adjust the “level control” to a higher
level setting. Use the recommended settings that follow to properly adjust the liquid level control settings.
B. It will be necessary to drain off several drinks to allow the chamber to fill and rebalance. It is
also then necessary to defrost the chamber and allow the product to refreeze. If the drink is still too hard, repeat the process taking the level control setting to the next higher value.
10.3 DRINK TOO LIQUID
A. If the drink is cold, but is still a liquid, adjust the level control to a lower level setting. Use the
recommended settings that follow to properly adjust the level control.
B. It will be necessary to drain off several drinks to allow the chamber to fill and rebalance. It is
then necessary to defrost the chamber and allow the product to refreeze. If the drink is still too liquid, repeat the process taking the level control to the next lower setting.
C. If the product is still too liquid, it may be necessary to adjust the THAW-FREEZE beater settings.
Refer to Section 11 (Changing Factory Thaw and Freeze Settings).
D. Drink temperature should be between 24°F and 28°F (-4.4°C to -2.2°C).
NOTE
If "Wet" or "Dry" drinks are common to all three chambers, adjust "Regulated CO2" up to lighten drink or down to make drink wetter before adjusting level controls!
Recommended “Level Control” Settings
Figure 10.1
17
Page 21
10.4 CHANGING THE DEFAULT LEVEL CONTROL SETTING
HIGHER THAW/FREEZE SETTING
HIGHER THAW/FREEZE SETTING
HIGHER THAW/FREEZE SETTING
FACTORY SETTING LOWER THAW/FREEZE SETTING LOWER THAW/FREEZE SETTING LOWER THAW/FREEZE SETTING
6 5
4 3 2 1 0
WARMER
DRINK
TEMPERATURES
COLDER
DRINK
TEMPERATURES
A. The level control setting is preset at the factory at a value of 3. B. If the drink is not frozen enough, or if the drink is too hard and too cold and dispenses slowly,
after the machine has been running for 10 to 15 minutes, it may be necessary to adjust the level control settings.
C. To change the machine’s level control settings, access the level two service menu.
1. Access the service level by pressing the “FWD” button on the control panel until the “SERVICE MENU” displays. Press the unmarked button on the right side of the panel. “Machine Settings” displays.
2. Pressing the “FWD” button scrolls through the left, center, and right setting options.
3. Press “SELECT” (on the barrel you wish to change) and “Level Control” displays.
4. Press the “SELECT” button and the default setting of “3” begins to flash. The level is raised by pressing the “FWD” button and lowered by pressing the “BACK” button. When the desired number is reached, press “SELECT” and the new setting stops flashing and is set into the computer.
D. When settings are complete, press the "CANCEL" button until "Copyright" displays.
NOTE
If the machine continues to yield a drink that is too liquid or too hard after changing level control settings, it may be necessary to adjust the THAW and FREEZE settings (refer to Section 11, Changing Factory Thaw And Freeze Settings).
11. CHANGING FACTORY THAW AND FREEZE SETTINGS
11.1 BEFORE CHANGING THAW AND FREEZE SETTINGS
A. Each machine ships with THAW and FREEZE values preset. These values should be correct
for normal operation of the machine and are designed to produce a drink temperature between 24 and 28 degrees. Before making any changes to THAW AND FREEZE settings, check drink temperature. If drink temperature is within correct range, DO NOT CHANGE THAW-FREEZE SETTINGS.
B. Before changing the THAW or FREEZE settings, verify that the level control and Brix settings
are properly set. After verifying the “Level Control”, defrost both chambers by pressing the “DEF” buttons located on the control panel. The machine may correct any problems with drink quality after going through a defrost cycle.
1. After the defrost and refreeze cycle, the compressor may cycle on and off several times to ensure that the product is uniformly frozen. Wait several minutes, and dispense several
drinks, before judging the quality of the product.
2. The product should freeze to a proper frozen texture, thaw, and refreeze to the same general texture. The compressor turns on when the thawed product requires refreezing and shuts off when the product is frozen enough.
3. If the product is freezing too cold (below 24°F), the THAW - FREEZE value may be increased. If the product is not cold enough (above 28°F), the THAW - FREEZE value may be decreased. Use the recommended settings that follow when making adjustments to the
THAW - FREEZE value.
Recommended THAW-FREEZE Settings
Figure 11.1
18
Page 22
11.2 CHANGING THAW AND FREEZE SETTINGS
The THAW-FREEZE values should only be changed if the drink quality is not as expected. Use the following steps to change THAW-FREEZE settings as necessary. Before changing the THAW-FREEZE settings, verify that the brix and level control settings (see Section 10.1) are properly set. THAW-FREEZE settings may not need changing if corrections are made to the level control settings.
A. Changing the THAW-FREEZE Settings
1. Access the service level by pressing the “FWD” button on the control panel until the “SERVICE MENU” displays. Press the unmarked button on the center barrel, “MACHINE SETTINGS” displays.
2. Pressing the “FWD” button scrolls through the left, center, and right setting options.
3. Press “SELECT” (on the barrel you wish to change) and “Level Control” displays.
4. Press the “FWD” button until “THAW-FREEZE” displays.
5. To change the THAW-FREEZE values, press “SELECT” and the number starts to flash.
6. Press “FWD” to change to a higher setting or press the “BACK” button to change to a lower setting.
7. Once the desired setting displays, press “SELECT” to save the new value.
8. Press “CANCEL” and “L SIDE SETTING” displays.
9. To change the other chambers, press “FWD” until “R SIDE SETTINGS” or C SIDE SETTINGS” displays. Repeat Steps 3-7 above.
10. When settings are complete, press the “CANCEL” button until “Copyright” displays.
12. BEVTRAK OPERATION
Bevtrak is a feature on the FBD553D that enables the unit to dial a toll free number every night and download current status information about the unit as well as daily sales numbers. The information is collected and cataloged on the FBD server and is readily available to subscribers via the Internet. The data available for viewing is:
• Sales totals for each barrel in daily, weekly or monthly periods
• Number of units not reporting in
• Number of machines currently in an "out of" state
• Number of machines in an "error" state
• Total of hours in a "product out" state Additionally, all machine settings can be viewed by qualified personnel to aid in trouble shooting problems
remotely.
12.1 NAVIGATING THE BEVTRAK MENU
A. To access the Bevtrak menu, press the "FWD" button on the control panel until the "SERVICE
MENU" appears. Press the unmarked button on the center barrel panel group. "MACHINE SETTINGS" displays. Press the "FWD" button repeatedly until "BEVTRAK" appears. Press "SELECT" to enter the Bevtrak menu. See figure 7.3 for a layout of the FBD553D menu structure.
B. The following selections are in the Bevtrak menu:
Phone # 9/18668983004#
and place two additional # symbols at the end of the string.
- Pressing "SELECT" when this displays will initiate a call and the data exchange sequence
Call
with the home server.
