Safety in case of faults 1
Fuse protection for power supply 1
Requirements for connection cables 1
Connector assignment and wire color for safety switch CES-AP-C.2-CH 1
Connection 1
Setup 1
LED indicators 1
Initial setup 1
Functional check 1
System status table 1
3
4
4
5
6
8
9
0
0
0
1
2
4
4
4
4
5
Technical data 1
Technical data for safety switch CES-AP-CR2-CH/CES-AP-CL2-CH 1
Technical data for actuator CES-A-BLN-... 1
Technical data for actuator CES-A-BDN 2
Ordering information and accessories 2
Inspection and service 2
Service 2
Declaration of conformity 2
6
6
8
0
1
2
2
3
Page 3
System Manual Safety Switch CES-AP-C.2-CH
About this manual
This manual is valid for all safety switches CES-AP-C.2-CH with version number
V 1.1.2 or higher.
Correct use
The Coded Electronic Safety switches series CES are safety devices for monitoring movable safety guards.
In combination with a separating safety guard, this safety component prevents
dangerous machine movements from being performed for as long as the safety
guard is opened. A stop command is triggered if the safety guard is opened during
the dangerous machine function.
Before safety switches are used, a risk assessment must be performed on the
machine, e.g., in accordance with:
EN ISO 13849-1, Safety of machinery. Safety related parts of control systems.
General principles for design
Important!
EN ISO 14121-1, Safety of machinery. Risk assessment. Principles
IEC 62061, Safety of machinery. Functional safety of safety-related electrical,
electronic and programmable electronic control systems.
Correct use includes compliance with the relevant requirements for installation
and operation, for example
EN ISO 13849-1, Safety of machinery. Safety related parts of control systems.
General principles for design
EN 1088, Safety of machinery. Interlocking devices associated with guards.
Principles for design and selection
EN 60204-1, Safety of machinery. Electrical equipment of machines. General
requirements
EN 60947-5-3, Specification for low-voltage switchgear and controlgear. Con
trol circuit devices and switching elements. Requirements for proximity devices
with defined behaviour under fault conditions
The safety switch must be used only in conjunction with the designated CES actuators from EUCHNER. On the use of different actuators, EUCHNER provides no
warranty for safe function.
The user is responsible for the integration of the device into a safe overall
system. For this purpose, the overall system must be validated, e.g. in accordance with EN ISO 13849-2.
In the estimation of the PL for the overall system, a maximum value of
100 years can be assumed for the MTTFd according to the limit value in
EN ISO 13849-1:2008, Section 4.5.2. This corresponds to a minimum value
for the PFHd of 2.47x10-8/h.
Correct use requires observing the permissible operating parameters (see
Technical data).
If a product data sheet is included with the product, the information on the
data sheet applies in case of discrepancies with the operating instructions.
Only components may be used that are permissible in accordance with the
table below.
-
3
Page 4
System Manual Safety Switch CES-AP-C.2-CH
4
Possible combinations for CES components
Actuator
Door hinge right
Safety switch
CES-A-BLN-R2-100776
100776
Door hinge right
CES-AP-CR2-CH
Door hinge left
CES-AP-CL2-CH
Door hinge left
CES-A-BLN-L2-104510
104510
Usage independent of
position of door hinge
CES-A-BLN-U2-103450
103450
Usage independent of
position of door hinge
CES-A-BDN-104730
104730
Key to symbols
Combination possible
Exclusion of liability and warranty
In case of failure to comply with the conditions for correct use stated above, or
if the safety instructions are not followed, or if any servicing is not performed as
required, liability will be excluded and the warranty void.
Page 5
System Manual Safety Switch CES-AP-C.2-CH
General safety instructions
Safety switches fulfill personal protection functions. Incorrect installation or tampering can lead to fatal injuries to personnel.
Check the safe function of the safety guard particularly
after any setup work
after the replacement of a CES component
after an extended period without use
after every fault
Independent of these checks, the safe function of the safety guard should be
checked at suitable intervals as part of the maintenance schedule.
Warning!
Danger of fatal injury in the event of incorrect connection or incorrect use.
