Fantech MUAS 1600, MUAS 2000, MUAS 750, MUAS 1200 Installation Manual

Installation Manual
MUAS Series
Makeup Air System & Controller
Item #: 497868
Rev Date: 2017-09-27
Technical / Customer Support:
United States Tel.: 800.747.1762 Canada Tel.: 800.565.3548
Note Warning /
Information Technical
Important
note
Warnings
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Installation work and electrical wiring must be done by a qualified person(s) in accordance with national electric codes, local electric codes, ordinances and regulations, including fire-rated construction codes and standards.
2. This system is not designed to provide combustion air for fuel­burning appliances.
3. Do not connect the system directly to a combustion appliance of any type.
4. Before servicing or cleaning any system component, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
5. When performing installation, servicing or cleaning of the system, it is recommended to wear safety glasses and gloves.
6. Locate the outside air inlet hood above any anticipated snow drift level and away from any architectural and landscape features to ensure that the intake area for the outside air duct is not blocked and provides a clear pathway for outside air to enter the system.
7. When cutting or drilling into wall or ceiling, do not damage electrical wiring or other hidden utilities.
8. When notching or drilling into framing including floor supports, rim joists, and wall studs, comply with code and manufacturer limitations on allowable modifications to these structural members.
9. This system can only be used for its intended design. Any internal wiring changes, modifications or bypass of any controls, or installation practices not according to the details of the instruction manual will void the product warranty. Follow all installation, wiring and setup instructions indicated in the manufacturer’s manual.
Practical tip
information
Caution
1. Do not locate outside air inlet near hazardous materials or explosives.
2. System shall not be installed to introduce air from crawlspaces, garages, attics, adjacent dwelling units, or other locations within the building shell. System shall be installed to introduce air directly from outdoors.
3. Do not install the makeup air system and supply ductwork directly above or closer than a distance of two feet to any furnace or its supply plenum, boiler, or other heat producing appliance.
4. Any ductwork used in conjunction with the system must be installed in compliance with all local and national codes that are applicable.
5. Do not operate the system until all system filters have been installed per the system design.
6. Please read the specification label on each system component for further information and requirements.
7. Each system component, including filters, should be inspected and maintained on a regular basis.
8. This system is intended for installation in a dry location protected from moisture.
9. This system must be installed in an accessible location which allows for system inspection and maintenance.
10. This system will automatically provide outdoor air into a building.
Coordinate with the HVAC designer/contractor the effects that the supply of outdoor air will have on the building’s comfort and mechanical systems. The HVAC designer should take into consideration the makeup air system's frequency and duration of use as well as the outdoor air flow quantity.
11. Use this system only in the manner intended by the manufacturer. If
you have questions, contact the manufacturer at the address or telephone number provided in this document.
12. When federal, provincial or state legislation comprises more
restrictive installation and/or certification requirements, the aforementioned requirements prevail over those of this document and the installer agrees to conform to these at his own expense.
fantech
13. Do not supply outdoor air to a space or duct system where water
pipes or water coils might be susceptible to freezing due to the supply of outdoor air.
Application
The Fantech Exhaust Makeup Air System is a low voltage controlled assembly of components which provides the automatic supply of outdoor air into a building. When controlled by the current sensing Fantech Makeup Air Controller “FMAC”, the system is suitable as compensation for single speed, multi-speed, and variable speed exhaust fans.
The FMAC initiates the makeup air system upon sensing the exhaust fan motor current, and controls the supply of outside air into the building in proportion to that being exhausted.
This system may be used to replace air being removed by a kitchen hood exhaust fan or other continuously or intermittently operating powered exhaust system. Mechanical replacement of exhaust air allows an exhaust system to function more effectively, helps to maintain pressure equilibrium between the building interior and the exterior, and allows for management (quantity, cleaning, tempering and location) of the introduction of outside air to the building’s interior space. An electric heater (optional) may be included as a system component. The heater is not intended to provide heating to the interior space, but rather to temper the supply of cold outdoor air before it is delivered to the building.
