Faber BF110V/Straight, BF120H/Relaxed Installation Manual And User's Manual

Page 1
Natural Fires
BF110V / Straight and BF120H / Relaxed
Installation Guide and User Manual
40010550
Page 2
UK/IRL
2 < < < <
Page 3
UK/IRL
> > > > 3
Content
Content....................................................................... 1
Content....................................................................... 3
1. Introduction.......................................................... 5
2. Safety instructions.................................................. 6
3. Installation requirements.......................................... 7
3.1 Builders opening and surround.................................................. 7
3.2 Dimensions of the fire place....................................................10
3.3 Flue requirements....................................... ... ... .. ... ..............17
3.3.1 Terminal position....................................................................... 20
3.3.2 Using an existing chimney as air inlet............................................... 21
4. Instalation-instructions ...........................................22
4.1 Gas connection ...................................................................22
4.2 Preparing the appliance................................... ......................22
4.3 Installing the appliance with the Faber false chimney breast ............23
4.4 Installing the appliance in an existing or different false chimney breast.23
4.4.1 Preparing the surround.................................................................... 23
4.4.2 Installing the appliance ................................................................... 24
4.4.3 levelling and fixating the appliance.....................................................24
4.4.4 Building the false chimney breast ....................................................... 24
4.5. Removing/placing the glass ...................................................25
4.5.1 Removing/placing the glass of the BF110V / Straight................................ 25
4.5.2 removing/placing the glass of the BF120H / Relaxed ................................ 26
4.6 placing and adjusting the frame...............................................27
4.7 Placing the log set with the log burner.......................................28
4.8 Placing the pebbles with pebble burner......................................28
5. Installation of the flue ............................................29
5.1 Connections with use of concentric duct material..................... .....29
5.2 Connection onto an existing chimney.........................................29
5.3 Remote control....................... ... .. ... ... .................................30
5.3.1 Installation remote control......................................... ...................... 31
6. Commisioning (functional checks) ..............................33
6.1. Check pilot ignition.............................................................33
6.2 Functional burner check .................................. ... .. ... ..............33
6.3 Functional balanced flue check................................................34
6.4 Check reference pressure and burner pressure .............................34
7. Final check and handing over....................................36
Page 4
UK/IRL
4 < < < <
8. Servicing.............................................................37
8.1 Routine servicing.................. .................................... ... .. ......37
8.1.1 Cleaning the glass ..........................................................................37
8.1.2 Cleaning the combustion chamber and burner ........................................ 38
8.1.3 Burner tray (dis)assembly................... ............................... ............... 39
8.1.4 Gas control block........................................................................... 39
8.2 Propane conversion ........................................ ... ... ................39
8.3 Combustion test......................... .. ... ... ... ..............................39
8.4 List of spare parts.......................................................... ... ...40
User guide...................................................................41
9. Safety instructions for the user .................................43
9.1 General safety instructions.....................................................43
10. Controlling the appliance.........................................45
10.1 General................................................................ ... ..... ...45
10.2 To light ...........................................................................46
10.3 To extinguish .................................................... .. ... ... ........46
10.3.1 When the pilot extinguishes.............................................................46
10.4 Remote control version.......................... ... .. ... ......................47
10.4.1 Using the remote control................................................................ 47
10.4.2 Setting the right transmission code... ................................................. 48
10.4.3 Changing the batteries. .................................................................. 48
11. Cleaning and service instructions...............................49
12. Disposal of packaging and appliance ...........................50
Appendix: technical data.................................................51
Page 5
UK/IRL
> > > > 5
1. Introduction
Note: these instructions should be read carefully and retained for future reference. Please leave these instructions with the user.
This guide is concerning the following types of appliances:
BF110V / Straight frameless with log burner (Faber false chimney breast optional);
BF110V / Straight frameless with pebble burner(Faber false chimney breast optional);
BF110V / Straight with frame and log burner;
BF110V / Straight with frame and pebble burner;
BF120H/Relaxed frameless with flat fibre burner and logset;
BF120H/Rlaxed frameless with pebble burner;
BF120H/Relaxed with frame and flat fibre burner and logset;
BF120H/Relaxed with frame and pebble brander.
Special features:
- The frameless models of the Natural Fires feature a patented window construction;
- A specially designed Faber prefab false chimney breast is optional (only for the frameless versions of the Natural Fires);
- Realistic flame and glow effect because of the "Log burner" technology;
- Room sealed appliance, inlet and outlet are led to the outside using a natural draught concentric pipe system (100 mm/150 mm). No additional ventilation required;
- Air supply and flue-gases go to outside atmosphere through wall or roof. A maximum horizontal extension of 6 meters is possible;
- Remote Control option on all appliances;
- Meets the essential requirements of the European Gas Appliance Directive (GAD) and
carries the CE mark according the NEN 613 standard.
Page 6
UK/IRL
6 < < < <
2. Safety instructions
Before installation, ensure that the local distribution conditions (identification of the type of gas and pressure) and the adjustment of the appliance are compatible. This information can be found on the data plate. This gas appliance is factory set and shall not be adjusted.
This appliance does not contain any component manufactured from asbestos or any asbestos related products.
The pilot and flame sensing device fitted to this fire is also a safety device. If for any reason any part of the pilot assembly is to be replaced, the entire assembly, including the pilot burner, thermocouple, electrode and injector, must be exchanged complete for a pilot assembly from the original manufacturer only.
Do not put extra (glow-)elements in the combustion chamber. This could affect the burning process in a negative way.
This appliance is room-sealed and doesn't require purpose provided ventilation.
It is the law in the UK that all gas appliances are installed and checked by a competent person in accordance with the Gas Safety (Installation and Use) Regulations (as amended), the relevant British Standards for Installation work, Building Regulations, Codes of Practice, and the manufacturer’s instructions.
The installation should also be carried out in accordance with the following where relevant:
British Standards: BS5871 Part1, BS5440 Parts 1 & 2 and BS1251;
Building Regulations Document J (as applicable);
Building Regulations and Standards issued as relevant by the Department of the
Environment or the Scottish Development Department.
In the Republic of Ireland installation should be carried out in accordance with IS813, ICP3, IS327, Building Regulations, Codes of Practice, the manufacturer’s instructions and any other rules in force.