Safety switches must not be bypassed (bridging of contacts), turned away,
removed or otherwise rendered ineffective.
On this topic pay attention in particular to the measures for reducing the possibility of bypassing from EN 1088:1995+A2:2008, Section 5.7.
Important!
The device is only allowed to be installed and placed in operation by authorized
personnel
who are familiar with the correct handling of safety components
who are familiar with the applicable EMC regulations
who are familiar with the applicable regulations on health and safety and ac-
cident prevention
who have read and understood the operating instructions and the system
manual
Prior to use, read the operating instructions and the system manual and keep
these in a safe place. Ensure the operating instructions and the system manual
are always available during mounting, setup and servicing. EUCHNER cannot
provide any warranty in relation to the readability of the CD for the storage period required. For this reason you should archive a printed copy of the system
manual. If you should lose the operating instructions or the system manual, you
can download these documents from www. EUCHNER.de.
5
Page 6
System Manual Safety Switch CES-AP-C.2-CH
6
Function
The safety switch CES-AP-CR2-CH/CES-AP-CL2-CH complies with the following
safety requirements:
Safety category 4, PLe according to EN ISO 13849-1
Proximity device with self-monitoring type PDF-M according to EN 60947-5-3
Redundant design of the circuit in the unit with self-monitoring.
This means that the safety system still functions even if an internal component
fails
The switch state of the semiconductor outputs is continuously monitored inter-
nally
Short circuit detection at the safety outputs by pulse signals
The following switch-on condition applies to safety outputs OA and OB (see also
System status table and the section Typical system times):
Safety guard closed
The non-contact safety switch CES consists of three components: coded actuator
(transponder), evaluation unit and read head.
The evaluation unit is integrated together with the read head in a housing compatible with EN IEC 60947-5-2.
Every EUCHNER actuator supplied has an electronic coding (unique coding) that is
read by the read head. Only if a correct coding is detected does the system accept
the actuator. The code in an actuator cannot be reprogrammed.
Unlike systems with unique code detection, on the CES-AP-C.2-CH a specific code
is not polled but instead it is only checked whether the actuator is of a type that
can be detected by the system (multicode detection). There is no exact comparison of the actuator code with the code defined in the safety switch (unique code
detection).
The safety switch is fastened to the fixed part of the safety guard.
The actuator attached to the movable part of the safety guard is moved towards
the read head fitted in the safety switch by closing the door. When the switch-on
distance is reached, power is supplied to the actuator by the read head by induction and data can be transferred.
If a permissible code is detected, the safety outputs are released.
Due to the combination of dynamic polling of the actuator and the redundant,
diverse design of the safety electronics with the two feedback safety outputs, the
safety switch will enter the safe state with every detectable fault.
When the safety guard is opened, the safety outputs switch off the safety circuit
and the monitoring output OUT is switched to high-resistance. The state of the
safety outputs is monitored internally by two microprocessors.
If faults are detected, the safety circuit is switched off and the DIA LED illuminates.
In case of devices with a DIA monitoring output, the output is set to HIGH.
The safety switch has a redundant circuit design with self-monitoring. This means
that the safety system is still effective even if a component fails.
The system is designed so that failures will not result in the loss of the safety function. The occurrence of failures is detected by cyclic self-monitoring at the latest
on the next demand to close the safety contacts (e.g. on starting).
Page 7
System Manual Safety Switch CES-AP-C.2-CH
If the safety door with the actuator should settle over time, the actuator can drift
out off the read head operating distance. The device recognizes this and indicates
that the actuator is in the boundary area (function available for V 1.1.2 and higher).
This allows the safety door to be readjusted in time.
7
Page 8
System Manual Safety Switch CES-AP-C.2-CH
8
min. 400 mm
Mounting
Caution!
Risk of damage to equipment as a result of incorrect installation. Safety switches
must not be used as a mechanical end stop.
Fit an additional end stop for the movable part of the safety guard.
Important!
From the assured switch-off distance Sar, the safety outputs are safely shut
down.
When mounting several safety switches, observe the stipulated minimum
distance to avoid mutual interference.
