EUCHNER CES-I-AR-M-C04 User Manual

Operating Instructions
Non-Contact Safety Switch
CES-I-AR-M-C04 (Multicode)
More than safety.
Operating Instructions Safety Switch CES-I-AR-M-C04
Contents
About this document 3
Correct use 3
Possible combinations for CES components 4
Exclusion of liability and warranty 4
General safety instructions 5
Function 6
Mounting 8
Electrical connection 9
Safety in case of faults 10 Fuse protection for power supply 10 Requirements for connection cables 10 Maximum cable lengths 11 Connector assignment, safety switch CES-I-AR 13 Connection of a single CES-I-AR 14 Connection of several CES-I-AR in a switch chain 16 Notes on operation with safe control systems 18
Setup 20
LED indicators 20 Initial setup 20 Functional check 20
System status table 21
Technical data 22
Technical data for safety switch CES-I-AR-M-C04 22 Technical data for actuator CES-A-BBN-C04 26 Technical data for actuator CES-A-BDN-06 28
Ordering information and accessories 29
Inspection and service 29
Service 30
Declaration of conformity 31
2
Operating Instructions Safety Switch CES-I-AR-M-C04
This document is valid for all safety switches CES-I-AR-M-C04.

Correct use

The Coded Electronic Safety switches series CES are safety devices for monitor­ing movable safety guards.
In combination with a separating safety guard and the machine control, this safety component prevents dangerous machine movements from occurring while the safety guard is open. A stop command is triggered if the safety guard is opened during the dangerous machine function.
Before safety switches are used, a risk assessment must be performed on the machine, e.g. in accordance with:
Ì EN ISO 13849-1, Safety of machinery. Safety related parts of control systems.
General principles for design
Ì EN ISO 12100, Safety of machinery - General principles for design - Risk as-
sessment and risk reduction
Ì IEC 62061, Safety of machinery - Functional safety of safety-related electrical,
electronic and programmable electronic control systems
Correct use includes compliance with the relevant requirements for installation and operation, for example
Ì EN ISO 13849-1, Safety of machinery. Safety related parts of control systems.
General principles for design
Ì EN 1088, Safety of machinery. Interlocking devices associated with guards.
Principles for design and selection
Ì EN 60204-1, Safety of machinery. Electrical equipment of machines. General
requirements
Ì EN 60947-5-3, Specification for low-voltage switchgear and controlgear. Con-
trol circuit devices and switching elements. Requirements for proximity devices with defined behavior under fault conditions
The safety switch must be used only in conjunction with the designated CES ac­tuators from EUCHNER. On the use of different actuators, EUCHNER provides no warranty for safe function.
Connection of several devices in an AR switch chain is permitted only using devices intended for series connection in an AR switch chain. Check this in the instructions of the device in question.
A maximum of 20 safety switches are allowed to be operated in a switch chain.
Important!
Ì The user is responsible for the integration of the device into a safe overall
system. For this purpose, the overall system must be validated, e.g. in ac­cordance with EN ISO 13849-2.
Ì Correct use requires observing the permissible operating parameters (see
Technical data).
Ì If a product data sheet is included with the product, the information on the
data sheet applies in case of discrepancies with the operating instructions.
3
Operating Instructions Safety Switch CES-I-AR-M-C04
Important!
Ì In the estimation of the PL for the overall system, a maximum value of 100
years can be assumed for the MTTFd according to the limit value in EN ISO 13849-1:2008, section 4.5.2. This corresponds to a minimum value for the PFHd of 2.47x10-8/h.
Ì When up to 11 devices are connected in series, these limit values can be
assumed for the entire switch chain as a subsystem. As a subsystem, this switch chain achieves PL e.
Ì In the case of series connection of more than 11 devices, the PFH
calculated according to one of the stated methods in EN ISO 13849-1:2008, section 4.5.1.
Ì If the simplified method according to section 6.3 of EN ISO 13849:2008-12
is used for validation, the Performance Level (PL) might be reduced when more than 11 devices are connected in series.
Ì It is only allowed to use components that are permissible in accordance with
the table below.
can be
d

Possible combinations for CES components

Actuator
CES-I-AR-M-C04-...
Key to symbols
Safety switch
Combination possible
CES-A-BBN-C04-115271 CES-A-BDN-06-104730
Note!
The devices can be operated on an AR evaluation unit. Please refer to the operating instructions for the relevant AR evaluation unit for more information.