Failure to comply with th e above could leave the installer liable to prosecution and invalidate the appliance warranty.
The construction of the fire place is not to be altered.
Safety instructions for the user can be found in chapter 9.
Page 7
UK/IRL
> > > > 7
3. Installation requirements
Note: Since the appliance is a source of heat, circula tion of air occurs. Therefore it is of importance that you do not use the appliance shortly after a renovation of the home. Because of the natural circulation of air, moist and volatile components from paint, building materials, carpet etc. will be attracted. These components can settle themselves down onto cold surfaces in the form of soot.
As on all heat producing appliances, soft furnishings such as blown vinyl wallpaper placed too near to the appliance may become scorched or discoloured. This should be born in mind when installing the appliance.
3.1 Builders opening and surround
Both the BF110V/Straight frameless and the BF110V/Straight frameless can be build in an optional
Faber prefab false chimney breast made of promatec. This false chimney breast is specially designed to accommodate this type (NOT for the models with frame) and is applicable for ceiling heights up to 2,9m. It consists of a base part and either a top part made of promatec or an ornamental flue pipe made of stainless steel.
The fire place can also be build in a non-combustible fire place or builders opening. This could be either an existing builders opening or a new made prefab builders opening. For the measurements, see paragraph 3.2.
When you apply your own false chimney breast design to all models of the BF110V/Straight or BF120H/Relaxed, you have to meet these general requirements:
The false chimney breast has to be made of inflamable material;
The minimum inner width of the false chimney breast has to be at least 976mm (see
paragraph 3.2) and is secured by the floor plate;
Minimum distance from the back of the appliance to the wall has to be 10 mm;
Always install the fire place first, before building up the false chimney breast;
Always ventilate the space above
the appliance using vents to assure a good air-
circulation;
If the appliance is to be fitted against a wall with combustible cladding, the cladding
must be removed from the area covered by the surround;
The plaster of the outside has to be resistant to a high temperature. Therefore use the
Page 8
UK/IRL
8 < < < <
plaster materials especially made for this, to prevent discoloring (min. 100 °C temperature resistant);
Make sure the plaster dries well before using the appliance. Let the thickness in mm
be the number of days the plaster has to dry, e.g. 3 mm plaster has to dry for 3 days.
Although the appliance is tested for installation without a hearth, the appliance must
not stand on combustible materials or carpets. If the appliance is placed on a combustible floor first place a fibrelux or similar heatproof board of 12 mm thickness. Any under floor vents or openings within the builders opening should be sealed off;
If the floor will be adjusted (e.g. by applying carpet or parquet), the floor under the
false chimney breast has to be adjusted to match the future floor height;
Do not place any material directly onto the appliance. If possible, apply a lintel made
of cement or something similar;
Make sure that both the gas control block and the main gas valve are easy accessable
at all times and can be operated if necessary.
Specific requirements for making a false chimney breast for the BF110V / Straight frameless:
The front opening of the false chimney breast has to be at least 460mm wide and
1100mm high, measured from the underside of the floor plate;
Minimum distance from the glass to any of the construction parts of the false chimney
breast should be at least 12 mm. This is the minimum distance with which the glass can still be taken out;
When using a material thicker than 12mm, e.g. 50mm thick stony material, the floor
plate has to be adjusted according to the indicated pattern (see paragraph 3.2 for construction details and dimensions);
Specific requirements for a false chimney breast for the BF110V / Straight with frame
:
The wall opening has to be 620x1100 mm. This is smaller than the appliance!!!
The gas control block can be mounted on either the left or right side of the floor plate,
depending on which side makes it easier to acces it.
Specific requirements for a false chimney breast for the BF120H / RELAXED frameless:
The (wall) opening has to be 1050x425 mm. This is smaller than the appliance;
The (wall) opening depth is 50 mm. The distance between the opening and the glass
should be at least 12 mm. This is measured after finishing!
Page 9
UK/IRL
> > > > 9
Use 12 mm Promatec for the front of the false chimney breast. Building up the false
chimney breast with e.g. Ytong blocks is not possible;
The gas block is normally mounted on the right side of the appliance but can be place
elsewhere, thanks to a 1.2 m flexible gas line;
Make sure the that the top ridge of the (wall) opening is left out! (see drawings in
§3.2). This is necessary to be able to remove the glass and assure a good air circulation!
Page 10
UK/IRL
10 < < < <
3.2 Dimensions of the fire place
* frame thickness with 3mm play ** distance higher than the floor plate *** Width floor plate / with DC-box **** Depth builders opening including distance to the glass
On the next few pages the dimensions of the BF110V / Straight and BF120H / Relaxed are visualised in drawings.
Model/dimensions
BF110V /
Straight
frameless
BF110V /
Straight
with frame
BF120H /
Relaxed
frameless
BF120H /
Relaxed
with fra me
Steel door
Frames
Max w idth outer frame n/a 640 n/a 1180 250 Max. height outer frame n/a 1125 n/a 650 300 Width opening inner frame n/a 460 n/a 960 150 Height opening inner frame n/a 945 n/a 430 200 Frame thickness n/a 36 n/a 38* n/a Distance bottom appliance - bottom frame n/a 62 n/a 41** free
Ins ta lla tio n D imen s io n s
Width wall opening/width dag 460 616 1050 1166 224 Height wall opening/height dag 1100 1100 425 636 270 Max. wall thickness/depth fireplace opening 75**** 24 62**** 24 zelf bepalen Bottom applicance - bottom wall opening n/a 74 159 43** n/a Max. width applicance 976/608*** 976/608*** 1600/1155**
*
1600/1160**
*
n/a Max. height applicance 1181 1181 688 688 12 Min. depth applicance (from wall) 348 309 388 310 12
Flue Dimensions
Distance wall - flue pipe 159 159 135 135 n/a Distance wall - DC-connection n/a n/a 139 139 n/a
Page 11
UK/IRL
> > > > 11
[ BF110V / Straight ]
Frameless
Top view false chimney breast:
Top view of the appliance:
Page 12
UK/IRL
12 < < < <
Front view false chimney breast:
[ BF110V / Straight ]
Frameless
Page 13
UK/IRL
> > > > 13
[ BF110V / Straight ]
With frame
Top View:
Front View
:
Page 14
UK/IRL
14 < < < <
[ BF120H / Relaxed ]
Frameless
Top view:
Front view
:
Cross section side view:
Cross section side view detail:
Page 15
UK/IRL
> > > > 15
Top View:
Front View
:
Front View
:
Cross section side
:
[ BF120H / Relaxed ]
With frame
Page 16
UK/IRL
16 < < < <
[ Operation door ]
Page 17
UK/IRL
> > > > 17
3.3 Flue requirements
The appliance is of the type C11/C31. The appliance will need to be supplied with the approved flue pipes and terminal, it is not possible to supply your own.