Installation options
The operating distance changes during the mounting of the actuator as a
function of the material used for the safety guard.
Installation options
Note the following points:
Actuator and safety switch must be easily accessible for inspection and re-
placement.
The switching operation must only be triggered by the specific actuator desig-
nated for this purpose. For permissible combinations please see the table of
possible combinations on page 4.
Actuator and safety switch must be fitted so that
the front faces are at the minimum switch-on distance 0.8 x Sao or closer
when the safety guard is closed (see section Operating distances). A minimum distance dependent on the actuator must be maintained for a side approach direction: - For CES-A-BLN-R2 6 mm
- For CES-A-BLN-L2 6 mm
- For CES-A-BLN-U2 6 mm
- For CES-A-BDN 10 mm
when the safety guard is open up to the distance Sar (assured switch-off dis-
tance), a hazard is excluded.
the actuator is positively mounted on the safety guard, e.g. by using the
safety screws included.
Pay attention to the maximum tightening torque for the safety switch and
actuator mountings of 1 Nm.
Page 9
System Manual Safety Switch CES-AP-C.2-CH
Electrical connection
Warning!
In case of an error, loss of the safety function through incorrect connection.
To ensure safety, both safety outputs (OA and OB) must always be evaluated.
The monitoring output OUT must not be used as a safety output.
Lay the connection cables with protection to prevent the risk of short cir-
cuits.
Caution!
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Do not use a control system with pulsing or switch off the pulsing function in
your control system. The device generates its own clock signal on the output
lines OA/OB. A downstream control system must tolerate these test pulses,
which may have a length of up to 0.4 ms.
No pulses are present when the safety outputs are switched off.
The inputs on an evaluation unit connected must be positive-switching, as the
two outputs on the safety switch deliver a level of +24 V in the switched-on
state.
All the electrical connections must either be isolated from the mains supply
by a safety transformer according IEC 61558-2-6 with limited output voltage
in the event of a fault, or by other equivalent isolation measures.
For use and operation as per the requirements, a power supply with the
feature "for use in class 2 circuits" must be used. The same requirement applies to the safety outputs.
Alternative solutions must comply with the following requirements:
a) Electrically isolated power supply unit with a max. open-circuit voltage of 30
V/DC and a limited current of max. 8 A.
b) Electrically isolated power supply unit in combination with fuse as per UL248.
This fuse should be designed for max. 3.3 A and should be integrated into
the 30 V/DC voltage section.
All electrical outputs must have an adequate protective circuit for inductive
loads. The outputs must be protected with a free-wheeling diode for this purpose.
Power devices which are a powerful source of interference must be installed
in a separate location away from the input and output circuits for signal processing. The cable routing for safety circuits should be as far away as possible from the cables of the power circuits.
Important!
If the device does not appear to function when operating voltage is applied (e.g.
green STATE LED does not flash), the safety switch must be returned unopened
to the manufacturer.
9
Page 10
System Manual Safety Switch CES-AP-C.2-CH
10
Safety in case of faults
The operating voltage UB is reverse polarity protected.
The contacts OA/OB are short circuit proof.
A short circuit between OA and OB is detected by the switch.
A short circuit in the cable can be excluded by laying the cable with protection.
Fuse protection for power supply
The power supply must be provided with fuse protection depending on the current
required for the outputs. The following rules apply:
Caution!
Max. current consumption of a switch I
I
= IUB + I
max
OUT
+ I
OA+OB
max
IUB = Switch operating current (30 mA)
I
= Monitoring output load current (max. 50 mA)
OUT
I
= Load current safety outputs OA + OB (2 x max. 150 mA)
OA+OB
Requirements for connection cables
Risk of damage to equipment or malfunctions as a result of incorrect connection cables.
Use connection components and connection cables from EUCHNER
On the usage of other connection components, the requirements in the fol-
lowing table apply. EUCHNER provides no warranty for safe function in case
of failure to comply with these requirements.
The connection cable must not be longer than 180 m in total.
