EUCHNER CET.-AP Series, CET.-AR Series Operating Instructions Manual

EN
Operating Instructions
Transponder-Coded Safety Switch With Guard Locking
CET.-AP-… (Unicode/Multicode)
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
2
(Translation of the original operating instructions) 2122242-04-05/18
Contents
1. About this document ............................................................................................. 4
1.1. Scope ............................................................................................................................................4
1.2. Target group ..................................................................................................................................4
1.3. Key to symbols ...............................................................................................................................4
1.4. Supplementary documents ..............................................................................................................4
2. Correct use .......................................................................................................... 5
3. Description of the safety function .......................................................................... 6
4. Exclusion of liability and warranty ......................................................................... 6
5. General safety precautions ................................................................................... 7
6. Function ............................................................................................................... 8
6.1. Guard locking monitoring .................................................................................................................8
6.2. Monitoring output (OUT) ..................................................................................................................8
6.3. Door monitoring output (OUTD) .......................................................................................................9
6.4. Diagnostic output (DIA) ....................................................................................................................9
6.5. Guard locking on version CET3 ........................................................................................................9
6.6. Guard locking on version CET4 ........................................................................................................9
6.7. Start button and feedback loop (optional) .......................................................................................10
6.8. Switching states ...........................................................................................................................10
7. Manual release ................................................................................................... 11
7.1. Auxiliary release and auxiliary key release (can be retrotted) ...........................................................11
7.1.1. Actuating auxiliary release .............................................................................................11
7.1.2. Actuating auxiliary key release .......................................................................................11
7.2. Emergency unlocking (can be retrotted) ........................................................................................12
7.2.1. Actuating emergency unlocking ......................................................................................12
7.3. Escape release (optional) ..............................................................................................................12
7.3.1. Actuating escape release...............................................................................................12
7.4. Wire front release (optional) ...........................................................................................................13
7.4.1. Laying wire front release ................................................................................................13
8. Changing the approach direction ........................................................................ 13
9. Mounting ............................................................................................................ 14
10. Electrical connection .......................................................................................... 16
10.1. Notes about .........................................................................................................................17
10.2. Safety in case of faults ..................................................................................................................17
10.3. Fuse protection for power supply ...................................................................................................17
10.4. Requirements for connection cables ...............................................................................................18
10.5. Connector assignment of safety switch CET-AP for connection to decentralized peripheral systems
with plug connectors 2 x M12 (5-pin; pin 5 not used) without door monitoring output .........................19
3
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
10.6. Connector assignment of safety switch CET-AP for connection to decentralized peripheral systems with plug connectors 2 x M12 (5-pin; pin 5 not used) and additional door monitoring output OUTD
on X2.2 .......................................................................................................................................19
10.7. Connector assignment of safety switch CET-AP with plug connector 1 x M12 (8-pin) ..........................19
10.8. Connector assignment of safety switch CET-AP with plug connector M23 (RC18) ...............................20
10.9. Connection ...................................................................................................................................21
10.10. Notes on operation with safe control systems .................................................................................22
10.11. Devices for direct connection to IP 65 eld modules........................................................................22
11. Setup ................................................................................................................. 23
11.1. LED displays ................................................................................................................................23
11.2. Teach-in function for actuator (only for unicode evaluation) ...............................................................23
11.2.1. Preparing device for the teach-in operation and teaching in actuator .................................24
11.3. Functional check ...........................................................................................................................25
11.3.1. Mechanical function test ................................................................................................25
11.3.2. Electrical function test ...................................................................................................25
12. System status table ............................................................................................ 26
13. Technical data .................................................................................................... 27
13.1. Technical data for safety switch CET.-AP-C..-AH-… ...........................................................................27
13.1.1. Typical system times .....................................................................................................28
13.2. Dimension drawing for safety switch CET.-AP-… .............................................................................. 29
13.3. Technical data for actuator CET-A-B… ............................................................................................31
13.3.1. Dimension drawing for actuator CET-A-BWK-50X ..............................................................31
14. Ordering information and accessories ................................................................. 32
15. Inspection and service ........................................................................................ 32
16. Service .............................................................................................................. 32
17. Declaration of conformity ................................................................................... 33
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
4
(Translation of the original operating instructions) 2122242-04-05/18
1. About this document
1.1. Scope
These operating instructions are valid for all CET.-AP from version V1.5.0 and for CET.-AP with lockout mechanism from V1.5.1. These operating instructions, the document “Safety information and maintenance” and any enclosed data sheet form the complete user information for your device.
1.2. Target group
Design engineers and installation planners for safety devices on machines, as well as setup and servicing staff possessing special expertise in handling safety components.
1.3. Key to symbols
Symbol/depiction Meaning
Printed document
www
Document is available for download at www.euchner.com
Document on CD
MEM
This section is applicable only if the memory card is used
DANGER
WARNING
CAUTION
Safety precautions
Danger of death or severe injuries Warning about possible injuries Caution Device damage possible
NOTICE
Important!
Important information
Tip Useful information
1.4. Supplementary documents
The overall documentation for this device consists of the following documents:
Document title (document number)
Contents
Safety information and maintenance CET-AR/ CET-AP (2105517)
Basic information about safe setup and maintenance
Operating Instructions (2122242)
(this document)
Possibly enclosed data sheet
Item-specic information about deviations or additions
Important!
Always read all documents to gain a complete overview of safe installation, setup and use of the device. The documents can be downloaded from www.euchner.com. For this purpose enter the doc. no. in the search box.
5
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
2. Correct use
Safety switches series CET-AP are interlocking devices with guard locking (type4). The device complies with the require­ments according to ENIEC60947-5-3. Devices with unicode evaluation possess a high coding level; devices with multicode evaluation possess a low coding level.
In combination with a movable guard and the machine control, this safety component prevents the guard from being opened while a dangerous machine function is being performed.
This means:
Ì Starting commands that cause a dangerous machine function must become active only when the guard is closed and
locked.
Ì The guard locking device must not be unlocked until the dangerous machine function has ended. Ì Closing and locking a guard must not cause automatic starting of a dangerous machine function. A separate start com-
mand must be issued. For exceptions, refer to ENISO12100 or relevant C-standards.
