EUCHNER CES-A-ABA-01, CES-A-ABA-01B Operating Instructions Manual

Page 1
EN
Operating Instructions
Non-Contact Safety System
CES-A-ABA-01/CES-A-ABA-01B (Unicode)
Page 2
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
2
(translation of the original operating instructions) 071873-15-07/15
Contents
1. About this document ............................................................................................. 4
1.1. Scope ............................................................................................................................................4
1.2. Target group ..................................................................................................................................4
1.3. Key to symbols ...............................................................................................................................4
1.4. Supplementary documents ..............................................................................................................4
2. Correct use .......................................................................................................... 5
3. Description of the safety function .......................................................................... 6
4. Exclusion of liability and warranty ......................................................................... 7
5. General safety instructions.................................................................................... 7
6. Function ............................................................................................................... 8
6.1. Block diagram CES-A-ABA-… ...........................................................................................................9
7. Mounting ............................................................................................................ 10
8. Electrical connection .......................................................................................... 11
8.1. Notes about ..........................................................................................................................11
8.2. Safety in case of faults ..................................................................................................................11
8.3. Fusing of the power supply and the safety contacts .........................................................................11
8.4. Correct connection .......................................................................................................................12
8.5. Connection example CES-A-ABA-01B ..............................................................................................13
9. Setup ................................................................................................................. 14
9.1. LED indicators ..............................................................................................................................14
9.2. Teach-in operation .........................................................................................................................14
9.2.1. Carrying out teach-in for rst actuator (default setting on delivery) ....................................15
9.2.2. Carrying out teach-in for a new actuator..........................................................................15
9.3. Functional check ...........................................................................................................................16
9.3.1. Self-test with test input TST ...........................................................................................16
10. System status table ............................................................................................ 17
11. Technical Data .................................................................................................... 18
11.1. Evaluation unit CES-A-ABA-... ..........................................................................................................18
11.2. Read head CES-A-LNA-… ...............................................................................................................20
11.3. Read head CES-A-LNA-SC ..............................................................................................................22
11.4. Read head CES-A-LCA-… ...............................................................................................................25
11.5. Read head CES-A-LMN-SC ..............................................................................................................29
11.6. Actuator CES-A-BBA/CES-A-BCA .....................................................................................................31
11.7. Actuator CES-A-BQA ......................................................................................................................32
11.8. Actuator CES-A-BDA ......................................................................................................................33
11.9. Actuator CES-A-BMB .....................................................................................................................34
Page 3
3
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
12. Ordering information and accessories ................................................................. 35
13. Inspection and service ........................................................................................ 35
14. Service .............................................................................................................. 35
15. Declaration of conformity ................................................................................... 36
Page 4
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
4
(translation of the original operating instructions) 071873-15-07/15
1. About this document
1.1. Scope
This document is valid for
Ì Non-Contact Safety System CES‑A‑ABA‑01, evaluation unit for 1 read head (order no. 071850) Ì Non-Contact Safety System CES‑A‑ABA‑01B, evaluation unit for 1 read head (order no. 083513)
1.2. Target group
Design engineers and installation planners for safety devices on machines, as well as setup and servicing staff possessing special expertise in handling safety components.
1.3. Key to symbols
Symbol/depiction Signicance
Printed document
www
Document is available for download at www.euchner.de
Document on CD
DANGER
WARNING
CAUTION
Signal word: DANGER WARNING CAUTION
Consequence if not observed:
Death or severe injuries Possibly death or severe injuries Possibly minor injuries
NOTICE
Important!
Signal word: NOTICE Important!
Malfunction or device damage possible Important information
Tip Useful information
1.4. Supplementary documents
The overall documentation for this device consists of the following documents:
Document title (document number)
Contents
Safety Information and Maintenance CES-A…/ CES-AZ/CES-FD (109083)
Ì Basic safety information Ì Maintenance instructions
Operating instructions (071873)
(this document)
Important!
Always read all documents to gain a complete overview of safe installation, setup and use of the device. The documents can be downloaded from www.EUCHNER.de. For this purpose enter the doc. no. in the search box.
Page 5
5
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
2. Correct use
Evaluation units of the series CES-A are used to evaluate safety-related signals from EUCHNER read heads. The system forms an interlocking device without guard locking. It meets the requirements according to ENIEC60947-5-3.
The system consists of evaluation unit, read head and actuator. It forms an interlocking device with high coding level (type4).
In combination with a movable safety guard and the machine control, this system prevents dangerous machine functions from occurring while the safety guard is open. A stop command is triggered if the safety guard is opened during the dangerous machine function.
This means:
Ì Starting commands that cause a dangerous machine function must become active only when the safety guard is closed. Ì Opening the safety guard triggers a stop command. Ì Closing a safety guard must not cause automatic starting of a dangerous machine function. A separate start command
must be issued. For exceptions, refer to EN 12100 or relevant C-standards.
