Falcon FN3K-2TXI, FN4K-2TXI, FN5K-2TXI, FN6K-2TXI, FN8K-2TXI Owner's Operating Manual

...
OWNER'S
OPERATING
MANUAL
FN SeriesTMUPS Plus
®
Parallel or N+1 Redundant 3kVA to 40kVA
Uninterruptible Power Supply Models:
FN3K-2TXI FN4K-2TXI FN5K-2TXI FN6K-2TXI FN8K-2TXI
FN10K-2TXI
FALCON®Electric, Inc., 5116 Azusa Canyon Rd., Irwindale, California 91706, (626) 962-7770, Fax (626) 962-7720, Email: sales@falconups.com
2011 Falcon®Electric Inc. All rights reserved. All other brand names and trademarks are the property of their respective owners. The information stated in this document is subject to change without notice. 2011-04-18 Falcon®, Falcon®Electric, FN and UPS Plus logos are registered trademarks of Falcon Electric, Inc.
FN Series Parallelable and N+1 Redundant UPS Features. . . . . 3
FN -2TXI Double-Conversion On-line UPS Block Diagram. . . . . 3
Important Safety Instructions (READ FIRST) . . . . . 4
Chapter 1. Introduction
1.1 Manual Overview. .... ..5
1.2 Brief FN Overview. .... ..5
Chapter 2. FN UPS Circuit Descriptions
Galvanically Isolated Output. . . . . . 6
Input & Power Factor Correction . . . . . 6
Power Factor Correction. . . . . . 6
DC/DC Converter. ..... ..6
DC/AC Inverter . . . . . . 6
Battery Packs ..... ..6
Internal Battery Charger .... ..6
Static Bypass Function. .... ..7
Automatic Bypass Transfers . . . . . 7
Output Filter ..... ..7
Chapter 3. Unpacking the UPS and Battery Bank
3.1 Unpacking Instructions . . . . . . 8
Chapter 4. Pre-installation Details
4.1 Floor Loading Requirements ...... 9
4.2 UPS Input Requirements. ......10
4.3 UPS Output Requirements ......11
4.4 UPS Output Ratings .......12
4.5 Hardwire Terminal Block Wiring Details .....13
4.6 UPS Rear Panel Details .......13
4.7 System Installation Wiring Diagram, Single UPS Unit ....15
4.8 System Installation Wiring Diagram, Multiple Parallel UPS Units . . 15
4.9 - 4.12 Parallel UPS Communications Bus Cabling ....16
1. Termination Resistor Switch Settings ....16
2. Primary N+1 UPS Setup Procedure
3. Second Through Fourth UPS N+1 UPS Setup Procedure
4.13 External Battery Charger Option Installation . ...17
Chapter 5. Displays & Controls
5.1 Control Button and LCD Locations . . . . . 18
5.2 Control Button Operation .... ..18
5.3 LED Display Modes ..... ..19
5.4 LCD Display Overview ..... ..20
5.5 LCD Icon Descriptions ..... ..20
5.6 Status & Error Code Descriptions . . . . . . 20
Chapter 6. Operation
6.1 How to start up the UPS with utility power present. . . . . 22
6.2 How to start up the UPS without utility power present. . . . 24
6.3 How to turn off the UPS inverter and place the UPS into bypass mode . . 24
6.4 How to completely shutdown the UPS . . . . . 24
6.5 How to display Readings. .... ..25
6.6 How to display Programmed Settings . . . . . 27
6.7 How to change the Programmed Settings . . . . . 30
6.8 How to use the Maintenance Bypass Switch. . . . 34
Chapter 7. Communications
7.1 Advanced Communications Option Cards Available . . . . 35
7.2 RS-232 Port ...... ..35
7.3 Remote Emergency Power Off .... ..36
7.4 Optional Communications Interface Board Details. . . . . 36
Chapter 8. Maintenance
1. UPS & Battery Care .... ..38
2. Storing the UPS and Batteries . . . . . 38
3. When to Replace Batteries . . . . . 38
4. Battery Pack Replacement . . . . . 38
8.1 FN -2TXI Internal Battery Pack Replacement. . . . . 39
8.2 How to replace the Internal UPS Battery Packs. . . . . 39
Chapter 9. FNB Extended Battery Bank Option Overview
9.1. How to connect the FNB Battery Bank . . . . . 41
Chapter 10. Parallel Mode Operation
10.1 How to configure FN -2TXI models for Parallel or N+1 Operation. . . 41
Chapter 11. Environmental
11.1 Recycling the Used Battery Packs . . . . . 41
11.2 FCC Considerations . . . . . . . 42
Chapter 12. Technical Support ..... ..43
Warranty ....... ..44
Specifications ...... ..45-50
TABLE OF CONTENTS
2
3
FN SeriesTMParallelable and N+1 Redundant UPS Features
FN -2TXI Model Double Conversion On-line UPS Block Diagram
Parallel Mode and N+1 Redundant Mode Operation True Double Conversion On-line Sinewave Design Output Galvanic Isolation LCD Display with Advanced Monitoring Remote Emergency Power Off (REPO) Input Power Factor Correction Wide Input Voltage Window Precision Output Voltage Regulation Superior Brownout, Surge and Transient Protection Frequency Converter Operation User-Replaceable and Hot-Swappable Battery Pack Optional Extended Battery Banks & Chargers RS-232, USB & Optional SNMP/HTTP Communications UPSilon UPS Monitoring & Management Software Two-Year Warranty
SAVE THESE INSTRUCTIONS
This manual contains important instructions which must be followed during the installation, operation and maintenance of the UPS and batteries. Please read all instructions before operat-
ing this equipment and save this manual for future reference.