Devices from this series are also suitable for process protection.
Before the device is used, a risk assessment must be performed on the machine, e.g. in accordance with the following standards:
Ì ENISO13849-1, Safety of machinery – Safety-related parts of control systems – Part 1: General principles for design Ì ENISO12100, Safety of machinery – General principles for design – Risk assessment and risk reduction Ì IEC62061, Safety of machinery – Functional safety of safety-related electrical, electronic and programmable electronic
control systems
Correct use includes observing the relevant requirements for installation and operation, particularly based on the following standards:
Ì ENISO13849-1, Safety of machinery – Safety-related parts of control systems – Part 1: General principles for design Ì ENISO14119, Safety of machinery – Interlocking devices associated with guards – Principles for design and selection Ì EN60204-1, Safety of machinery – Electrical equipment of machines – Part 1: General requirements
The safety switch is allowed to be operated only in conjunction with the intended EUCHNER actuator and the related connec­tion components from EUCHNER. On the use of different actuators or other connection components, EUCHNER provides no warranty for safe function.
Important!
Ì The user is responsible for the proper integration of the device into a safe overall system. For this
purpose, the overall system must be validated, e.g. in accordance with ENISO13849-2.
Ì It is only allowed to use components that are permissible in accordance with the table below.
Table 1: Possible combinations for CET components
Safety switch
Actuator
CET-A-B…
CET.-AP-… (Unicode/Multicode)
Key to symbols Combination possible
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
6
(Translation of the original operating instructions) 2122242-04-05/18
3. Description of the safety function
Devices from this series feature the following safety functions:
Monitoring of guard locking and the position of the guard (interlocking device with guard locking according to ENISO14119)
Ì Safety function (see chapter 6.8. Switching states on page 10):
- The safety outputs are switched off when guard locking is released (monitoring of the locking element).
- The safety outputs are switched off when the guard is open (monitoring of the door position).
- Guard locking can be activated only when the actuator is located in the switch head (failsafe locking mechanism).
Ì Safety characteristics: category, Performance Level, PFH
D
(see chapter 13. Technical data on page 27).
Activation of guard locking
If the device is used as guard locking for personnel protection, control of guard locking must be regarded as a safety function.
The device does not feature a safety characteristic for the control of the guard locking, because the guard locking solenoid is completely disconnected from outside the device (no control function within the device). It therefore does not contribute to the failure probability.
The safety level for the control of guard locking is determined exclusively by the external control (e.g. PFH
D
ext.
for the
standstill monitor).
Guardlocking Device
PFH
D
ext.
(e.g. standstill
monitor)
(locking mean)
4. Exclusion of liability and warranty
In case of failure to comply with the conditions for correct use stated above, or if the safety instructions are not followed, or if any servicing is not performed as required, liability will be excluded and the warranty void.
7
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
5. General safety precautions
Safety switches fulll personnel protection functions. Incorrect installation or tampering can lead to fatal injuries to personnel.
Check the safe function of the guard particularly
Ì after any setup work Ì after the replacement of a CET component Ì after an extended period without use Ì after every fault
Independent of these checks, the safe function of the guard should be checked at suitable intervals as part of the mainte­nance schedule.
WARNING
Danger to life due to improper installation or due to bypassing (tampering). Safety components perform a personnel protection function.
Ì Safety components must not be bypassed, turned away, removed or otherwise rendered ineffec-
tive. On this topic pay attention in particular to the measures for reducing the possibility of bypass­ing according to ENISO14119:2013, section 7.
Ì The switching operation must be triggered only by actuators designated for this purpose. Ì Prevent bypassing by means of replacement actuators (only for multicode evaluation). For this
purpose, restrict access to actuators and to keys for releases, for example.
Ì Mounting, electrical connection and setup only by authorized personnel possessing the following
knowledge:
- specialist knowledge in handling safety components
- knowledge about the applicable EMC regulations
- knowledge about the applicable regulations on occupational safety and accident prevention.
Important!
Prior to use, read the operating instructions and keep these in a safe place. Ensure the operating instructions are always available during mounting, setup and servicing. EUCHNER cannot provide any warranty in relation to the readability of the CD for the storage period required. For this reason you should archive a printed copy of the operating instructions. You can download the operating instruc­tions from www.euchner.com.
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
8
(Translation of the original operating instructions) 2122242-04-05/18
6. Function
The device permits the locking of movable guards.
The system consists of the following components: coded actuator (transponder) and switch.
Whether the device learns the complete actuator code (unicode) or not (multicode) depends on the respective version.
Ì Devices with unicode evaluation: The actuator must be assigned to the
safety switch by a teach-in operation so that it is detected by the system. This unambiguous assignment ensures a particularly high level of protection against tampering. The system thus possesses a high coding level.
Ì Devices with multicode evaluation: Unlike systems with unique code detec-
tion, on multicode devices a specic code is not requested but instead it is only checked whether the actuator is of a type that can be detected by the system (multicode detection). There is no exact comparison of the actuator code with the taught-in code in the safety switch (unique code detection). The system pos­sesses a low coding level.
When the guard is closed, the actuator is moved towards the safety switch. When the switch-on distance is reached, power is supplied to the actuator by the switch and data are transferred.
The safety outputs are switched on when the locking pin is in the recess (state: door closed and locked) and a permissible code is detected.
When guard locking is released, the safety outputs and the monitoring output (OUT) are switched off.
Important!
Ì CET3 (closed-circuit current principle)
The activation of the guard locking solenoid results in the shutdown of the safety outputs OA/OB and the monitoring output OUT.
Ì CET4 (open-circuit current principle)
The interruption (>5ms) of the power supply to UCM results in the shutdown of the safety outputs OA/OB and the monitoring output OUT.
Ì In both cases the outputs are shut down independent of the actual posi-
tion of the solenoid.
Ì For more detailed information, see also chapter 10.10. Notes on opera‑
tion with safe control systems on page 22.
In the event of a fault in the safety switch, the safety outputs are switched off and the DIA LED illuminates red. The occurrence of faults is detected at the latest on the next demand to switch on the safety outputs (e.g. on starting).