Hang up - Terminates the call sequence. Reset Modem Bevtrak Enable = 1 - A value of 1 enables Bevtrak while a value of 0 turns it off. Retry times = 50 Ret inv m = 6 (Retry interval minutes) - The wait time in minutes between retries.
(Continued next page)
- Resets the modem should it stop working properly.
- Number of times the unit will attempt to call the server.
- If the "9" is not needed to obtain an outside line, eliminate the "9/"
19
Page 23
(Continued from previous page)
Timeout m = 3 (Timeout minutes) - The amount of time the unit will wait from the start of a call
to the completion of the call. If the call has not completed by then it will hang up.
Bt manual
= 0 (Bevtrak manual mode) In the Manual mode (=1) the unit will schedule calls at
the call period after the call delay. In Auto (=0) the calls will be rescheduled by the server,
Call per m = 1440
1440 is one call per day
Call delay m = 1
the first call.
: MM/DD/YY HH:MM:SS - The next time the unit is scheduled to call the home server.
CT Display Modbus error = 1 - A value of 1 displays "MODBUS ERROR" when the modem sends
a bad "packet" of information due to static on the telephone line. Avalue of 0 does not show a modbus error. Note: This does not mean the call was a failure, the unit will re-send the data.
12.2 NORMAL OPERATION
A. In automatic mode (Bt manual = 0), the unit will place a call when it is scheduled. If the unit
finds the phone line is busy, it will hang up and wait the retry interval (Ret inv m) and then try to place the call again. If the call does not finish within the timeout period (Timeout m), the unit will hang up and wait the retry interval to try again. It will keep trying for the number of times in the retry times value. Once the call connects to the server, the unit will exchange user name and password information with the server. The server will then request data from the unit and send information to the unit. One of the things the server sends is the recall time. The unit will use this time to reschedule the next call if in auto mode. In manual mode, it will use the call period. When completed, the server will send a hang up command to the unit. They will both hang up and wait until time for the next call.
B. The server will reschedule the next call to fall in the window of midnight to 5 AM local time to the
unit. This is based on the unit's time of day clock. The data collected is processed at 6 AM and posted on the Bevtrak web site.
C. To access the data on the Internet, you must be a subscriber, and have a user name and
password assigned to you. You will then be able to view only the data from units you own or manage.
D. Each unit is assigned a unique serial number. That serial number is entered into the machine
during final test. It is by this serial number that the Bevtrak server knows to whom the unit data belongs to.
E. During a successful call, the display will show the following sequence:
1. Bevtrak calling (placing a call)
2. Modem connected (the unit has found the server modem)
3. Bevtrak online (user name and passwords have been exchanged)
4. Bevtrak shutdown OK (the server has sent a shutdown command)
5. Bevtrak call done (ready to place the next call at the scheduled time)
13. CRITICAL INFORMATION
(Bevtrak call period) - This the time between calls when in the manual mode.
(Call delay minutes) - The delay in minutes from when Bevtrak is enabled till
The following information is critical to proper machine operation. Prior to troubleshooting problems with the unit, review the following information.
13.1 DEFROST AND RUN TIME DELAY
When either the RUN or the DEF button on the control panel is pressed, the message “RUN BEATER” or “DEF BEATER” is displayed. This is a time delay before the compressor starts running. The delay can be as long as two (2) minutes before the unit starts running or defrosting. Do not press the buttons again. Wait, and the machine will start defrosting, then freezing.
13.2 CHAMBERS 90% FULL ON INITIAL SET UP
Before beginning a RUN-FREEZE cycle, the chambers should be filled approximately 90% full (up to relief valve). If the chambers are above the 90% level, with Fill Off, open the dispensing valve and allow a small amount of liquid to drain out. If the chambers are not 90% full, press “OFF”, then “FILL”, and then slowly pull the vent ring on the faceplate to vent gas, and allow liquid to fill. The
20
Page 24
screen will display “Filling”. Fill slowly and do NOT let the pressure drop more than three to four
(3-4) PSI.
13.3 LINE VOLTAGE DROP
The unit requires a separate electrical circuit complete with a 30 AMPbreaker or fuse on a 30 AMP service. The unit will not function properly if the line voltage drops more than 10 volts between the power source and the machine.
13.4 LONG TUBING RUNS
A. Long runs of supply tubing can cause problems if the pressure drop (between the CO
syrup source and the unit) is too much. Runs longer than 25 feet (7.62 m) will require special attention. The machine’s sensors may indicate that the machine is out of syrup, water, or CO Consider the following solutions:
1. Increase the tubing size from 3/8 inch diameter to 1/2 inch diameter.
2. Install booster pumps in the supply lines. Use a vacuum regulating valve with syrup booster pumps.
3. Increase primary CO
2 regulator pressure from bulk or tank CO2 to 105 - 120 PSIG (723.9
to 828.0 KPa). A secondary regulator will be necessary for pumps (syrup, water) to avoid exceeding manufacturer’s recommended operating pressures.
14. TROUBLESHOOTING GUIDE
The following information is a listing of the most common problems that could keep the FBD553D Dispenser from operating properly. Contact the factory for details, when necessary.
2 tank or
2.
TROUBLE
CAUSE REMEDY
MECHANICAL
14.1 Chamber will not fill. A. “Fill“ off. A. Press “Fill” button. “Filling” or
“Fill Hold” will appear on LCD display.
B. Pressure in chamber above B. Gently pull faceplate relief valve
“RFill” (refill) point. ring to relieve pressure in chamber.
C. “Defrosting” or “Sleeping”. C. Press “Def”. then “Run” Wait for
unit to freeze and red light to go out.
D. Out of CO2, Syrup or Water. D. Check LCD messages for
"Out of ……." condition.
E. Tank Pressure readout not E. Observe "Tank Transducer" in
moving between 18 and "Readouts". Check transducer and 40 psi or doesn’t lower when replace if necessary. chamber pressure is reduced.
F. CO2 solenoid valve won’t F. In “Manual On/Off, energize
open. solenoid and check for 24VAC at
coil. Clean or replace solenoid if necessary
G. Relay board not sending G. Test solenoid relay on relay board
power to solenoid coils. for 24VAC output and 5VDC input.
Replace Relay Board, if necessary.
H. Lower Board problem. H. Test Lower Board for +5, +15, and
–15 outputs using test points (see Figure 14.3). Replace Lower Board, if necessary.
I. 353 VATransformer problem. I. Test transformer for 220VAC input.
Also check for 24VAC and 12VAC output (see Figure 14.3). Replace transformer if necessary.
14.2 Chamber fills even A. Solution solenoid plunger A. In “Manual On/Off”, energize when turned off sticking. solenoid and check for 24VAC at
(Section 14.2 continued on next page.)
coil. Clean or replace solenoid, if necessary.
21
Page 25
TROUBLE CAUSE REMEDY
(Section 14.2 continued from previous page.)