All of the models presented herein are intended for installation in a controlled environment.
This UPS operates from utility power and contains a number of high current back-up batteries; this information is important to all personnel involved. Please read this manual first before continuing to unpack, install or operate this UPS.
STORAGE AND TRANSPORTATION
This UPS must be handled with care and given special attention due to the high amount of energy stored within its internal sealed, lead acid batteries. Please retain the UPS shipping container in the event the UPS needs to be returned for service. It has been designed to ship the UPS safely, without shipping damage.
INSTALLATION
This UPS must be installed in a clean environment, free from moisture, flammable gases or fumes and corrosive substances. This UPS is for use in a protected environment with an ambient
temperature range from 32ºF to a maximum of +104ºF (0ºC to +40ºC).
This UPS is designed for use with industrial, scientific or data processing class equipment.
WARNING
NEVER USE THIS UPS TO POWER LIFE SUPPORT EQUIPMENT OR ANY EQUIPMENT USED FOR “LIFE CRITICAL” APPLICATIONS.
The maximum UPS output load (in watts) must never exceed that shown on the UPS rating label. NEVER CONNECT equipment that could overload the UPS or demand half-wave rectification from the UPS, for example: electric drills, vacuum cleaners or hair dryers.
Storing magnetic media on top of the UPS may result in data loss or corruption.
WARNING
This UPS should be installed according to the instructions in this manual. Failure to do so could result in unsafe operation and could invalidate your warranty.
WARNING
Once batteries have reached the end of their life, ensure they are disposed of properly.
PLEASE REFER TO YOUR LOCAL LAWS AND REGULATIONS FOR BATTERY RECYCLING REQUIREMENTS. NEVER DISPOSE OF BATTERIES IN A LAND FILL.
Do not dispose of battery pack or batteries in a fire. The battery may explode. Do not open or mutilate the battery pack. Released electrolyte is harmful to skin and eyes. It may be toxic.
WARNING
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
* Remove watches, rings, and other metal objects. * Use tools with insulated handles.
4
5
1.0 INTRODUCTION
Manual Overview
This user manual has been written to provide basic information about Falcon FN Series -2TXI models. The FN Series is a rugged, double conversion, "on-line" UPS. It has galvanic output isolation configured for a split-phase (3 wire plus ground) 120/240Vac output. The FN Series provides continuous power conditioning and accepts a wide range input voltage, while providing tight output voltage regulation, with a true sinewave output. The FN Series UPS is specifically designed to protect sensitive computers and equipment against the widest range of power problems. These problems include power failures, voltage sags, voltage surges, brownouts, utility line noise, high voltage spikes, frequency variations, common mode noise, switching transients, and harmonic distortion.
This manual also details unpacking, unit installation and the major features of the FN Series UPS, in addition to detailed UPS operation, configuration and troubleshooting information.
The specifications section at the end of this manual provides detailed operating parameters and general information on approvals and certifications.
FN UPS Overview
The Falcon FN Series UPS is designed to be easily installed in a floor standing configuration.
The FN Series front panel features a graphical LCD display, providing detailed operational information at a glance. The display enables the user or field service engineer to easily monitor and troubleshoot localized power problems, in addition to UPS operation. UPS control and programming are easily accessed using push buttons located adjacent to the LCD display.
