EUCHNER CES-I-AS2A-M-C04 Operating Instructions Manual

Page 1
Operating Instructions
Non-Contact Safety Switch
CES-I-AS2A-M-C04 (Multicode)
EN
Page 2
Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04
1. About this document ............................................................................................. 4
1.1. Scope ............................................................................................................................................4
1.2. Target group ..................................................................................................................................4
1.3. Key to symbols ...............................................................................................................................4
1.4. Supplementary documents ..............................................................................................................4
2. Correct use .......................................................................................................... 5
3. Description of the safety function .......................................................................... 6
4. Exclusion of liability and warranty ......................................................................... 6
5. General safety instructions.................................................................................... 6
6. Function ............................................................................................................... 7
6.1. Limit-range monitoring ....................................................................................................................7
6.2. Switching states .............................................................................................................................7
7. Mounting .............................................................................................................. 8
8. Electrical connection ............................................................................................ 9
8.1. Notes about ...........................................................................................................................9
8.2. Setting the AS-Interface address ....................................................................................................10
8.3. Conguration in the AS-Interface safety monitor ..............................................................................10
8.3.1. Dual-channel dependent ....................................................................................................10
8.3.2. Dual-channel positively driven ............................................................................................10
8.4. AS-Interface status messages ........................................................................................................ 10
8.5. Connector assignment of safety switch CES-I-AS2A-M-C04 ...............................................................10
9. Setup ................................................................................................................. 11
9.1. LED indicators ..............................................................................................................................11
9.2. Initial setup ...................................................................................................................................11
9.3. Functional check ...........................................................................................................................11
9.3.1. Electrical function test ......................................................................................................11
10. System status table ............................................................................................ 12
11. Technical data .................................................................................................... 13
11.1. Technical data of safety switch CES-I-AS2A-M-C04 ...........................................................................13
11.1.1. Typical system times ........................................................................................................14
11.1.2. Dimension drawing of safety switch CES-I-AS2A-M-C04 .......................................................14
11.2. Technical data of actuator CES-A-BBN-C04 ......................................................................................15
11.2.1. Dimension drawing ...........................................................................................................15
11.2.2. Switching distances .........................................................................................................15
11.2.3. Typical operating distance in approach direction A .............................................................. 16
11.3. Technical data of actuator CES-A-BDN-06 ........................................................................................17
11.3.1. Dimension drawing ...........................................................................................................17
11.3.2. Switching distances .........................................................................................................17
2
(translation of the original operating instructions) 2120545-05-08/18
Page 3
Operating Instructions
Non-Contact Safety Switch CES-I-AS2A-M-C04
12. Ordering information and accessories ................................................................. 18
13. Inspection and service ........................................................................................ 18
14. Service .............................................................................................................. 18
15. Declaration of conformity ................................................................................... 19
2120545-05-08/18 (translation of the original operating instructions)
EN
3
Page 4
Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04
1. About this document
1.1. Scope
These operating instructions are valid for all CES-I-AS2A-M-C04. These operating instructions, the document “Safety infor­mation and maintenance” and any enclosed data sheet form the complete user information for your device.
1.2. Target group
Design engineers and installation planners for safety devices on machines, as well as setup and servicing staff possessing special expertise in handling safety components.
1.3. Key to symbols
Symbol/depiction Meaning
Printed document
www
DANGER
WARNING
Document is available for download at www.euchner.com
Document on CD
Safety precautions
Danger of death or severe injuries Warning about possible injuries Caution slight injuries possible
CAUTION
Notice about possible device damage
NOTICE
Important!
Tip Useful information
Important information
1.4. Supplementary documents
The overall documentation for this device consists of the following documents:
Document title (document number)
Safety information and maintenance CES-I-AS2A (2120543)
Operating instructions (2120545)
Possibly enclosed data sheet
Contents
Basic information for safe setup and service
(this document)
Item-specic information about deviations or additions
Important!