B. Solution solenoid energized. B. Test solenoid relay on relay board
for 24VAC output and 5VDC relay coil input. Replace Relay Board, if necessary.
C. Solution solenoid left “ON” C. In “Manual On/Off”, turn “solenoid
in “Manual”. off.
14.3 Out of Product A. Unit receiving no water, syrup A. Assure water is on and CO2 supply displayed (Out of and/or CO2. is not empty or turned off. Also Water, Syrup or CO2). check to see that syrup container
is not empty and is hooked up.
B. Restriction in lines. B. Assure all lines are free of crimps
or restrictions.
C. Regulator pressures (unit C. Check pressure readouts (H2O,
and syrup pumps) too low. CO2 and Syrups) for 70-72 psi.
Adjust regulators, if necessary.
D. Syrup or Water Pump failure. D. Check all pumps and replace, if
necessary.
E. CO2 or water can’t keep up E. Reroute water or CO2 lines to
with unit demand. maximize supply pressure. Install
Water Booster if necessary.
F. Excessive pressure drops F. Observe “Syrup Press” readouts
in syrup lines. as chamber fills to verify. Increase
line diameter or relocate syrup source closer to unit. Syrup pressures may only be raised (by increasing pump CO2 pressure) if separate regulators are installed for unit and syrup pumps. Never exceed pump manufacturer’s recommended maximum CO2 inlet pressure. (see Section 12.4).
H. Transducer problem (H2O, H. Check pressure readouts (H2O,
CO2 or Syrup). CO2 and Syrup) for 70-72 psi. If
not within 2psi, adjust regulator and/or check transducer. Replace transducer, if necessary.
I. Lower Board problem I. Test lower board for +5, +15, and
–15 outputs using test points (see Figure 14.3).
J. Upper Board Problem J. Circuits within Main Control (Upper)
Board electronics read transducer pressures. Replace Main Control (Upper) Board, if necessary
14.4 Product does not flow A. Faulty CO2 check valve. A. Inspect CO2 check valve. Clean or freely or does not flow replace. at all from dispensing B. CO2 solenoid valve won’t B. In “Manual On/Off, energize valve. open. solenoid and check for 24VAC at
(Section 14.4 continued on next page.)
coil. Clean or replace solenoid, if necessary.
C. Solution solenoid valve C. In “Manual On/Off”, energize
won’t open. solenoid and check for 24VAC at
coil. Clean or replace solenoid, if necessary.
D. Ice particles in dispensing D. Run defrost cycle. If necessary,
valve. open and close dispensing valve
several times or run warm water over valve.
22
Page 26
TROUBLE CAUSE REMEDY
(Section 14.4 continued from previous page.)
E. Product in cylinder is frozen E. 1. Check water/syrup flow
too hard or solid. rates and brix. Adjust, if
necessary (see Section 6.2).
2. Check Level Control setting. Adjust if necessary (see Section 10).
3. Check Thaw/Freeze settings. Adjust if necessary (see Section 11).
4. Defrost chamber. Assure chamber is filled to 90%, then press "Run".
14.5 Product leaking from A. Beater drive seal is worn or A. Replace with new seal. rear of cold pack. damaged.
B. Beater drive coupling is worn. B. Replace coupling. C. Seal is not positioned C. From inside chamber, reseat seal,
correctly. making sure it is flush with back of
chamber.
14.6 Brix sample valve A. Damaged or failed o-rings A. Turn off CO2 and water, and leaks. on valve. disconnect syrup. Depressurize by
pressing sample valve shaft, change o-rings, and reinstall.
B. Inside hole of plastic header B. Replace upper header block.
block is scratched or damaged.
14.7 Low water pressure or A. Water not turned on or line A. Turn on water. Check for line no water pressure. restriction. restrictions.
B. CO2 not turned on or too low. B. Assure CO2 is turned on and verify
"CO2 Press" readout is 70-72 PSIG (482.6-496.4 KPa). Adjust if necessary.
C. Water pressure transducer C. Verify "H2O Pressure" readout at
failure. 70-72 psi. Check transducer and
replace, if needed.
D. Water pump failure. D. Check water pump and replace, if
necessary.
14.8 Noisy condenser fan. A. Fan contacting condenser, A. Remove fan guard and adjust fan
fan blade guard, or other up or down as required. Remove part. obstruction as necessary. Reinstall
fan guard.
B. Fan blade not balanced. B. Remove fan guard, slide fan blade
weights (on 3 blades) to balance fan. Replace fan, if necessary. Reinstall fan guard.
C. Loose fan bracket fasteners. C. Tighten loose fasteners.
ELECTRICAL
14.9 Solenoids not A. Solenoid plunger not lifting. A. In “Manual On/Off”, energize
activating. solenoid on and off checking for
plunger movement and 24VAC at coil. Clean or replace solenoid, if necessary.
B. Relay Board failure. B. Test solenoid relay on Relay Board
through manual ON/OFF menu. Replace, if necessary.
C. Connectors not plugged in C. Assure connections are clean and
at board or solenoid. secure at boards and solenoid coils.
23
Page 27
TROUBLE CAUSE REMEDY
14.10 Solenoids continuously A. Solenoid plunger not dropping. A. In “Manual On/Off”, energize
activated. solenoid on and off checking for
plunger movement and 24VAC at coil. Clean or replace solenoid, if necessary.
B. Solenoid Relay stuck. B. Test solenoid relay on Relay Board
through manual ON/OFF menu. Replace, if necessary.
C. Transducer failure. C. Observe "Tank Pressure" readouts
and check corresponding transducer. Replace transducer, if necessary.
14.11 Line voltage low A. Low voltage to unit (below A. Check voltage at L1 & L2 of on LCD. 215 volts). contactor and at wall receptacle.
Install Buck/Boost transformer, if necessary (see Section 4).
B. Incorrect voltage offset. B. Access “Machine Settings” menu
and adjust voltage offset so "Line Voltage" readout equals L1 and L2 contactor voltage. (see Section 7.3).
C. Voltage Offset transformer C. Check input on upper board for
problem. (Transformer 24VAC. Replace transformer, located on lower board.) if necessary.
14.12 Low beater counts. A. Chamber is frozen too hard A. Verify correct brix, Level Control
or solid. and Thaw/Freeze settings. Defrost
chamber, refill to 90% and refreeze. (see Sections 9.1, 10 and 11).
B. Lower motor control board B. Replace board.
failure.
C. Beater motor capacitor. C. Check motor capacitor and replace,
if necessary.
D. Beater motor problem. D. Replace beater motor.
14.13 Excessively rapid A. Lower Board problem. A. Replace lower board. rising/falling beater B. Buck/Boost transformer B. Disconnect and replace counts. problem (if used). Buck/Boost transformer.