The minimum effective height of the flue system must be 0.5 or 1 meter, depending on the appliance.
Flue routing;
- The terminal locations, through the wall as well as through the roof;
- A horizontal extension with elbows is allowed for a maximum of 6 meters (depending
on the type and situation);
- Vertical max. 12 meters.
Determine on the base of the table 2 and 3, depending on the type and terminal position, if the desired situation is possible. To establish this you will need to calculate:
- The effective height (this is the real difference in height between the upper side of the appliance and the terminal);
- The total horizontal extensio n. This is the total horizontal flue length where:
o Each elbow, which is in the horizontal area, counts for 2 meters; o Each 45-degree bend, which is in the horizontal area, counts for 1 meter; o Elbows and bends at the transition of horizontal to vertically are not to be
counted;
o The wall mounted terminal counts for 1 meter.
Flue restrictor
If applicable, in the table is also stated the size of a flue restrictor. This restrictor needs to be fitted in the combustion chamber when placing the appliance (see chapter 4.2). Normally the smallest flue restrictor is fitted.
Page 18
UK/IRL
18 < < < <
Example calculation 1:
Calculating horizontal extension fig. 2a:
Flue lenght C + E = 1m + 1m 2 m Elbows D = 2m 2 m Total horizontal extension 4 m
Measure or calculate effective height (Hvert)
Flue lenght A 1 m Roof mounted terinal 1 m Total effective height 2 m
When calculating on basis of the Widescreen table nr. 2: It is allowed. Remove the flue restrictor!
When calculating on basis of the MV100 table nr. 3: Allowed but without flue restrictor. Remove the flue restrictor! When calculating on basis of theMV150 table nr. 4: Allowed but without flue restrictor. Remove the flue restrictor! When calculating on basis of the Roundscreen table nr. 5: Allowed but without flue restrictor. Remove the flue restrictor!
Example calculation 2
Calculati0n horizontal extension fig. 2b
:
Flue lenght J + L = 0,5 + 0,5 1 m Elbows K + M = 2m + 2m 4 m Terminal 1 m Total horizontal extension 6 m
Vertical
Flue lenght
H 1 m
When calculating on basis of the Widescreen table nr. 2: Combination not allowed.
When calculating on basis of the MV100 table nr. 3: Allowed but without flue restrictor. Remove the flue restrictor!
When calculating on basis of the MV150 table nr. 4: Combination not allowed.
When calculating on basis of the Roundscreen table nr. 5: Combination not allowed.
Page 19
UK/IRL
> > > > 19
BF110V with logburner Note: the BF110V / Straight with logburner can be lead directly to the wall, using a pipe
bend.
Determine according to the table 2 the right total horizontal and vertical length. When meeting an x, and when the values are outside the table, the combination is not allowed. The 30 mm flue restrictor is normally preinstalled.
*The BF110V / Straight with logburner can be lead directly to the wall, using a bend pipe.
0 1 2 3 4 5 6 0 1 2 3 4 5 6
0 x
0*
x x x x x x x x x x x x
0,5 x
30
x x x x x x 0 x x x x x
1 x
30 0 0 0
x x x
0 0 0
x x x
1,5
40 30 0 0 0 0
x
30 30 0 0 0
x x
2
40 30 0 0 0 0 0 30 30 0 0 0 0 0
3
40 40 30 0 0 0 0 30 30 0 0 0 0 0
4
50 40 40 30 0 0 0 40 40 30 0 0 0 0
5
50 50 40 40 30 30 0 50 50 40 30 0 0 0
6
50 50 50 40 40 30 0 50 50 50 30 30 0 0
7
60 50 50 40 40 40
x
50 50 40 30 30 0
x
8
60 60 50 50 50
x x
50 40 30 30 0
x x
9
60 60 60 50
x x x
50 50 40 30
x x x
10
65 60 60
x x x x
55 55 50
x x x x
11
65 65
x x x x x
55 55
x x x x x
12
65
x x x x x x
55
x x x x x x
Tabel 2: Possible lenth and height combinations
Hoogteverschil in meters
BF110V / Straight
BF120
H
/ Relaxed
Page 20
UK/IRL
20 < < < <
3.3.1 Terminal position
Verify if the required terminal position meets the local installation regulations regarding disturbance, good functioning and ventilation (Also see: safety requirements).
Note:
The terminal must be located so that the outlet is not obstructed. If the flue terminal is located within 2 meters of a footway, path or where people could come into contact with it then a suitable terminal guard must be fitted.
Terminals located close to shared walkways, footpaths etc. could be subject to legal constraints and this should be pointed out to the customer before installation. If in any doubt about flue location advice should be sought from local building control, or if appliance-related, from the manufacturer including wherever possible a dimensioned sketch.
Avoid locating the terminal in close proximity to plastic materials such as gutters or other combustibles. If this is unavoidable then a suitable deflector should be made.
Some important requirements for a good functioning are:
- The wall-mounted terminal has to be at a distance of at least 0.5 meters off:
o Corners of the building; o Below eaves; o Balcony's etc. unless the duct is dragged to the front side of the overhanging
part.
- The roof mounted terminal has to be at a distance of at least 0.5 meters of the sides
of the roof, excluded the ridge.