6.1. Guard locking monitoring
All versions feature two safe outputs for monitoring guard locking (OA and OB). The safety outputs are switched off when guard locking is released.
6.2. Monitoring output (OUT)
The monitoring output is switched on as soon as guard locking is active (state: door closed and locked) and the transponder has been detected.
Ramp/switch head
Plunger
Ramp
Transponder
Spring­mounted guard locking pin
Recess
9
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
6.3. Door monitoring output (OUTD)
Versions CET3 and CET4 feature a door monitoring output (OUT D). The door monitoring output is switched on as soon as the actuator is above the extended plunger (state: guard closed and not locked). The door monitoring output also remains switched on when guard locking is active.
6.4. Diagnostic output (DIA)
Some versions have a diagnostic output. The diagnostics output is switched on in the event of a fault (switch-on condition as for DIA LED).
6.5. Guard locking on version CET3
(Guard locking actuated by spring force and released by power-ON)
Activating guard locking: close guard; no voltage at the solenoid.
Releasing guard locking: apply voltage to the solenoid.
The spring-operated guard locking functions in accordance with the closed-circuit current principle. If the voltage is interrupted at the solenoid, the guard locking remains active and the guard cannot be opened directly.
Important!
If the guard is open when the power supply is interrupted and is then closed, guard locking is activated. This can lead to persons being locked in unintentionally.
The actuator’s guard locking pin cannot be moved out of the recess and the guard is locked as long as the plunger is pressed down by the actuator.
When voltage is present at the guard locking solenoid, the plunger is extended and lifts the actuator’s guard locking pin above the edge of the recess. The guard can be opened.
6.6. Guard locking on version CET4
(Guard locking actuated by power-ON and released by spring force)
Important!
Use as guard locking for personnel protection is possible only in special cases, after strict assessment of the accident risk (see ENISO14119:2013, section 5.7.1)!
Activating guard locking: apply voltage to the solenoid.
Releasing guard locking: disconnect voltage from the solenoid.
The magnetically actuated guard locking operates in accordance with the open-circuit current principle. If the voltage is interrupted at the solenoid, the guard locking is released and the guard can be opened directly!
The guard can be opened as long as the plunger is held in the extended position.
The plunger is released when voltage is present at the guard locking solenoid. The actuator’s guard locking pin can now press the plunger down. The guard is locked as soon as the guard locking pin is fully inserted into the recess.
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
10
(Translation of the original operating instructions) 2122242-04-05/18
6.7. Start button and feedback loop (optional)
A start button and a feedback loop can be connected (for monitoring downstream relays and contactors) (inputY).
Important!
Faults on the start button/in the feedback loop are not detected. This can lead to unintentional auto­matic starting.
On devices with start button and feedback loop, safety outputs are switched on only when the start button is pressed and the feedback loop is closed. Start button and feedback loop must be closed for at least500 ms.
The monitoring output OUT is switched on as soon as guard locking is active. The status of the feedback loop/the start button has no effect on this aspect (see also chapter 12. System status table on page 26).
6.8. Switching states
The detailed switching states for your switch can be found in the system status table. All safety outputs, monitoring outputs and LED displays are described there.
Guard closed and locked Guard closed and not locked Guard open
Voltage on guard locking solenoid CET3 off on (irrelevant)
Voltage on guard locking solenoid CET4 on off (irrelevant)
Safety outputs OA and OB
on off off
Monitoring output OUT on off off
Door monitoring output OUT D
(only CET3 and CET4)
on on off
11
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
7. Manual release
Some situations require the guard locking to be released manually (e.g. malfunctions or an emergency). A function test should be performed after release.
More information on this topic can be found in the standard ENISO14119:2013, section 5.7.5.1. The device can feature the following release functions:
7.1. Auxiliary release and auxiliary key release (can be retrotted)
In the event of malfunctions, the guard locking can be released with the auxiliary release irrespective of the state of the solenoid.
The safety outputs are switched off when the auxiliary release is actuated. Use the safety outputs to generate a stop command.
The monitoring output OUT is switched off; OUTD can assume an undened state. Open the guard and close it again after resetting the auxiliary release. The device will then operate normally again.
7.1.1. Actuating auxiliary release
1. Unscrew locking screw.
2. Using a screwdriver, turn the auxiliary release to in the direction of the arrow.
¨ Guard locking is released.
Important!
Ì The actuator must not be under tensile stress during manual release. Ì After use, reset the auxiliary release and screw in and seal the locking
screw (e.g. with sealing lacquer).
Ì The auxiliary key release must not be used to lock the switch during
servicing to prevent activation of guard locking, for example.
Ì Loss of the release function due to mounting errors or damage during
mounting.
Ì Check the release function every time after mounting. Ì Please observe the notes on any enclosed data sheets.
7.1.2. Actuating auxiliary key release
On devices with auxiliary key release (can be retrotted), simply turn the key to release. Function as for auxiliary release. For mounting, see the auxiliary key release supplement.
Locking screw
Auxiliary release
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
12
(Translation of the original operating instructions) 2122242-04-05/18
7.2. Emergency unlocking (can be retrotted)
Permits opening of a locked guard from outside the danger zone without tools. For mounting, see the mounting supplement.
Important!
Ì It must be possible to operate the emergency unlocking manually from outside the protected area
without tools.
Ì The emergency unlocking must possess a marking indicating that it may be used only in an emer-
gency.
Ì The actuator must not be under tensile stress during manual release. Ì The emergency unlocking must be sealed or the misuse of the release function must be prevented
in the control system.
Ì The unlocking function meets all other requirements from ENISO14119. Ì The emergency unlocking meets the requirements of Category B according to
ENISO13849-1:2015.
Ì Loss of the release function due to mounting errors or damage during mounting. Ì Check the release function every time after mounting. Ì Please observe the notes on any enclosed data sheets.
7.2.1. Actuating emergency unlocking
Ì Turn emergency unlocking clockwise until it clicks into place.
¨ Guard locking is released.
