EVCO EC6295S001 User Manual

EC 6-295P220S001
frigerating units
Version 1.01 of 15th March 2005
File ec6295p220s001_eng_v1.01.pdf
PT
EVCO S.r.l.
Via Mezzaterra 6, 32036 Sedico Belluno ITALY
Phone 0039-0437-852468 • Fax 0039-0437-83648
info@evco.it • www.evco.it
1 PREPARATIONS
1.1 How to install the instrument
On DIN rail (it is not supplied by the builder).
DIN rail installation (it is not supplied by the builder).
Evco S.r.l. • EC 6-295 P220 S001 • Sheet 1/3
ENGLISH
2 OPERATION
2.1 How to turn the instrument ON/OFF
If you have to turn the instrument ON/OFF:
• press
During the normal operation the instrument shows the cabinet
temperature.
2.2 How to silence the buzzer
If you have to silence the buzzer:
• press
2.3 How to activate the defrost by hand
If you have to activate the defrost by hand:
• press
Unless the evaporator temperature is below the defrost end tem-
smart guide
perature you have set with the parameter d2, the defrost will
not be activated.
2.4 How to turn the cabinet light ON/OFF
If you have to turn the cabinet light ON/OFF:
• press
2.5 Compressor thermal protection
The activation of this input forces the compressor OFF by hard-
ware and software.
3 REAL TIME CLOCK
3.1 How to set the clock
Press
Press or for selecting
If you have to modify the value of the hour:
• press
If you have to modify the value of the minutes:
• release
• press
If you have to quit the procedure:
• press
and or
and press it again during the
or
or as long as the instrument
for 2 s
for 4 s
for 2 s : the instrument
will show
modification of the hour,
then ...
shows the cabinet tem-
perature or do not oper-
ate for about 30 s.
4 WORKING SETPOINT
4.1 How to set the working setpoint
If you have to modify the working setpoint value:
• press
(1) you can set the working setpoint between the limits you have set with the param-
eters r1 and r2
(2) unless the parameter r5 has value 0, you can not modify the working setpoint.
and or
(1) (2)
5 CONFIGURATION PARAMETERS
5.1 How to set the configuration parameters
Configuration parameters are arranged on two levels.
If you have to gain access the first level:
• press
and for 4 s : the instrument
will show
If you have to select a parameter:
• press
or
If you have to modify the value of the parameter:
• press
and or
If you have to gain access the second level:
• gain access the first level
• press
or for selecting
• press and or for setting “ -19
• press
and for 4 s : the instrument
will show
If you have to quit the procedure:
• press
and for 4 s or do not op-
erate for about 60 s.
6 ADDITIONAL FUNCTIONS
6.1 How to gain access the additional functions
If you have to gain access the additional functions:
• press
for 2 s : the instrument
will show
If you have to quit the procedure:
• press
or as long as the instrument
shows the cabinet tem-
perature or do not oper-
ate for about 30 s.
6.2 Evaporator temperature showing
If you have to show the evaporator temperature:
• gain access the additional functions
• press
or for selecting
• press
6.3 Temperature alarm storage
If you have to show the temperature the instrument has stored
during the lower temperature alarm:
• gain access the additional functions
• press
or for selecting
(3)
• press
If you have to show the temperature the instrument has stored
during the upper temperature alarm:
• gain access the additional functions
• press
or for selecting
(4)
• press
If you have to erase the temperature the instrument has stored
during the lower or upper temperature alarm:
• gain access the additional functions
• press
or for selecting or
• press for 4 s : the instrument
will show
(3) unless the parameter A8 has value 1 or 3, the label AL will not be showed
(4) unless the parameter A8 has value 2 or 3, the label AH will not be showed.