Observe the following requirements with respect to the connection cables:
ParameterValueUnit
Wire cross-section min.0.14mm²
R max.150W/km
C max.120nF/km
L max.0.65mH/km
Recommended cable typeLIYY 8x or 5x0.14 mm²
Page 11
System Manual Safety Switch CES-AP-C.2-CH
S1.1
S1.3
S1.6
S1.2
S1.4
S1.5
+UB
0V
NC
OA
OB
OUT
5
1
4
6
2
3
S1.1
S1.3
S1.2
S1.4
S1.5
+UB
0V
OA
OB
n.c.
4
1
5
2
3
S1.1
S1.3
S1.2
S1.4
S1.5
+UB
0V
OA
OB
OUT
Connector assignment and wire color for safety switch
CES-AP-C.2-CH
Plug connector with latching connection, 6-pin
View on the connection side of the safety switch
Figure 1: Connector assignment, plug connector with latching connection
Coding lug
Pin DesignationDescriptionWire color
1UBPower supply, DC 24 V BN
2OASafety output, channel 1WH
30VGround, DC 0 VBU
4OBSafety output, channel 2BK
5OUTMonitoring outputGY
6-Not usedPK
Connection cable with M12 plug connector, 5-pin
5-pin5-pin,
View on the connection side of the safety switch
Figure 2: Connector assignment, connection cable with M12 plug connector
pin 5 not used
Coding lug
Pin
5-pin
Pin 5
used
11UBPower supply, DC 24 V BN
22OASafety output, channel 1WH
330VGround, DC 0 VBU
44OBSafety output, channel 2BK
5-OUTMonitoring outputGY
5-pin
DesignationDescriptionWire color
not
11
Page 12
System Manual Safety Switch CES-AP-C.2-CH
12
GND
DC 24 V
-F1
CES-AP-C.2-...
UB1
OA2
OB4
NC6
M8 plug-connector
(6-pin)
OUT5
0V3
-V1
-K1
-V2
-K2
L1
M
3
~
-M1
L2L3
Connection
Connect the device as shown in Figure 3. The OUT output can be connected to a
control system as a monitoring output.
Important!
The subsystem CES-AP complies with PL e in accordance with EN 13849-1. To
integrate the subsystem in a category 3 or 4 structure, it is necessary to monitor
the downstream load (the feedback loop must be monitored).
These examples show only an excerpt that is relevant for connection of the CES
system. The example illustrated here does not show complete system planning.
The user is responsible for safe integration in the overall system.
Figure 3: Connection example CES-AP-CR2-CH/CES-AP-CL2-CH
Page 13
System Manual Safety Switch CES-AP-C.2-CH
GND
DC 24 V
CES-AP-C.2-...
UB1
OA2
OB4
NC6
M8 plug-connector
(6-pin)
OUT5
0V3
-K1
-K2
-M1-M2
MM
A1
A2
A1
A2
13
14
13
14
Warning!
In case of an error, loss of the safety function through incorrect connection.
To ensure safety, both safety outputs (OA and OB) must always be evaluated.
Single-channel use of the safety outputs leads to a reduction of the category
in accordance with EN ISO 13849-1.
Figure 4: Example of incorrect connection.
13
Page 14
System Manual Safety Switch CES-AP-C.2-CH
14
Setup
LED indicators
LEDColorStateSignificance
illuminated
STATE
DIA
Initial setup
Apply operating voltage to the safety switch.
1.
The green LED flashes quickly
A self-test is performed during this time. After this, the LED flashes cyclically
one time and signals that it is in standby state.
Move actuator to the read head (observe distance < Sao).
2.
green
red
flashing
illuminated
Normal operation: Door closed
- Door open
- Actuator in boundary area
(refer to the status table for further signal functions)
- Internal electronics fault
- Fault at the inputs/outputs
Warning!
The green LED illuminates continuously and indicates the detection of the
actuator.
If the green LED is flashing at approx. 2 Hz, the actuator is in the boundary area.
In this case the safety guard must be re-adjusted such that the actuator is completely in the read area.
Functional check
After installation and any fault, the safety function must be fully checked. Proceed
as follows:
Danger of fatal injury as a result of faults in installation and functional check.
Before carrying out the functional check, make sure that there are no per-
sons in the danger area.