Exclusion of liability and warranty

In case of failure to comply with the conditions for correct use stated above, or if the safety instructions are not followed, or if any servicing is not performed as required, liability will be excluded and the warranty void.
4
Operating Instructions Safety Switch CES-I-AR-M-C04

General safety instructions

Safety switches fulfill personal protection functions. Incorrect installation or tamper­ing can lead to fatal injuries to personnel.
Check the safe function of the safety guard particularly
Ì after any setup work Ì after the replacement of a CES component Ì after an extended period without use Ì after every fault
Independent of these checks, the safe function of the safety guard should be checked at suitable intervals as part of the maintenance schedule.
Warning!
Loss of safety function in the event of incorrect connection or incorrect use.
Ì Safety switches must not be bypassed (bridging of contacts), turned away,
removed or otherwise rendered ineffective. On this topic pay attention in particular to the measures for reducing the pos­sibility of bypassing from EN 1088:1995+A2:2008, section 5.7.
Important!
The device is only allowed to be installed and placed in operation by authorized personnel
Ì who are familiar with the correct handling of safety components Ì who are familiar with the applicable EMC regulations Ì who are familiar with the applicable regulations on health and safety and ac-
cident prevention
Ì who have read and understood the operating instructions
Prior to use, read the operating instructions and keep these in a safe place. Ensure that the operating instructions are always available during mounting, setup and servicing. EUCHNER cannot provide any warranty in relation to the readability of the CD for the storage period required. For this reason you should archive a printed copy of the operating instructions. You can download the operating instructions from www.EUCHNER.de.
5
Operating Instructions Safety Switch CES-I-AR-M-C04

Function

The device complies with the following safety requirements:
Ì Safety category 4, PLe according to EN ISO 13849-1 Ì Redundant design of the circuit in the unit with self-monitoring Ì This means that the safety system still functions even if an internal component
fails
Ì The switch state of the semiconductor outputs is continuously monitored inter-
nally
Ì Short circuit detection at the safety outputs by pulsed signals
The following switch-on condition applies for the safety outputs FO1A and FO1B (see also System status table and section Typical system times):
Ì Safety guard closed Ì Both safety inputs FI1A and FI1B must be switched on.
The CES system consists of the following components: coded actuator (transpon­der) and switch.
Every EUCHNER actuator supplied has an electronic coding (unique coding) that is read by the read head. Only if a correct coding is detected does the system accept the actuator. The code in an actuator cannot be reprogrammed.
Unlike systems with unique code detection, on the CES-I-AP-M-C04 a specific code is not polled but instead it is only checked whether the actuator is of a type that can be detected by the system (multicode detection). There is no exact comparison of the actuator code with the code defined in the safety switch (unique code detection).
The safety switch is fastened to the fixed part of the safety guard.
The actuator attached to the movable part of the safety guard is moved towards the read head fitted in the safety switch by closing the door. When the switch-on distance is reached, power is supplied to the actuator by the read head by induc­tion and data can be transferred.
If a permissible code is detected, the safety outputs are released. Independent of the safety outputs, monitoring output OD switches on as soon as the actuator is in the operating distance.
Due to the combination of dynamic polling of the actuator and the redundant, diverse design of the safety electronics with the two feedback safety outputs, the safety switch will enter the safe state with every detectable fault.
When the safety guard is opened, the safety outputs switch off the safety circuit and the monitoring output OD is switched off. The state of the safety outputs is monitored internally by two microprocessors.
If faults are detected, the safety circuit is switched off and the DIA LED illuminates. In case of devices with a monitoring output OI, the output is switched on.
The safety switch has a redundant circuit design with self-monitoring. This means that the safety system is still effective even if a component fails.
6
Operating Instructions Safety Switch CES-I-AR-M-C04
The system is designed so that failures will not result in the loss of the safety func­tion. The occurrence of failures is detected by cyclic self-monitoring at the latest on the next demand to switch the safety outputs (e.g. on starting).
If the safety door with the actuator should settle over time, the actuator can drift out of the switch operating distance. The device recognizes this situation and indicates that the actuator is in the limit range. This allows the safety door to be readjusted in time.
7
Operating Instructions Safety Switch CES-I-AR-M-C04

Mounting

Caution!
Risk of damage to equipment as a result of incorrect installation. Safety switches must not be used as a mechanical end stop.
Ì Fit an additional end stop for the movable part of the safety guard.
Important!
Ì From the assured switch-off distance S
down.
, the safety outputs are safely shut
ar
Ì When mounting several safety switches and actuators, observe the stipu-
lated minimum distance to avoid mutual interference.
Installation options
min. 140 mm
Ì The operating distance changes during the mounting of the actuator as a
function of the material used for the safety guard. Observe direction of arrow on the device (see figure below).
Permissible approach directions
A B
C D
Note the following points:
Ì Actuator and safety switch must be easily accessible for inspection and re-
placement.
Ì The switching operation must only be triggered by the specific actuator desig-
nated for this purpose. For permissible combinations please see the table of possible combinations on page 4.
Ì Actuator and safety switch must be fitted so that
Ì the front faces are at the minimum switch-on distance 0.8 x S
when the safety guard is closed (see section Operating distances). A mini­mum distance dependent on the actuator and the approach direction must be maintained for a side approach direction:
- for CES-A-BBN-C04-115271 6 mm (A + B) / 2 mm (C + D)
- for CES-A-BDN-06-104730 10 mm
Ì when the safety guard is open up to the distance S
tance), a hazard is excluded.
(assured switch-off dis-
ar
or closer
ao
Ì the actuator is positively mounted on the safety guard, e.g. by using the
safety screws included.
Ì Pay attention to the maximum tightening torque of 0.8 Nm for the safety
switch and actuator mountings.
8
Operating Instructions Safety Switch CES-I-AR-M-C04