To reset, press the snap-in bolt inward using a small screwdriver or similar tool and turn the emergency unlocking back.
The safety outputs are switched off when the emergency unlocking is actuated. Use the safety outputs to generate a stop command.
The monitoring output OUT is switched off; OUTD can assume an undened state. Open the guard and close it again after resetting the emergency unlocking. The device will then operate normally again.
7.3. Escape release (optional)
Permits opening of a locked guard from the danger zone without tools (see chapter 13.2. Di‑ mension drawing for safety switch CET.‑AP‑… on page 29).
Important!
Ì It must be possible to actuate the escape release manually from in-
side the protected area without tools.
Ì It must not be possible to reach the escape release from the outside. Ì The actuator must not be under tensile stress during manual release. Ì The escape release meets the requirements of Category B according
to ENISO13849-1:2015.
7.3.1. Actuating escape release
Ì Press the red release knob to the stop.
¨ Guard locking is released.
Pull the knob out again to reset.
The safety outputs are switched off when the escape release is actuated. Use the safety outputs to generate a stop command.
The monitoring output OUT is switched off; OUTD can assume an undened state. Open the guard and close it again after resetting the escape release. The device will then operate normally again.
Snap-in bolt
13
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
7.4. Wire front release (optional)
Release via a pull wire. Depending on the type of attachment, the wire front release can be used as emergency unlocking or escape release.
The following applies to non-latching wire front releases.
If the release is to be used as emergency unlocking, one of the following measures must be taken (see EN ISO 14119:2013, section 5.7.5.3):
Ì Install the release so that it can be reset only with the aid of a tool. Ì Alternatively, the reset can be undertaken at the control system level, e.g. by means of a
plausibility check (status of the safety outputs does not match the guard locking activation signal).
The emergency-unlocking specications in chapter 7.2 on Page 12 apply irrespective of this information.
Important!
Ì The wire front release meets the requirements of Category B accord-
ing to ENISO13849-1:2015.
Ì The correct function depends on the laying of the pull wire and on the
attachment of the pull handle, and this is the responsibility of the plant manufacturer.
Ì The actuator must not be under tensile stress during manual release.
7.4.1. Laying wire front release
Important!
Ì Loss of the release function due to mounting errors, damage or wear. Ì Check the release function every time after mounting. Ì When routing the wire front release, ensure that it operates smoothly. Ì Observe the min. bending radius (100mm) and minimize the number of bends. Ì The switch is not allowed to be opened. Ì Observe the notes on the enclosed data sheets.
8. Changing the approach direction
1. Remove the screws from the safety switch
2. Set the required direction
3. Tighten the screws with a torque of 1.5Nm
Figure 1: Changing the approach direction
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
14
(Translation of the original operating instructions) 2122242-04-05/18
9. Mounting
CAUTION
Safety switches must not be bypassed (bridging of contacts), turned away, removed or otherwise rendered ineffective.
Ì Observe ENISO14119:2013, section7, for information about reducing the possibilities for by-
passing an interlocking device.
Ì The max. achievable category according to EN13849-1 depends on the installation position (see
chapter 13. Technical data on page 27).
NOTICE
Risk of damage to equipment and malfunctions as a result of incorrect installation.
Ì Safety switches and actuators must not be used as an end stop. Ì Observe ENISO14119:2013, sections 5.2 and 5.3, for information about fastening the safety
switch and the actuator.
Ì Protect the switch head against damage, as well as penetrating foreign objects such as swarf,
sand and blasting shot, etc. The switch should be installed with the actuating head down for this purpose.
Ì Observe the min. door radii (see gure below). Ì Ensure that the actuator contacts the ramp in the designated area (see gure below). Marks on the
ramp specify the prescribed approach zone.
Tip!
EUCHNER offers special cover plates to improve protection against tampering. These accessories can be found at www.euchner.com.
min R=300
min R=1000
min R800
Figure 2: Door radii and approach zone
15
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
Note the following points:
Actuator and safety switch must be tted so that
Ì the active faces of the actuator and the safety switch are parallel with each other. Ì the actuator is fully inserted into the switch recess when the guard is closed. Ì no dirt can accumulate in the recess.
!
!
= 90°
74,5 ± 4 mm
Anfahrbereich/ Approach Zone
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
16
(Translation of the original operating instructions) 2122242-04-05/18
10. Electrical connection
WARNING
If there is a mistake, loss of the safety function due to incorrect connection.
Ì To ensure safety, both safety outputs (OA and OB) must always be evaluated. Ì Monitoring outputs must not be used as safety outputs. Ì Lay the connection cables with protection to prevent the risk of short circuits.
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Ì The power supply for the evaluation electronics is electrically isolated from the power supply for
the guard locking solenoid.
Ì The teach-in input and feedback loop are at ground potential 0VU
B
.
Ì The device generates its own test pulses on the output lines OA/OB. A downstream control system
must tolerate these test pulses, which may have a length of up to 0.3ms. The test pulses are output only if the safety outputs are switched on. Depending on the inertia of the downstream device (control system, relay, etc.), this can lead to short switching processes.
Ì The inputs on an evaluation unit connected must be positive-switching, as the two outputs on the
safety switch deliver a level of +24V in the switched-on state.
Ì The device is suitable for operation on earth-leakage monitors. Ì All the electrical connections must either be isolated from the mains supply by a safety transformer
according to IEC 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent isolation measures (PELV).
Ì All electrical outputs must have an adequate protective circuit for inductive loads. The outputs
must be protected with a free-wheeling diode for this purpose. RC interference suppression units must not be used.
Ì Power devices which are a powerful source of interference must be installed in a separate location
away from the input and output circuits for signal processing. The cable routing for safety circuits should be as far away as possible from the cables of the power circuits.
Ì To avoid EMC interference, the physical environmental and operating conditions at the in-
stallation site of the device must comply with the requirements according to the standard EN60204-1:2006, section 4.4.2 (EMC).
Please pay attention to any interference elds from devices such as frequency converters or induction heating systems. Observe the EMC instructions in the manuals from the respective manufacturer.
Important!
If the device does not appear to function when operating voltage is applied (e.g. green STATE LED does not ash), the safety switch must be returned unopened to the manufacturer.