Observe the valid accident prevention regulations.
Switch on operating voltage.
1.
The green LED STATE then flashes at regular intervals.
Close all safety guards.
2.
The machine must not start automatically.
The green STATE LED illuminates continuously.
Enable operation in the control system.
3.
Open the safety guard.
4.
The machine must switch off and it must not be possible to start it as long as
the safety guard is open.
The green LED STATE flashes at regular intervals.
Repeat steps 2-4 for each safety guard.
Page 15
System Manual Safety Switch CES-AP-C.2-CH
System status table
LED indicator
output
Operating mode
Normal operation
Fault display
Key to symbols
State
Actuator/door posi-
tion
Safety outputs OA
and OB
closedonNormal operation, door closed
closedon
openoff1 xNormal operation, door open
closedoff3 xDefective actuator (e.g. fault in code or code not readable)
Xoff4 xOutput fault (e.g. short-circuit, loss of switching capability)
Xoff5 xInternal fault (e.g. component faulty, data fault)
STATE (green)
flashes
quickly
2 Hz
10 Hz (8 s)
3 x
XAny state
DIA (red)
Normal operation, door closed, actuator in the boundary area Re-adjust door
LED not illuminated
LED illuminated
LED flashes for 8 seconds at 10 Hz
LED flashes three times, and this is then repeated
Important!
After the cause has been remedied, faults can generally be reset by opening and
closing the door. If the fault is still displayed afterward, use the reset function or
briefly interrupt the power supply. Please contact the manufacturer if the fault could
not be reset after restarting.
If you do not find the displayed device state in the System status table, this
indicates an internal device fault. In this case, you should contact the manufacturer.
15
Page 16
System Manual Safety Switch CES-AP-C.2-CH
16
Technical data
Note!
If a product data sheet is included with the product, the information on the data
sheet applies in case of discrepancies with the operating instructions.
Technical data for safety switch
CES-AP-CR2-CH/CES-AP-CL2-CH
ParameterValueUnit
min.typ.max.
Housing materialPlastic PBT
Dimensions95 x 30 x 12mm
Weight0.04kg
Ambient temperature at UB = DC
Safety classIII
Degree of contamination 3
Installation positionAny
ConnectionPlug connector or connection cable
Operating voltage UB (reverse polar-
ity protected, regulated, residual
ripple < 5%)
For the approval according to
the following applies
Current consumption30mA
Switching load according to
External fuse
(operating voltage)
Safety outputs OA/OBSemiconductor outputs, p-switching, short circuit-proof
- Output voltage U(OA)/U(OB)
HIGH
HIGH
LOW
Switching current per safety output1-150mA
Utilization category according to
EN IEC 60947- 5-2
Off-state current I
Classification
acc. to EN IEC 60947-5-3
Monitoring output OUT
- Output voltage0.8 x U
- Max. load--50mA
Rated insulation voltage U
Rated impulse withstand voltage
U
imp
Resilience to vibration
Switching frequency--1Hz
Repeat accuracy R ≤ 10%
EMC protection requirementsAs per EN IEC 60947-5-3
Reliability values according to EN ISO 13849-1
Category4
Performance LevelPL e
PFH
d
Mission time20years
1) Values at a switching current of 50 mA without taking into account the cable lengths.
r
1)
U(OA)
U(OB)
U(OA)/U(OB)01
1)
i
- 30
(IP 67 for version with M12 plug connector)
Operation only with UL Class 2 power supply, or equivalent
0.25
UB-1.5-U
Caution: outputs must be protected with a freewheeling diode in
Semiconductor output p-switching, short circuit-proof
--75V
--1.5kV
24 ± 15%
measure
DC 24 V, class 2
DC-13 24 V 150 mA
case of inductive loads.
≤ 0.25mA
PDF-M
B
As per EN IEC 60947-5-2
1.8 x 10
-+ 65
V DC
-1.5A
-U
-9
/ h
B
B
V DC
V DC
°C
Page 17
System Manual Safety Switch CES-AP-C.2-CH
5,5
95
85
+0,5
75,5
19,5
11
30
4,4
6,9
4,25
6
12
3
Ø
STATE
DIA
23
5,5
95
85
+0,5
75,5
19,5
11
30
4,4
4,25
6
12
3
6,9Ø
STATE
DIA
23
Typical system times
Ready delay: After switching on, the unit carries out a self-test. The system is
ready for operation only after this time.