7 SIGNALS
7.1 Signals
LED MEANING
Compressor LED
if it is lighted, the compressor will be ON
if it flashes, a compressor delay will be running (look at the parameters
C0, C1, C2, C4, n1 and n4)
Defrost LED
if it is lighted, the defrost output will be activated
if it flashes:
• a defrost delay will be running (look at the parameters C0, C1, C2, C4,
n1 and n4)
• the dripping will be running (look at the parameter d7)
• the freezing fluid heating will be running (look at the parameter dP)
(16) do not set more instruments as master
(17) the time between the master implements a control and the slave implements the same control is “n1 x n4”
(18) except the control turning ON and OFF; it will immediately be implemented
(19) if among the remote controls the slave has to implement there is the defrost activation, the parameter d5 will set a time you will have to add to the one you have set with the
parameters n1 and n4 (the slave will implement the control even if the conditions will not allow the master of activating the defrost); if the master is in the STAND-BY mode and
among the remote controls the slave has to implement there is not the turning ON and OFF, the slave will work with the local settings.
11 ELECTRICAL CONNECTION
11.1 Electrical connection
(20) short-circuit terminals 1 and 5 and/or 1 and 7 if you do not use the lock input and/or the compressor thermal protection
(21) the position of the probe for compressor thermal protection could compromise the insulation between low voltage and high voltage parts.
nA 0 15 --- 0 remote control the slave has to implement (0 = no controls, 1 and 9 = compressor status,
2 and 10 = defrost activation, 3 and 11 = compressor status and defrost activation,
4 and 12 = turning ON and OFF, 5 and 13 = compressor status and turning ON and OFF,
6 and 14 = defrost activation and turning ON and OFF, 7 and 15 = compressor status,
defrost activation and turning ON and OFF, 8 = reserved)
(19)
LABEL MIN. MAX. U.M. DEF. ENERGY SAVING (the working setpoint becomes r8)
Hr1 0.0 23.5 h.damin
Hr2 0.0 23.5 h.damin
(6)
0.0 Energy Saving cycle activation time
(6)
0.0 Energy Saving cycle length
LABEL MIN. MAX. U.M. DEF. REAL TIME DEFROST
Hd1 0.0 23.5 h.damin
Hd2 0.0 23.5 h.damin
Hd3 0.0 23.5 h.damin
Hd4 0.0 23.5 h.damin
Hd5 0.0 23.5 h.damin
Hd6 0.0 23.5 h.damin
(5) the unit of measure depends on the parameter /8
(6) damin = 10 minutes
(7) unless the evaporator temperature is below the defrost end temperature you have set with the parameter d2, the defrost will not be activated
(8) if the time the compressor is ON is lower than 30 s, the compressor will never be ON; if the cabinet probe failure takes place during a compressor delay, the compressor will be
forced OFF for 1 min; the parameter C1 sets the minimum delay between the end of the cabinet probe failure and the following activation of the compressor (if the parameter
C1 has value 0, the compressor will be forced off for 2 min)
(9) if at the moment of the defrost activation the cabinet temperature is below the value “working setpoint + r0” , the instrument will not show temperatures above that value; if
at the moment of the defrost activation the cabinet temperature is above the value “working setpoint + r0” , the instrument will not show the increases of the temperature (if
the increase takes place below the value “working setpoint + r0” , look at the previous case); the instrument restores the normal operation once the after dripping evaporator
fan delay ends and the cabinet temperature falls below the freeze temperature
(10) if at the moment of the defrost activation the compressor is ON since a time lower than the one you have set with the parameter, the compressor will be forced ON for a time
such as to finish the time you have set with the parameter
(11) if the lower temperature alarm takes place during the count of the delay, this last will be cleared
(12) if the temperature alarm does not disappear at the end of the times you have set with the parameters A3 and AA, it will further be excluded for the time you have set with the
parameter A6; if the temperature alarm takes place during the defrost and does not disappear at the end of the time you have set with the parameter A7, it will further be
excluded for the time you have set with the parameter A6; if the temperature alarm takes place during the multifunction input activation, it will be excluded for the time
"A5 + A6" since the input activation or for the time you have set with the parameter A6 since the input deactivation
(13) the evaporator fan stop temperature is “cabinet temperature - F1” ; you always have to consider the parameter F1 with positive sign
(14) the instrument will automatically verify the maximum value of the parameter; it always has to be lower than the value you have set with the parameter i4