Page 21
UK/IRL
> > > > 21
Site in accordance with BS 5440-1:2000 and the document J
3.3.2 Using an existing chimney as air inlet
The appliance can be connected onto an existing chimney. The existing chimney then functions as air supply, where a flexible stainless steel liner (to BS715) of 100 mm performs the flue function. Requirements:
- Any existing chimney used as an air supply must only service this appliance;
- A chimney that has previously been used for solid fuel must be swept before use;
- The existing chimney needs to be airtight;
- The existing chimney needs to have an opening of min. 150 x 150 mm;
- The chimney needs to be intact and well looked after;
- Use the adjustable roof-mounted-terminal especially made for this, and the chimney
connection set;
- The minimum distance between two terminals should be at least 450 mm.
Page 22
UK/IRL
22 < < < <
4. Instalation-instructions
4.1 Gas connection
- Installation pipes should be in accordance with BS 6891. Pipe work from the meter to the appliance must be of adequate size.
- The complete installation including the meter must be tested for soundness and purged as described in the above code.
- A means of isolation must be provide in the supply to facilitate servicing.
- The connection should be made in 8 mm copper or similar semi flexible tube (max 1
meter). Ensure that th e gas pipe does not interfere with the removal or replacement of the burner tray of the controls.
- The gas connection is nut and olive suitable for 8 mm pipe.
Make sure there is a gas connection with a diameter of 8 mm goes directly from the gas meter to the appliance, with a CE-approved sealing valve G 1/2". This valve has to be accessable at all times. Check the connection for gas leaks.
The gas connection is positioned on the right of the appliance.
You can choose to place the sealing valve on the in- or outside the false chimney breast. When mounted inside, a small hatch has to be installed (can be ordered separately).
If the gas connection comes out of the floor in the false chimney breast, a hole of sufficient size has to be drilled.
Mount the supplied nut and olive of 8 mm directly on the gas unit. Then you can go on installing a fixed or flexible connection. This has to be CE certified.
When installed as described above, the burner can always be disassembled for servicing.
4.2 Preparing the appliance
1. Remove the screws from the front legs, see figure;
2. You can now remove the appliance from the floor plate.
Page 23
UK/IRL
> > > > 23
4.3 Installing the appliance with the Faber false chimney breast
When the appliance is purchased with a Faber false chimney breast, then first follow the instructions delivered with the package of the false chimney breast.
4.4 Installing the appliance in an existing or different false chimney
breast.
Read the requirements described in paragraph 3.1 before continuing with the installation!
4.4.1 Preparing the surround
1. Check if the floor and wall are sufficiently level. If necessary, improve it;
2. If the floor will be raised higher (e.g. by installing carpet or parquet), the floor
underneath the fire place has to be equall y raised;
3. Insulate the back wall with promatec of comparable inflammable material;
4. Drill holes for the flue routing. Minimum height with flue routing through the back wall
is the height of the appliance plus the pipe bend. When going through the roof, a hole with a diameter 200mm has to be drilled in the ceiling at a distance of 170 mm from the wall to the heart of the hole. This hole indicates the centre of the false chimney breast. Moving it afterwards is not possible.
5. Adjust the fl oor plate, if necessary:
Drill a hole on the floor pla te where
the gas connection will come out of the floor;
Cut off the knockouts (A en B, see
figure) which are meant for the Faber false chimney breast;
6. Position the floor plate and mount it to the
floor;
7. Prepare the gas connection, see paragraph
4.1.
Page 24
UK/IRL
24 < < < <
4.4.2 Installing the appliance
1. Turn the 4 legs until they are extended 20 mm
2. Install the appliance with the two front l egs
positioned between the supports on the floor plate;
3. Lift the appliance gently over the supports, then put
it down;
4. Make sure that the gas connection isn’t stuck
between the receiver holder and the floor plate
4.4.3 levelling and fixating the appliance
1. Level the appliance in all directions by adjusting the legs underneath the appliance;
2. Secure the legs;
3. Secure the appliance to the wall;
4. Install the flue routing as describes in chapter 5.
4.4.4 Building the false chimney breast
You are now ready to build a false chimney breast construction. If you purchased the BF110V / Straight
Frameless, you can use the distance holders on top of the appliance to fixate the construction and keep the builders o pening at a minimum width of 460 mm. Keep in mind that this is measured with
the finishing (e.g. plaster).
Note:
The width of 460 mm of the builders opening is very critical, since this is the minimum width with which the glass can be taken out. If the opening is made much wider, the construction of the appliance can become visible;
Frequently check the distance from the front of the glas s to any of the construction parts of the false chimney breast is at least 12 mm for the
20mm
Page 25
UK/IRL
> > > > 25
BF110V / Straight Frameless. Again, this is to be able to take out the glass.
4.5. Removing/placing the glass
the BF110V / Straight as well as the BF120V / Relaxed use the same kind of securing system for the glass. The only difference is in the place where the glass is secured. This has an effect on how the glass has to be removed: sideways for the BF110V / Straight, and up for the BF120H / Relaxed. on the following two pages removing the glass will be explained using pictures
4.5.1 Removing/placing the glass of the BF110V / Straight
1. Take away the frame or the
stainless steel door.
2. Unscrew the two screws
underneath on either side of the glass a few centimeters.
3. Move both handles as far towards
you as possible. The glass is now unsecured;
4. Grab the glass both under above.
Move the left side of the glass towards you, then move it to the left and down as far as possible;
5. Bring the right side of the glas
towards you, out of the false chimney breast;
6. To place the glass back on the
handle
screw
5
6 7 8 1 2 3 4
Page 26
UK/IRL
26 < < < <
appliance, follow these steps in reverse order.
Note:
make sure that both handles are moved as far towards you as possible, otherwise securing the glass won’t be possible.
The glass is protected with a foil which should be removed only after the whole installation and finishing of the appliance and false chimney breast is completed.
Make sure that the foil is removed when the appliance is used!
4.5.2 removing/placing the glass of the BF120H / Relaxed
1. Take away the frame of the BF120H / Relaxed (see §4.6).
2. slide the strips on either side of the appliance to the
outside
3. unscrew the screw mounted on the right side of the
appliance which secures a handle (see fig. 3 and 4).
4. Move the handle towards you. The glass is now unsecured.
5. gently grab the glass on either side. Tilt the glass a little
bit backwards. If this not possible, move the handle more downwards.
6. lift the glass with its top in th false chimney breast.