Electrical connection

The following connection options are available:
Ì Separate operation Ì Series connection with Y-distributors from EUCHNER (only with M12 plug con-
nector)
Ì Series connection, e.g. with wiring in the control cabinet Ì Operation on an AR evaluation unit.
Warning!
In case of an error, loss of the safety function through incorrect connection.
Ì To ensure safety, both safety outputs (FO1A and FO1B) must always be
evaluated.
Ì The monitoring output OD must not be used as a safety output. Ì Lay the connection cables with protection to prevent the risk of short cir-
cuits.
Caution!
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Ì Do not use a control system with pulsing or switch off the pulsing function in
your control system. The device generates its own clock signal on the output lines FO1A/FO1B. A downstream control system must tolerate these test pulses, which may last up to 1 ms. Depending on the inertia of the connected device (control system, relay, etc.), this can lead to short switching processes.
Ì The inputs on an evaluation unit connected must be positive-switching, as the
two outputs on the safety switch deliver a level of +24 V in the switched-on state.
Ì All the electrical connections must either be isolated from the mains supply
by a safety transformer according to IEC 61558-2-6 with limited output volt­age in the event of a fault, or by other equivalent isolation measures (PELV).
Ì For use and operation as per the requirements, a power supply with the
feature "for use in class 2 circuits" must be used. The same requirement ap­plies to the safety outputs. Alternative solutions must comply with the following requirements: a) Electrically isolated power supply unit with a max. open-circuit voltage of 30
V/DC and a limited current of max. 8 A.
b) Electrically isolated power supply unit in combination with fuse as per UL248.
This fuse should be designed for max. 3.3 A and should be integrated into the 30 V/DC voltage section.
Ì For use and operation as per the requirements*, a connection cable
listed under the UL category code CYJV2 must be used. The connection cables from EUCHNER meet these requirements. The same requirement ap­plies to the safety outputs.
Ì All electrical outputs must have an adequate protective circuit for inductive
loads. The outputs must be protected with a free-wheeling diode for this pur­pose. RC interference suppression units must not be used.
Ì Power devices which are a powerful source of interference must be installed
in a separate location away from the input and output circuits for signal pro­cessing. The cable routing for safety circuits should be as far away as pos­sible from the cables of the power circuits.
* Note on the scope of the UL approval: Only for applications as per NFPA 79 (Industrial Machinery) The devices have been tested as per the requirements of UL508 (protection against electric shock and fire).
9
Operating Instructions Safety Switch CES-I-AR-M-C04
Caution!
Ì In order to avoid EMC interference, the physical environmental and operating
conditions at the installation site of the device must comply with the require­ments according to the standard EN 60204-1:2006, section 4.4.2 (EMC).
Important!
If the device does not appear to function when operating voltage is applied (e.g. green STATE LED does not flash), the safety switch must be returned unopened to the manufacturer.

Safety in case of faults

Caution!
Ì The operating voltage U
is reverse polarity protected.
B
Ì The contacts FO1A/FO1B are short circuit-proof. Ì A short circuit between FO1A and FO1B is detected by the switch. Ì A short circuit in the cable can be excluded by laying the cable with protection.

Fuse protection for power supply

The power supply must be provided with fuse protection depending on the current required for the outputs. The following rules apply:
Max. current consumption of a switch I
I
= IUB + IOD + I
max
= Switch operating current (35 mA)
I
UB
= Monitoring output load current (max. 50 mA)
I
OD
I
FO1A+FO1B
= Load current of safety outputs FO1A + FO1B (2 x max. 200 mA)
FO1A+FO1B
max

Requirements for connection cables

Risk of damage to equipment or malfunctions as a result of incorrect connec­tion cables.
Ì Use connection components and connection cables from EUCHNER Ì On the usage of other connection components, the requirements in the fol-
lowing table apply. EUCHNER provides no warranty for safe function in case of failure to comply with these requirements.
Ì The connection cable must not be longer than 200 m in total.
Observe the following requirements with respect to the connection cables:
Parameter Value Unit
Conductor cross-section 0.14 ... 0.34 mm² R max. 150 W/km C max. 120 nF/km L max. 0.65 mH/km Recommended cable type LIYY 8x0.34 mm²
10
Operating Instructions Safety Switch CES-I-AR-M-C04