(15) when there is 1 min to the end of the time you have set with the parameter, the cabinet light will be turned OFF just for 1 s; press during the time you have set with the
parameter to turn the cabinet light ON and to exclude the function, press again before the end of the time you have set with the parameter to recover the function
(if the remaining time of the parameter is higher than 1 min, the time will be forced at 1 min and the cabinet light will be turned OFF just for 1 s)
(6)
- - - first defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(6)
- - - second defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(6)
- - - third defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(6)
- - - fourth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(6)
- - - fifth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(6)
- - - sixth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
(7)
(7)
(7)
(7)
(7)
Evaporator fan LED
if it is lighted, the evaporator fan will be ON
if it flashes, the after dripping evaporator fan delay will be running (look
at the parameter F5)
Cabinet light LED
if it is lighted, the cabinet light will be ON
if it flashes, the multifunction input will be active (look at the parameters
i0, i1 and i7)
Lock input/thermal protection LED
if it is lighted, there will have been a number of lock input/thermal pro-
tection alarms such as to give the lock of the instrument (turn the instru-
ment OFF and turn it ON again, look at the parameters i2, i3, i4 and i5)
if it flashes, the lock input/thermal protection will be active (look at the
parameters i2, i3, i4 and i5)
ON STAND-BY LED
if it is lighted, the instrument will be in the STAND-BY mode
if it flashes, the instrument will be set as slave but it will not be author-
ized to implement the remote controls coming from the master (look at
the parameter n3)
if it flashes every two seconds, the instrument will be set as slave and
among the remote controls, coming from the master, the slave has to
implement, there will be the turning ON and OFF (look at the param-
eter nA)
INDICAT.
the instrument will be set as slave and among the remote controls, com-
ing from the master, the slave has to implement, there will be the com-
pressor status (look at the parameter nA).
If you have to show the cabinet temperature, press
the instrument will be set as slave, among the remote controls, coming
every 2 s
from the master, the slave has to implement, there will be the compres-
sor status but there will not be the turning ON and OFF, both the master
and the slave will be in the STAND-BY mode (look at the parameter nA).
If the master is in the STAND-BY mode and the slave is ON, the indica-
tion will be showed alternated with the cabinet temperature
Evco S.r.l. • EC 6-295 P220 S001 • Sheet 2/3
MEANING
8 ALARMS
8.1 Alarms
CODE
corrupted
memory
data
person
into the
cabinet
(you can
not
silence
the
buzzer)
lock
input/
thermal
protection
alarm
cabinet
probe
alarm
REASONS
there is the corruption
of the configuration
data of the memory of
the instrument
the lock input/thermal
protection and the
multifunction input are
active
the lock input/thermal
protection is active.
If there has been a
number of lock input/
thermal protection
alarms such as to give
the lock of the instru-
ment, for 3 s
every 4 (if you
have to restore the
normal operation, turn
the instrument OFF
and turn it ON again)
• the kind of cabinet
probe you have con-
nected is not right
• the cabinet probe
plays up
REMEDIES
switch off the power
supply of the instru-
ment: unless the alarm
disappears, you will
have to change the
instrument
• deactivate the inputs
(look at the param-
eters i0, i1, i2, i3, i4
and i5)
• turn the instrument
OFF and turn it ON
again
• deactivate the input
(look at the param-
eters i2, i3, i4 and i5)
• turn the instrument
OFF and turn it ON
again
• look at the param-
eter /0
• test the integrity of
the probe
• test the instrument-
probe connection
EFFECTS
• you can not gain
access the setting
procedures
• all outputs will be
forced OFF
• the compressor will
be forced OFF
• if the defrost is run-
ning, it will immedi-
ately end
• the defrost will
never be activated
• you will get the ac-
tion you have cho-
sen with the param-
eter i0
• the compressor will
be forced OFF
• if the defrost is run-
ning, it will immedi-
ately end
• the defrost will
never be activated
• the compressor will
work in accordance
with the parameters
C5 and C6
evapora-
tor probe
alarm
multi-
function
input
alarm
upper
tempera-
ture alarm
• the connection in-
strument-cabinet
probe is wrong
• the cabinet tempera-
ture is outside the
limits allowed by the
working range of
the instrument
• the kind of evapora-
tor probe you have
connected is not
right
• the evaporator
probe plays up
• the connection in-
strument-evaporator
probe is wrong
• the evaporator tem-
perature is outside
the limits allowed by
the working range
of the instrument
the multifunction input
is active.