Switch-on time of safety outputs: The max. reaction time from the moment
when the actuator is at the operating distance (safety door closed) to moment
when the safety outputs switch on Ton is 400 ms.
Risk time according to EN 60947-5-3: If an actuator moves outside the operating distance, the safety outputs OA and OB are deactivated after a maximum
of 260 ms.
Difference time: The safety outputs OA and OB switch with a slight time offset.
They have the same signal state at the latest after a difference time of 10 ms.
Dimension drawings and connector assignments
Connection cable with M12
plug connector
Length of cable piece:
200 mm
Safety switch CES-AP-CL2-CH...
with connection
cable
Active face
LEDs
Safety switch CES-AP-CR2-CH...
Active face
LEDs
Active face
with connection
cable
Connection cable with
M12 plug connector
Fastening lug with
reinforcement plate
Length of cable piece:
200 mm
Active face
Fastening lug with
reinforcement plate
17
Page 18
System Manual Safety Switch CES-AP-C.2-CH
18
95
85
+0,5
75,5
19,5
11
30
4,4
4,25
12
3
4,4
30
45
55
35
11
4,25
19,5
12
3,5
95
85
+0,5
75,5
19,5
11
30
4,4
4,25
12
3
Technical data for actuator CES-A-BLN-...
ParameterValueUnit
min.typ.max.
Housing materialPlastic PBT
Dimensions
- CES-A-BLN-R2/CES-A-BLN-L2
- CES-A-BLN-U2
Weight
- CES-A-BLN-R2/CES-A-BLN-L2
- CES-A-BLN-U2
Ambient temperature- 40-+ 70°C
Degree of protection acc. to EN
IEC 60529
Installation positionActive face opposite read head
Power supplyInductive via read head
Dimension drawing
CES-A-BLN-R2CES-A-BLN-U2
95 x 30 x 12
55 x 30 x 12
0.04
0.02
IP 69K
mm
kg
Fastening lug with
reinforcement plate
Active face
Active face
CES-A-BLN-L2
Active face
Active face
Fastening lug with
reinforcement plate
Active
face
Fastening lug with
reinforcement plate
Active face
Page 19
System Manual Safety Switch CES-AP-C.2-CH
Z
-2
5
-3
0
X
10
5
15
20
-2
0
-2
5
-3
0
-4
0
-3
5
-1
5
-1
0
-5
-10
20
25
30
15
10
40
35
5
Y
15
20
25
5
-5
-15
30
10
-20
Switching distances
Operating distance for center offset m = 0
(only in combination with actuator CES-A-BLN-...)
ParameterValueUnit
min.typ.max.
Switch-on distance-15-
Assured switch-on distance s
Switching hysteresis
Assured switch-off distance s
- in x/z direction
- in y direction
Typical operating distance
(only in combination with actuator CES-A-BLN-...)
1)
ao
1)
ar
10--
12-
-
-
mm
-
-
40
60
For a side approach direction for the actuator and safety switch, a minimum distance of s = 6 mm
must be maintained so that the operating distance of the side lobes is not entered.
Figure 5: Typical operating distance
19
Page 20
System Manual Safety Switch CES-AP-C.2-CH
20
26
0
+
0,5
Ø
30
* min.
30
*
30
*
6,1
0
+
0,1
z
y
x
6
Technical data for actuator CES-A-BDN
ParameterValueUnit
min.typ.max.
Housing materialMacromelt PA-based plastic
Dimensions26 x ∅ 6mm
Weight
Ambient temperature- 40-+ 70°C
Degree of protection acc. to EN
IEC 60529
Installation positionActive face opposite read head
Power supplyInductive via read head
1) With flush installation
Dimension drawing
operating distance
0.005
IP 67 / IP 69K
kg
1)
Installation options
* metal-free zone
Caution!
Do not mount at temperatures below 0 °C.