7. Take the glass out of the false chimney breast.
8. To place the glass back on th e appliance, follow the s e
steps in reverse order.
Note:
when placing the glass make sure that the handle is moved backwards sufficiently. If this is not the case, securing the glass will not be possible.
The glass is protected with a foil which should be removed only after the whole installation and finishing of the appliance and false chimney breast is completed.
Make sure that the foil is removed when the appliance is used!
1
2
3
4
5
6
Page 27
UK/IRL
> > > > 27
4.6 placing and adjusting the frame
1) After the appliance is properly installed,
the frame has to be placed. for this purpose a movable lip is mounted on top of the appliance
2) This lip can be secured by fastening two
bolts on either side of the appliance
3) Adjust the position of the lip so that its top
edge is positioned about 3mm from the wall (including finishing)
4) Place the frame over the lip. Make sure it is
positioned in the middle.
5
3 4 1 2
6
Met opma
a
Page 28
UK/IRL
28 < < < <
4.7 Placing the log set with the log burner
To guarantee good combustion, the log set may only be installed in the way specified on the picture below. Never place extra elements of any kind into the combustion chamber. This could affect the combustion in a negative way. Any other arrangement can lead to soot on logs or window. Do not use the fire w ith broken or missing logs.
When preferred, ember (immitation-ash) kan be spread around the logs. Attention! Beware that there are no embers on the air-inlet at the back.
4.8 Placing the pebbles with pebble burner
Spread the pebbles over the bottom plate. To ensure a good combustion, spread the pebbles equally. Make sure that the pilot burner stays free from the pilot. The pebbles do not need further servicing. See pictures above for more details
BF110V / Straight log burner
BF110V / Straight pebble burner
BF120H / Relaxed flat fibre burner
BF120H / Relaxed Pebble burner
Page 29
UK/IRL
> > > > 29
5. Installation of the flue
5.1 Connections with use of concentric duct material
1. Drill a hole of ø 153 mm for the wall or roof mounted terminal;
2. Horizontal parts of the pipe have to be installed with an angle of at least 3 degrees;
3. Build up the system from the appliance;
4. Make sure you place the pipes in the right direction, the narrow end towards the
appliance;
5. Make sure the pipes are fixed sufficiently, a wall clamp every 2 m. T his way the weight
of the pipes is not resting onto the appliance.
6. The outside of the pipe can be hot (140 degrees). Stay at least 50 mm away from wall
surface or ceiling. Make sure to provide sufficient heat resistant isolation when going through the wall or roof.
7. The concentric pipes can turn loose due to expansion or cooling down. It is
recommended to fix the spring clip with a self tapping screw at inaccessible places.
8. To get the exact measure flue length you can use cut down concentric pipe, wall
mounted terminal or roof mounted terminal. To obtain a smoke sealed connection, the inner pipe must be 20 mm longer then the outside pipe.
5.2 Connection onto an existing chimney
You can connect the appliance onto an existing chimney. The existing chimney then functions as an air supply channel, where a flexible stainless steel liner (to BS715) of 100 mm performs the flue function. Any existing chimney used as an air supply channel must only service this appliance.
Requirements:
- 300 mm of free space above the appliance;
- The chimney only supply’s air to this appliance;
- The existing chimney needs to be clean and very well swept;
- The existing chimney needs to be airtight;
- The existing chimney
needs to have an opening of min. 150 x 150 mm.
Page 30
UK/IRL
30 < < < <
Chimney side
1. Place the aluminium closure plate (A) onto the
chimney. Permanently attach and make airtight.
2. Pull the liner (C) through the chimney.
3. Connect the liner onto the roof terminal and fix it with
the clamp provided with the chimne y connection set.
4. Place the roof terminal onto the closure plate. Fixing
the chimney sealing plate (D) and place the 150 mm grommet into the hole of the sealing plate.
Fire place side
5. Fixing the chimney sealing plate (D) and place the 150 mm grommet into the hole of the sealing plate.
6. if necessary, install an MV-pipe on the fire place in such a way that the chimney connection and the MV­system is 500 mm;
7. Fix the sealing plate air tight into the builders opening (use the isolation rope from the chimney connection set to make the plate air tight);
8. Slide the pipe (E) 150 mm length 500mm into the sealing plate. Slide this pipe so far that you will have a space of 200 mm later on for assembling the liner;
9. Install the appliance;
10. Connect the flexible stainless steel liner onto a pipe using the 200 mm long,
Ø 100 mm
pipe (F) as adapter;
11. Slide the outside pipe onto the appliance or concentric extension so that you have a air
tight connection.
5.3 Remote control
The remote control is only meant to regulate the flames, it functions only when the pilot burner is ignited. It is therefore not possible to ignited the appliance with the remote control or to shut-off the pilotflame. The radio-frequency remote control is intended for
Fig18
Page 31
UK/IRL
> > > > 31
fireplaces installed in a domestic setting in all EU countries except Austria, Denmark, Finland and Greece.
Features:
- Manual control will always remain possible.
- The remote control is a radio frequency type and has been approved internationally.
- The remote control generates a unique safety code every time you activate the
transmitter, its similar to those used in a car.
- The remote control is easy to install retrospectively.
5.3.1 Installation remote control
1. Connect the mains adapter to the receiver box. The adapter is set to the correct voltage in the factory: 4.5 V.
2. Slide the receiver box into the holder.
3. Connect the wires to the gas valve (see fig. 22).
4. Check that there are batteries in the transmitter.
5. See "Replacing batteries", see chapter 10.4.4.
6. Set the on/off switch on the receiver to "on".
fig. 22
Page 32
UK/IRL
32 < < < <
Setting the right transmission code
The receiver has to learn the code from the transmitter, which is already done at the factory. However the code disappears if the receiver is disconnected from the mains for a longer period.
1. Push the "mod" button on the receiver and hold it for 3 seconds.
2. The green control lamp will light up and stay on. Repeat this step if it doesn't.
3. Push a button on the remote control. The control lamp on the receiver should now go out.
4. Again push a button on the remote control. The lamp starts flashing and will switch off eventually.
5. The receiver now recognizes the remote control. The remote control now functions.
6. Check if you can hear a sound and the motor runs when you push a button on the
remote control.