14.14 Display door light out A. Failed fluorescent tube. A. Replace fluorescent tube. or flickering. B. Blown fuse. B. Check inline fuse (in electrical box.)
Check wiring from contactor, through ballast, to lamp connection.
C. Failed or failing fluorescent C. Replace ballast.
ballast.
14.15 Ammonia smell in A. Start capacitor has failed. A. Verify blown capacitor. Replace electrical box. start capacitor and check start
relay. Replace if necessary.
14.16 Fan motor not running. A. Unit in "Defrost" cycle. A. Check fan after completion of
defrost cycle.
B. Failed compressor or fan B. Test compressor or fan relays on
relay on relay board. Relay Board in manual ON/OFF
menu. Replace Relay Board, if necessary.
C. Lower motor control board C. Replace lower board.
failure.
D. Contactor not engaging. D. Check for 24 volt at coil and
220 volt at T1 and T2. Replace contactor, if necessary.
E. Bad fan motor. E. Replace fan motor.
24
Page 28
TROUBLE CAUSE REMEDY
ELECTRONIC CONTROLS
14.17 LCD readout garbled A. Voltage spike or noise. A. Press “CANCEL” several times.
or blank. B. Low or no voltage to unit or B. Check L1 & L2 of contactor for
loss of 5VDC signal. 220 VAC and test points on lower
and upper board for +5 VDC (see Figure 14.3). Install Buck/Boost transformer or replace board, if necessary.
14.18 One or more keypad A. Cable connecting Main A. Check for loose or incorrect buttons will not Control (upper) board to connections. function. keypad not connected
properly.
B. Faulty control cable. B. Replace keypad.
14.19 Clock shows incorrect A. Initial setting incorrect. A. Change clock settings as described time/date. in Section 7.2 of this manual.
B. Clock battery failure. B. Replace clock battery on upper
board.
14.20 Faulty tank pressure A. Pressure transducer failure. A. Check transducer and replace, if reading on LCD. necessary.
B. Possible short in wiring from B. Clean and dry both ends of cable,
transducer to PC board. and check for loose connections. C. Poor contact within connector. C. Reposition or replace transducer. D. Low 15VDC from Lower D. Check for 15VDC on lower board
Board. test points (see Figure 14.3).
Replace lower board, if necessary.
E. Upper board failure. E. Replace main control (Upper)
board.
REFRIGERATION
14.21 Compressor won't start. A. Incorrect start procedure. A. Press “Def”, then “Run” to start.
B. In 2 minutes, compressor B. “Run Beater” or “Def Beater”
delay. indicates delay mode C. Out of CO2, Syrup or Water. C. Check pressure readouts for
70-72 psi (482.6-496.4 KPa), adjust regulators,if necessary.
D. Start capacitor or relay D. Test start capacitor and start relay.
problem. Replace, if necessary. E. Contactor failure. E. 1. In Manual On/Off, activate
“Compressor” . DO NOT RUN
COMPRESSOR FOR MORE THAN 10 SECONDS! If
contactor energizes, quickly check voltage across contactor T1 and T2 for 220 volt. If no voltage reading, replace contactor.
2. In Manual On/Off, activate “Compressor”. DO NOT RUN
COMPRESSOR FOR MORE THAN 10 SECONDS! If
contactor does not energize, quickly check voltage across contactor coil terminals for 24VAC. If voltage is present, replace contactor.
F. Relay board not sending F. Test contactor relay board through
power to contactor coil. manual ON/OFF menu. Replace
relay board, if necessary.
(Section 14.21 continued on next page.)
25
Page 29
TROUBLE CAUSE REMEDY
(Section 14.21 continued from previous page.)
G. Lower Board problem. G. Test lower board for +5, +15, and
–15 outputs on test points (see Figure 14.3).
H. 353 VATransformer problem. H. Test transformer for 220VAC input
and 24VAC and 12VAC output (see Figure 14.3).
I. Compressor failure, or I. Wait for compressor to cool.
overheated. Check amperage draw (normal
running 18 amps) on compressor. Check compressor wiring and terminals. Replace compressor, if necessary.
14.22 Compressor runs long A. Return temperature not A. Verify that Return Temperature time but won’t freeze dropping. drops below 20°F. Return down. Temperature should achieve 20°F
within 7 to 25 minutes of startup (no drinks dispensed).
B. Airflow through condenser B. Clear condenser of blockage.
is blocked. Dirty filter. Clean air filter.
C. Hot gas valve is activated C. Select "Defrost Sol" in
in Manual On/Off “Manual ON/OFF”; test solenoid,
then turn off.
D. Base refrigeration settings. D. Load all Defaults to ensure factory
settings.
E. Hot gas valve is stuck open, E. Recover refrigerant and remove
or debris is preventing valve blockage or replace valve, if from closing. necessary. Recharge system with
65.0 oz. of R404-A.
F. Expansion valve not opening. F. 1. Test expansion valve coil to
ensure it is receiving 24VAC. Replace expansion valve if plunger inside doesn't move. Recover refrigerant and replace valve. Recharge system with
65.0 oz. of R404-A.
2. Test relay board for 24VAC output and 5VDC relay coil input. Replace, if necessary.
G. Expansion valve restriction. G. Recover refrigerant and remove
blockage or replace valve if necessary. Recharge system with
65.0 oz. of R404-A.
H. Refrigeration leak or low H. Put gages on system and check
refrigerant charge. pressures. Single side suction
should be 32-35 psi, dual side 42-45 psi. Single and dual side discharge should be 275-300 psi. Check for and repair leaks, recharge system with 65.0 oz. of R404-A.
CAUTION
DO NOT PRESSURIZE LOW SIDE (EVAPORATOR AND COMPRESSOR SUCTION) ABOVE 150 PSI FOR ANY REASON! COMPONENTS WILL FAILAND WARRANTIES WILL BE VOID.
14.23 High head/suction A. Condensor air flow restricted. A. Check for air flow restriction, clean pressure. Contact condensor and air filter.
FBD Warranty Dept. B. Compressor damage B. Check amp draw on compressor before tapping system (normal running 18 amps). if unit is under C. High ambient temperature. C. Temperature surrounding unit warranty! should be less than 90°F.
26
Page 30
TROUBLE CAUSE REMEDY
14.24 Low head/suction A. Low refrigerant level. A. See item 14.22.H above. pressure. Contact FBD Warranty Dept. B. Compressor damage. B. Check amp draw on compressor before tapping system (normal running 18 amps). if unit is under warranty!
DRINK QUALITY
14.25 Drink too “Wet” or A. Chamber not filled properly. A. Defrost, then assure chamber is
“Liquid”. 90% full.
B. CO2 check valve clogged. B. Clean or replace check valve. C. CO2 solenoid not opening. C. Activate "CO2 Sol" in
“Manual On/Off”. Check for 24VAC at coil. Clean solenoid or replace, if necessary.
