Fantech, Inc. and Systemair
Mfg. certify that the ventilators shown herein are licensed
to bear the AMCA Seal. The
ratings shown are based
on tests and procedures
performed in accordance with
AMCA Publication 211 and
AMCA Publication 311 and
comply with the requirements
of the AMCA Certied Ratings
Program.
2
NoteWarning /
InformationTechnical
Important
note
Always disconnect, lock, and tag power source before installing or
servicing. Failure to disconnect power source can result in fire, shock, or
serious injury. Motor will restart without warning after thermal protector
trips. Do not touch operating motor, it may be hot enough to cause injury.
Do not place any body parts or objects in fan, motor openings, or drives
while motor is connected to power source.
Do NOT use this equipment in explosive atmospheres!
1. Read and follow all instructions and cautionary markings. Make sure
electrical power source conforms to requirements of equipment.
2. Ventilators should be assembled, installed, and serviced by a qualified
technician. Have all electrical work performed by a qualified
electrician.
3. Follow all local electrical and safety codes in the United States and
Canada - National Electrical Code (NEC), the Occupational Safety and
Health Act (OSHA), and the National Fire Protection Association
(NFPA) Bulletin 96 in the United States. Ground motor in accordance
with NEC Article 250 (grounding). Follow the Canadian Electric Code
(CEC) in Canada.
Practical tip
information
4. Motor and fan must be securely grounded (bare metal) to a suitable
electric ground, such as a grounded water pipe or ground wire
system.
In United States, to reduce the risk of injury to persons, OSHA complying
guards are required when fan is installed within 8 feet of floor, ground, or
working level.
In Canada, to reduce the risk of injury to persons, CSA complying guards
are required when fan is installed below 2.5 meters (8.2 feet) above floor
or grade level.
5. Do not kink power cable or allow it to come in contact with sharp
objects, oil, grease, hot surfaces, or chemicals.
6. Never open access door to a duct with the ventilator running.
7. Do not operate direct drive fans with speed controller less than 50%
of maximum fan speed.
Description
Power roof ventilators are designed, depending on model number, to either supply air to, or exhaust air from, commercial, institutional, and industrial
buildings. Ventilators are available in a multitude of configurations including direct-drive or belt-drive units; roof, wall, or combination roof/wall mount
and upblast or downblast discharge designs. Some units feature additional certifications required for use in kitchen ventilation systems.
Models 5DDU08 thru 5DDU18, 5DDW08 thru 5DDW18, 5BDD10 thru 5BDD49, 5BDU10 thru 5BDU36, 5ADE10 thru 5ADE24, 5ADS12 thru
5ADS24, 5DDD08 thru 5DDD18, 5FSU10 thru 5FSU20, 5ABE18 thru 5ABE36, and 5FSU10 thru 5FSU20 are UL Listed, Standard 705, & CSA
Certified when sold complete with motor and drive. Upblast Centrifugal Roof Ventilators 5BDU10 thru 5BDU36, 5DDU10 thru 5DDU18, 5DDW10
thru 5DDW18 are UL Listed, Subject 762, when sold complete with motor and drive.
Storage
If fans are stored for any length of time, they should be stored in a clean, dry location to prevent rust and corrosion. Outdoor storage is not recommended. When outdoor storage is necessary, fans should be protected from the elements as completely as possible. Cover the fan inlet and outlet
and keep motors dry and clean.
For extended storage (more than 3 months) motor shafts and bearings should be rotated monthly. If stored longer than 6 months, bearing grease in
motor and fan should be purged and replaced with compatible grease. Belts should be rechecked for proper tension. Storage records should be kept
to assure proper maintenance. The factory can advise warranty centers to provide motor and bearing service if needed.
fantech
INSTALLATION AND MAINTENANCE INFORMATION
Receiving, Inspection & Unpacking
When the equipment is received all items should be carefully checked
against the bill of lading to be sure all crates and cartons have been
received. Before accepting delivery, carefully inspect each carton or
crate for visible shipping damage. If any damage is noticed, the carrier
should make the proper notation on the delivery receipt acknowledging
the damage. Make notations of all damage on all copies of the bill of
lading and have all copies countersigned by the delivering carrier. The
carrier should also fill out a Carrier Inspection Report. File claim for
damage with the carrier. Physical damage to the unit after acceptance is
not the responsibility of Fantech.