Page 33
UK/IRL
> > > > 33
6. Commisioning (functional checks)
6.1. Check pilot ignition
1. Push in and turn the control knob A from anticlockwise to the (sma ll flame) setting. You will hear a tick meaning there is ignition. Hold the knob in and wait for a few seconds while the air is purged.
2. Bring the knob back in the start position and turn the knob several times to the (large flame) position. Check that the pilot has lit.
3. Continue to hold in the control knob for a further ten seconds to ensure that the pilot flame is stable.
4. Release the knob. The pilot should remain alight.
6.2 Functional burner check
1. Turn knob (B) to max. clockwise.
2. Turn the knob (A) more anticlockwise to the position
(large flame). Now it is
possible to light the main burner.
3. Turn knob B anticlockwise to max. The main burner should light. Check for gas soundness at all joints with leak detection fluid!
4. Check the ignition of the main burner on low and high setting.
5. Turn knob B clockwise till . The main burner is off.
6.
Turn the knob A to . The pilot should go out.
Page 34
UK/IRL
34 < < < <
6.3 Functional balanced flue check
1. Set the appliance on max. input.
2. Verify the flame picture, this means no flames against the window, the flame have to come besides the logs, if not check the log layout.
3. Check if the flames are yellow after 10 minutes of operation. If you still have a blue flame or the appliance goes out, check:
- If the flue pipes are fitted correctly (no leakage);
- If the wall mounted terminal is placed with the correct side up;
-
If the maximum allowable length of the flue pipe was exeeded;
-
If the appliance has the right set up. Check the ;
-
If the correct flue restrictor is installed.
6.4 Check reference pressure and burne r pressure
The appliance is preset to give the correct heat input. No further adjustment is necessary. Fit a pressure gauge at the burner pressure test point D to check the burner pressure. The pressure should be checked with the appliance alight and at max.input.The setting pressure should be as shown at the technical data. After checking the pressure, turn off the appliance. Remove the pressure gauge and close the sealing screw. Re-light the appliance. Turn to max. input and test around the test point D for gas soundness using a suitable leak detection fluid.
Measuring the pressure(voordruk):
1. Turn off the gas valve on the appliance;
2. Turn the Inlet pressure test point C (see fig. 22) some and apply the (meetslang);
A
. Governor
B. Adjusting screw pilot
flame C. Inlet pressure test point D. Burner pressure test
point
Page 35
UK/IRL
> > > > 35
3. Check if the measured pressure is the same as the prescribed pressure;
4. Perform this measuring when the appliance burns on full capacity and when only the pilot ignition burns;
5. When the press ure is too low, check if the gas pipes are made of material wit the right diameter;
6. When the pressure is too high (more than 5 mBar) you can’t install the appliance and you should contact your gas company;
7. Always check the burner pressure when the functional pressure is right.You can measure the burner pressure by using sensor D.The pressure should match the prescribed pressure. If this is not the case, then contactn the supplier.
Note:
After checking the burner pressure, the Inlet pressure test point has to be shut and
checked for gas-tightness.
Page 36
UK/IRL
36 < < < <
7. Final check and handing over
- Instruct the customer on the full operation of the appliance.
- Advise the customer how to clean the appliance including the glass.
- Instruct the customer on the operation of the remote control, including the
replacement of batteries and how to set the right transmissions code.
- Hand over these instructions including the user guide to the consumer.
- Recommend that the appliance should be serviced by a competent person at least once
a year.
Page 37
UK/IRL
> > > > 37
8. Servicing
To ensure safe and efficient operation of the appliance, it is necessary to carry out routine servicing at regular intervals. It is recommended, that the fire is inspected/serviced by a competent person at least once a year.
Important
: turn off the gas supply before commencing any servicing. Always test for gas
soundness after refitting the appliance.
The appliance and flue connection have to be checked for gas and smoke soundness after installation.
8.1 Routine servicing
1. Clean (if necessary):
- the pilot system;
- the burner;
- the combustion chamber;
- the glass.
2. Check the log lay and replace the embers (if applicable).
3. Do the functional test as described at page 34.
4.
Check the flue system and terminal on damage and soundness (visual inspection)
8.1.1 Cleaning the glass
Depending on the intensity of use, you can get a deposit on the glass. Normally this can be removed with an ordinary dry towel. If necessary special ceramic glass cleaner (ceramic cook-top cleaner) can be used. To clean the glass:
1. Remove the glass as described in paragraph 4.5;
2. Clean the glass. Handle the glass with clean hands, wear gloves if possible;
3. To fit the glass, proceed in reverse order. Make sure that:
1. the log set has been installed correctly before fixing the glass.
2. the glass sealing rope is in good condition and makes an effective seal
3. Important:
be sure that there are no fingerprints on the glass. They are
burned in the glass when not removed.
Page 38
UK/IRL
38 < < < <
8.1.2 Cleaning the combustion chamber and burner
1. Carefully remove the logs.
2. You can clean the comb ust ion cham ber with a vacu um clea n er.
3. Place back the logs as described in paragraph 4.6.
If the burner is visibly damaged, this can affect the distribution of the flame. If so, then replace the burner.
A. Pilot assembly B. Burner C. Fixation plate D. Injector E. Gas control F. Receiver
Logburner
Pebble burner /
Flat fibre burner
Met opma
a
Aangepast
e
(RGB(41;3
7
Met opma
a
Tekstkleur: (RGB(41;3
7
Met opma
a
Tekstkleur: (RGB(41;3
7
Page 39
UK/IRL
> > > > 39
8.1.3 Burner tray (dis)assembly
1. Break the gas supply at the control valve;
2. Remove the glass, the log set, grid and burner tray cover;
3. Detach the gas connection at the 8 mm nut and olive;
4. Unscrew the burner assembly and take them out of the combustion chamber.
8.1.4 Gas control block
1. Unscrew and remove the pilot system from its support and the burner plate;
2. Disconnect the ignition/spark cabel;
3. Disconnect the thermocouple from the pilot system;
4. Disconnect the gas connection from the pilot system. Mind the injector: it’s unattached;
5. The pilot system can now be removed;
6. To assemble the pilot system again, follow the steps above in reversed order.
8.2 Propane conversion
For conversion from propane to natural gas, you have t o order a complete new propane burner unit. Contact your supplier and give the serial number from the data plate.