D. CO2 level in drink too low. D. 1. To affect BOTH chambers,
raise "Reg.CO2" within 28-32 psi (193.0 - 220.8 KPa) range.
2. To affect ONE chamber, lower the level control settings using the instructions in Section 10.2 of this manual.
E. Secondary CO2 regulator E. Check Secondary Regulator.
malfunctioning. Repair or replace secondary
regulator if necessary.
F. Reg'd CO2 Transducer F. Check "Reg'd CO2" in readouts,
malfunctioning. compare with regulator gauge.
Test transducer, replace if necessary.
G. Incorrect Brix or water/syrup G. Check water and syrup flows and
flow rates. adjust if necessary. Then check
brix (see Section 6.2).
H. Tank Pressure readout not H. Observe Tank Transducer, check
moving between 18 and and replace, if necessary. 40 psi or doesn’t lower when chamber pressure is reduced.
I. Relay board not sending I. Test relay board for 24VAC output
power to CO2 solenoid coil. and 5VDC input on solenoid relay.
Replace Relay Board, if necessary.
J. “THAW/FREEZE” settings J. Lower the “THAW/FREEZE”
are set too high. settings, using the instructions in
Section 11.2, this manual.
K. CO
2 orifice is blocked. K. Remove blockage.
14.26 Drink quality is too A. Chamber not filled properly. A. Defrost and assure chamber is light. 90% full..
B. Incorrect Brix or water/syrup B. Check water and syrup flows and
C. CO
D. Secondary Regulator D. Pressure rising out of 28-32 psi
(Section 14.26 continued on next page.)
flow rates. adjust if necessary. Then check
brix (see Section 6.2).
2 level in drink too high. C. 1. To affect BOTH chambers,
lower "Reg.CO2" within 28-32 psi (193.0 - 220.8 KPa) range.
2. To affect ONE chamber, raise the level control settings using the instructions in Section 10.2 of this manual.
pressure rise. (193.0 - 220.8 KPa) range. Repair
or replace the secondary regulator, if necessary.
27
Page 31
TROUBLE CAUSE REMEDY
(Section 14.26 continued from previous page.)
E. “THAW/FREEZE” settings E. Raise the “THAW/FREEZE”
set too low. settings using the instructions in
Section 11.2 of this manual.
F. Volumetric Valve F. Activate "Solution Disp" in Manual
malfunctioning and not On/Off and check for flow. Also allowing the chamber to fill. check for 24VAC at Volumetric
Valve PCB. Clean solenoid or replace, if necessary.
14.27 Drinks “collapse” or A. Chamber not filled properly. A. Defrost and assure chamber is “fall”. (CO
2 is 90% full. Then press "Run".
escaping from the) B. CO2 level in drink too high. B. 1. To affect BOTH chambers, drink. lower "Reg.CO2" within
28-32 psi (193.0 - 220.8 KPa) range.
2. To affect ONE chamber, raise the level control settings (using the instructions in Section 10.2 of this manual).
C. “THAW/FREEZE” settings A. Raise the “THAW/FREEZE” using
are set too low. the instructions in Section 11.2.
D. Air not cleared from chamber D. Follow "Filling the chamber"
prior to filling chamber. instructions in Section 6.3.
E. Contaminated Syrup supply. E. Syrup being used is more than
three (3) months old, or is not an FCB syrup.
F. Solution Solenoid is F. Activate “Solution Sol” in Manual
malfunctioning and not On/Off. Check for 24VAC at coil. allowing the chamber to fill. Clean solenoid or replace, if
necessary.
G. Relay board not sending G. Test relay board for 24VAC output
power to solution solenoid and 5VDC input on solenoid relay coil. Replace relay board, if necessary.
14.28 Drink tends to “grow” A. “THAW/FREEZE” settings are A. Lower the “THAW/FREEZE” or continue to expand set too high. settings using the instructions in in volume after drawn Section 11.2, this manual. into cup.
B. Incorrect Brix or water/syrup B. Check water and syrup flows and
flow rates. adjust if necessary. Then check
brix (see Section 6.2).
C. CO2 level in drink too high. C. 1. To affect BOTH chambers,
lower "Reg.CO2" within 28-32 psi (193.0 - 220.8 KPa) range.
2. To affect ONE chamber, raise the level control settings using the instructions in Section 10.2 of this manual.
LCD DISPLAY ERROR MESSAGES
14.29 PMAX A. Chamber pressure above A. Dispense one (1) drink; see if
55 psi. PMAX recurs.
B. Expansion tank pressure B. Replace expansion tank regulator.
system not working properly. NOTE: This is not the same
regulator as used on the header.
C. Tank transducer shorted C. Replace transducer.
at 99 psi.
D. Level Control set too high. D. Level Control settings may need to
be lowered. Set the Level Control using the instructions in Section 10.2 of this manual.
(Section 14.29 continued on next page.)
28
Page 32
TROUBLE CAUSE REMEDY
(Section 14.29 continued from previous page.)
E. Level Control too low. E. Level Control settings may need to
be raised due to excessive CO2 in the chamber. Raise the Level Control settings using the instructions in Section 10.2 of this manual.
F. "Regulated CO2" transducer F. Insure that the tank transducers
reading inaccurately. are reading the CO
2 regulated
pressure correctly [i.e., filling about 5-7 PSIG (34.5-48.3 KPa) below “REG CO2”].
G. Secondary regulator G. Insure CO2 regulator has not
pressure creeping up. climbed above preset
28-32 PSIG (193.0-220.8 KPa).
H. CO2 check valve problem. H. Inspect CO2 check valve. Clean
or replace if necessary.
14.30 Max Fill A. Secondary CO2 pressure is A. Check Secondary CO2 for correct set above 40 psi. setting of 28-32 psi (193.0 - 220.8
KPa).
B. Secondary regulator B. Insure CO2 regulator has not
pressure creeping up. climbed above 32 PSIG. Clean or
repair or replace regulator, if necessary.
14.31 DefPRESmax A. Tank pressure above 55 psi. A. See 14.29.
14.32 DefProdOut A. Product supply is out during A. Replenish product supply
defrost stage. (i.e., water, CO
2, syrup).
14.33 BTR-LO-ERR A. Product freezing too hard. A. 1. Check brix and correct, if Beater % below 450. necessary.
2. Check Level Control and correct, if necessary.
3. Check for restriction of beater blades.
4. Check for failed beater motor.
B. Bad capacitor on motor. B. Check capacitor and replace as
required.
C. Motor control board failure. C. 1. Check connector from Beater
Motor to lower control board.
2. Change lower control board if necessary.
14.34 Syrup Out A. Unit receiving no syrup. A. Check to see that syrup container is not empty and is hooked up.
B. Restriction in lines. B. Assure all lines are free of crimps
or restrictions.
C. Regulator pressures (unit C. Check Syrups pressure readouts
and syrup pumps) too low. for 70-72 psi. Adjust regulators, if
necessary.