Always read all documents to gain a complete overview of safe installation, setup and use of the device. The documents can be downloaded from www.euchner.com. For this purpose enter the doc. no. in the search box.
4
(translation of the original operating instructions) 2120545-05-08/18
Page 5
Operating Instructions
Non-Contact Safety Switch CES-I-AS2A-M-C04
2. Correct use
The series CES-I-AS Coded Electronic Safety switches from EUCHNER are operated as slaves on the safety bus AS-Interface Safety at Work and function as interlocking devices with low coding level without guard locking (type4). The device meets
the requirements according to ENIEC60947-5-3.
In combination with a movable safety guard and the machine control, this safety component prevents dangerous machine functions from occurring while the safety guard is open. A stop command is triggered if the safety guard is opened during the dangerous machine function.
This means:
Ì Starting commands that cause a dangerous machine function must become active only when the safety guard is closed. Ì Opening the safety guard triggers a stop command. Ì Closing a safety guard must not cause automatic starting of a dangerous machine function. A separate start command
must be issued. For exceptions, refer to ENISO12100 or relevant C-standards.
Before safety switches are used, a risk assessment must be performed on the machine, e.g., in accordance with:
Ì EN ISO 13849-1, Safety of machinery – Safety-related parts of control systems – Part 1: General principles for design Ì EN ISO 12100, Safety of machinery – General principles for design – Risk assessment and risk reduction Ì IEC 62061, Safety of machinery – Functional safety of safety-related electrical, electronic and programmable electronic
control systems.
Correct use includes observing the relevant requirements for installation and operation, e.g.
Ì EN ISO 13849-1, Safety of machinery – Safety-related parts of control systems – Part 1: General principles for design Ì ENISO14119, Safety of machinery – Interlocking devices associated with guards – Principles for design and selection Ì EN 60204-1, Safety of machinery. Electrical equipment of machines. General requirements.
The safety switch must be used only in conjunction with the designated CES actuators from EUCHNER. On the use of different actuators, EUCHNER provides no warranty for safe function.
Important!
Ì The user is responsible for the proper integration of the device into a safe overall system. For this
purpose, the overall system must be validated, e.g. in accordance with ENISO13849-2.
Ì In the estimation of the PL for the overall system, a maximum value of 100 years can be assumed
for the MTTFD according to the limit value in EN ISO 13849-1:2008, section 4.5.2. This corre­sponds to a minimum value for the PFHD of 2.47 x 10-8/h.
Ì Correct use requires observing the permissible operating parameters (see Technical data). Ì If a product data sheet is included with the product, the information on the data sheet applies.
Ì It is only allowed to use components that are permissible in accordance with the table below.
Table 1: Possible combinations for CES components
Actuator
Safety switch
CES-A-BBN-C04-115271 CES-A-BDN-06-104730
CES-I-AS2A-M-C04-...
Key to symbols Combination possible
2120545-05-08/18 (translation of the original operating instructions)
EN
5
Page 6
Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04
3. Description of the safety function
Devices from this series feature the following safety functions:
Monitoring of the position of the safety guard (interlocking device according to ENISO14119)
Ì Safety function:
- When the safety guard is open, no valid code sequence is sent (see chapter 6.2. Switching states on page 7).
Ì Safety characteristics: category, Performance Level, PFH
(see chapter 11. Technical data on page 13).
D
4. Exclusion of liability and warranty
In case of failure to comply with the conditions for correct use stated above, or if the safety instructions are not followed, or if any servicing is not performed as required, liability will be excluded and the warranty void.
5. General safety instructions
Safety switches fulll personal protection functions. Incorrect installation or tampering can lead to fatal injuries to personnel.
Check the safe function of the safety guard particularly
Ì after any setup work Ì after the replacement of a system component Ì after an extended period without use Ì after every fault
Independent of these checks, the safe function of the safety guard should be checked at suitable intervals as part of the maintenance schedule.
WARNING
Danger to life due to improper installation or due to bypassing (tampering). Safety components perform a personal protection function.