8.3 Combustion test
A BS7967 combustion analysis check should be carried out using an analyser to BS7927 positioned in the flue outlet.
Ratio CO/CO2 should be less than 0.01 within 30 minutes (100 ppm CO per 1% CO2). A reading of CO in the room centre should give a rise of less than 9p pm over ambient,
peak reading.
A
. Governor
B. Adjusting screw pilot
flame C. Inlet pressure test point D. Burner pressure test
point
Page 40
UK/IRL
40 < < < <
8.4 List of spare parts
Straight Relaxed Description Number Number
Surround antracite 20847448 20847548 Surround Stainless steel 20847803 50847903 Glass 04510300 04510500 Burner G20 FB x 20900233 Burner G20 PB 20900231 20900232 Burner G20 LB 20900230 x Burner LPG LB 20900224 x Adapter 20604100 20604100 Log set 20798200 20798900 Spark wire 06022030 06022030 Receiver 20604610 20604610 Remote control 20603900 20603900 Gas Control NL NG 37003089 37003089 Motor (remote control) 37003086 37003086 Pilot burner assemb. NG 20900145 x Pilot burner assemb. LPG 20900154 x Thermocouple 37002046 37002046 Oxypilot L1200 2 0605300 20605300 Snoer oxypilot L1200 06022050 06022050 Spark electrode 06006600 06006600 Embers 20793400 20793400 spray for comb. Chamber 09000008 09000008 spray for frame 09000014 09000014
Page 41
UK/IRL
> > > > 41
User guide
Page 42
UK/IRL
42 < < < <
Page 43
UK/IRL
> > > > 43
9. Safety instructions for the user
9.1 General safety instructions
These instructions should be read carefully and retained for future reference.
Do not place flamable materials in the combustion chamber.
If a gas leak is found or suspected, turn off the gas supply at the meter and contact
your installer or gas emergency service.
Do not use the fire with a broken or damaged glass.
The fire has a safety device which turns off the gas supply if there is a build up from flue
gasses in the combustion room or a temporary gas cut-off. Wait at least 5 minutes before turning the appliance on again.
Contact a qualified installer when the appliance goes off regularly.
The appliance has been designed for heating purposes. This means that all surfaces,
including the glass, can become very warm (over 100 °C). An exception to this is the lower side of the door and the control buttons.
Due to the newness of materials, they may give off a slight smell for a period after initial lighting. This is normal, odours will disperse after a few hours use.
Do not place curtains, clothing, laundry, furniture or other flammable materials nearby the appliance. The required minimum dista nce is 100 cm.
Switch off the receiver of the remote control if you don’t use the fire for a long time. Do not let children use the remote control without supervision.
Children should only use the remote control under supervision.
IMPORTANT
A suitable Fireguard conforming to BS6539 and BS6778 should be used with this appliance to protect children, the elderly or infirm. Care should also be taken with pets.
In your own interest and that of safety, all gas appliances must be installed by competent persons. Installation must be in accordance with National Regulations. CORGI registered
Page 44
UK/IRL
44 < < < <
installers are required to work to recognised standards.
Note:
Since the appliance is a source of heat, circulation of air occurs. Therefore it is of importance that you do not use the appliance shortly after a renovation of the home. Because of the natural circulation of air, moist and volatile components from paint, building materials, carpet etc. will be attracted. These components can settle themselves down onto cold surfaces in the form of soot. As on all heat producing appliances, soft furnishings such as blown vinyl wallpaper placed too near to the appliance may become scorched or discoloured. This should be born in mind when installing the appliance.
Page 45
UK/IRL
> > > > 45
10. Controlling the appliance
10.1 General
If the main burner or pilot light is extinguished for any reason, don’t try to relight the pilot within 5 minutes. Contact a qualified installer when the appliance goes off regularly.
Depending on the model, the gas control block is positioned:
BF110V /Straight Frameless: behind a stainless steel door at the underside of the appliance, mounted in the middle of the floorplate of the app liance;
BF110V / Straight with frame: Within the false chimney breast or surround at either the left or right side of the appl iance, mounted on the floor plate of the appliance. An optional hatch can be purchased with this model for easy access to the gas block.
With control button A you can light the pilot. With the control button B you can adjust the height of the flames (see figure). All Natural Fire models feature a remote control which controls the height of the flames.
Knob A
The
is the OFF position preventing any gas from passing through the control valve to either the pilot burner or to the main burner. By pressing the knob in it is possible to turn it anticlockwise. The first function is to turn on the gas to the pilot- this occurs just before reaching the
position (if the fire has not been lit for some time it may be necessary to hold the knob in this position for some seconds to clear the air from the pipe and allow gas to reach the pilot burner). Once gas is available at the pilot, continued rotation anti­clockwise will cause the piezo igniter to spark. This is accompanied by a click at the valve and should result in the pilot burner igniting. Once the pilot is lit, the control knob should be held pressed in for 10 seconds. In this time the pilot flame will have heated the flame
fig. 25 Gas control box
A
B
Page 46
UK/IRL
46 < < < <
supervision thermocouple sufficiently to operate a hold-on magnet within the valve. Now turn the control knob A to the
position. This allows gas to enter contro l knob B.
Knob B
The { is the OFF position preventing gas entering the main burner if the pilot is lit. The knob should be turned slowly anticlockwise. This allows gas to enter the burner and be ignited by the pilot flame. Once ignition has taken place, the fire may be set to any level between min. and max. by adjusting the control knob B.
10.2 To light
1. Push in and turn the control knob (A) from anticlockwise to the setting (small
flame). You will hear a ignition click. Check that the pilot is lit (if not, repeat).
2. Continue to hold in the control knob for a further ten seconds to ensure that the pilot
flame is stable.
3. Release the knob. The pilot should remain alight.
4. Turn the control knob A to the
position.
5. Turn knob B slowly anticlockwise, the fire should then ignite.
6. Adjust flames to the required level.
10.3 To extinguish
1. For the main burner turn the control knob B clockwise to position .
2. To disable knob B turn knob A to the
position.