D. Syrup Pump failure. D. Check pump and replace,
if necessary.
E. Excessive pressure drops E. Observe “Syrup Press” readouts
in syrup lines. as chamber fills to verify. Increase
line diameter or relocate syrup source closer to unit. Syrup pressures may only be raised (by increasing pump CO2
pressure) if separate regulators are installed for unit and syrup pumps. Never exceed pump manufacturer’s recommended maximum CO2inlet pressure (see Section 12.4).
(Section 14.34 continued on next page.)
29
Page 33
TROUBLE CAUSE REMEDY
(Section 14.34 continued from previous page.)
F. Syrup Transducer problem. F. Check syrup pressure readouts
for 70-72 psi . If not within 2 psi, adjust regulator and/or check transducer. Replace transducer, if necessary.
G. Lower Board problem. G Test lower board for +5, +15, and
–15 outputs on lower board test points (see Figure 14.3).
H. Upper Board Problem. H. Circuits within Main Control (Upper)
Board electronics read transducer pressures. Replace Main Control (Upper) Board, if necessary.
14.35 H20 Out A. Unit receiving no water. A. Assure water is turned on. B. Restriction in lines. B. Assure all lines are free of crimps
or restrictions.
C. Regulator pressures (unit C. Check pressure readouts (H
water pump) too low or CO2 CO2) for 70-72 psi. Adjust out. regulators, if necessary. Replenish
CO2 supply.
D. Water Pump failure. D. Check pump and replace, if
necessary.
E. Water pressure too low, E. Reroute water to maximize supply
can’t keep up with unit pressure. Install Water Booster, if demand. necessary.
F. Water Transducer problem. F. Check water pressure readout for
70-72 psi. If not within 2 psi, adjust regulator and/or check transducer. Replace transducer, if necessary.
G. Lower Board problem. G. Test lower board for +5, +15, and
–15 outputs on lower board test points (see Figure 14.3).
H. Upper Board Problem. H. Circuits within Main Control (Upper)
Board electronics read transducer pressures. Replace Main Control (Upper) Board, if necessary.
2O and
14.36 CO2 Out A. Unit receiving no CO2. A. Assure CO2 supply is not empty or
turned off.
B. Restriction in lines. B. Assure all lines are free of crimps
or restrictions.
C. Regulator pressures (to unit C. Check pressure readout ( CO2) for
and syrup pumps) too low. 70-75 psi (483.0-517.5 KPa).
Adjust regulators, if necessary.
D. CO2 can’t keep up with D. Reroute CO2 lines to maximize
unit demand. supply pressure or supply unit
dedicated CO2 source. Bulk regulator must be 105 psi (723.9 KPa) minimum, CO2 line must be tied to main branch of bulk system, with step down regulator [set 70­75 psi (483.0-517.5 KPa)] between tie-in and unit.
E. CO2 Transducer problem. E. Check CO2 pressure readout for
70-75 psi (483.0-517.5 KPa). If not within 2 psi, adjust regulator and/or check transducer. Replace transducer, if necessary.
F. Lower Board problem. F. Test lower board for +5, +15, and
–15 outputs on lower board test points (see Figure 14.3).
(Section 14.36 continued on next page.)
30
Page 34
TROUBLE CAUSE REMEDY
(Section 14.36 continued from previous page.)
G. Upper Board Problem. G. Circuits within Main Control (Upper)
Board electronics read transducer pressures. Replace Main Control (Upper) Board, if necessary
14.37 RtnTempErr A. Temperature Sensor error A. 1. Check for short in sensor and or failure. cable. LED on Main Control
board goes bright if short occurs, goes out if open circuit and stays dim if working properly.
2. Check for poor connection in sensor plug.
3. Replace temperature sensor.
14.38 InletTempErr A. Temperature Sensor error A. 1. Check for short in sensor and or failure. cable. LED on Main Control
board goes bright if short occurs, goes out if open circuit and stays dim if working properly.
2. Check for poor connection in sensor plug.
3. Replace temperature sensor.
NOTES
31
Page 35
LCD DISPLAY MESSAGES
FBD553D FROZEN BEVERAGE DISPENSER
MESSAGE DESCRIPTION
Sleeping Unit in “Sleep” mode. Unit is shut down. Cmpr StDly This delay is before compressor starts. The time period varies from 1 to 30 seconds. Cmpr Start This is displayed when compressor starts freezing or defrosting. Cmpr Run This is displayed only on Left Side, when compressor is running on either side. DEFWait This side is waiting to defrost. DEFBeater If “DEF” is pressed and if the beater has not been running, then this is displayed for a maximum
time delay of two (2) minutes.
DEF Cmp Wt Time delay prior to opening the Defrost Solenoid. Defrosting This is displayed when side is DEFROSTING. DEFSuspnd This is displayed when a side has been interrupted by the other side freezing. After the other side
has frozen down, then defrost is resumed.
Run Off This is displayed when freeze is off or when the side is turned off. Run HotGasW This is displayed on the opposite side when a side has defrosted and is waiting to refreeze or when
one side is defrosting and the other side is in Run Thaw Mode.
Run Cmp Wt This is displayed, prior to starting a freeze down; this is a time delay before the Refrigeration
Solenoid opens.
Run Frz Wt This is displayed after the freeze down has finished. Run Freeze This is displayed when a side is freezing down. Run Thaw W This is displayed after the Thaw percent has been reached. Run Thaw This is displayed when a side is Thawing before refreezing. Run Beater If “Run” is pressed and if the beater has not been running then this is displayed for a maximum
time delay of two (2) minutes.
Fill Off The unit will not fill with product when this is displayed. L Fill Hld This is displayed during first freeze and defrost only. The pressure in the chamber has not dropped
below the fill pressure.
Fill Hold This is displayed during normal operations when the pressure in the chamber has not dropped
below the fill pressure.
Fl Pre CO2 This is displayed prior to filling the chamber with solution. This only allows CO
for a specified time period.
Fl CO2 SOL This is displayed prior to filling the chamber with solution. This only allows CO2 and solution to fill
the chamber until four (4) PSI is reached in the chamber.
L Filling This is displayed during first freeze and defrost only. The unit is filling the chamber. Filling This is displayed during normal operations when the chamber is filling.
2 into the chamber
32
Page 36
LCD DISPLAY ERROR MESSAGES
FBD553D FROZEN BEVERAGE DISPENSER
MESSAGE DESCRIPTION
DEFPresMax Chamber pressure is above 55 PSIG during defrost only. DEFProdOut Product is out during defrost only. BTR-LO-ERR Low beater percent. Below 450%. BTR-HI-ERR High beater percent. Above 1200%. SYRUP OUT Syrup pressure is below 45 PSIG. H2OOUT Water pressure is below 45 PSIG. CO2OUT CO2 pressure is below 45 PSIG. PRESMAX Chamber pressure is above 55 PSIG during normal operations only. RunProdOut Product out during normal operations. RtnTempErr High return temperature detected or temperature sensor broken (-40). Unit still functions. Max Fill Regulated CO2 pressure is at or above 40 PSIG limit. TankPsi=0 Filling has been on for five (5) seconds and chamber pressure equals to zero (0). SFillError Filling on for four (4) minutes but chamber pressure between one (1) PSIG and fill PSIG. Product Out Product out when side is off. InletTempErr High return temperature detected or temperature sensor broken (-40). Unit still functions.