The actuator can be damaged during mounting.
Switching distances
Operating distance for center offset m = 0
(only in combination with actuator CES-A-BDN-...)
ParameterValueUnit
Switch-on distance-19-
Assured switch-on distance s
Switching hysteresis
Assured switch-off distance s
- in x/z direction
- in y direction
1)
ao
1)
ar
min.typ.max.
14--
-2-
-
-
-
-
40
60
mm
Page 21
System Manual Safety Switch CES-AP-C.2-CH
Ordering information and accessories
DesignationVersionOrder
CES-AP-CR2-CH-SF-100775
CES-AP-CL2-CH-SF-104509
CES-AP-CR2-CH-SB-106550
CES-AP-CL2-CH-SB-106551
CES-AP-CR2-CH-L05-105600
CES-AP-CL2-CH-L05-105602
CES-AP-CR2-CH-L10-106189
CES-AP-CL2-CH-L10-106190
CES-AP-CR2-CH-L20-106193
CES-AP-CL2-CH-L20-106194
CES-AP-CR2-CH-SB-109168
CES-AP-CL2-CH-SB-109167
Connection cable with plug connector with latching connection,
6-pin
Connection cable with M12 plug
connector, 5-pin
Actuator CES-A-BLN-R295 mm x 30 mm x 12 mm, door hinge right100776
Actuator CES-A-BLN-L295 mm x 30 mm x 12 mm, door hinge left104510
Actuator CES-A-BLN-U255 mm x 30 mm x 12 mm103450
Actuator CES-A-BDN-06
connection cable PUR with M12 plug connector, 5-pin
connection cable PUR with M12 plug connector, 5-pin
connection cable PUR with M12 plug connector, 5-pin,
connection cable PUR with M12 plug connector, 5-pin,
multicode, door hinge right,
Plug connector with latching connection, 6-pin
multicode, door hinge left,
Plug connector with latching connection, 6-pin
multicode, door hinge right,
multicode, door hinge left,
multicode, door hinge right,
connection cable PVC, length 5 m
multicode, door hinge left,
connection cable PVC, length 5 m
multicode, door hinge right,
connection cable PVC, length 10 m
multicode, door hinge left,
connection cable PVC, length 10 m
multicode, door hinge right,
connection cable PVC, length 20 m
multicode, door hinge left,
connection cable PVC, length 20 m
multicode, door hinge right,
pin 5 not used
multicode, door hinge left,
pin 5 not used
5 m, PVC103556
10 m, PVC103557
15 m, PVC103558
20 m, PVC103559
25 m, PVC103560
5 m, PVC100183
10 m, PVC100184
20 m, PVC100185
∅ 6 mm104730
26 mm x
no.
100775
104509
106550
106551
105600
105602
106189
106190
106193
106194
109168
109167
21
Page 22
System Manual Safety Switch CES-AP-C.2-CH
22
Inspection and service
Warning!
Loss of the safety function because of damage to the system.
In case of damage, the related component must be replaced completely. The
replacement of individual parts of a component is not allowed.
Regular inspection of the following is necessary to ensure trouble-free long-term
operation:
Check the switching function (see section Functional check)
Check the secure fastening of the devices and the connections
Check for soiling
No servicing is required, repairs to the device are only allowed to be made by the
manufacturer.
Note!
Service
The year of manufacture can be seen in the lower right corner of the type plate.
The current version number in the format (V X.X.X) can also be found on the
device.
The safety door must be re-adjusted when the device indicates that the actuator
is in the boundary area.
If service support is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstrasse 16
D-70771 Leinfelden-Echterdingen
Service telephone:
07 11 / 75 97 - 301
E-mail:
info@euchner.de
Internet:
www.euchner.de
Page 23
System Manual Safety Switch CES-AP-C.2-CH
Declaration of conformity
23
Page 24
System Manual Safety Switch CES-AP-C.2-CH
24
Page 25
System Manual Safety Switch CES-AP-C.2-CH
25
Page 26
More than safety.
Euchner GmbH + Co. KG
Kohlhammerstrasse 16
D-70771 Leinfelden-Echterdingen