1. About this document
1.1. Scope
These operating instructions are valid for all CKS-K-AS2A-U-C20-PC. These operating instructions, the document “Safety
information and maintenance” and any enclosed data sheet form the complete user information for your device.
1.2. Target group
Design engineers and installation planners for safety devices on machines, as well as setup and servicing staff possessing
special expertise in handling safety components.
1.3. Key to symbols
Symbol/depictionSignicance
Printed document
www
DANGER
WARNING
Document is available for download at www.euchner.de
Document on CD
Safety precautions
Danger of death or severe injuries
Warning about possible injuries
Caution minor injuries possible
CAUTION
Notice about possible device damage
NOTICE
Important!
TipTip/useful information
Important information
1.4. Supplementary documents
The overall documentation for this device consists of the following documents:
Document title
(document number)
Safety information and
maintenance CKS-AS-C20
(123913)
Operating instructions
(123914)
Possibly enclosed data
sheet
Contents
Basic information on safe setup and service
(this document)
Item-specic information about deviations or additions
Important!
Always read all documents to gain a complete overview of safe installation, setup and use of the
device. The documents can be downloaded from www.euchner.de. For this purpose enter the doc.
no. in the search box.
123914-01-05/15 (translation of the original operating instructions)
EUCHNER key adapters series CKS-K-AS are operated as a slave on the safety bus AS-Interface Safety at Work
This safety component allows dangerous machine movements to be undertaken as long as a valid key is inserted. A stop
command is triggered if the key is removed during the dangerous machine function.
Before use, a risk assessment must be performed on the machine, e.g. in accordance with:
Ì ENISO 13849-1, Safety of machinery. Safety related parts of control systems. General principles for designÌ EN ISO 12100, Safety of machinery - General principles for design - Risk assessment and risk reductionÌ IEC 62061, Safety of machinery - Functional safety of safety-related electrical, electronic and programmable electronic
control systems.
Correct use includes compliance with the relevant requirements for installation and operation, for example
Ì ENISO 13849-1, Safety of machinery. Safety related parts of control systems. General principles for designÌ EN 60204-1, Safety of machinery. Electrical equipment of machines. General requirements
The key adapter must be used only in conjunction with the designated CKS keys from EUCHNER. On the use of different
keys, EUCHNER provides no warranty for safe function.
Important!
Ì The user is responsible for the proper integration of the device into a safe overall system. For this
purpose, the overall system must be validated, e.g. in accordance with ENISO13849-2.
Ì In the estimation of the PL for the overall system, a maximum value of 100 years can be assumed
for the MTTFd according to the limit value in EN ISO 13849-1:2008, section 4.5.2. This corresponds to a minimum value for the PFHd of 2.47x10-8/h.
Ì Correct use requires observing the permissible operating parameters (see Technical data).Ì If a product data sheet is included with the product, the information on the data sheet applies in
case of discrepancies with the operating instructions.
Ì It is only allowed to use components that are permissible in accordance with the table below.
Table 1: Possible combinations for CES components
Key
Key adapter
CKS-K-AS2A-U-C20-PC
Key to symbolsCombination possible
CKS-A-BK1-RD-113461
4
(translation of the original operating instructions) 123914-01-05/15
Page 5
Operating Instructions
Key Adapter CKS-K-AS2A-U-C20-PC
3. Description of the safety function
The safety function is dened by the related application.
Ì Device safety function:
- The zero sequence is sent if the key is removed (see chapter 6.1. Switching states on page 6).
In case of failure to comply with the conditions for correct use stated above, or if the safety instructions are not followed,
or if any servicing is not performed as required, liability will be excluded and the warranty void.
5. General safety instructions
Safety components fulll personal protection functions. Incorrect installation or tampering can lead to fatal injuries to personnel.
Check the safe function of the safety guard particularly
Ì after any setup workÌ after the replacement of a system componentÌ after an extended period without useÌ after every fault
Independent of these checks, the safe function of the safety guard should be checked at suitable intervals as part of the
maintenance schedule.