Ì Safety components must not be bypassed, turned away, removed or otherwise rendered ineffec-
tive. On this topic pay attention in particular to the measures for reducing the possibility of bypass­ing according to ENISO14119:2013, section 7.
Ì The switching operation must be triggered only by actuators designated for this purpose. Ì Mounting, electrical connection and setup only by authorized personnel possessing the following
knowledge:
- specialist knowledge in handling safety components
- knowledge about the applicable EMC regulations
- knowledge about the applicable regulations on occupational safety and accident prevention.
Important!
Prior to use, read the operating instructions and keep these in a safe place. Ensure the operating instructions are always available during mounting, setup and servicing. EUCHNER cannot provide any warranty in relation to the readability of the CD for the storage period required. For this reason you should archive a printed copy of the operating instructions. You can download the operating instruc­tions from www.euchner.com.
6
(translation of the original operating instructions) 2120545-05-08/18
Page 7
Operating Instructions
Non-Contact Safety Switch CES-I-AS2A-M-C04
6. Function
The safety switch monitors the position of movable safety guards. When the actuator is moved to/removed from the oper­ating distance, a corresponding bit sequence is sent via the AS-Interface bus.
The system consists of the following components: coded actuator (transponder) and switch.
Whether the device learns the complete actuator code (unicode) or not (multicode) depends on the respective version.
Devices with unicode evaluation: The actuator must be assigned to the safety switch by a teach-in operation so that it is detected by the system. This unambiguous assignment ensures a particularly high level of protection against tampering. The system thus possesses a high coding level.
Devices with multicode evaluation: Unlike systems with unique code detection, on multicode devices a specic code is not requested but instead it is only checked whether the actuator is of a type that can be detected by the system (multicode detection). There is no exact comparison of the actuator code with the taught-in code in the safety switch (unique code detection). The system possesses a low coding level.
When the safety guard is closed, the actuator is moved towards the safety switch. When the switch-on distance is reached, power is supplied to the actuator by the switch and data is transferred.
When the safety guard is closed and the code is permissible, each CES-I-AS transmits a switch-specic, unique safety code sequence with 8x4 bits via the AS-Interface bus.
The zero sequence is transmitted via the AS-Interface bus when the safety guard is opened.
In the event of a fault in the safety switch, the zero sequence is sent and the DIA LED illuminates red. The occurrence of faults is detected at the latest on the next demand to close the safety outputs (e.g. on starting).
6.1. Limit-range monitoring
If the safety door with the actuator should settle over time, the actuator can drift out of the read head operating distance. The device recognizes this situation and indicates that the actuator is in the limit range by ashing the STATE LED. This allows the safety door to be readjusted in time. Also see chapter 10. System status table on page 12.
6.2. Switching states
The detailed switching states for your switch can be found in the system status table. All safety outputs, monitoring outputs and display LEDs are described there.
(actuator in the operating distance and permissi-
Safety guard closed
ble code detected)
(actuator not in the operating distance)
Safety guard open
Programming State D0, D1 D2, D3 Monitor diagnosis
Dual-channel
dependent
Synchronization time
≥100ms /
Dual-channel
positively driven
Safety guard closed Code sequence
Intermediate state during opening or closing of the
safety guard.
Switch S1 (internal) open
Intermediate state during opening or closing of the
safety guard.
Switch S2 (internal) open
Safety guard open 00 00 Red
Address 0 or communication disrupted Gray
Half-se­quence
00
00
Half-se­quence
If start-up test selected:
Yellow ashing on start-up
During opening: Yellow ashing
During closing: Red
After expiration of the synchronization time:
Yellow ashing
2120545-05-08/18 (translation of the original operating instructions)
Green
EN
7
Page 8
Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04
7. Mounting
CAUTION
Safety switches must not be bypassed (bridging of contacts), turned away, removed or otherwise rendered ineffective.
Ì Observe ENISO14119:2013, section 7, for information about reducing the possibilities for by-
passing an interlocking device.
NOTICE
Risk of damage to equipment and malfunctions as a result of incorrect installation.