Unpack each carton or crate and verify that all required parts and proper
quantities of each item have been received. Refer to drawings for part
descriptions. Report shortages or missing items to your local
representative to arrange for replacement parts.
Due to availability of carriers and truck space, it is not possible to
guarantee that all items will be shipped together. Verification of
shipments must be limited to only those items on the bill of lading.
The unit nameplate must be checked to make sure the voltage agrees
with the power supply available.
3
General Installation
CAUTION: Sheet metal parts, screws, clips and similar items
inherently have sharp edges, and it is necessary that the
installer and service personnel exercise caution.
The installation of this equipment shall be in accordance with the
regulations of authorities having jurisdiction and all applicable codes.
This equipment is to be installed by an experienced installation company
and fully trained personnel.
The mechanical installation of the exhaust ventilator consists of making
final connections between the unit and building services, duct
connections.
When motors and drive packs are shipped in separate cartons from the
fan, check the carton labels to make sure the motor and drive pack you
received are the correct combination for the fan being purchased. Refer
to the fan components list included in these instructions.
Motor and Drive Pack Installation
Before mounting the motor to the fan motor/bearing support plate check
the nameplate voltage of the motor to insure that it is compatible with the
supply voltage. If the motor is a dual or tri voltage make sure the
connections inside the motor are properly wired to match the supply
voltage. Refer to the wiring schematic on the motor nameplate or inside
the junction box. Record the motor that was installed and the voltage that
the fan is wired for on the fan nameplate by checking the appropriate
boxes.
Mount the motor to the fan in a slot pattern on the motor/bearing support
plate that matches the motor frame footprint. The motor is mounted on
the same side of the motor/bearing support plate as the bearings and fan
shaft. The motor is usually mounted to the right side of the fan shaft. Use
the hardware provided which is located in the motor compartment of the
fan. Loosely snug the bolts at this time. Sizes 15, 16 and 18 have a
spacer bolt pack included. The junction box on certain motors will hit the
shaft. Use the spacers to raise the motor junction box above the shaft.
Install the adjustable sheave onto the motor shaft and the fixed sheave
onto the fan shaft. Align the sheaves as shown on page 5 of these
instructions and torque the set screws from 70 to 87 in-lbs. Install the
V-belt around the sheaves and slide the motor in the slots provided to
tension the belt (see page 4 for procedure). Once the belt is properly
tensioned and the alignment is correct tighten down the motor mounting
bolts.
Electrical Connection
1. Connect supply wiring to the disconnect switch (if supplied). Check the
wiring diagrams on the motor for connections.
2. The motor is factory set at the voltage marked on the fan nameplate.
Check the line voltage with the nameplate voltage and wiring
diagrams.
3. The main power wiring should be sized for the amperage shown on
the nameplate. Size wires in accordance with the ampacity tables in
Article 310 of the National Electrical Code. If long wires are required,
it may be necessary to increase wire size to prevent excessive
voltage drop. Wires should be sized for a max of 3% voltage drop.
CAUTION: Use copper conductors only.
CAUTION: Protect wiring from sharp edges. Leave some slack
in the line to prevent damage.
4. Disconnect switches (if supplied) are not fused. The power leads must
be protected at the point of distribution in accordance with the fan
nameplate.
5. On fans without a thermal protector integral to the motor (refer to
unit or motor nameplate to determine if protector is present) a
separate overload device is required. Refer to Sections 430-32 of the
N.E.C. for sizing.
6. All units must be electrically grounded in accordance with local codes
or, in the absence of local codes, with the latest edition of the
National Electrical Code (ANSI/NFPA 70). A ground lug is provided as
standard in the unit terminal box. Size grounding conductor in
accordance with Table 250-95 of the National Electrical Code. DO
NOT use the ground lug for connecting a neutral conductor.
7. Supply voltage to the power ventilator should not vary by more than
10% of the value indicated on the unit nameplate. Phase unbalance
must not exceed 2%.
WARNING: Failure of motor due to operation on improper line
voltage or with excessive phase unbalance constitutes product
abuse and may cause severe damage to the unit’s electrical
components.
fantech
4
Roof Fan Installation
Downblast Fans:
1.Position the fan with its wiring conduit in line
with the wiring coming up through the roof
curb and damper (if present). If the fan has
an external disconnect switch, position the
fan with the junction box towards the power
supply.