3. To extinguish the pilot turn control knob A to position
, although it is in order lo
leave the pilot permanently lit.
10.3.1 When the pilot extinguishes
Warning! When the pilot extinguishes, for whatever reason, you should wait at least 5 minutes before trying to turn it on again. Possible causes of pilot extin guish are:
- Operating error.
- Interference of the safety device.
Page 47
UK/IRL
> > > > 47
- Failure in the pilot flame system. Contact a qualified installer when the appliance goes off regularly.
10.4 Remote control version
The remote control is only meant to regulate the flames from ‘off’ till ‘max.’. It functions only when the pilot burner is ignited and knob A is in (big flame) position. It is therefore not possible to ignite or extinguish the pilot flame with the remote control.
Note:
The radio-frequency remote control is intended for fireplaces installed in a
domestic setting in all EU countries except Austria, Denmark, Finland, and Greece. Features:
Manual control will always remain possible;  The remote control is a radio frequency type and had been approved
internationally;
The remote control generates a unique safety code every time you activate the
transmitter, its similar to those used in a car;
The remote control is easy to install retrosp ectively.
10.4.1 Using the remote control
1. Light the appliance as described in 10.2;
2. Set the on/off switch on the receiver to "on” and control the flames:
Low flame
High flame
3. Use (high) and (low) to achieve the desired heating and flame effect;
4. You will hear a beep every time the receiver recognises a signal. (If not, see 10.4.3,
setting the right transmission code);
5.
When the fire is not be used for a prolonged period, turn off the pilot (see 10.4.2). If the appliance is not used for an extensive period of time, it can be necessary to set the right transmission code again.
Page 48
UK/IRL
48 < < < <
10.4.2 Setting the right transmission code
The receiver has to learn the code from the transmitter. This is already done at the factory. However the code disappears if the receiver is disconnected from the mains too long.
1. Set the on/off switch on the receiver to "on";
2. Push the "mod" button on the receiver and hold it for 3 seconds;
3. The green control lamp will light up and stay on. Repeat this step if it
doesn't;
4. Push a button on the remote control. The control lamp on the receiver
should now go out;
5. Again push a button on the remote control. The lamp s tarts flashing
and will switch off eventually;
6. The receiver now recognizes the remote control. The remote control
now functions;
7. Check if you can hear a sound and the motor runs when you push a
button on the remote control.
10.4.3 Changing the batteries
The batteries in the remote control should have a life span of about one year, depending on the frequency of use.There is no risk of electric shock as the low voltage supply is similar to that used in torches. Always turn off the appliance before changing batteries.
Remote control
1. Remove the cover on the back of the remote control;
2. Carefully remove the battery clip along the side. Pay attention not to
pull the wires;
3. If necessary, remove the old batteries and place the new ones:
2x LR03 /AAA Alkalin e long life 1.5 V.
4. Click the battery clip into the remote control and close the cover;
5. It might be possible that you have to set the transmission code after changing the
batteries (see 10.4.3).
Note:
Batteries are chemical waste and should be disposed in accordance with local
regulations.
fig. 27 Rear of
remote control
Page 49
UK/IRL
> > > > 49
11. Cleaning and service instructions
Important:
Turn off the fire and allow it to cool down before commencing cleaning.
It is recommended that the fire is inspected/serviced, by a competent person at least once a year. To maintain the finish on the trim wipe with soft damp cloth only. Do not use abrasive cleaners, polish or solvents as these can damage the surface finish.
Cleaning the glass:
To remove the glass to clean it, follow the steps described in paragraph 4.5; To clean the glass, follow the steps and suggestions described in paragrapg 8.1.1;
Be sure that there are no fingerprints on the glass. It is not possible to remove those prints after you burn the appliance for a while (t hey are burnt in).
Page 50
UK/IRL
50 < < < <
12. Disposal of packaging and appliance
The appliance packaging is recyclable. The packaging could include the following materials:
Cardboard;
CFC-free foam (soft);
Wood;
Plastic;
Paper;
Batteries.
These materials shoul d be disposed responsibly and in conformity with government regulations.
Batteries are considered chemical waste. The batteries should be disposed of responsibly and in conformity with government regulations. Remove the batteries before disposing of the remote control.
Information on how to responsibly dispose of discarded appliances can be obtained from the local authorities.
Page 51
UK/IRL
> > > > 51
Appendix: technical data
BF110V /Straight BF120H / Relaxed
Type of burner log burner Pebble burner flatfiber/log Pebble burner Country UK/IRL UK/IRL UK/IRL UK/IRL
Category I2H I2H I2H I2H Type C11 of C31 C11 of C31 C11 of C31 C11 of C31
Gas unit specifications
Type of gas G20 G20 G20 G20 Heat input Hi (net) [kW] 7,2 7,3 8,2 8,2
Efficiency class 2 2 2 2 NOX class 4 4 4 4 Working pressure [mbar] 20 20 20 20 gas rate ( 15º C en 1013 mbar) [l/h] 761 780 870 870 Setting pressure [mbar] 9,5 10 13 13 Injector size [mm] 2 x 1,60 + 1,5 0 2,55 2,55 2,55 Reduced input restrictor [mm] 1,8 1,8 1,8 1,8
Pilot assembly
Type SIT 160 SIT 160 SIT 160 OP9709 code injector Nr 51 Nr 51
Flue system
MV size [mm] 100-150 100-150 100-150 100-150 Preinstalled flue restrictor [mm] 30 30 30 30 Gas control
GV36-
C5AOEHC68M
GV36-
C5AOEHC68M
GV36-
C5AOEHC68M
GV36-
C5AOEHC68M
Remote control
V
oltage adaptor [V] 4,5 4,5 4,5 4,5
Batteries [V]
2x LR03 1.5V
Alkaline
2x LR03 1.5V
Alkaline
2x LR03 1.5V
Alkaline
2x LR03 1.5V
Alkaline
Gas connection 8 mm nut & 8 mm nut & 8 mm nut & 8 mm nut &
Page 52
UK/IRL
52 < < < <
Saturnus 8 NL - 8448 CC Heerenveen Postbus 219 NL - 8440 AE Heerenveen T. +31(0)513 656500 F. +31(0)513 656501
Loading...