Ì Safety switches and actuators must not be used as an end stop. Ì Observe ENISO14119:2013, sections 5.2 and 5.3, for information about fastening the safety
switch and the actuator.
Ì From the assured switch-off distance S Ì When mounting several safety switches, observe the stipulated minimum distance to avoid mutual
interference.
, the safety outputs are safely shut down.
ar
min. 140 mm
.
Ì If the actuator is installed ush, the switching distance changes as a function of the installation
depth and the safety guard material.
Ì Observe direction of arrow on the device (see gure below).
Permissible approach directions
A B
Note the following points:
C D
Ì Actuator and safety switch must be easily accessible for inspection and replacement. Ì Actuator and safety switch must be tted so that
- the front faces are at the minimum switch-on distance 0.8xSao or closer when the safety guard is closed. To avoid entering the area of possible side lobes, a minimum distance is to be maintained in case of a side approach direction. See chapter 11. Technical data, section Typical operating distance for the related actuator.
- when the safety guard is open up to the distance Sar (assured switch-off distance), a hazard is excluded.
- the actuator is positively mounted on the safety guard, e.g. by using the safety screws included.
- they cannot be removed or tampered with using simple means.
Ì Pay attention to the maximum tightening torque for the read head or safety switch and actuator mountings of 0.8Nm.
8
(translation of the original operating instructions) 2120545-05-08/18
Page 9
8. Electrical connection
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Ì Power devices which are a powerful source of interference must be installed in a separate location
away from the input and output circuits for signal processing. The cable routing for safety circuits should be as far away as possible from the cables of the power circuits.
Ì To avoid EMC interference, the physical environmental and operating conditions at the in-
stallation site of the device must comply with the requirements according to the standard EN60204-1:2006, section 4.4.2 (EMC).
Ì Please pay attention to any interference elds in case of devices such as frequency converters or
induction heating systems. Observe the EMC instructions in the manuals from the respective man­ufacturer.
Important!
If the device does not appear to function when operating voltage is applied (e.g. green STATE LED does not ash), the safety switch must be returned unopened to the manufacturer.
Operating Instructions
Non-Contact Safety Switch CES-I-AS2A-M-C04
8.1. Notes about
Important!
Ì For use and operation as per the requirements
Ì For use and applications as per the requirements
1) Note on the scope of the UL approval: Only for applications as per NFPA79 (Industrial Machinery). The devices have been tested as per the requirements of UL508 (protection against electric shock and re).
1)
, a power supply with the feature “for use in
class 2 circuits” must be used.
Alternative solutions must comply with the following requirements:
Ì Electrically isolated power supply unit in combination with fuse as per UL248. This fuse should be
designed for max. 3.3A and should be integrated into the 30VDC voltage section.
1)
, a connection cable listed under UL cate-
gory code CYJV must be used.
2120545-05-08/18 (translation of the original operating instructions)
EN
9
Page 10
Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04
8.2. Setting the AS-Interface address
The address can be set prior to or after assembly.
The AS-Interface address of the safety switch is set using an AS-Interface programming device. Addresses 1 to 31 are valid.
The unit is programmed by connecting the programming device to the M8 plug connector of the safety switch with a pro­gramming cable.
The AS-Interface address can also be set directly on the AS-Interface bus with a master.
Default setting on delivery is address 0 (the AS-Interface LED illuminates red).
8.3. Conguration in the AS-Interface safety monitor
(see operating instructions for the AS-Interface safety monitor)
8.3.1. Dual-channel dependent
The safety switch is congured in the AS-Interface safety monitor with the AS-Interface address set as follows:
Ì Dual-channel dependent Ì With or without start-up test Ì Synchronization time 100 ms
8.3.2. Dual-channel positively driven
The safety switch is congured in the AS-Interface safety monitor with the AS-Interface address set as follows:
Ì Dual-channel positively driven Ì With or without start-up test
8.4. AS-Interface status messages
A dual LED on the M8 plug connector (red/green) depicts the colors red and green. The following table provides assistance with troubleshooting.