17
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
10.1. Notes about
Important!
Ì For use and operation as per the requirements*, a power supply with the feature “for use in
class 2 circuits” must be used. The same requirement applies to the safety outputs. Alternative solutions must comply with the following requirements:
- Electrically isolated power supply unit in combination with fuse as per UL248. This fuse should be designed for max. 3.3A and should be integrated into the 30VDC voltage section.
Ì For use and applications as per the requirements
1
, a connection cable listed under UL cate-
gory code CYJV/7 must be used.
1
Note on the scope of the UL approval: the devices have been tested as per the requirements of UL508 and CSA/ C22.2 no. 14 (protection against electric shock
and re).
10.2. Safety in case of faults
Ì The operating voltage U
B
and the solenoid voltage UCM are reverse polarity protected.
Ì The safety outputs OA/OB are short circuit-proof. Ì A short circuit between OA and OB is detected by the switch. Ì A short circuit in the cable can be excluded by laying the cable with protection.
10.3. Fuse protection for power supply
The power supply must be provided with fuse protection depending on the number of switches and current required for the outputs. The following rules apply:
Max. current consumption I
max
I
max
= IUB + I
OUT
+ IOA+OB (+ I
OUTD
*)
IUB = Switch operating current (80mA)
I
OUT
/ I
OUT D
= Load current of monitoring outputs (2x max. 50mA)
I
OA+OB
= Load current of safety outputs OA + OB (2xmax. 200mA)
* only for version with door monitoring output
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
18
(Translation of the original operating instructions) 2122242-04-05/18
10.4. Requirements for connection cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection cables.
Ì Use connection components and connection cables from EUCHNER Ì On the usage of other connection components, the requirements in the following table apply.
EUCHNER provides no warranty for safe function in case of failure to comply with these require­ments.
Observe the following requirements with respect to the connection cables:
For safety switch CET-AP with plug connector M12
Parameter Value Unit
Conductor cross-section, min. 0.25 mm² R max. 60 W/km C max. 120 nF/km L max. 0.65 mH/km Recommended cable type LIYY 8 x 0.25mm²
For safety switch CET-AP with plug connector M23 (RC18)
Parameter Value Unit
Conductor cross-section, min. 0.25 mm² R max. 60 W/km C max. 120 nF/km L max. 0.65 mH/km Recommended cable type
LIFY11Y min. 19-core
19
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
10.5. Connector assignment of safety switch CET-AP for connection to decentralized peripheral systems with plug connectors 2 x M12 (5-pin; pin 5 not used) without door monitoring output
Wiring diagram A
Plug connector
(view of connection side)
Pin Designation Function
Wire color of
connection cable
1)
2 x M12
X2.5
X2.4
X2.3
X2.1
X2.2
X1.5
X1.4
X1.3
X1.1
X1.2
X 1.1 U
B
Operating voltage, 24 V DC BN X 1.2 OA Safety output channelA WH X 1.3 0V Operating voltage, 0 V BU X 1.4 OB Safety output channelB BK X 1.5 - n.c. GY
X 2.1 - n.c. BN X 2.2 - n.c. WH X 2.3 0V U
CM
0V solenoid BU
X 2.4 U
CM
Operating voltage of guard locking solenoid 24 V DC BK
X 2.5 - n.c. GY
1) Only for standard EUCHNER connection cable
10.6. Connector assignment of safety switch CET-AP for connection to decentralized peripheral systems with plug connectors 2 x M12 (5-pin; pin 5 not used) and additional door monitoring output OUTD on X2.2
Wiring diagram B
Plug connector
(view of connection side)
Pin Designation Function
Wire color of
connection cable
1)
2 x M12
X2.5
X2.4
X2.3
X2.1
X2.2
X1.5
X1.4
X1.3
X1.1
X1.2
X 1.1 U
B
Operating voltage, 24 V DC BN X 1.2 OA Safety output channelA WH X 1.3 0V Operating voltage, 0 V BU X 1.4 OB Safety output channelB BK X 1.5 - n.c. GY
X 2.1 - n.c. BN X 2.2 OUT D Door monitoring output WH X 2.3 0V U
CM
0V solenoid BU
X 2.4 U
CM
Operating voltage of guard locking solenoid 24 V DC BK
X 2.5 - n.c. GY
1) Only for standard EUCHNER connection cable
10.7. Connector assignment of safety switch CET-AP with plug connector 1 x M12 (8-pin)
Wiring diagram C/D
Plug connector
(view of connection side)
Pin Designation Function
Wire color of
connection cable
1)
1 x M12
8
5
6
7
2
4
3
1
1 U
CM
Operating voltage of guard locking solenoid 24 V DC WH
2 U
B
Operating voltage, 24 V DC BN
3 OA Safety output channelA GN 4 OB Safety output channelB YE
5
OUT
Monitoring output GY
DIA 6 OUT D Door monitoring output PK 7 0 V U
B
Operating voltage, 0 V BU
8 0V U
CM
0V solenoid RD
1) Only for standard EUCHNER connection cable
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
20
(Translation of the original operating instructions) 2122242-04-05/18
10.8. Connector assignment of safety switch CET-AP with plug connector M23 (RC18)
Wiring diagram E
Plug connector
(view of connection side)
Pin Designation Function
Wire color of
connection cable
1)
1 x RC18
12
1
2
3
4
5
6
7
8
9
10
11
18
13
14
15
16
17
19
1 U
CM
Operating voltage of guard locking solenoid 24 V DC VT 2 - n.c. ­3 - n.c. ­4 OA Safety output channelA RDBU 5 OB Safety output channelB GN 6 U
B
Operating voltage, 24 V DC BU 7 RST Reset GYRD 8 OUT D Door monitoring output WHGN 9 - n.c. -
10 OUT Monitoring output WHGY 11 - n.c. ­12 FE Function earth YEGN 13 J Teach-in input PK 14 - n.c. Do not connect to 0 V! ­15 - n.c. BNGN 16 - n.c. YEBN 17 - n.c. ­18 0V U
CM
0V solenoid YE
19 0 V U
B
Operating voltage, 0 V BN
1) Only for standard EUCHNER connection cable
21
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
10.9. Connection
Connect the device as shown in Figure 3. The monitoring outputs can be routed to a control system.