Before use, a risk assessment must be performed on the machine, e.g.according to the following standards:
Ì ENISO13849-1, Safety of machinery – Safety-related parts of control systems – Part 1: General principles for design Ì ENISO12100, Safety of machinery – General principles for design – Risk assessment and risk reduction Ì IEC62061, Safety of machinery – Functional safety of safety-related electrical, electronic and programmable electronic
control systems.
Correct use includes observing the relevant requirements for installation and operation, e.g. according to the following standards:
Ì ENISO13849-1, Safety of machinery – Safety-related parts of control systems – Part 1: General principles for design Ì ENISO14119, Safety of machinery – Interlocking devices associated with guards – Principles for design and selection Ì EN60204-1, Safety of machinery – Electrical equipment of machines – Part 1: General requirements
The following components can be connected to the evaluation unit CES-A-ABA…:
Ì CES read heads Ì CEM read heads Ì CET read heads
For further information, refer to the operating instructions of the corresponding component and to Table 1: Possible com‑
binations for CES components on page 6.
Important!
Ì The user is responsible for the proper integration of the device into a safe overall system. For this
purpose, the overall system must be validated, e.g.in accordance with ENISO13849-2.
Ì Correct use requires observing the permissible operating parameters (see Technical data). Ì If a data sheet is included with the product, the information on the data sheet applies. Ì It is only allowed to use components that are permissible in accordance with the table below.
Page 6
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
6
(translation of the original operating instructions) 071873-15-07/15
Table 1: Possible combinations for CES components
Evaluation unit Read head
Actuator
CES-A-BBA
071840
CES-A-BCA
088786
CES-A-BDA
084720
CES-A-BMB
077791
CES-A-BQA
098108
CES-A-NBA-...
All items
CES-A-BPA
098775
CEM-A-BE05
094805
CEM-A-BH10
095175
CET-A-BWK-50X
096327
CES-A-ABA-01
071850
CES-A-LNA...
All items
CES-A-LNA-SC
077715
CES-A-LCA...
All items
CES-A-LMN-SC
077790
CES-A-LQA-SC
095650
CES-A-ABA-01B
083513
CES-A-LNA...
All items
CES-A-LNA-SC
077715
CES-A-LCA...
All items
CES-A-LMN-SC
077790
CES-A-LQA-SC
095650
CEM-A-LE05K-S2
094800
CEM-A-LE05R-S2
095792
CEM-A-LH10K-S3
095170
CEM-A-LH10R-S3
095793
CET-AX
Key to symbols
Combination possible
Combination possible, guard locking for process protection
Combination possible, guard locking for personal protection
Combination not permissible
3. Description of the safety function
Devices from this series feature the following safety functions:
The following applies in combination with read heads without guard locking (CES read heads) and read heads with guard locking for process protection (CEM/CET read heads):
Monitoring of the position of a safety guard (interlocking device according to EN ISO 14119)
Ì Safety function:
- The safety contacts are switched off when the safety guard is open (see chapter 11. Technical Data on page 18).
Ì Safety characteristics: Category, Performance Level, PFH
d
(see Technical data CES‑A‑ABA‑01B on page 19).
Page 7
7
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
4. Exclusion of liability and warranty
In case of failure to comply with the conditions for correct use stated above, or if the safety instructions are not followed, or if any servicing is not performed as required, liability will be excluded and the warranty void.
5. General safety instructions
WARNING
Danger to life due to improper installation or due to bypassing (tampering). Safety components fulll a personal protection function.
Ì Safety components must not be bypassed, turned away, removed or otherwise rendered ineffec-
tive. On this topic pay attention in particular to the measures for reducing the possibility of bypass­ing according to ENISO14119:2013, section 7.
Ì The switching operation must be triggered only by actuators designated for this purpose. Ì Mounting, electrical connection and setup only by authorized personnel possessing the following
knowledge:
- specialist knowledge in handling safety components
- knowledge about the applicable EMC regulations
- knowledge about the applicable regulations on occupational safety and accident prevention.
Ì The number of teach-in and switching operations is saved in the internal memory of the evaluation
unit. If necessary, this memory can be read by the manufacturer.
Important!
Prior to use, read the operating instructions and keep these in a safe place. Ensure the operating instructions are always available during mounting, setup and servicing. EUCHNER cannot provide any warranty in relation to the readability of the CD for the storage period required. For this reason you should archive a printed copy of the operating instructions. You can download the operating instructions from www.EUCHNER.de.
Page 8
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
8
(translation of the original operating instructions) 071873-15-07/15
6. Function
The safety system consists of three components:
Ì Coded actuator Ì Read head Ì Evaluation unit
1 read head can be connected to the evaluation unit.
The read heads and actuators are assigned to the device in a special teach-in operation.