State of ASI LED Explanation
green Normal operation
No data exchange between master and slave
red
red
red/green
Cause:
- Master in STOP mode
- Slave not in LPS
- Slave with wrong IO/ID
No data exchange between master and slave Cause: slave address = 0
Device fault in the slave. Contact EUCHNER.
8.5. Connector assignment of safety switch CES-I-AS2A-M-C04
View of
safety switch plug connector
1 AS-Interface + 3 AS-Interface ­4 Not used
4
1
3
Figure 1: Terminal assignment, AS-Interface M8 plug connector
10
(translation of the original operating instructions) 2120545-05-08/18
Page 11
Operating Instructions
Non-Contact Safety Switch CES-I-AS2A-M-C04
9. Setup
9.1. LED indicators
You will nd a detailed description of the signal functions in chapter 10. System status table on page 12.
LED Color
STATE green
DIA red
9.2. Initial setup
1. Apply operating voltage to the safety switch.
¨ The red LED ashes briey
A self-test is performed during this time. After this, the green LED ashes cyclically one time and signals that it is in standby state.
LEDs
2. Move actuator to the read head (observe distance < Sao).
¨ The green LED illuminates continuously and indicates the detection of the actuator.
If the green LED is ashing quickly, the actuator is in the limit range. In this case the safety guard must be re-adjusted such that the actuator is completely in the read area.
9.3. Functional check
WARNING
Danger of fatal injury as a result of faults in installation and functional check.
Ì Before carrying out the functional check, make sure that there are no persons in the danger area. Ì Observe the valid accident prevention regulations.
9.3.1. Electrical function test
After installation and any fault, the safety function must be fully checked. Proceed as follows:
1. Switch on operating voltage.
¨ The machine must not start automatically.
¨ The safety switch carries out a self-test. The green STATE LED then ashes at regular intervals.
2. Close all safety guards.
¨ The machine must not start automatically.
¨ The green STATE LED illuminates continuously.
3. Enable operation in the control system.
4. Open the safety guard.
Ì The machine must switch off and it must not be possible to start it as long as the safety guard is open. Ì The green STATE LED ashes at regular intervals.
Repeat steps 2-4 for each safety guard.
2120545-05-08/18 (translation of the original operating instructions)
EN
11
Page 12
Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04
10. System status table
CES LED indicator
Output
Operating mode
Normal operation
Fault display
Key to symbols
Actuator/door po-
sition
closed Normal operation, door closed
closed
open 1 x Normal operation, door open
closed 3 x Defective actuator (e.g. fault in code or code not readable)
X Internal fault (e.g. component faulty, data error)
STATE (green)
ashing
quickly
10 Hz (8 s)
3 x
X Any state
State
DIA (red)
Normal operation, door closed, actuator in limit range ¨ Re-adjust door
LED not illuminated
LED illuminated
LED ashes for 8 seconds at 10 Hz
LED ashes three times, and this is then repeated
After the cause has been remedied, faults can generally be reset by opening and closing the safety guard. If the fault is still displayed afterward, briey interrupt the power supply. Please contact the manufacturer if the fault could not be reset after restarting.
Important!
If you do not nd the displayed device status in the system status table, this indicates an internal device fault. In this case, you should contact the manufacturer.
12
(translation of the original operating instructions) 2120545-05-08/18
Page 13
Operating Instructions
Non-Contact Safety Switch CES-I-AS2A-M-C04
11. Technical data
NOTICE
If a data sheet is included with the product, the information on the data sheet applies.