This error will occur during the DEFROST CYCLE.
Cmp ran too The compressor has run for more than one hour straight. Check the air filter or the long OFF refrigeration charge.
HOT PRODUCT This means the product in the barrel is getting hot. A bad return temperature sensor SHUT DOWN may also be at fault.
Stop BTR Long The beater shuts off after 3 hours of a PMAX error. It will restart automatically when PMAX the error is cleared.
Stop BTR The beater shuts off after 3 hours of a sold-out condition. It will restart automatically when LongPrd Out the sold-out has been cleared.
WARNING LIGHTS
FBD553D FROZEN BEVERAGE DISPENSER
PROBLEM CAUSE SOLUTION
Left red light Left side - out of syrup. Replace empty syrup container flashing. (Left Side flavor), see Section 13.29.
Center red light Center - out of syrup. Replace empty syrup container flashing. (Center flavor), see Section 13.29.
Right red light Right side - out of syrup. Replace empty syrup container flashing. (Right Side flavor), see Section 13.29.
All red lights Out of CO2. Replace empty CO2 tank. flashing. Out of Water (H2O). Check Water (H2O) Supply.
Left red light on Unit defrosting If on defrost during peak draw, cancel (not flashing). (Left Side of unit). defrost by pushing “DEF” button, then
push “RUN”.
Center red light on Unit defrosting If on defrost during peak draw, cancel (not flashing). (Center of unit). defrost by pushing “DEF” button, then
push “RUN”.
Right red light on Unit defrosting If on defrost during peak draw, cancel (not flashing). (Right Side of unit). defrost by pushing “DEF” button, then
push “RUN”.
Red lights on, but Unit in “Sleep” mode or Restart unit by pushing “DEF” button, beaters not turning. turned off. then “RUN” button on both sides.
No lights, unit Check to make sure power Plug unit in and/or reset circuit breaker. not running. cord is plugged in. Check Then restart unit by pushing “DEF”
to see if circuit breaker has button, then “RUN” button on both been tripped. sides of unit.
33
Page 37
15. ILLUSTRATIONS, PART LISTINGS, AND DIAGRAMS
16.75" 1.75"
11.50"
34.50"
20.25"
22.0"
MACHINE MUST
EDGE OF
USE 1/2" DRILL
EDGE OF MACHINE
BIT (4 HOLES)
MACHINE
BE SUPPORTED TO
THIS POINT
1.0"
15.1 MOUNTING DIAGRAM
This Figure illustrates the locations of threaded mounting holes in the base of the FBD553D machine.
34
Page 38
15.2 FLOW DIAGRAM/SCHEMATIC
FBD 553D, FLOW DIAGRAM
CTRL P14 - LEFT SOLUTION
CTRL P13 - LEFT SYRUP IN
CTRL P17 - H2O IN
CTRL P16 - CO2 REG.
CTRL P15 - CO2 UN-REG.
CTRL P18 - CENTER SYRUP IN
CTRL P19 - CENTER SOLN. OUT
CTRL P22 - RIGHT SYRUP IN
CTRL P23 - RIGHT SOLN. OUT
CONDENSER WATER
12-2606-0001
12-2718-0001
22-0390-0001(12”)
36-2029-0001
SET PRESSURE:
COMPRESSOR HIGH (ACCESS VALVE)
CONDENSER WATER - OUT
CONDENSER WATER - IN
CONDENSER WATER
OUT
IN
250 PSIG
22-0390-0001(50”)
22-0390-0001(40”)
12-2611-0001
34-0103-0002
38-0126-0001
12-2615-0001
12-2610-0001
12-2609-0001
12-2608-0001
22-0389-0001(37”)
12-2146-0002
12-0316-0001
12-0316-0001
12-0316-0001
22-0389-0001(43”)
22-0389-0001(47”)
RIGHT SYRUP - IN
CENTER SYRUP - IN
LEFT SYRUP - IN
H2O - IN
CO2 - IN
30 PSIG
30 PSIG
30 PSIG
RIGHT
BARREL
CENTER
BARREL
LEFT
BARREL
NOTE:
PORT LOCATIONSAT
REAR OF EQUIPMENT
SYRUP
RIGHT
SYRUP
CENTER
SYRUP
LEFT
WATER
CO2
12-2150-0001
12-2150-0001
12-2150-0001
35
Page 39
T2
L2
GRN/YEL
C
OIL B
M
AIN GND
SECONDARY GND3
S
ECONDARY GND1
SECONDARY GND2
L6-30P
MAIN GROUND
WHT
W
HT/RED
G
RN/YEL
G
RN/YEL
GRN/YEL
G
RN
CONTACTOR, 2POLE 30AMP
C
OIL A
COIL B
B
RN
5
L
T BLUE
LT BLUE G
RN/YEL
GRN/YEL
LT BLUE
B
RN
Line
1
N
C
B
LK
2
Common
RED
BLUE
189-227 uF @ 250 VAC
S
TART CAP.
4
0 uF @ 370 VAC
RUN CAP.