WARNING
Danger to life due to improper installation or due to bypassing (tampering). Safety components perform
a personal protection function.
Ì The switching operation may be triggered only by keys specially designated for this purpose.Ì The key must be completely pulled out of the key adapter in order to switch the safety circuit off
safely.
Ì Mounting, electrical connection and setup only by authorized personnel possessing the following
knowledge:
- specialist knowledge in handling safety components
- knowledge about the applicable EMC regulations
- knowledge about the applicable regulations on occupational safety and accident prevention.
Important!
Prior to use, read the operating instructions and keep these in a safe place. Ensure the operating
instructions are always available during mounting, setup and servicing. EUCHNER cannot provide any
warranty in relation to the readability of the CD for the storage period required. For this reason you
should archive a printed copy of the operating instructions. You can download the operating instructions from www.euchner.de.
123914-01-05/15 (translation of the original operating instructions)
The key adapter CKS can, e.g., be used as a lockout mechanism. As soon as the key is in the key adapter, this is reported
via the AS-Interface bus. Each delivered key possesses a unique electronic coding and so is a unique element in the system
used.
The code of a key cannot be reprogrammed.
If a permissible code is detected, a bit sequence is sent via the AS-Interface bus to signal that the key is inserted.
The zero sequence is sent via the AS-Interface bus when the key is removed from the key adapter. The machine cannot be
started.
If there is a fault in the key adapter, the zero sequence is sent and the LED illuminates.
6.1. Switching states
The detailed switching states for your key adapter can be found in the system status table. All indicator LEDs are described
there.
Key insertedKey removed
113461
CKS
FR
LED indicatorGreenYellow
DO, D1, D2, D3Code sequenceZero sequence
6
(translation of the original operating instructions) 123914-01-05/15
Page 7
Operating Instructions
Key Adapter CKS-K-AS2A-U-C20-PC
7. Mounting
NOTICE
Risk of damage to equipment and malfunctions as a result of incorrect installation.
Ì To achieve the degree of protection IP 67, it is necessary to install the key adapter in a clean,
at metal plate at least 2 mm thick and to tighten the screws with a tightening torque of 0.25 ...
0.35Nm.
Ì The device may be damaged if the tightening torque applied exceeds 0.35Nm.Ì A suitable strain relief must be provided for the connection cables in order to avoid damage to the
connection sockets or malfunctions.
The key adapter is intended for mounting in control panels with a cut-out measuring 33mmx68mm according to DIN43700.
The device is fastened using screw clamp elements from the rear side of the panel.
1. Insert the key adapter, with seal already bonded in place, into the mounting cut-out from the front.
2. Insert screw clamp elements in the housing of the key adapter from the side up to the end stop and tighten with
0.25…0.35Nm.
3. After mounting, again check the key adapter for rm seating and correct sealing of the front panel.
123914-01-05/15 (translation of the original operating instructions)
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Ì Power devices which are a powerful source of interference must be installed in a separate location
away from the input and output circuits for signal processing. The cable routing for safety circuits
should be as far away as possible from the cables of the power circuits.
Ì In order to avoid EMC interference, the physical environmental and operating conditions at the
installation site of the device must comply with the requirements according to the standard
EN60204-1:2006, section 4.4.2 (EMC).
Ì Please pay attention to any interference elds in case of devices such as frequency converters or
induction heating systems. Observe the EMC instructions in the manuals from the respective manufacturer.
Important!
If the device does not appear to function when the operating voltage is applied (e.g. green LED does
not ash), the key adapter must be returned unopened to the manufacturer.
8.1. Notes about
Important!
Ì For use and operation as per the requirements, a power supply with the feature "for use in
class 2 circuits" must be used.
Alternative solutions must comply with the following requirements:
a) Electrically isolated power supply unit with a max. open-circuit voltage of 30V/DC and a limited
current of max. 8A.
b) Electrically isolated power supply unit in combination with fuse as per UL248. This fuse should be
designed for max. 3.3A and should be integrated into the 30VDC voltage section.