Upblast Fans:
1. Position the fan with its wiring conduit,
coming through the outer fan housing or its
external disconnect, towards the power
supply.
2. Run wires through the conduit to the switch.
Leave some slack in the wire in the motor
BEFORE START-UP: Disconnect power to this unit
before servicing the unit.
1. Check to verify that the wheel is free to
rotate.
2. For optimum fan performance make sure
that the wheel to inlet venturi overlap
(0.25”) is maintained.
3. Verify that supply voltage on the line side
of disconnect agrees with voltage on fan
nameplate and is within the 10% utilization
voltage.
4. Apply power to unit and check rotation of
wheel with the directional arrow on the unit.
WARNING: Rotation is critical. If
allowed to operate in the wrong
direction, the motor will overload and
bum out. Wheel rotation is clockwise
(CW) when viewed from the top
or drive side of the fan. Especially
check three-phase units for rotation.
For three-phase, rotation can be
changed by interchanging any two of
the three line leads. If unit is checked
on temporary wiring, it should
be rechecked when permanently
installed. Motor bum-out or tripped
overload protection devices are
usually the result of wrong rotation.
5. Electrical Input Check: Perform check of
fan ampere draw and verify that motor
nameplate amps are not exceeded. Take into
account the service factor range if the motor
is nameplated above a 1.0 service factor.
6. Fan RPM should be checked and veried with
a tachometer.
fantech
compartment so the motor and wheel
assembly can be lifted for inspection and
cleaning.
3. Bolt the fan base to the roof curb through
the holes provided on the base using eight
(8) lag bolts.
4. Make connection to the disconnect switch
per above electrical instructions.
5. Restaurant fan installation must be in
compliance with local codes and the
National Fire Protection Association’s NFPA-
96.
NOTE: The fan should not need
balancing, as it was balanced at
the factory to be within stringent
vibration levels before shipment.
However, there are several things
that may cause vibration, such as
rough handling in shipment and
installation, weak foundations and
alignments.
V-Belts
V-belts on these belt driven fans are oil, heat,
and static resistant type and oversized for
continuous duty. With proper installation and
maintenance, years of operating efciency can
be added to the lifespan of the V-belt drive.
The condition of V-belts and the amount of belt
tension should be checked prior to start-up
(see Figure1). When it becomes necessary
to adjust belt tension, do not over-tension as
bearing damage will occur. Recommended
belt tension should permit 1/64 deection per
inch of span of the belt at the center of the
belt span. To nd this point, measure halfway
between the pulley centerlines as shown in
Figure 2. Extreme care must be exercised when
adjusting V-belts as not to misalign the pulleys.
Any misalignment will cause a sharp reduction
in belt life and will also produce squeaky,
annoying noises (see Figure 3). On units
equipped with 2 groove pulleys, adjustments
must be made so that there is equal tension on
all belts (see Figure 4).
1. When tensioning loosen the motor mounting
bolts and slide motor until proper tension is
obtained.
2. Always loosen tension adjustment enough
to place belts on sheaves without running
Check, Test & Start Procedure
WARNING: Electric shock hazard.
Could cause severe injury or death.
Failure to bond the frame of this
equipment to the building electrical
ground by use of the grounding
terminal provided or other acceptable
means may result in electrical shock.
Disconnect electric power before
servicing equipment. Service to be
performed only by qualified
personnel.
belts over the edge of either sheave. A new
belt may be seriously damaged internally by
careless handling (see Figure 5).
WARNING: When removing or
installing belts, never force belts over
pulleys without loosening motor rst
to relieve belt tension. The fan has
been checked for mechanical noises
at the factory prior to shipment. If
mechanical noise should develop, then
some suggestions are offered here as
a guide toward remedying the cause.
1. Check rotating members for adequate
clearance.
2. Check proper belt tension and pulley
alignment.
3. Check installation and anchoring.
4. Check fan bearings.
Figure 1. Eliminate Slack
Figure 2. Belt Deection
Slack belts wear excessively, cause slippage
and deliver less power. For the longest belt life,
always provide proper tension.
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.