O
UTPUT
L2
L1
T
2
T
1
COIL A
I
NPUT
M
AIN AC-P1
230 VAC NEU
230VAC LINE
WHT
BLK
T1
L
1
S
R
C
B
RN
COMPRESSOR
DIAGRAM
CONTACTOR, 2POLE 30A
L
1
L
2
G
ND
R
ELAY
STARTER
BRN
2
12
LPB-P14
BTR 230VAC LINE
230AC LINE 230AC NEUTRAL CHASSIS GND
POS LAMPS
B
TR_EN RIGHT
B
TR_CHASSIS
230AC NEU.[SW'D]
230VAC LINE
CHASSIS GND
XFMR
PCB, LOWER POWER DISTRIBUTION
FAN
WHT/YEL
24VAC INPUT
GND
GND
12VAC
24VAC
LPB-P9
1
3 4
2
LOAD1 CTRL P5-9
BTR2 CTRL P5-7
BTR1 CTRL P5-8
BTR3 CTRL P5-6
AC_REF_IN CTRL P5-5
LOAD REF CTRL P5-3
LOAD3 CTRL P5-10
LOAD2 CTRL P5-4
+5VDC1_CNTLR_P12-1 +5VDC2_CNTLR_P12-2 +
15VDC_CNTLR_P12-3
-
15VDC_CNTLR_P12-4
ANA GND_CNTLR_P12-5
DIG GND1_CNTLR_P12-7 DIG GND2_CNTLR_P12-9
FAN RUN CTRL P5-12
COMP RUN CTRL P5-1
+5 VDC 2 IN
+5 VDC 1 IN
+15VDC IN
-15VDC IN ANA GND
DIG GND 1 DIG GND 2
GRN
GRN
RED RED
YEL ORG GRN
1
8
7
3
6
5
4
2
24VAC RTN
24VAC RTN
WHT/RED
WHT/GRN
4
3
2
1
WHT
LOAD2
2
WHT WHT WHT WHT WHT WHT WHT
LOAD3 B
TR1 BTR2 BTR3 LOAD REF AC_REF_IN
7 8
4 5 6
3
WHT
LOAD1
LPB-P13
1
LPB-P10
24VAC
24VAC
WHT
FAN
10
11
12
COMP RUN
9
LT BLUE
BRN
1 2 3
LPB-P4
8
5
8
7
6
7
6
5
RED
1
2
3
4
1
4
3
2
325VA 24VAC_CT
WHT
BLK
GRN
1 2 3
LPB-P3
ORN GRN/YEL
3
2
3
2
1
BRN BLUE GRN/YEL
START CAP
FAN 1
LPB-P12
3
BLK
3
C
OMP_RUN
2
4 VAC
C
ONTACTOR COIL
BTR MOTOR 1
BTR MOTOR 2
B
TR_CHASSIS
B
TR_EN LEFT
BTR 230VAC LINE
SW_230 VAC LINE T1-3 SW_230 VAC NEU T2-3 SECONDARY GND 2
230VAC NEU L2-2 SECONDARY GND 1
230VAC LINE L1-2
2
1
3
L
PB-P2
SWITCHED AC INPUT
1
3
2
LPB-P1
M
AIN AC INPUT
WHT/RED WHT
2 3
1
4
LPB-P8
BLK
LPB-P7
BLK
L
PB-P6
RED GRN/YEL
2 3
1
G
RY
1
LEFT
T
AN
GRN
B
TR
G
RY
1
3
CENTER
T
AN
BTR
GRN
BLK
2
1
1
3
2
PCB, LOWER POWER DISTRIBUTION
R
ED
R
ED
WHT
YEL YEL
BRN
LT BLU
RED
WHT
LEGEND: FUSE RATINGS F1-LEFT BEATER (2.5A/230V)
F2-RIGHT BEATER (2.5A/230V) F3-AIR COMP. (2.5A/230V) F4-T1 (2.5A/230V) F5-MERCHANDISER (2.5A/230V)
P2
P12 P1
BALLAST
RED RED BLUE BLUE
FLUORESCENT LAMP
BTR MOTOR 2
BTR_CHASSIS
BTR_EN RIGHT
BTR 230VAC LINE
LPB-P5
BLK
2 3
GRN/YEL
YEL
1
11
33
22
B
TR
RIGHT
G
RY
BLK
T
AN
GRN
A
A
T1
K101
LPB1
F1
F2
F
3
F4
F
5
CONTACTOR
C101
C102
F5 F4 F3 F2 F1
P13
P14
P3 P4 P5 P6 P7
P8 P9 P10
B
C
D
15.3 ELECTRICAL/SCHEMATIC-01
36
Page 40
1
REF 3
4
2
GAS
GAS
TANK RIGHT
SYRUP RIGHT
TANK CENTER
SYRUP CENTER
WATER
S
ECONDARY
PRIMARY
Looking into board connector.
an 'X' pattern.
Note that sensor connection forms
2
1
3
4
P
RESSURE SENSORS
+
5.12 REF
FAN
12
PCB, UPPER BOARD
5
VDC IN 5 VDC IN +15 VDC IN
-15 VDC IN ANA GND
DIG GND DIG GND
+
5.12 A
10
NC
CNTLR P12
5 6 7 8
2
4
3
1
SHIELD DRAIN WIRE
SHIELD DRAIN WIRE
SHIELD DRAIN WIRE
SHIELD DRAIN WIRE
4
1
3
2
2
1
4
3
CNTLR P23
CNTLR P22
CNTLR P19
3 4
1 2
SHIELD DRAIN WIRE
SHIELD DRAIN WIRE
S
HIELD DRAIN WIRE
C
NTLR P18
C
NTLR P17
CNTLR P16
4
1
3
2
2
1
4
2 3
1
4
3
4
3
7
LOAD 1 LOAD 3 ANA GND
COMP
AC_REF_IN
LOAD_REF LOAD_2
6
+
5V
uP
DIG
7
G
ND
GND
ANA
8
9
BTR 3 B
TR 2 BTR 1
C
NTLR P5
11
8 9 10
9 10
1
3 4
2
8
7
6
5
2
4VAC
O
UT OF 3 O
UT OF 2 O
UT OF 1
+5V PWR
2
+5V
+
15V
3
4
-
15V
5
PRESSURES
D
EF 2
REF 1
REF 2
DEF 1
CNTLR P2
CNTLR P9
5 6
2
4
3
1
2
4
3
1
8
7
6
5
M
EMBRANE KEYPAD
L
OUT
C
OUT
TANK LEFT
S
YRUP LEFT
24VAC RTN
2
4VAC RTN
CNTLR P6
SHIELD DRAIN WIRE
S
HIELD DRAIN WIRE
24VAC
2
4VAC
C
NTLRP14
C
NTLR
P
15
C
NTLR P13
4
1
3
2
1
4
1
3
2
2 3
1
4
2
4VAC
24VAC
G
AS 2 GAS 1
24VAC
2
4VAC
GAS 3
TEST POINTS
DEF 3
S
OL 1
S
OL 2
SOL 3
CNTLR P8
C
NTLR P7
1
3
2
1
3
5
4
2
8
7
6
L
DEF
L
SOL
1
2
1
2
1
2
1
2
R
DEF
C
SOL
2
1
2
1
2
1
2
1
2
1
1
2
1
2
C
REFLREF
R
CO2
C
CO2
2
1
1
2
1
2
1
2
1
2
D
B
C
TEMPERATURE SENSORS
R RTNC INLET
CNTLR P25
3 4
1 2
L RTNL INLET
2 3 4
1
CNTLR P24
CNTLR P26
2
4
3
R RTNR INLET
R
OUT
1
2
1
2
1
C
DEF RREF
2
1
2
1
G
RN
O
RG
RED
RED
GRN GRN
YEL
W
HT
W
HT/RED WHT/RED B
LU
R
ED
G
RN ORN BLK
1
2
1
2
R
SOL
2
1
2
1
L
CO2
WHT WHT/RED W
HT/RED WHT WHT WHT W
HT WHT
WHT/RED WHT W
HT W
HT
15.4 ELECTRICAL/SCHEMATIC-02
37
Loading...