8
(translation of the original operating instructions) 123914-01-05/15
Page 9
Operating Instructions
Key Adapter CKS-K-AS2A-U-C20-PC
8.2. Setting the AS-Interface address
The address can be set prior to or after assembly.
The AS-Interface address of the key adapter is set using an AS-Interface programming device. Addresses 1 to 31 are valid.
The unit is programmed by connecting the programming device to the ASi connection on the key adapter using a programming cable.
The AS-Interface address can also be set directly on the AS-Interface bus with a master.
The default setting for the address on delivery is 0.
8.3. Conguration in the AS-Interface safety monitor
(see operating instructions for the AS-Interface safety monitor)
8.3.1. Dual-channel positively driven
The key adapter is congured in the AS-Interface safety monitor with the AS-Interface address set as follows:
Ì Dual-channel positively drivenÌ With or without start-up test
You will nd a detailed description of the signal functions in chapter 10. System status table on page 12.
LED colorSignicance
GreenKey inserted
YellowReadiness for operation
RedFault
9.2. Teach-in function for key
The key must be allocated to the key adapter using a teach-in function before the system forms a functional unit.
The zero sequence is sent during the teach-in operation.
Important!
Ì The teach-in operation may be performed only if the device functions awlessly. The red LED must
not be illuminated.
Ì The key adapter disables the code of the previous key if teach-in is carried out for a new key.
Teach-in is not possible again immediately for this actuator if a new teach-in operation is carried
out. The disabled code is released again in the key adapter only after a third code has been
taught-in.
Ì The key adapter can only be operated with the last key taught-in.Ì If the key adapter detects the key that was most recently taught-in when in the teach-in standby
state, this state is ended immediately and the key adapter changes to normal operation.
Ì If the key to be taught-in is within the operating distance for less than 60s, it will not be activated
and the most recently taught-in key will remain saved.
9.2.1. Preparing device for teach-in operation and teaching-in key
1. Insert new key
2. Connect AS-Interface bus to the key adapter.
¨ Teach-in operation starts, the LED ashes green (approx. 1 Hz). During the teach-in operation, the key adapter checks
whether the key is a disabled key. Provided this is not the case, the teach-in operation is completed after approx. 60
seconds, and the green LED goes out. The new code has now been stored, and the old code is disabled.
3. To activate the new key code from the teach-in operation in the key adapter, the key adapter must then be disconnected
from the AS-Interface bus for min. 3seconds.
10
(translation of the original operating instructions) 123914-01-05/15
Page 11
Operating Instructions
Key Adapter CKS-K-AS2A-U-C20-PC
9.3. Functional check
WARNING
Danger of fatal injury as a result of faults in installation and functional check.
Ì Before carrying out the functional check, make sure that there are no persons in the danger area.Ì Observe the valid accident prevention regulations.
9.3.1. Electrical function test
After installation and any fault, the safety function must be fully checked. Proceed as follows:
1. Switch on operating voltage.
¨ The machine must not start automatically.
¨ The key adapter carries out a self-test. The LED then ashes green (3min).
2. Insert key.
¨ The LED illuminates green.
3. Enable operation in the control system.
4. Remove key.
Ì The machine must switch off and it must not be possible to start it as long as a key is not inserted.Ì The LED illuminates yellow.
Repeat steps 2…4 for each key adapter.
123914-01-05/15 (translation of the original operating instructions)
NoNormal operation, no key inserted AS-i bus connected and in operation
Yes1 HzNormal operation, key inserted but not taught-in, AS-i bus connected and in operation
Teach-in standbyNo3 xDevice is ready for teach-in of another key (only short time after power-up)
Yes1 HzTeach-in operation
Setup
X
Yes3 xDefective key (e.g. fault in code or code cannot be read)
Fault display
XInternal fault (e.g. component faulty, data error)
X4 xError: AS bus connected, no communication with the master
Green
Yellow
State
Red
Positive acknowledgment after completion of teach-in operation or device not connected
LED not illuminated
LED illuminated
Key to symbols
10 Hz (8 s)
3 x
XAny state
LED ashes for 8 seconds at 10 Hz
LED ashes three times, and this is then repeated
After the cause has been remedied, faults can generally be reset by removing and inserting again the key. If the fault is still
displayed afterward, briey interrupt the power supply. Please contact the manufacturer if the fault could not be reset after
restarting.