11.1. Technical data of safety switch CES-I-AS2A-M-C04
Parameter Value Unit
min. typ. max. Housing material Plastic PBT Rubber-support material NBR 80 ±5 Shore Fixing screw tightening torque - - 0.8 Nm Dimensions 42 x 25 x 18 mm Weight (without connection cable) 0.04 kg Ambient temperature at UB = DC 30 V -25 - +65 Storage temperature -25 - +70 Degree of protection IP67 Safety class III Degree of contamination 3 Installation position Any Installation method Non-ush Connection M8 plug connector, 3-pin For the approval according to UL the following applies Operation with UL-class 2 power supply only Rated insulation voltage U Rated impulse withstand voltage U Resilience to vibration In acc. with EN IEC 60947-5-2 Switching frequency - - 1 Hz Ready delay - 0.5 - s Risk time - - 260 ms Switch-on time 300 ms
AS-Interface data EA code: 0 ID code: B AS-i operating voltage 19 - 31.6 DC V Total current consumption - - 50 mA Valid AS-Interface addresses 1 - 31 AS-Interface inputs Acc. to AS-Interface Safety at Work Door monitoring contact D0 - D3
Reliability values according to EN ISO 13849-1
Category 4 Performance Level PL e PFH
D
Mission time 20 years
i
imp
- - 300 V
- - 1.5 kV
-9
4.5 x 10
/ h
°C
2120545-05-08/18 (translation of the original operating instructions)
EN
13
Page 14
Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04
11.1.1. Typical system times
Please refer to the technical data for the exact values.
Ready delay: After switching on, the unit carries out a self-test. The system is ready for operation only after this time.
Switch-on time: The max. reaction time ton is the time from the moment when the actuator is in the operating distance to
sending the code sequence.
Risk time according to EN 60947-5-3: If an actuator moves outside the operating distance, the zero sequence is sent via the AS-Interface bus.
11.1.2. Dimension drawing of safety switch CES-I-AS2A-M-C04
Active face
25
ASi green/red
8
LED status indication
4,8
Rubber support (included)
14,5
15,5
10,6
M8
LED status indication
42
With rubber support
4,1
13
32
Active face
14
(translation of the original operating instructions) 2120545-05-08/18
Page 15
Non-Contact Safety Switch CES-I-AS2A-M-C04
14
11.2. Technical data of actuator CES-A-BBN-C04
Operating Instructions
Parameter
Housing material Plastic PBT Rubber-support material NBR 80 ±5 Shore Dimensions 42 x 25 x 18 mm Weight 0.03 kg Ambient temperature - 40 - + 65 °C Degree of protection IP67/IP69K Installation position Active face opposite read head Power supply Inductive via read head
min. typ. max.
Value
11.2.1. Dimension drawing
Active face
6
4,5
42
32
25
18
14,5
15,5
With rubber support
Unit
NOTICE
Ì 2 safety screws M4x20 included. Ì Rubber support included.
11.2.2. Switching distances
Operating distance for center offset m = 0
Approach direction Parameter Value Unit
A B min. typ. max.
1) On approach in Z direction
Approach direction Parameter Value Unit
C D min. typ. max.
Rubber support
Switch-on distance - 15 -
Assured switch-on distance s
Switching hysteresis
Assured switch-off distance s
- in x/z direction
- in y direction
Switch-on distance - 11 -
Assured switch-on distance sao
Switching hysteresis
Assured switch-off distance s
- in x/z direction
- in y direction
1)
1)
1)
ao
ar
1)
ar
10 - -
1 2 -
-
-
6 - -
1 2 -
-
-
-
-
-
-
mm
40 60
EN
mm
40 60
1) On approach in x direction
2120545-05-08/18 (translation of the original operating instructions)
15
Page 16
Operating Instructions
Y
Z
Non-Contact Safety Switch CES-I-AS2A-M-C04
11.2.3. Typical operating distance in approach direction A
(only in combination with actuator CES-A-BBN-C04)
40
35
30
25
-30
-25
15
20
X
20
15
10
5
-5
5
5
10
-5
-10
-15
-20
-25
-30
-35
-40
-20
-15
-10
10
15
20
25
30
For a side approach direction (y direction) for the actuator and safety switch, a
minimum distance of s = 6 mm must be maintained so that the operating dis-
tance of the side lobes is not entered.