Maximum cable lengths

Switch chains are permitted up to a maximum overall cable length of 200 m taking into account the voltage drop as a result of the cable resistance (see table below with example data and case example).
l
=200 m
max
l
1
l
n
u
= 24 V -10%
min
i
SPS PLC
out
l
2
un = 24 V -20%
5 x 0,34 mm
oder
5 x 0,14 mm
n
Max. number of
switches
5
6
10
2
2
5 x 0,34 mm
2
5 x 0,34 mm
CES-I-AR # n CES-I-AR # n-1 CES-I-AR # 1
l1 (m)
I
(mA)
out
Possible output current per channel
FO1A/FO1B
10 70 140 25 50 110
50 35 80 100 25 50 200 13 25
10 60 120
25 50 90
50 35 70 100 20 50 200 13 25
10 35 70
25 30 60
50 25 50 100 15 35 200 10 20
Max. cable length from the last switch
to the control system with conductor
cross-section
0.14 mm² 0.34 mm²
2
Important!
The cables between the Y-distributors must have a conductor cross-section of
0.34 mm².
11
Operating Instructions Safety Switch CES-I-AR-M-C04
Determining cable lengths using the example table
Example: 6 switches are to be used in series. Cabling with a length of 40 m is routed from a safety relay in the control cabinet to the last switch (#6) (conduc­tor cross-section 0.34 mm²). Cables with a length of 20 m each are connected between the individual CES-I-AR safety switches.
l
= 140 m
max
l
= 5 x 20 m
2
Sicherheits­relais
Safety Relay
l1 = 40 m
i
= min. 75 mA
out
l
= 20 m
n
un = min. 19,2 V
CES-I-AR # 6
CES-I-AR # 5 CES-I-AR # 4 CES-I-AR # 3
CES-I-AR # 2 CES-I-AR # 1
Figure 1: Circuit example with six CES-I-AR
A safety relay is connected downstream which consumes 75 mA on each of the two safety inputs. This operates over the whole temperature range with a voltage of 19.2 V (corresponds to 24 V -20%).
All the relevant values can now be determined using the example table:
1. Select the corresponding section in the column n (max. number of switches). Here: 6 switches.
2. In column I
(possible output current per channel FO1A/FO1B), find a current
out
greater than or equal to 75 mA. Here: 100 mA.
¨ It is then possible to determine the maximum cable length from the last switch
(#6) to the control system from column l
. Here: a length of 50 m is permissible
1
with a conductor cross-section of 0.34 mm².
Result: The desired cable length l table. The overall length of the switch chain l
of 40 m is below the permitted value from the
1
of 140 m is less than the maximum
max
value of 200 m.
12
Operating Instructions Safety Switch CES-I-AR-M-C04

Connector assignment, safety switch CES-I-AR

RST
UB
0V
FI1A
FI1B
FO1A
FO1B
OD
8 2 7 6 1
7
8
1
3 4 5
View on the connection side of the safety switch
Coding lug
6
5
4
3
2
Figure 2: Connector assignment, safety switch CES-I-AR
Pin Designation Description Wire color
1 FI1B Enable input for channel 2 white 2 UB Power supply, DC 24 V brown 3 FO1A Safety output, channel 1 green 4 FO1B Safety output, channel 2 yellow 5 OD Monitoring output gray 6 FI1A Enable input for channel 1 pink 7 0V Ground, DC 0 V blue 8 RST Reset input red
13
Operating Instructions Safety Switch CES-I-AR-M-C04

Connection of a single CES-I-AR

If a single CES-I-AR is used, connect the switch as shown in Figure 3. The OD output can also be connected here to a control system as a monitoring output.
The switch can be reset via the RST input. To do this, a voltage of 24 V is applied to the RST input for at least 3 seconds. The RST input must be connected to 0 V if it is not used.
Important!
The subsystem CES-I-AR complies with PL e in accordance with EN 13849-1. To integrate the subsystem in a category 3 or 4 structure, it is necessary to monitor the downstream load (the feedback loop must be monitored). These examples show only an excerpt that is relevant for connection of the CES system. The example illustrated here does not show complete system planning. The user is responsible for safe integration in the overall system.
DC 24 V
A1
FI1B1
WH
UB2
BN
FO1A3
GN
FO1B4
YE
OD5
GY
FI1A6
PK
0V7
BU
RST8
RD
-K1
A2
Plug connector (8-pin)
CES-I-AR #1
GND
Figure 3: Connection example for a single CES-I-AR
-K2
13
14
A1
13
A2
14
M
-M1
14
Operating Instructions Safety Switch CES-I-AR-M-C04
Warning!
In case of an error, loss of the safety function through incorrect connection.
Ì To ensure safety, both safety outputs (FO1A and FO1B) must always be
evaluated. Single-channel use of the safety outputs leads to a loss of the category in accordance with EN ISO 13849-1.
DC 24 V
A1
FI1B1
WH
UB2
BN
FO1A3
GN
FO1B4
YE
OD5
GY
FI1A6
PK
0V7
BU
RST8
RD
-K1
A2
Plug connector (8-pin)
CES-I-AR #1
GND
Figure 4: Example of incorrect connection.
A1
-K2
A2
13
14
M M
-M1 -M2
13
14
15
Operating Instructions Safety Switch CES-I-AR-M-C04