Due to its component-based, eld-assembled nature, the Fantech Makeup Air System offers exibility as to where and how it can be installed into a building. The installation location should be suitable for periodic inspection and maintenance. It is not required that the individual system components be installed in a linear (straight line) arrangement. System components may be connected by duct work (by others) to permit lengths and elbows for accommodating the physical space available for installation. It is important to adhere to all instructions included with each system component for proper installation, however, keeping service clearances and straight duct lengths upstream and downstream of components as required.
Depending upon the version of the building code that governs the installation, there are potentially many code-compliant methods of introducing the makeup air into the building.
Realizing this, Fantech deems it unacceptable to use central HVAC system
equipment and duct work for treatment and conveyance of makeup air.
Reasons for this include:
• Furnace manufacturers often limit the temperature of air entering the heat exchanger to no less than 50-55ºF. The equipment warranty could be voided if the limit is broken.
• Residential HVAC heating and cooling systems typically cycle on/ off with one or two stages of capacity on a signal from the space thermostat. To put it another way, the central HVAC system is intended to maintain a condition in the living space, and it only operates when the living space condition becomes uncomfortable. Since makeup air comes directly from outdoors, it is often quite uncomfortable. The uncomfortable makeup air would be conditioned only when the space thermostat is calling for action.
• The temperature difference between the indoor condition and the outdoor condition can at times be signicant. Cold makeup air could cause the formation of condensation on the exterior of poorly insulated duct work and equipment. Very humid makeup air could result in condensation on the interior of poorly insulated duct work and equipment.
The air discharged from the Fantech Makeup Air System will almost always be contained in duct work (by others), so that the supply of makeup air may be routed to a suitable location for delivery to the interior space.
The Fantech Makeup air system components and the system's duct work must be insulated to prevent the formation of condensation.
Fantech recommends that makeup air be ducted to the space from where the compensated exhaust is being removed. For example, makeup air used to compensate a kitchen exhaust hood should be delivered directly to the kitchen space. For this same example, it is advisable that the air be delivered to the kitchen in such a way as to not disturb the exhaust air pattern at the hood. In general, this can be accomplished by locating the makeup air supply grille at least a few feet away from the footprint of the kitchen hood, and ensuring that no streams of makeup air supply are directed toward the area between the range top and the hood. Depending on the makeup air ow rate, grilles might be suitably located above kitchen cabinets, behind refrigerators, or simply at a convenient location on a wall or the ceiling.
fantech
Exhaust Makeup Air System Components
7
2
Figure 1. Makeup Air System for Exhaust Fan
1 Wall Intake Hood, FML
2 Fast Clamp, FC
3 Shut-off Damper, ADC
4 Filter cassette, FGR HV
6
5
2
2
5 Makeup Air Fan, prioAir EC or FKD
EC
6 Silencer, LD
7 Duct Heater, Stelpro (optional)
8 Controller, FMAC*
8
4
3
1
2
2
*The FMAC Controller includes a transducer, system control board, 24V transformer, NEMA enclosure,
enclosure back plate for mounting transformer and controller, 4" x 4" electrical box for supporting the transformer.
Items Which Must Be Furnished By Others:
a. Insulation b. Wiring c. Electrical Wiring Boxes d. Equipment Supports/Hangers e. Duct work f. Electrical Disconnect Means g. Miscellaneous Hardware and Any Other Items not described in this document
fantech
Dimensions
J
MUAS 750 & MUAS 1200
Ø
A
B
C
D
E
F
G
Model A B C D E F H (optional) G J
MUAS 750 10 10 30 1/2 7 7/8 26 5/8 85 14 99 8
MUAS 1200 10 10 30 1/2 9 13/16 38 1/2 98 13/16 14 112 13/16 10
Dimensions are in inches.
MUAS 1600 and MUAS 2000
A
B
C
Ø
J
D
E
H
Ø
K
H
Model A B C D E F H (optional) G J K
MUAS 1600 10 1/2 12 30 1/2 18 7/8 38 1/2 110 3/8 14 124 3/8 12 12
MUAS 2000 10 3/4 14 30 1/2 20 /8 38 1/2 114 1/8 24* 138 1/8 14 12
All dimensions are in inches. *
This dimension includes a 14"-12" duct size reducer (not shown), not provided.
F
G
fantech
Loading...
+ 11 hidden pages