Unless the parameter
i6 has value 1, the in-
strument will not show
any indication
the cabinet tempera-
ture is outside the limit
you have set with the
parameter A1b
• test the temperature
close to the probe (it
has to be between
the limits allowed by
the working range)
• look at the param-
eter /0
• test the integrity of
the probe
• test the instrument-
probe connection
• test the temperature
close to the probe (it
has to be between
the limits allowed by
the working range)
deactivate the input
(look at the parameters
i0, i1 and i6)
test the temperature
close to the probe
(look at the parameters
A0, A1b and A2b)
• if the defrost is run-
ning, it will immedi-
ately end
• the defrost will
never be activated
• if the parameter dE
has value 2, the in-
strument will work
as if the parameter
had value 0
• if the parameter F7
has value 3 or 4, the
evaporator fan will
work in accordance
with the compres-
sor, except what
you have set with
the parameters F4
and F5
• the defrost will end
by time (parameter
d3)
you will get the action
you have chosen with
the parameter i0
no effects
for 3 s
every 4
lower
tempera-
ture alarm
for 3 s
every 4
real time
clock
alarm
slave
alarm
there has been an up-
per temperature alarm
the cabinet tempera-
ture is outside the limit
you have set with the
parameter A1A
there has been a lower
temperature alarm
there is the corruption
of the data of the clock
of the instrument
the instrument will be
set as slave, among
the remote controls,
coming from the mas-
ter, the slave has to
implement there will
be the comp. status
and there will be one
of the alarms you saw
in the previous cases.
If the master is in the
STAND-BY mode and
the slave is ON, the in-
dication will be
showed every 2 s alter-
nated with the alarm
code
look at the parameters
A0, A1b, A2b, A8 and
A9
test the temperature
close to the probe
(look at the parameters
A0, A1A and A2A)
look at the parameters
A0, A1A, A2A, A8 and
A9
set the clock again
• if you have to show
the alarm code,
press
• look at the remedies
of that case
no effects
no effects
no effects
• if the parameter dE
has value 3, the in-
strument will work
as if the parameter
had value 0
• the Energy Saving
cycle will never be
activated
look at the effects of
that case
LABEL MIN. MAX. U.M. DEF. DIGITAL INPUTS
i0 0 7 --- 4 action given by the multifunction input activation (0 = inactive, 1 = once d5 has passed, the
(7)
defrost will be activated
, 2 = the cabinet light will be turned ON, 3 = the compressor will be
forced ON for A5 and the cabinet light will be turned ON, 4 = the compressor and the
evaporator fan will be forced OFF for A5 and the cabinet light will be turned ON,
5 = the evaporator fan will be forced OFF for A5 and the cabinet light will be turned ON,
6 = the working setpoint becomes r8, 7 = the working setpoint becomes r8 and the cabinet
light will be turned OFF); look at i7 as well
i1 0 1 --- 0 kind of contact of the multifunction input (it is important if i0 0; 0 = NO, 1 = NC)
i2 1 2 --- 1 action given by the lock input/thermal protection activation (1 = the compressor will be forced
OFF, 2 = in accordance with i3, i4 and i5)
i3 0 15 --- 0 lock input/thermal protection alarms number such as to give the lock of the instrument (it is
important if i2 = 2; 0 = the lock of the instrument will never take place)
i4 i5 240 min 0 time without lock input/thermal protection alarms able to clear the lock input/thermal pro-
tection alarms counter (it is important if i2 = 2)
(14)
i5 0 15
min 0 minimum delay between the lock input/thermal protection deactivation and the following
compressor activation (it is important if i2 = 2)
i6 0 1 --- 1 indication “Ain” flashing on the display during the multifunction input activation (it is impor-
tant if i0 0)
i7 0 240 min 0 delay between the multifunction input deactivation and the cabinet light gets OFF (it is
important if i0 = 2, 3, 4 or 5)
(15)
LABEL MIN. MAX. U.M. DEF. SERIAL NETWORK (EVCOBUS)
L1 1 15 --- 1 instrument address
L2 0 7 --- 0 instrument group
L4 0 3 --- 1 baud rate (0 = 1,200 baud, 1 = 2,400 baud, 2 = 4,800 baud, 3 = 9,600 baud)