Connection of several CES-I-AR in a switch chain

Important!
Ì An AR switch chain may contain a maximum of 20 safety switches. Ì In the estimation of the PL for the overall system, a maximum value of 100
years can be assumed for the MTTFd according to the limit value in EN ISO 13849-1:2008, section 4.5.2. This corresponds to a minimum value for the PFH
of 2.47x10-8/h.
d
Ì When up to 11 devices are connected in series, these limit values can be
assumed for the entire switch chain as a subsystem. As a subsystem, this switch chain achieves PL e.
Ì In the case of series connection of more than 11 devices, the PFH
calculated according to one of the stated methods in EN ISO 13849-1:2008, section 4.5.1.
Ì If the simplified method according to section 6.3 of EN ISO 13849:2008-12
is used for validation, the Performance Level (PL) might be reduced when more than 11 devices are connected in series.
The series connection is shown here based on the example of the version with plug connectors M12. The switches are connected one behind the other with the aid of pre-assembled connection cables and Y-distributors. If a safety door is opened or if a fault occurs on one of the switches, the system shuts down the machine. A higher level control system cannot, however, detect which safety door is open or on which switch a fault has occurred with this connection technology. A special AR evaluation unit is required for this purpose (see section Information on operation on an AR evaluation unit).
can be
d
The series connection can also be realized via additional terminals in a control cabinet.
The safety outputs are permanently assigned to the respective safety inputs of the downstream switch. FO1A must be routed to FI1A and FO1B to FI1B. If the connec­tions are interchanged (e.g. FO1A to FI1B), the unit will switch to the fault state)
Always use the RST input in series connections. All switches in a chain can be reset at the same time with this reset input. To do this, a voltage of 24 V must be applied to the RST input for at least 3 seconds. If input RST is not used in your application, it should be connected to 0 V.
Note the following on this aspect:
Ì A common signal must be used for all switches in the chain. This can be a
changeover switch or the output of a control system. A button is not suitable because Reset must always be connected to GND during operation (see switch S1 in Figure 5).
Ì Reset must always be performed simultaneously for all switches of the chain.
Information on operation on an AR evaluation unit
The devices can be operated on an AR evaluation unit. Please refer to the operating instructions for the relevant AR evaluation unit for more information.
16
Operating Instructions Safety Switch CES-I-AR-M-C04
V
0V
24
12
-S1
11 14
UBRSTFI1AFI1B 0V OD FO1A FO1B
Eval Unit
Safety Outputs
2861 7 5 3
SafetyInputs
UB
FI1A0VFI1B
RST
5
2
4
1
3
3 4
Safety Outputs
5 42861 7 5 3 4
FO1B FO1A OD 0V UB
Y-distributor
1 6 2 78 5 3 4
135
2
4
UB
FO1A0VFO1B
RST
RST FI1A FI1B
Y-distributor Y-distributor
Y-distributor
2861 7
Safety InputsSafety Inputs
Safety Outputs
UBRSTFI1AFI1B 0V OD FO1A FO1B UBRSTFI1AFI1B 0V OD FO1A FO1B
Read Head
Read Head
CES CESCES
Terminating plug
2
4
1UB
Terminating plug
FI1A
FI1B
Figure 5: Connection example for series connection with reset and changeover switch.
17
Read Head
Operating Instructions Safety Switch CES-I-AR-M-C04

Notes on operation with safe control systems

Please observe the following requirements for connection to safe control systems:
Ì Use a common power supply for the control system and the connected safety
switches.
Ì A pulsed power supply must not be used for UB. Tap the supply voltage direct-
ly from the power supply unit. If the supply voltage is connected to a terminal of a safe control system, this output must provide sufficient electrical current.
Ì Always connect inputs FI1A and FI1B directly to a power supply unit or to
outputs FO1A and FO1B of another EUCHNER AR device (series connection). Pulsed signals must not be present at inputs FI1A and FI1B.
Ì Outputs FO1A and FO1B can be connected to the safe inputs of a control sys-
tem. Prerequisite: The input must be suitable for pulsed safety signals (OSSD signals, e.g. from light curtains). The control system must tolerate clock puls­es on the input signals. This normally can be set up by parameter assignment in the control system. Observe the notes of the control system manufacturer. For the pulse duration of your safety switch, please refer to the section “Typi- cal system times” on page 23.
A detailed example of connecting and setting the parameters of the control system is available for many devices at www.euchner.de in the area Download » Applications » CES. The features of the respective device are dealt with there in greater detail.
18
Operating Instructions Safety Switch CES-I-AR-M-C04
24V0V
M
3
DC24V
2
PWR
Supply of
the control
DI4 DI0DO..M DO..P DO
4/8 F-DI4 F-DO
Digital
Output
-X1-X1
ET200
0V(UCM)
J
X2:5
UCM
X2:4
LED1
OB
4
OA
3
Safety Output
OUT
5
0V
7
UB
RST
8
IA
6
Safety Inputs
IB
1
Safety Output
Y-distributor Y-distributor
2861 7 5 3 4 2
CET
CES
Y-distributor
Terminating plug
Safety InputsSafety Inputs
Safety Output
7 5 3 4 X2:1
UBRSTFI1AFI1B 0V OD FO1A FO1B UBRSTFI1AFI1B 0V OD FO1A FO1B
2861 X2:3
Read Head
CES
Read Head
Figure 6: Connection example for mixed series connection (2 x CES and 1 x CET) on ET200
19
Operating Instructions Safety Switch CES-I-AR-M-C04

Setup

LED indicators

LED Color State Significance
illumi­nated
STATE
DIA
green
red
flashing
illumi­nated

Initial setup

1. Apply operating voltage to the safety switch.
¨ The green LED flashes quickly (approx. 5 Hz).
A self-test is performed during this time (8 s). After this, the green LED flash­es cyclically one time and signals that it is in standby state.
Normal operation: Door closed
- Power Up
- Door open
- Actuator in the limit range (refer to the status table for further signal functions)
- Internal electronics fault
- Fault at the inputs/outputs
Warning!
2. Move actuator to the read head (observe distance < S
).
ao
¨ The green LED illuminates continuously and indicates the detection of the
actuator. If the green LED is flashing quickly, the actuator is in the limit range. In this case the safety guard must be re-adjusted such that the actuator is com­pletely in the read area.