Figure 2: Typical operating distance
16
(translation of the original operating instructions) 2120545-05-08/18
Page 17
Operating Instructions
Non-Contact Safety Switch CES-I-AS2A-M-C04
11.3. Technical data of actuator CES-A-BDN-06
Parameter Value Unit
min. typ. max.
Housing material Macromelt PA-based plastic Dimensions 26 x 6 mm
Weight
Ambient temperature - 40 - + 70 °C
Degree of protection acc. to ENIEC60529 IP67 / IP69K
Installation position Active face opposite read head
Power supply Inductive via read head
1) With ush installation
11.3.1. Dimension drawing
Installation options
6
Operating
distance
0.005
1)
Approach
direction
kg
* min. 30 Ø
+
0,1
6,1
0
+
0,5
26
30
*
0
30
*
* Metal-free zone
CAUTION
Ì Do not mount at temperatures below 0 °C. Ì The actuator can be damaged during mounting.
11.3.2. Switching distances
Operating distance for center offset m = 0
Approach direction Parameter Value Unit
A min. typ. max.
Switch-on distance - 19 -
Assured switch-on distance s
Switching hysteresis
Assured switch-off distance s
- in x/z direction
- in y direction
1) The values apply to surface installation of the actuator
C
A
1)
ao
1)
ar
14 - -
- 2 -
-
-
-
-
mm
40 60
Approach direction Parameter Value Unit
C min. typ. max.
Switch-on distance - 15 -
Assured switch-on distance sao
Switching hysteresis
1)
Assured switch-off distance s
- in x/z direction
- in y direction
1) The values apply to surface installation of the actuator
2120545-05-08/18 (translation of the original operating instructions)
1)
ar
10 - -
- 2 -
-
-
-
-
40 60
mm
EN
17
Page 18
Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04
12. Ordering information and accessories
Tip!
Suitable accessories, e.g. cables or assembly material, can be found at www.euchner.com. To order, enter the order number of your item in the search box and open the item view. Accessories that can be combined with the item are listed under “Accessories”.
13. Inspection and service
WARNING
Loss of the safety function because of damage to the system.
Ì In case of damage, the entire device must be replaced. Ì Only accessories or spare parts that can be ordered from EUCHNER may be replaced.
Regular inspection of the following is necessary to ensure trouble-free long-term operation:
Ì Check the switching function (see chapter 9.3. Functional check on page 11) Ì Check the secure fastening of the devices and the connections Ì Check for soiling
No servicing is required; repairs to the device are only allowed to be made by the manufacturer.
NOTICE
The year of manufacture can be seen in the lower right corner of the type label. The current version number in the format (VX.X.X) can also be found on the device.
14. Service
If service support is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen
Service telephone:
+49 711 7597-500
E-mail:
support@euchner.de
Internet:
www.euchner.com
18
(translation of the original operating instructions) 2120545-05-08/18
Page 19
15. Declaration of conformity
Operating Instructions
Non-Contact Safety Switch CES-I-AS2A-M-C04
2120545-05-08/18 (translation of the original operating instructions)
EN
19
Page 20
Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04
20
(translation of the original operating instructions) 2120545-05-08/18
Page 21
Operating Instructions
Non-Contact Safety Switch CES-I-AS2A-M-C04
2120545-05-08/18 (translation of the original operating instructions)
EN
21
Page 22
Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04
22
(translation of the original operating instructions) 2120545-05-08/18
Page 23
Operating Instructions
Non-Contact Safety Switch CES-I-AS2A-M-C04
2120545-05-08/18 (translation of the original operating instructions)
EN
23
Page 24
Euchner GmbH + Co. KG Kohlhammerstraße 16 70771 Leinfelden-Echterdingen info@euchner.de www.euchner.com
Edition: 2120545-05-08/18 Title: Operating Instructions Non-Contact Safety Switch CES-I-AS2A-M-C04 (translation of the original operating instructions) Copyright: © EUCHNER GmbH + Co. KG, 08/2018
Subject to technical modications; no responsibility is accept­ed for the accuracy of this information.
Loading...