The switches can be reset via the RST input. To do this, a voltage of 24V is applied to the RST input for at least 3s.
WARNING
If there is a mistake, loss of the safety function due to incorrect connection.
Ì To ensure safety, both safety outputs (OA and OB) must always be evaluated.
Important!
Ì The example shows only an excerpt that is relevant for connection of the CET system. The exam-
ple illustrated here does not show complete system planning. The user is responsible for safe inte­gration into the overall system. Detailed application examples can be found at www.euchner.com. Simply enter the order number in the search box. All available connection examples for the device can be found in “Downloads.”
24 V DC
GND
-F1 -F2
Connected load
Door monitoring
Monitoring Output
Read Head
Actuator
RST
7
Safety Outputs
NC14NC
15
-B10
UB
6
UCM
1
0V(UCM)
18
NC
17
J
13
0V
19
OUTD
8
OUT
10
OA
4
OB
5
NC2NC3NC9NC
11
12
FE
NC
16
CET
-S1
-S2
Figure 3: Connection example for CET-AP with plug connector M23 (wiring diagram E)
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
22
(Translation of the original operating instructions) 2122242-04-05/18
10.10. Notes on operation with safe control systems
Please observe the following requirements for connection to safe control systems:
Ì Use a common power supply for the control system and the connected safety switches. Ì The device tolerates interruptions in the operating voltage of up to 5ms at U
B
and UCM. If the supply voltage is connect-
ed to a terminal of a safe control system, this output must provide sufcient electrical current.
Ì The safety outputs (OA and OB) can be connected to the safe inputs of a control system. Prerequisite: the input must
be suitable for pulsed safety signals (OSSD signals, e.g. from light grids). The control system must tolerate test pulses on the input signals. This normally can be set up by parameter assignment in the control system. Observe the notes of the control system manufacturer. For the test-pulse duration of your safety switch, please refer to chapter 13.1. Techni‑ cal data for safety switch CET.‑AP‑C..‑AH‑… on page 27.
A detailed example of connecting and setting the parameters of the control system is available for many devices at www.euchner.com in the area Download » Applications » CET. The features of the respective device are dealt with there in greater detail.
10.11. Devices for direct connection to IP 65 eld modules
The version CET.-AP-...-SI-... (wiring diagram A) is optimized for connection to decentralized peripheral systems, such as the ET200pro series from Siemens. The devices are parameterized and connected like an OSSD (e.g. like light curtains).
The two 5-pin M12 plug connectors can be connected directly to the sockets of an IP 65 eld module (e.g. ET200pro). If ying leads are used, connection to IP 20 input and output modules (e.g. ET200s) is naturally also possible.
Important!
Observe the following notes prior to connection:
Ì Use only CET-AP versions that are intended to be used for this purpose. Ì Parameter assignment must be performed for the input/output modules (see application example
at www.euchner.com in the area Download » Applications » CET).
Ì Additionally observe notes from the control system manufacturer where necessary.
23
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
11. Setup
11.1. LED displays
You will nd a detailed description of the signal functions in chapter 12. System status table on page 26.
LED Color
STATE green
DIA red
LED1 red
LED2 green
NOTICE
Ì With hard-wired LEDs the following applies:
- LED1: red = Solenoid activated (voltage present at solenoid)
- LED2: green = OUT D is switched on (door is closed)
Ì Depending on version, the function of LED1 and LED2 can differ. Detailed information is available
on the enclosed data sheet or at www.euchner.com. Simply enter the order number in the search box.
11.2. Teach-in function for actuator (only for unicode evaluation)
The actuator must be allocated to the safety switch using a teach-in function before the system forms a functional unit.
During a teach-in operation, the safety outputs and the monitoring output OUT are switched off, i.e. the system is in the safe state.
Depending on the version, the teach-in operation is automatic or is undertaken with the aid of the teach-in input J.
Tip!
We recommend performing the teach-in operation prior to mounting. Mark switches and actuators that belong together in order to avoid confusion.
Important!
Ì The teach-in operation may be performed only if the device functions awlessly. The red DIA LED
must not be illuminated.
Ì The safety switch disables the code of the previous actuator if teach-in is carried out for a new
actuator. Teach-in is not possible again immediately for this actuator if a new teach-in operation is carried out. The disabled code is released again in the safety switch only after a third code has been taught in.
Ì The safety switch can be operated only with the last actuator taught in. Ì Version without teach-in input: After starting, the device remains in teach-in standby state for
3min. If no new actuator is detected in this time, the device changes to normal operation. If the switch detects the actuator that was most recently taught in when in the teach-in standby state, this state is ended immediately and the switch changes to normal operation.
Ì Versions with teach-in input: Teach-in operation ends when the power supply to the teach-in input is
interrupted, but no later than after 3min. If no actuator was detected during this time, the device enters the fault state.
Ì The actuator to be taught in is not activated if it is within the operating distance for less than 60s.
LED2 (gn)
STATE (gn) DIA (rd)
LED1 (rd)
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
24
(Translation of the original operating instructions) 2122242-04-05/18
11.2.1. Preparing device for the teach-in operation and teaching in actuator
1. Connect the switch as shown below, but do not apply any voltage to UB yet.
In case of version with teach-in input: For the teach-in standby state, the teach-in input J must be connected to +24VDC.
In case of version without teach-in input: The circuit is the same, but connection J is omitted.
Observe different control of guard locking for CET3 and CET4.
CET4CET3
GND
DC 24 V
0V UB
UB
-F1 -F2
0V UCM
UCM
J
GND
DC 24 V
0V UB
UB
-F1 -F2
0V UCM
UCM
J
Devices with teach-in input: Connect J to 24 V for teach-in
CET3-...: No voltage at UCM (guard locking active)
Devices with teach-in input: Connect J to 24 V for teach-in
CET4-...:
Voltage at UCM (guard locking active)
2. Switch on operating voltage UB.
¨ A self-test is performed for approx. 1s. After this, the green STATE LED ashes
cyclically three times and signals that it is in standby state for teach-in. Standby state for teach-in remains active for approx.3 min.