Functional check

After installation and any fault, the safety function must be fully checked. Proceed as follows:
Danger of fatal injury as a result of faults in installation and functional check.
Ì Before carrying out the functional check, make sure that there are no per-
sons in the danger area.
Ì Observe the valid accident prevention regulations.
1. Switch on operating voltage.
Ì The safety switch carries out a self-test.
The green STATE LED flashes for 8 s with 5 Hz. The STATE LED then flashes at regular intervals.
2. Close all safety guards.
Ì The machine must not start automatically. Ì The green STATE LED illuminates continuously.
3. Enable operation in the control system.
4. Open the safety guard.
Ì The machine must switch off and it must not be possible to start it as long as
the safety guard is open.
Ì The green STATE LED flashes at regular intervals.
Repeat steps 2-4 for each safety guard.
20
Operating Instructions Safety Switch CES-I-AR-M-C04

System status table

LED indicator,
output
Operating mode
Self-test
Normal operation
Fault display
Actuator/door posi-
tion
Safety outputs FO1A
and FO1B
X off off
closed on on
closed on on
closed off on
open off off
open off off
X off off
closed off off
X off off
X off off
Monitoring output OD
STATE (green)
5 Hz
(8 s)
flashing
quickly
1 x in­verse
1 x Normal operation, door open
2 x Normal operation, door open, no actuator taught
2 x
3 x Defective actuator (e.g. fault in code or code not readable)
4 x Output error (e.g. short circuits, loss of switching ability)
State
DIA (red)
Self-test after power up
Normal operation, door closed, safety outputs on the preceding device in the switch chain switched on
Normal operation, door closed, actuator in limit range ¨ Re-adjust door
Normal operation, door closed, safety outputs on the preceding device in the switch chain switched off
Input fault (e.g. missing test pulses, illogical switch state from previous switch in the switch chain)
Internal fault (e.g. component faulty, data error)
Key to symbols
Important!
LED not illuminated
LED illuminated
5 Hz (8 s)
3 x
X Any state
LED flashes for 8 seconds at 5 Hz
LED flashes three times, and this is then repeated
After the cause has been remedied, faults can generally be reset by opening and closing the door. If the fault is still displayed afterward, briefly interrupt the power supply. Please contact the manufacturer if the fault could not be reset after restarting.
If you do not find the displayed device status in the System status table, this indi­cates an internal device fault. In this case, you should contact the manufacturer.
21
Operating Instructions Safety Switch CES-I-AR-M-C04

Technical data

Note!
If a product data sheet is included with the product, the information on the data sheet applies in case of discrepancies with the operating instructions.