LABEL MIN. MAX. U.M. DEF. SERIAL NETWORK (EVCONET)
n0 0 2 --- 0 operation of the instrument in the network (0 = instrument not enabled to work in the
network, 1 = master, 2 = slave)
(16)
n1 0 8 --- 0 address of the instrument in the network (it is important if n0 0; 0 = master address,
1 ... 8 = first ... eighth slave address)
n3 0 1 --- 0 authorization to implement the remote controls coming from the master (it is important if
n0 = 2 and n1 0; 1 = YES)
n4 0 240 s 0 time between the master implements a control and the slave implements the same control (it
is important if n0 = 2 and n1 0); look at nA as well
(17) (18)
LABEL MIN. MAX. U.M. DEF. ALARMS
A0 0.1 15.0 °C/°F
A1A -99 99.9 °C/°F
(5)
2.0 hysteresis (differential, it is relative to A1A and A1b, it is important if A2A and/or A2b 0)
(5)
-10 lower temperature alarm threshold; look at A2A as well
A2A 0 2 --- 1 kind of lower temperature alarm (0 = it will never be activated, 1 = lower temperature alarm
relative to the working setpoint, 2 = absolute lower temperature alarm)
A1b -99 99.9 °C/°F
(5)
10.0 upper temperature alarm threshold; look at A2b as well
A2b 0 2 --- 1 kind of upper temperature alarm (0 = it will never be activated, 1 = upper temperature alarm
relative to the working setpoint, 2 = absolute upper temperature alarm)
A3 0 240 min 120 upper temperature alarm exclusion time since you turn the instrument ON (it is important if
(11)
A2b 0)
A5 -1 120 min 30 buzzer exclusion time since the multifunction input activation (it is important if i0 0;
-1 = the buzzer will never be activated)
A6 0 240 min 5 temperature alarm exclusion time (it is important if A2A and/or A2b 0)
(12)
A7 0 240 min 15 upper temperature alarm exclusion time since the end of the after dripping evaporator fan
delay (since the end of F5, it is important if A2b 0)
(11)
A8 0 3 --- 0 kind of temperature alarm the instrument has to store (it is important if A2A and/or A2b 0;
0 = it will never be stored, 1 = lower temperature alarm, 2 = upper temperature alarm,
3 = both the lower temperature alarm and the upper one)
A9 1 15 s 1 time between two records of the temperature alarm in succession (it is important if
A2A and/or A2b 0 and A8 0)
AA 0 240 min 0 temperature alarms relative to the working setpoint exclusion time since the multifunction
input activation/deactivation (it is important if i0 = 6 or 7) and since the activation/end of the
Energy Saving cycle
LABEL MIN. MAX. U.M. DEF. EVAPORATOR FAN
(5)
F1 -99 99.9 °C/°F
-1.0 evaporator fan stop temperature (evaporator temperature, it is important if F7 = 3 or 4); look
at F6 as well
F2 0.1 15.0 °C/° F
(5)
2.0 hysteresis (differential, it is relative to F1, it is important if F7 = 3 or 4)
F4 0 2 --- 0 evaporator fan action during the defrost and dripping (0 = it will be forced OFF,
1 = it will be forced ON, 2 = it will work in accordance with F7)
F5 0 15 min 2 after dripping evaporator fan delay
F6 0 1 --- 0 kind of evaporator fan stop temperature (it is important if F7 = 3 or 4; 0 = absolute evapora-
tor fan stop temperature, 1 = evaporator fan stop temperature relative to the cabinet tem-
(13)
perature)
F7 0 4 --- 1 evaporator fan action during the normal operation (0 = it will be forced OFF, 1 = it will be
forced ON, 2 = it will work in accordance with the compressor, 3 = it will work in accordance
with F1 and F2, 4 = if the compressor is ON, it will work in accordance with F1 and F2, if the
compressor is OFF, it will be forced OFF)
• the value of the pa-
serial
rameters n0, n1 and
network
The instrument shows the indications above alternated with the cabinet temperature,
except the indication “E2“ (it flashes), “E0“ (it is alternated with the indication
“- - -” ) and “nEt” (slave alarm, it is a fixed indication) and the buzzer utters an intermit-
tent beep.
alarm
n3 is wrong
• the connections of
the instrument are
wrong
• look at the param-
eters n0, n1 and n3
• test the connections
of the instrument
the instrument will
work with the local
settings
9 TECHNICAL DATA
9.1 Technical data
Box: self-extinguishing grey.