All FN -2TXI model rear panels have the following features and functions:
a. Two input Circuit Breakers. Bypass and UPS input circuit breakers are provided as supplemental protection devices. The UPS circuit breaker acts as the main on/off switchs for the UPS. It may be turned off to simulate a utility power loss or for performing battery runtime testing. The UPS can be completely shutdown when both the UPS and bypass circuit breakers are turned off, and the “Off” push button is depressed.
b. Single-phase 208-240Vac, 2 wire plus ground, hardwire input on a common terminal block.
c. Split-phase 120/240Vac, 3 wire plus ground, hardwire output on a common terminal block.
d. RS-232 Port - This port may be used to provide communications between the UPS and a network server
or other computer system. When used in conjunction with the supplied UPSilon software, remote UPS monitoring and control are facilitated. The software will automatically save all open computer files and initiate an unattended, orderly operating system shutdown in the event of a utility power outage. UPSilon supports most MS Windows and Linux operating systems. An optional UNIX version is available through Falcon at an additional cost.
e. Two Communications Option Board Expansion Slots - The slots support the installation of an
optional SNMP/HTTP Agent or contact closure interface boards. The SNMP/HTTP Agent board is a TCP-IP addressable solution to remote UPS monitoring and management via LAN, WAN or the Internet. The agent board is supplied with client software that will remotely shut down multiple servers or computers through the Ethernet LAN. A CD containing software clients and a SNMP MIB II compliant MIB is provided that supports most popular operations systems.
f. Two RJ45 connectors for connection of UPS parallel operation or remote maintenance
bypass interface cables.
Used when (2) or more FN -2TXI units are connected in parallel.
WARNING: Only FN models of identical power ratings may be connected in parallel. For example, a FN3K-2TXI may only be connected in parallel with another FN3K-2TXI unit. The FN5K-2TXI may only be connected in parallel with another FN5K-2TXI. The same is true for the FN6K-2TXI model.
6
g. One Local Maintenance Bypass Switch. The switch provides a manual means of placing the UPS
into bypass mode to allow for minor servicing to be performed on the UPS.
2.0 FN UPS CIRCUIT DESCRIPTIONS
Galvanically Isolated Output
The FN -2TXI models provide a galvanically isolated, 120/240Vac, hardwire output. To meet UL and code requirements, a dedicated electrical panel should be provided by your electrical contractor or electrician. The FN -2TXI output configuration gives the required split-phase output necessary to hardwire the UPS to most standard 3 wire plus ground type electrical panels. This both allows for the use of readily available branch rated circuit breakers and simplifies the distribution to 240Vac and 120Vac loads. The outputs of up to four FN -2TXI units may be connected in parallel. Please refer to pages 12-13 of this manual for wiring details.
Additionally, the FN galvanic output isolation in conjunction with a derived neutral greatly reduces common mode noise and ground loops.
Input & Power Factor Correction
All FN -2TXI models require a 2 wire plus ground type 208-240Vac at 50 or 60Hz. Each FN -2TXI unit input must be connected to a dedicated circuit having a branch rated circuit breaker. If multiple FN units are to be connected in parallel, care must be taken to verify the source electrical panel has enough capacity. It must be rated to supply the total power requirements of the FN Series units, all optional extended battery chargers, and any other circuits that may be connected to the panel. Please have your electrical contractor review the FN datasheet located at the end of this manual and perform a site survey several weeks in advance of the installation date.
While the FN Series UPS is operating from the utility power, the power factor correction circuit converts utility AC power into regulated DC power for inverter use. The circuit corrects the input current to maintain a sine waveform to minimize the amount of current distortion that will be reflected back to the utility.
DC/DC Converter
The DC/DC converter utilizes energy from the batteries and boosts up the DC voltage to a level required by the inverter. This allows the inverter to operate continuously at optimum efficiency and voltage. The converter incorporates a patented circuit which reduces the amount of ripple current and EMI interference to the battery, increasing the overall battery life.
DC/AC Inverter
In utility mode operation, the inverter utilizes the regulated DC output and converts it back into clean, regulated sinewave AC power. When utility power fails, the inverter will receive its energy from the battery through the DC/DC converter. In both modes of operation, the UPS inverter is online and continuously generates clean, regulated AC output power to the load. The IGBT, PWM inverter is of a very robust design and produces a pure sinewave output with a +/-2% voltage regulation. Having a very low output impedance, it can supply the high current demands of high inrush and non-linear loads.