¨ If the red DIA LED is illuminated, there is a fault. Teach-in is not possible. The green
STATE LED indicates the error code. For diagnostics see section 12. System status table on page 26.
3. Activate guard locking.
CET3: no voltage at UCM. CET4: Voltage at UCM.
4. Fully insert new actuator into the recess. Do not cant it; place it in the center of the recess (see picture on right).
¨ Teach-in operation starts, green STATE LED ashes (approx. 1 Hz). The teach-in
operation is completed after approx. 60s, and the green STATE LED goes out.
5. Switch off operating voltage UB (min. 3 s).
¨ The code of the actuator that was just taught in is activated in the safety switch.
6. In case of version with teach-in input: Disconnect the teach-in input from +24 V and leave open.
7. Switch on operating voltage UB.
¨ The device operates normally.
!
= 90°
25
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
11.3. Functional check
WARNING
Danger of fatal injury as a result of faults in installation and functional check.
Ì Before carrying out the functional check, make sure that there are no persons in the danger zone. Ì Observe the valid accident prevention regulations.
11.3.1. Mechanical function test
The actuator must slide easily into the recess on the actuating head. Close the guard several times to check the function. For devices with mechanical release (emergency unlocking or escape release), the correct function of the release must be checked as well.
11.3.2. Electrical function test
After installation and any fault, the safety function must be fully checked. Proceed as follows:
1. Switch on operating voltage.
¨ The machine must not start automatically.
¨ The safety switch carries out a self-test. The green STATE LED then ashes at regular intervals.
2. Close all guards. Guard locking by solenoid force: activate guard locking.
¨ The machine must not start automatically. It must not be possible to open the guard.
¨ The green STATE LED illuminates continuously.
3. Enable operation in the control system.
¨ It must not be possible to deactivate guard locking as long as operation is enabled.
4. Disable operation in the control system and deactivate guard locking.
¨ The guard must remain locked until there is no longer any risk of injury.
¨ It must not be possible to start the machine as long as the guard locking is deactivated.
Repeat steps 2-4 for each guard.
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
26
(Translation of the original operating instructions) 2122242-04-05/18
12. System status table
Operating mode
Actuator/door position
Safety outputs OA and
OB
Monitoring output OUT
Door monitoring output
OUTD
(only CET3 and CET4)
LED indicator
Output
State
STATE (green)
DIA (red)
Normal operation
closed on on on Normal operation, door closed and locked
closed off on on
1 x in-
verse
Normal operation, door closed and locked, safety outputs not switched because:
- Feedback loop not closed (if tted)
closed off off on 1 x Normal operation, door closed and not locked
open off off off 1 x Normal operation, door open
Teach-in operation
(only unicode)
open off off off 3 x
Door open; device is ready for teach-in for a new actuator (only short time after power-up)
closed off off off 1 Hz Teach-in operation
X off off off 1
Acknowledgment after successful teach-in operation (DIA ashes once, no repetition)
Fault display
X off off X 2 x
Fault on the power supply (e.g. shutdown pulse duration for pulsed power supply too long)
X off off off 1 x
Fault in the teach-in operation (only unicode) (e.g. actuator removed from the operating distance prior to the end of the teach-in operation or disabled actuator in the operating distance)
X off off off 3 x Actuator faulty
X off off off 4 x
Output fault (e.g. short circuits, loss of switching ability)
X off off off 5 x
Internal fault (e.g. component faulty, data error or impermissible pulsing on UB)
X off off off X X Internal error
Key to symbols
LED not illuminated
LED illuminated
10Hz (10s)
LED ashes for 10s at 10Hz
3 x
LED ashes three times, and this is then repeated
X Any state
After the cause has been remedied, faults can generally be reset by opening and closing the guard. If the fault is still dis­played afterward, use the reset function or briey interrupt the power supply. Please contact the manufacturer if the fault could not be reset after restarting.
Important!
If you do not nd the displayed device status in the system status table, this indicates an internal device fault. In this case, you should contact the manufacturer.
27
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
13. Technical data
NOTICE
If a data sheet is included with the product, the information on the data sheet applies.
13.1. Technical data for safety switch CET.-AP-C..-AH-…
Parameter Value Unit
min. typ. max.
General Material, ramp Stainless steel Material, safety switch housing Die-cast aluminum Installation position Any (recommendation: switch head downward) Degree of protection with plug connector M12
IP67 with plug connector M23 (RC18)
IP65/IP67
Safety class III Degree of contamination 3 Mechanical life 1 x 106 operating cycles Ambient temperature at U
B
-20 - +55 °C Actuator approach speed, max. 20 m/min Locking force F
max
6,500 N Locking force FZh in acc. with test principles GS-ET-19
FZh = F
max
/1.3 = 5,000 N
Weight Approx. 1.0 kg Degrees of freedom (actuator in recess) X, Y, Z X and Y: ± 5; Z: ± 4 mm Connection type (depending on version) 2 plug connectors M12, 5-pin, 1 plug connector M12, 8-pin,
1 plug connector M23 (RC18), 19-pin Operating voltage UB (reverse polarity protected, regulated, residual ripple < 5%)
1)
24 ± 15% (PELV) V DC
Current consumption I
B
80 mA
External fuse (operating voltage UB)
0.5 - 3 A
External fuse (solenoid operating voltage UCM)
0.5 - 2 A
Rated insulation voltage U
i
- - 75 V
Conditional short-circuit current
100 A
Resilience to vibration
Acc. to EN 60947-5-2
EMC protection requirements
Acc. to EN IEC 60947-5-3 Ready delay - - 1 s Risk time - - 400 ms Switch-on time - - 500 ms Discrepancy time - - 10 ms Test-pulse duration - - 0.3
2)
ms
Safety outputs OA/OB
Semiconductor outputs (p-switching, short circuit-proof)
- Output voltage UOA/UOB
3)
V DC
HIGH UOA/U
OB
UB - 1.5 - U
B
LOW UOA/U
OB
0 - 1 Switching current per safety output 1 - 200 mA Utilization category according to EN 60947-5-2 DC-13 24 V 200 mA
Caution: outputs must be protected with a free-wheeling diode in case of inductive loads Switching frequency 0.5 Hz Monitoring outputs OUT and OUT D (optional) (p-switching, short circuit-proof) Output voltage
0.8 x U
B
- U
B
V DC
Max. load - - 50 mA
Teach-in input J or feedback loop input Y
HIGH
15 - 26.4
V
LOW 0 - 1
Solenoid
Solenoid operating voltage UCM (reverse polarity protected, regulated, residual ripple < 5%)
1)
DC 24 V +10%/-15%
Solenoid current consumption I
CM
480 mA Power consumption Max. 12 W Duty cycle
100 %
Reliability values acc. to EN ISO 13849-1 Head downward or horizontal Head upward
Mission time 20 20 years
Monitoring of guard locking and the guard position Head downward or horizontal Head upward
Category 4 3 Performance Level (PL) e e PFH
D
3.1x10
-9
/h 4.29x10
-8
/h
Activation of guard locking
Category
Depends on external control
Performance Level (PL) PFH
D
1) The device tolerates voltage interruptions of up to 5ms.