Size: 106 x 90 x 58 mm (4.17 x 3.54 x 2.28 in, 6 DIN modules).
Installation: on DIN rail (it is not supplied by the builder).
Frontal protection: IP 40.
Connections: screw terminal blocks with pitch 5 mm (0.19 in) for cables up to
2.5 mm² (0.38 sq in, power supply, inputs and outputs), 5 poles single line female
connector with pitch 2.5 mm (0.09 in, serial port).
Ambient temperature: from 0 to 55 °C (32 to 131 °F, 10 ... 90% of relative humidity
without condensate).
Power supply: 230 Vac, 50/60 Hz, 4 VA.
Clock data maintenance without power supply: 24 hours (the instrument must
have been ON for 2 min at least).
Alarm buzzer: included.
Measure inputs: 2 (cabinet and evaporator probe) for PTC or NTC probes.
Digital inputs: 2 inputs: one multifunction input (NO or NC contact) and one lock
input, without voltage (they work with 5 mA).
Working range: from -50 to 99.9 °C (-58 to 212 °F) for PTC probe, from -40 to 99.9 °C
(-40 to 212 °F) for NTC probe.
Setpoint range: from -99 to 99.9 °C (-99 to 99 °F).
Resolution: 1 °F with unit of measure in Fahrenheit, 0.1 or 1 °C with unit of measure
in Celsius.
Display: one red LED 3-digit display 13.2 mm (0.51 in) high, output status indicators,
instrument mode indicator.
Outputs: 5 relays: one 16 A @ 250 Vac relay for one 1½ HP @ 230 Vac compressor
control (NO contact), one 8 A @ 250 Vac relay for evaporator fan control (NO contact),
one 8 A @ 250 Vac relay for defrost system control (change-over contact),
one 8 A @ 250 Vac relay for cabinet light control (NO contact) and one 8 A @ 250 Vac
Evco S.r.l. • EC 6-295 P220 S001 • Sheet 3/3
relay working in accordance with the instrument mode (the relay will be activated if the
instrument is ON and it will be deactivated if the instrument is in the STAND-BY mode,
change-over contact).
Kind of defrost: electric and hot gas defrost.
Defrost control: defrost interval, defrost end temperature, defrost maximum length
and defrost interval count mode (automatic, by hand and remote).
Serial port: TTL with EVCOBUS communication protocol, adapt for serial interface
EC IFC 02.
10 WORKING SETPOINT AND CONFIGURATION PARAMETERS
10.1 Working setpoint
LABEL MIN. MAX. U.M. DEF. WORKING SETPOINT
r1 r2 °C/°F
(5)
0.0 working setpoint
10.2 First level parameters
LABEL MIN. MAX. U.M. DEF. PASSWORD
PA -55 99 --- 0 password
LABEL MIN. MAX. U.M. DEF. MEASURE INPUTS
/1A -10 10.0 °C/°F
/1b -10 10.0 °C/°F
(5)
0.0 cabinet probe calibration
(5)
0.0 evaporator probe calibration
LABEL MIN. MAX. U.M. DEF. REGULATOR
r0 0.1 15.0 °C/°F
(5)
2.0 hysteresis (differential, it is relative to the working setpoint)
LABEL MIN. MAX. U.M. DEF. REGULATOR
r0 0.1 15.0 °C/°F
r1 -99 r2 °C/°F
r2 r1 99.9 °C/°F
(5)
2.0 hysteresis (differential, it is relative to the working setpoint)
(5)
-50 minimum value you can assign to the working setpoint
(5)
50.0 maximum value you can assign to the working setpoint
r5 0 1 --- 0 working setpoint modification lock-out (1 = YES)
(5)
r8 -99 99.9 °C/°F
0.0 auxiliary working setpoint (it is the working setpoint during the multifunction input activa-
tion if i0 = 6 or 7 and during the Energy Saving cycle)
LABEL MIN. MAX. U.M. DEF. COMPRESSOR PROTECTION
C0 0 240 min 0 minimum delay between you turn the instrument ON and the first compressor activation