Battery Packs
FN -2TXI models utilize flame retardant batteries packaged in (5) user-replaceable, hot-swappable packs that are accessible by removing the UPS lower front panel. There are (4) 12V, 7AH valve-regulated, sealed lead acid (VRLA) batteries in each pack (Yuasa NP7-12). See replacement instructions on page 38.
To maintain the optimum battery life, the UPS should be installed in an environment with an ambient temperature of 68ºF to 77ºF (20ºC to 25ºC). Due to the battery manufacturer specification, the FN Series UPS batteries may be operated at 32ºF to 104ºF (0ºC - 40ºC), but battery life will be substantially reduced if contin­uously operated at the higher temperature levels. Optional extended battery banks and charger modules are available through Falcon to extend the amount of battery runtime.
Internal Battery Charger
The internal UPS battery charger utilizes energy from the utility power to continuously charge the UPS batteries. The charger operates in "constant power" mode. The UPS batteries are being charged whenever the UPS is plugged in, turned on and operating from utility power. The internal UPS battery charger output is rated at 1.9 amps.
Static Bypass Function
NOTE: Bypass power will only be available If the bypass input is connected at the time of UPS installation.
A manual static bypass pushbutton is located on the FN front control panel. When the UPS is operating from utility in the normal utility mode on-line state, depressing this button will cause the UPS to transfer to bypass. Depressing the bypass button again will return the UPS to normal inverter operation.
Automatic Bypass Transfers
NOTE: Bypass power will only be available if the bypass input is connected at the time of UPS installation.
The FN Series UPS will automatically switch to bypass mode under the following conditions: To energize the connected load when the UPS is first turned on; encounters an overload; encounters an over temperature condition; or upon a UPS failure condition. Should any of these events occur, the UPS will transfer to bypass mode, sound an audible alarm and provide a "BPS" indication on the LCD display.
Output Filter
As with the input filter stage, the output filter maintains conducted (EMC) and RFI levels below FCC Class A limits.
7
8
3.0 UNPACKING THE UPS AND BATTERY BANK
Due to their size and weight, FN -2TXI model UPS units and optional battery banks are shipped secured to shipping pallets. Removal of the UPS and battery bank should never be attempted by one person.
Upon unpacking the UPS or battery bank, verify the following items were shipped. Should you have not received any of the items listed below, please contact Falcon Electric Customer Service at 1-800-842-6940
.
FN -2TXI UPS Models FNB1S7-6K6 Extended Battery Bank
Shipping pallet contents: Shipping pallet contents:
(1) FN -2TXI UPS (verify the exact model shipped) (1) FN Extended Battery Bank (1) RS-232 Cable (1) Interface Cable (1) UPSilon Software CD (1) Installation Kit (1) Software Interface Cable (1) Owner’s Manual
NOTE: If multiple FN UPS units were received for connection in parallel, please verify
that one parallel interface cable kit has been received for each FN unit received.
3.1 Unpacking Instructions
1. Cut the bands securing the protective carton and lift it off of the UPS or battery bank.
2. Remove the (8) upright boards from the upper and lower crate assemblies.
3. Remove the upper crate piece off of the top of the UPS or battery bank.
4. Using a fork lift position the forks under the UPS or battery bank and lift it out of the lower shipping cradle.
Note: The UPS or extended battery bank weighs over 300 pounds. It is not
recommended that you attempt to lift and remove them from the shipping pallet without the proper equipment.
Unpacking Details
9
4.0 PRE-INSTALLATION DETAILS
Falcon Electric, Inc. is not responsible for shipping damage or for filing shipping damage claims. Visually inspect the UPS for freight damage. If any equipment has been damaged during shipment, retain the shipping pallet and packing materials for inspection by the carrier, and immediately file a claim for “shipping damage” with the carrier. If you discover damage after acceptance, file a claim for “concealed damage”.
To file a claim for shipping damage or concealed damage:
a. YOU MUST file with the carrier within 15 days of receipt of the equipment; b. YOU MUST send a copy of the damage claim within 15 days to Falcon Electric, Inc.
WARNING
The UPS and Battery Module are very heavy. Use the proper lifting equipment and take the proper precautions when lifting or moving them.