2) Applies to a load with C < 30 nF and R < 20 kohm
3) Values at a switching current of 50 mA without taking into account the cable lengths.
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
28
(Translation of the original operating instructions) 2122242-04-05/18
13.1.1. Typical system times
Please refer to the technical data for the exact values.
Ready delay: After switching on, the device carries out a self-test. The system is ready for operation only after this time.
Switch-on time of safety outputs: The max. reaction time ton is the time from the moment when the guard is locked to
the moment when the safety outputs switch on.
Risk time according to EN 60947-5-3: If an actuator moves outside the operating distance, the safety outputs (OA and OB) are deactivated at the latest after the risk time.
Discrepancy time: The safety outputs (OA and OB) switch with a sight time offset. They have the same signal state no later than after the discrepancy time.
Test pulses at the safety outputs: The device generates its own test pulses on the safety outputs (OA and OB). A downstream control system must tolerate these test pulses.
This can usually be set up in the control systems by parameter assignment. If parameter assignment is not possible for your control system or if shorter test pulses are required, please contact our support organization.
The test pulses are output only if the safety outputs are switched on.
29
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
13.2. Dimension drawing for safety switch CET.-AP-…
42
67,2
30
16
130
167
28
25
25
11
5
34
15
74,5
±4 mm
<15>
43,6
52
91,2
CET.-AR...CRA...
CET.-AR...CDA...
20
11,3
SW
19
75
7
8
26,5
10,5
4
(15)
M12
41
15
X1X2
Plunger
Auxiliary release
LED2 LED1
6.5 For M6 screw DIN1207/ISO4762
Basic position for escape release
Release by pressing
With escape release
STATE DIA
Version with plug connectors 2xM12
With angle connectors
With escape release
Version with plug connectors 1xM12
22
21
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
30
(Translation of the original operating instructions) 2122242-04-05/18
42 30
22
M23x1
21,5
Version with plug connector M23(RC18)
Dimensions with plug connector M23
60
52
26
Cable exit left Cable exit right
With auxiliary key release
16,7
5,8
20
30
35,5
Ø
With emergency unlocking
25
30,4
71
With wire front release
30,5
83
31
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
13.3. Technical data for actuator CET-A-B…
Parameter Value Unit
min. typ. max. Housing material Stainless steel Stroke, max. 15 mm
Weight
0.25
kg
Ambient temperature - 20 - + 55 °C
Degree of protection IP67
Mechanical life 1x106 operating cycles
Locking force, max. 6,500 N
Installation position Active face opposite switch head
Power supply
Inductive via switch
13.3.1. Dimension drawing for actuator CET-A-BWK-50X
34
8
22
5
15 16
38
5
6,2
34
45
8
15 16
5
6,2
15
71
15
Hub/
Stroke
Active face
NOTICE
Ì Four safety screw M5x16 are included with the actuator. Ì All four safety screws must always be used.
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
32
(Translation of the original operating instructions) 2122242-04-05/18
14. Ordering information and accessories
Tip!
Suitable accessories, e.g. cables or assembly material, can be found at www.euchner.com. To order, enter the order number of your item in the search box and open the item view. Accessories that can be combined with the item are listed in “Accessories.”
15. Inspection and service
WARNING
Loss of the safety function because of damage to the device.
Ì In case of damage, the entire device must be replaced. Ì Only accessories or spare parts that can be ordered from EUCHNER may be replaced.
Regular inspection of the following is necessary to ensure trouble-free long-term operation:
Ì Check the switching function (see chapter 11.3. Functional check on page 25) Ì Check all additional functions (e.g. escape release, lockout bar, etc.) Ì Check the secure fastening of the devices and the connections Ì Check for soiling
No servicing is required. Repairs to the device are only allowed to be made by the manufacturer.
NOTICE
The year of manufacture can be seen in the lower right corner of the type label. The current version number in the format (V X.X.X) can also be found on the device.
16. Service
If service support is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen
Service telephone:
+49 711 7597-500
E-mail:
support@euchner.de
Internet:
www.euchner.com
33
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
17. Declaration of conformity
Operating Instructions Transponder-Coded Safety Switch CET.-AP-…
34
(Translation of the original operating instructions) 2122242-04-05/18
35
2122242-04-05/18 (Translation of the original operating instructions)
Operating Instructions
EN
Euchner GmbH + Co. KG Kohlhammerstraße 16 70771 Leinfelden-Echterdingen info@euchner.de www.euchner.com
Edition: 2122242-04-05/18 Title: Operating Instructions Transponder-Coded Safety Switch CET.-AP-… (Translation of the original operating instructions) Copyright: © EUCHNER GmbH + Co. KG, 05/2018
Subject to technical modications; no responsibility is accept­ed for the accuracy of this information.
Third-party trademark information: SIMATIC ET200pro and ET200S are trademarks of SIEMENS AG.
Loading...