Technical data for safety switch CES-I-AR-M-C04

Parameter Value Unit
min. typ. max. Housing material Plastic PBT Dimensions 42 x 25 x 18 mm Mass (without connection cable) 0.05 kg Ambient temperature -25 - + 65 °C Connection - Plug connector M8, 8-pin or
Degree of protection IP67
Safety class III Degree of contamination 3 Installation position Any Installation method Non-flush Operating voltage UB (reverse po-
larity protected, regulated, residual ripple <5%)
Current consumption max. without load
External fuse (operating voltage)
Safety outputs FO1A/FO1B Semiconductor outputs, p-switching, short circuit-proof
- Output voltage U(FO1A)/U(FO1B)
HIGH
HIGH
LOW
Switching current per safety output 1 - 200 mA Utilization category
according to EN IEC 60947-5-2
Off-state current I Monitoring output OD Semiconductor output p-switching, short circuit-proof
- Output voltage 0.8 x U
- Max. load - - 50 mA Rated insulation voltage U Rated impulse withstand voltage U Resilience to vibration Switching frequency - - 1 Hz Repeat accuracy R 10 % EMC protection requirements In accordance with EN IEC 60947-5-3 and EN IEC 61326-3-1
Reliability values acc. to EN ISO 13849-1
Category 4 Performance Level PL e PFH
d
Mission time 20 years
1) Values at a switching current of 50 mA without taking into account the cable length.
1)
U(FO1A)
U(FO1B)
U(FO1A)/U(FO1B) 0 - 1
r
i
- Connection cable PUR, 0.14 mm², with plug connector M12, 8-pin, or
- Connection cable PUR with flying lead, 8 x 0.14 mm²
IP69K (only version with plug connector M8 and mating connec-
Caution: outputs must be protected with a free-wheeling diode in
imp
tor with the same degree of protection)
24 ± 15% (PELV) V DC
0.25 - 8 A
U
-1.5 - U
B
DC-13 24 V 200 mA
case of inductive loads.
0.25 mA
B
- - 300 V
- - 1.5 kV In acc. with EN IEC 60947-5-2
4.1 x 10
35 mA
V DC
V DC
- U
-9
/ h
B
B
22
Operating Instructions Safety Switch CES-I-AR-M-C04
Typical system times
Ready delay: After switching on, the unit carries out a self-test for 8 s. The system
is ready for operation only after this time.
Switch-on time of safety outputs: The max. reaction time from the moment when the actuator is at the operating distance (safety door closed) to the moment when the safety outputs switch on T
Simultaneity monitoring, safety inputs FI1A/FI1B: If the safety inputs have different switching states for longer than 150 ms, the safety outputs FO1A/FO1B will be switched off.
Risk time according to EN 60947-5-3: If an actuator moves outside the operat­ing distance, the safety outputs FO1A and FO1B are deactivated after a maximum of 260 ms. This value applies to a single switch. For each additional switch in a chain the risk time increases by 5 ms.
Difference time: The safety outputs FO1A and FO1B switch with a slight delay in relation to each other. They have the same signal state at the latest after a dif­ference time of 10 ms.
Test pulses at the safety outputs: The device generates its own clock signal on the output lines FO1A/FO1B. A downstream control system must tolerate these
test pulses, which may last up to 1 ms.
is 300 ms (400 ms for switch chains).
on
This can usually be set up in the control systems by parameter assignment. If parameter assignment is not possible for your control system or if shorter test pulses are required, please contact our support organization.
The test pulses are also output when the safety outputs are switched off.
23
Operating Instructions Safety Switch CES-I-AR-M-C04
M12x1
12,9
Dimension drawings
Connection cable with M12 plug connector
Connection cable with
flying lead
With M8 plug connector
10,6
4,1
Active
face
ca. 1000
8
25
LEDs
4,8
Rubber support (included)
14,5
18
15,5
10,6
LEDs
With rubber support
29,2
4,1
42
32
Active face
24
Operating Instructions Safety Switch CES-I-AR-M-C04
max. 45
4
85
3
12
Connector assignment for
safety switch CES-I-AR
(8-pin plug)
and
Y-distributor (8-pin socket)
Pin Function
1 FI1B
2 U
3 FO1A
4 FO1B
5 OD
6 FI1A
7 0 V
8 RST
B
Bridging plug 097645
4-pin, plug
Y-distributor
with connection cable
Y-distributor
097627
111696 or 112395
15,1
Mx1
12
Socket
6
7
( )
45°
097627
Mx1
12
Ø 14,6
2
2
1
3 5
4
Pin Function
1 U
B
2 FI1A
3 0 V
4 FI1B
5 RST
3
5
4
1
20,5
35,1
B
Socket
485
3
2
1
M12x1
15 15
41
M12x1
Ø 14,5
6
7
M12x1
45
Order no.
Length l [mm]
111696 200
Length l
33
A
B
112395 1,000
44
Plug Socket
M12x1
15
2
Plug Socket
3
5
4
1
Pin Function
1 U
2 FO1A
3 0 V
4 FO1B
5 RST
2
3
5
4
1
Pin Function
1 U
Pin Function
B
1 U
B
2 FI1A
3 0 V
2 FO1A
3 0 V
4 FO1B
5 RST
4 FI1B
5 RST
25
Operating Instructions Safety Switch CES-I-AR-M-C04
14

Technical data for actuator CES-A-BBN-C04

Parameter Value Unit
min. typ. max. Housing material Plastic PBT Dimensions 42 x 25 x 18 mm
Mass 0.03 kg
Ambient temperature - 40 - + 65 °C
Degree of protection IP67/IP69K
Installation position Active face opposite read head
Power supply Inductive via read head
Dimension drawing
Active face
2 safety screws M4x20 included
6
4,5
42
32
25
18
14,5
15,5
With rubber support
Rubber support (included)
26
Operating Instructions Safety Switch CES-I-AR-M-C04
Z
Operating distances
Operating distance for center offset m = 0
(only in combination with actuator CES-A-BBN-C04 from approach direction A or B)
Approach direction
A B
Approach direction
C D
Parameter Value Unit
min. typ. max.
Switch-on distance - 15 -
Assured switch-on distance s
Switching hysteresis
1)
Assured switch-off distance s
- in x/z direction
- in y direction
1) On approach in Z direction
ao
ar
10 - -
1 2 -
-
-
-
-
mm
40 60
1)
Operating distance for center offset m = 0
(only in combination with actuator CES-A-BBN-C04 from approach direction C or D)
Parameter Value Unit
min. typ. max.
Switch-on distance - 11 -
1)
Assured switch-on distance s
Switching hysteresis
1)
Assured switch-off distance s
- in x/z direction
- in y direction
1) On approach in x direction
ao
ar
6 - -
1 2 -
-
-
-
-
mm
40 60
Typical operating distance in approach direction A
(Only in combination with actuator CES-A-BBN-C04)
-30
For a side approach direction (y direction) for the actuator and safety switch,
a minimum distance of s = 6 mm must be maintained so that the operating distance
of the side lobes is not entered.
Figure 7: Typical operating distance
-25
Y
40
35
30
25
20
15
10
5
-5
5
5
10
15
20
X
-5
-10
-15
-20
-25
-30
-35
-40
-20
-15
-10
10
15
20
25
30
27
Operating Instructions Safety Switch CES-I-AR-M-C04