1. Install the UPS indoors in a controlled environment.
2. Place the UPS in an area with unrestricted airflow around the unit, away from water, flammable liquids,
gases, corrosive, and conductive contaminants.
3. Maintain a minimum clearance of 12 inches in the front and rear of the UPS.
4. Maintain an ambient temperature range of 32ºF to 104ºF (0ºC to 40ºC). To assure the maximum life of the
batteries, UPS operation in an ambient temperature of 68ºF to 77ºF (20ºC to 25ºC) is recommended.
OPERATION IN TEMPERATURES ABOVE 77ºF (25ºC) WILL REDUCE BATTERY LIFE.
5. The FN Series UPS and optional extended battery banks must be installed in an upright position on a flat
surface. After installation, all (4) UPS caster locks must be depressed and set to the locking position.
6. When selecting a suitable location for the UPS and extended battery bank(s) always verify:
4.1 Floor Loading Requirements
a. THE FLOOR OR SUPPORTING SURFACE IS RATED TO SUPPORT THE WEIGHT OF THE UPS AND
ALL EXTENDED BATTERY BANKS TO BE CONNECTED.
UPS with internal batteries:
(1) FN3K-2TXI or FN4K-2TXI or FN5K-2TXI or FN6K-2TXI = 286.6 lbs. (130 kg), 8 & 10kVA 328 lbs. (148.7) (2) FN3K-2TXI or FN4K-2TXI or FN5K-2TXI or FN6K-2TXI = 573 lbs. (260 kg), 8& 10kVA 657 lbs. (298) (3) FN3K-2TXI or FN4K-2TXI or FN5K-2TXI or FN6K-2TXI = 859.8 lbs. (390 kg), 8 & 10kVA 985.5 lbs.(447) (4) FN3K-2TXI or FN4K-2TXI or FN5K-2TXI or FN6K-2TXI = 1146 lbs. (520 kg), 8 & 10kVA 1314 lbs. (596)
Extended Battery Banks (for all FN -2TXI models)
(1) FNB-1S7 or FNB-1S9 = 180 lbs. (81.7 kg) (2) = 360 lbs. (163.3 kg) ­(3) = 540 lbs. (245 kg) (4) = 729 lbs. (327 kg)
(1) FNB-2S7 or FNB-2S9 = 290 lbs. (131.6 kg) (2) = 580 lbs. (263.1 kg) (3) = 870 lbs. (394.7 kg) (4) = 1,160 lbs. (526.2 kg)
(1) FNB-3S7 or FNB-3S9 = 400 lbs. (181.5 kg) (2) = 800 lbs. (362.9 kg) (3) = 1,200 lbs. (545 kg) (4) = 1,600 lbs. (726 kg)
4.2 UPS Input Requirements
CAUTION - To reduce the risk of fire, connect the UPS input to a circuit provided with branch rated circuit breaker protection per the following table, in accordance with the National Electrical Code and ANSI/NFPA 70 requirements
a. VERIFY THE PROPER UPS INPUT POWER IS AVAILABLE (for each UPS installed)
FN3K-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 20A, single-phase, 2 wire plus ground
Branch Rated Circuit Breaker Rating = 20A Use only #10 AWG, 75C copper wire and torque terminal block screws to 17.7 in-lb.
FN4K-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 30A, single-phase, 2 wire plus ground
Branch Rated Circuit Breaker Rating = 30A Use only #10 AWG, 75C copper wire and torque terminal block screws to 17.7 in-lb.
FN5K-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 40A, single-phase, 2 wire plus ground
Branch Rated Circuit Breaker Rating = 40A Use only #10 AWG, 75C copper wire and torque terminal block screws to 17.7 in-lb.
FN6K-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 40A, single-phase, 2 wire plus ground
Branch Rated Circuit Breaker Rating = 40A Use only #10 AWG, 75C copper wire and torque terminal block screws to 17.7 in-lb.
FN8K-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 50A, single-phase, 2 wire plus ground
Branch Rated Circuit Breaker Rating = 50A Use only #8 AWG, 75C copper wire and torque terminal block screws to 23 in-lb.
FN10K-2TXI Input -- Hardwire, 208-240Vac, 50/60Hz, 65A, single-phase, 2 wire plus ground
Branch Rated Circuit Breaker Rating = 65A Use only #6 AWG, 75C copper wire and torque terminal block screws to 23 in-lb.
10
4.3 UPS Output Requirements
CAUTION - An output disconnect circuit breaker must be provided. To reduce the risk of fire, connect on to a circuit provided with branch rated circuit breaker over-current protection. Please refer to the table below for the specific branch rated circuit breaker amperage rating.