Important!
If you do not nd the displayed device status in the System status table, this indicates an internal
device fault. In this case, you should contact the manufacturer.
12
(translation of the original operating instructions) 123914-01-05/15
Page 13
Operating Instructions
Key Adapter CKS-K-AS2A-U-C20-PC
11. Technical data
NOTICE
If a product data sheet is included with the product, the information on the data sheet applies.
min.typ.max.
Housing materialPlastic PA6-GF30 black
Fixing screw tightening torque--0.35Nm
Dimensions75 x 40 x 73mm
Weight (without connection cable)0.13kg
Ambient temperature at UB = DC 30 V-10-+65°C
Degree of protectionIP 67
Safety classIII
Degree of contamination 2
Installation positionOn the front
Mounting cut-out according to DIN4370033 x 68mm
ConnectionScrew terminal 2-pole
For the approval according to UL the following appliesOperation with UL-class 2 power supply only
Rated insulation voltage U
Rated impulse withstand voltage U
Resilience to vibrationIn acc. with EN IEC 60947-5-2
Ready delay-0.5-s
Risk time--260
Switch-on time--300
AS-Interface dataEA code: 0ID code: B
AS-i operating voltage19-31.6DC V
Total current consumption--50mA
Valid AS-Interface addresses1 - 31
AS-Interface inputsAcc. to AS-Interface Safety at Work
Inuenced by keyD0 - D3
Reliability values according to EN ISO 13849-1
Category4
Performance LevelPL e
PFH
d
Mission time20years
i
imp
--300V
--1.5kV
in mounted condition (only access side)
-9
4.5 x 10
/ h
ms
123914-01-05/15 (translation of the original operating instructions)
Please refer to the technical data for the exact values.
Ready delay: After switching on, the unit carries out a self-test. The system is ready for operation only after this time.
Risk time according to EN 60947-5-3: If a key moves outside the operating distance, the zero sequence is sent via the
AS-Interface bus.
Switch-on time: The max. reaction time ton is the time from the moment when the key is in the operating distance to
sending the code sequence.
11.1.2. Dimension drawing of key adapter CKS-K-AS2A-U-C20-PC
(Gummidichtung/
rubber seal)
14
(translation of the original operating instructions) 123914-01-05/15
Page 15
11.2. Technical data, key CKS-A-BK1-RD-113461
40
∅
31
Operating Instructions
Key Adapter CKS-K-AS2A-U-C20-PC
Parameter
Housing materialPlastic PC
Dimensions42 x 25 x 18mm
Weight0.004kg
Ambient temperature- 20-+ 70°C
Degree of protectionIP67
Power supplyInductive via key adapter
min.typ.max.
Value
11.2.1. Dimension drawing
113461
CKS
FR
∅
25,4
aktive Fläche /
active face
5
Unit
123914-01-05/15 (translation of the original operating instructions)
Loss of the safety function because of damage to the system.
Ì In case of damage, the entire device must be replaced. Ì Only accessories or spare parts that can be ordered from EUCHNER may be replaced.
Regular inspection of the following is necessary to ensure trouble-free long-term operation:
Ì Check the switching function (see chapter 9.3. Functional check on page 11)Ì Check the secure fastening of the devices and the connectionsÌ Check for soiling
No servicing is required. Repairs to the device are only allowed to be made by the manufacturer.
NOTICE
The year of manufacture can be seen in the lower right corner of the rating plate. The current version
number in the format (VX.X.X) can also be found on the device.
13. Service
If service support is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
D-70771 Leinfelden-Echterdingen
Service telephone:
+49 711 7597-500
E-mail:
support@euchner.de
Internet:
www.euchner.de