C1 0 240 min 5 minimum delay between two compressor activation in succession
C2 0 240 min 3 minimum delay between the compressor gets OFF and the following activation
C4 0 1 --- 0 fixed delay since the compressor gets ON and OFF (1 = YES, for 3 s)
C5 1 240 min 10 cycle time for the compressor activation during the cabinet probe alarm
C6 0 100 % 50 percentage of C5 the compressor is ON during the cabinet probe failure
(8)
LABEL MIN. MAX. U.M. DEF. SERIAL NETWORK (EVCONET)
n3 0 1 --- 0 authorization to implement the remote controls coming from the master (it is important if
n0 = 2 and n1 0; 1 = YES)
LABEL MIN. MAX. U.M. DEF. ENERGY SAVING (the working setpoint becomes r8)
Hr1 0.0 23.5 h.damin
Hr2 0.0 23.5 h.damin
(6)
0.0 Energy Saving cycle activation time
(6)
0.0 Energy Saving cycle length
LABEL MIN. MAX. U.M. DEF. REAL TIME DEFROST
Hd1 0.0 23.5 h.damin
Hd2 0.0 23.5 h.damin
Hd3 0.0 23.5 h.damin
Hd4 0.0 23.5 h.damin
Hd5 0.0 23.5 h.damin
Hd6 0.0 23.5 h.damin
(6)
- - - first defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(6)
- - - second defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(6)
- - - third defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(6)
- - - fourth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(6)
- - - fifth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(6)
- - - sixth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
(7)
(7)
(7)
(7)
(7)
10.3 Second level parameters
LABEL MIN. MAX. U.M. DEF. MEASURE INPUTS
/0 1 3 --- 1 kind of probe (1 = PTC, 3 = NTC)
/1A -10 10.0 °C/°F
/1b -10 10.0 °C/°F
(5)
0.0 cabinet probe calibration
(5)
0.0 evaporator probe calibration
/5 0 1 --- 1 temperature resolution (it is important if /8 = 1; 0 = 1 degree, 1 = 0.1 degrees)
/8 0 1 --- 1 temperature unit of measure (0 = Fahrenheit degree, 1 = Celsius degree)
LABEL MIN. MAX. U.M. DEF. DEFROST
(7)
d0 0 99 h 8 defrost interval (it is important if dE 3); look at dE as well
(0 = the defrost will never
automatically be activated)
d1 0 1 --- 1 kind of defrost (0 = electric defrost, 1 = hot gas defrost)
d2 -99 99.9 °C/°F
(5)
2.0 defrost end temperature (evaporator temperature)
d3 0 99 min 30 defrost maximum length (0 = the defrost will never be activated)
d4 0 1 --- 0 defrost activation every time you turn the instrument ON (1 = YES)
(7)
d5 0 99 min 0 delay between you turn the instrument ON and the defrost activation (it is important if
d4 = 1)
d6 0 1 --- 1 freeze of the temperature showed by the instrument during the defrost (1 = YES)
(9)
d7 0 15 min 2 dripping time
d9 0 1 --- 0 compressor protections cleaning at the moment of the defrost activation (it is important if
d1 = 1; 1 = YES)
dE 0 3 --- 0 defrost interval count mode; look at d0 as well (0 = the instrument counts the working time,
1 = the instrument counts the sum of the times the compressor is ON,
2 = the instrument counts the sum of the times the evaporator temperature is below dF,
3 = real time defrost, the defrost will be activated at the times you have set with the param-
eters Hd1 ... Hd6)
dF -99 99.9 °C/°F
(5)
0.0 defrost interval count freeze threshold (evaporator temperature, it is important if dE = 2)
dP 0 99 min 0 minimum time the compressor must have been ON at the moment of the defrost activation
in order that the defrost can be activated (it is important if d1 = 1)
(10)
Loading...