11
4.4 UPS Output Ratings
WARNING: If the (50 or 60Hz) constant frequency mode is enabled, the UPS output(s) must be derated by 25%. Please refer to the fixed frequency output mode ratings for your model in the specifications located
at the end of this manual.
FN3K-2TXI:
Output Marking: No.1 (Output2 0V L1- Output2 120V L2): 1.5KVA, 120 V. No.2 (Output1 0V L1- Output1 120V L2(N)): 1.5KVA, 120 V. No.3 (Output1 0V L1- Output2 88V L2): 3KVA, 208 V No.4 (Output1 0V L1- Output2 120V L2): 3KVA, 240 V.
Use only #10 AWG, 75C copper wire and torque terminal block screws to 17.7 in-lb.
FN4K-2TXI:
Output Marking: No.1 (Output2 0V L1- Output2 120V L2): 2KVA, 120 V. No.2 (Output1 0V L1- Output1 120V L2(N)): 2KVA, 120 V. No.3 (Output1 0V L1- Output2 88V L2): 4KVA, 208 V No.4 (Output1 0V L1- Output2 120V L2): 4KVA, 240 V.
Use only #10 AWG, 75C copper wire and torque terminal block screws to 17.7 in-lb.
FN5K-2TXI:
Output Marking: No.1 (Output2 0V L1- Output2 120V L2): 2.5KVA, 120 V. No.2 (Output1 0V L1- Output1 120V L2(N)): 2.5KVA, 120 V. No.3 (Output1 0V L1- Output2 88V L2): 5KVA, 208 V No.4 (Output1 0V L1- Output2 120V L2): 5KVA, 240 V.
Use only #10 AWG, 75C copper wire and torque terminal block screws to 17.7 in-lb.
FN6K-2TXI:
Output Marking: No.1 (Output2 0V L1- Output2 120V L2): 3KVA, 120 V. No.2 (Output1 0V L1- Output1 120V L2(N)): 3KVA, 120 V. No.3 (Output1 0V L1- Output2 88V L2): 6KVA, 208 V No.4 (Output1 0V L1- Output2 120V L2): 6KVA, 240 V.
Use only #10 AWG, 75C copper wire and torque terminal block screws to 17.7 in-lb.
FN8K-2TXI:
Output Marking: No.1 (Output2 0V L1- Output2 120V L2): 4KVA, 120 V. No.2 (Output1 0V L1- Output1 120V L2(N)): 4KVA, 120 V. No.3 (Output1 0V L1- Output2 88V L2): 8KVA, 208 V No.4 (Output1 0V L1- Output2 120V L2): 8KVA, 240 V.
Use only #8 AWG, 75C copper wire and torque terminal block screws to 23 in-lb.
FN10K-2TXI:
Output Marking: No.1 (Output2 0V L1- Output2 120V L2): 5KVA, 120 V. No.2 (Output1 0V L1- Output1 120V L2(N)): 5KVA, 120 V. No.3 (Output1 0V L1- Output2 88V L2): 10KVA, 208 V. No.4 (Output1 0V L1- Output2 120V L2): 10KVA, 240 V.
Use only #6 AWG, 75C copper wire and torque terminal block screws to 23 in-lb.
12
4.5 Hardwire Terminal Block Wiring Details
FN -2TXI Models Hardwire Terminal Designations
Wiring Detail for a 120/240Vac Split-Phase Output
Wiring Detail for a 120/208Vac Output
13
4.6 Rear Panel Details
14
15
4.9 System Installation Wiring Diagram (single UPS unit, 120/240V Output)
4.10 System Installation Wiring Diagram (typical multiple parallel UPS units, 120/240V Output)
WARNING: The 50 or 60Hz constant frequency model must not be set if multiple FN units are to be connected in parallel or used in N+1 mode.
Suggested UPS Output Panel & Circuit Breakers
UPS Output Panel = Square D P/NQQ12L125G (1 each) Panel Master Circuit Breaker 120A = QQM110VH (1 Each)
Individual UPS Circuit Breakers
3kVA -- 20A Square D P/N QQ220VH 4kVA to 6kVA -- 30A Square D P/N QQ230VH 8kVA -- 40A Square D P/N QQ240VH 6kVA -- 50A Square D P/N QQ250VH
Loading...
+ 35 hidden pages