Technical data for actuator CES-A-BDN-06

Parameter Value Unit
min. typ. max. Housing material Macromelt PA-based plastic Dimensions 26 x 6 mm
Mass 0.005 kg
Ambient temperature - 40 - + 70 °C
Degree of protection IP67 / IP69K
Installation position Active face opposite read head
Power supply Inductive via read head
1) With flush installation
Dimension drawing
Operating
distance
1)
Installation options
6
Approach
direction
Caution!
* min. 30 Ø
+
0,1
6,1
0
+
0,5
26
30
*
0
30
*
C
A
* Metal-free zone
Do not mount at temperatures below 0 °C. The actuator can be damaged during mounting.
Operating distances
Operating distance for center offset m = 0
(only in combination with actuator CES-A-BDN-... from approach direction A)
Parameter Value Unit
min. typ. max.
Switch-on distance - 19 -
Assured switch-on distance s
Switching hysteresis
1)
Assured switch-off distance s
- in x/z direction
- in y direction
1)
ao
ar
14 - -
- 2 -
-
-
-
-
40 60
mm
Operating distance for center offset m = 0
(only in combination with actuator CES-A-BDN-... from approach direction C)
Parameter Value Unit
min. typ. max.
Switch-on distance - 15 -
Assured switch-on distance s
Switching hysteresis
1)
Assured switch-off distance s
- in x/z direction
- in y direction
28
1)
ao
ar
10 - -
- 2 -
-
-
-
-
40 60
mm
Operating Instructions Safety Switch CES-I-AR-M-C04

Ordering information and accessories

Designation Version Order no.
CES-I-AR-M-C04-U05-119475 Safety switch, multicode, connection cable PUR 5 m, flying lead 8 x 0.14 mm² 119475
CES-I-AR-M-C04-U10-119476 Safety switch, multicode, connection cable PUR 10 m, flying lead 8 x 0.14 mm² 119476
CES-I-AR-M-C04-U20-119477 Safety switch, multicode, connection cable PUR 20 m, flying lead 8 x 0.14 mm² 119477
CES-I-AR-M-C04-USA-119479 Safety switch, multicode, connection cable PUR 1,000 mm with M12 plug connector, 8-pin 119479
CES-I-AR-M-C04-SG-119474 Safety switch, multicode, M8 plug connector, 8-pin 119474
Bridging plug
Y-distributor
Y-distributor with connecting cable
Connection cable with plug connector M12 8-pin, PVC, flying lead, conductor cross-section
0.25 mm²
Connection cable with plug connector M8 8-pin, PUR, flying lead, conductor cross-section
0.14 mm²
Connection cable with plug connector M8 8-pin, PVC, flying lead, conductor cross-section
0.14 mm²
CES-A-BBN-C04-115271 Actuator 42 x 25 x 18 mm 115271
CES-A-BDN-06-104730 Actuator 26 mm x 6 mm 104730
M12, 4-pin, plug 097645
M12, 1x8-pin, 2x5-pin 097627
M12, 1x8-pin, 2x5-pin 111696
M12, 8-core, 5 m 100177
M12, 8-core, 10 m 100178
M12, 8-core, 20 m 100179
M8, 8-pin, 5 m 106671
M8, 8-pin, 10 m 106672
M8, 8-pin, 20 m 106673
M8, 8-pin, 5 m 110933
M8, 8-pin, 10 m 110934
M8, 8-pin, 15 m 110935
M8, 8-pin, 20 m 111603

Inspection and service

Warning!
Regular inspection of the following is necessary to ensure trouble-free long-term operation:
Ì Check the switching function (see section Functional check) Ì Check the secure fastening of the devices and the connections Ì Check for soiling
No servicing is required. Repairs to the device are only allowed to be made by the manufacturer.
Note!
The year of manufacture can be seen in the lower right corner of the rating plate. The current version number in the format (V X.X.X) can also be found on the device.
The safety door must be re-adjusted when the device indicates that the actuator is in the limit range.
Loss of the safety function because of damage to the system. In case of damage, the related component must be replaced completely. Only accessories or spare parts that can be ordered from EUCHNER may be replaced.
29
Operating Instructions Safety Switch CES-I-AR-M-C04

Service

If service support is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
D-70771 Leinfelden-Echterdingen
Service telephone:
+49 711 7597-500
E-mail:
info@euchner.de
Internet:
www.euchner.de
30
Operating Instructions Safety Switch CES-I-AR-M-C04

Declaration of conformity

31
Operating Instructions Safety Switch CES-I-AR-M-C04
32
Operating Instructions Safety Switch CES-I-AR-M-C04
33
More than safety.
Euchner GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen
info@euchner.de www.euchner.de
Edition: 119562-04-05/14 Title: Operating Instructions Safety Switch CES-I-AR-M-C04 (transla­tion of the original operating instructions) Copyright: © EUCHNER GmbH + Co. KG, 05/2014
Subject to technical modifications; no responsibility is ac­cepted for the accuracy of this information.
Loading...