Each delivered actuator possesses a unique electronic coding and so is a unique element in the system used. The code in an actuator cannot be reprogrammed.
The read head is fastened to the xed part of the safety guard and is connected to the evaluation unit via a two-core screened cable (terminals H11, H12 and SH1).
The actuator fastened to the movable part of the safety guard is moved towards the read head by closing the door. When the switch-on distance is reached, power is supplied to the actuator by the read head by induction and data can be transferred. The read code is compared with the taught-in code in the evaluation unit.
If all data for match, the door monitoring output OUT (semiconductor output) is set to HIGH and the safety outputs (relay output) are enabled. The OUT LED illuminates.
Due to the combination of dynamic polling of the actuators and the redundant, diverse design of the safety electronics with redundantly controlled safety outputs, the evaluation unit will enter the safe state with every detectable fault.
When a safety guard is opened, the safety outputs switch off the safety circuit and the OUT LED goes out. The state of the safety outputs is monitored internally by positively driven NC contacts (relay output).
Independent of the switching state of the safety circuit, the position of the safety door can be polled via the output OUT.
If an internal fault occurs in the evaluation unit, the safety circuit is switched off, the diagnostic output (ERR) is set HIGH and the ERROR LED illuminates red.
The safety contacts on the safety switch CES can also switch small currents. This allows the user to connect the device directly to a safe control system.
Page 9
9
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
6.1. Block diagram CES-A-ABA-…
24V
TST
TST input not connected:
Operation without external testing
0V
OUT ERR GND
H11
10k
10k
H12
141323 24
SH1
DDSP
CPU-A CPU-B
KA
KB
white
brown
Screen connection
DDSP: Double Dynamic Safety Part with fault
monitoring of the actuator, read head and the cable to the read head
CES evaluation unit
Read head
Coded actuator
Trans-
ponder
Illustration: Actuator not in the operating distance
TST Test input (see 9.3.1. Self‑test with test input TST on page 16) OUT Door monitoring output (not a safety output) ERR Diagnostic output GND 0 V (connected internally to 0 V for the operating voltage) H11/H12 Read head connection SH1 Read head screen connection 13/14 Connection for relay contact A, safety relay enable 23/24 Connection for relay contact B, safety relay enable
Page 10
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
10
(translation of the original operating instructions) 071873-15-07/15
7. Mounting
NOTICE
Device damage due to improper installation or unsuitable ambient conditions.
Ì Read heads and actuators must not be used as a mechanical end stop. Ì Observe EN ISO 14119:2013, sections 5.2 and 5.3, for information about fastening the safety
switch and the actuator.
Ì Observe EN ISO 14119:2013, section 7, for information about reducing the possibilities for by-
passing an interlocking device.
Ì The evaluation unit must be mounted in a control cabinet with a minimum degree of protection of
IP54. A snap-in element on the rear of the device is used for fastening to a mounting rail.
Ì If several evaluation units are mounted side by side in a control cabinet without air circulation
(e.g.fan), a minimum distance of 10mm must be maintained between the evaluation units. This distance enables the heat from the evaluation unit to dissipate.
Important!
Ì From the assured switch-off distance S
ar
, the safety outputs are safely shut down.
Ì When mounting several read heads, observe the stipulated minimum distance to avoid mutual in-
terference.
- For CES-A-LNA/-LCA s
min
=50mm
- For CES-A-LMN s
min
=20mm
- For CES-A-LQA s
min
=80mm
s
min
Ì If the actuator is installed ush, the switching distance changes as a function of the installation
depth and the safety guard material.
Operating
distance
Actuator
Operating
distance
Actuator
Flush mounting Surface mounting
Note the following points:
Ì Actuator and read head must be tted so that
- the front faces are at the minimum switch-on distance 0.8xSao or closer when the safety guard is closed (see section Operating distances). To avoid entering the area of possible side lobes, a minimum distance is to be maintained in case of a side approach direction. See section Typical operating distance for the related actuator.
- a hazard is excluded until the assured switch-off distance (Sar) is reached when the safety guard is open.
- the actuator is positively mounted on the safety guard, e.g.by using the safety screws included.
- they cannot be removed or tampered with using simple means.
Ì Pay attention to the maximum tightening torque for the read head or safety switch and actuator mountings of 1Nm. For
read heads/actuators made of PE-HD, the maximum tightening torque is only 0.5Nm.
Page 11
11
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
8. Electrical connection
WARNING
In case of an error, loss of the safety function through incorrect connection.
Ì Monitoring outputs must not be used as safety outputs. Ì Lay the connection cables with protection to prevent the risk of short circuits.
NOTICE
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Ì All the electrical connections must either be isolated from the mains supply by a safety transform-
er according to IEC 61558-2-6 with limited output voltage in the event of a fault, or by other equiv­alent isolation measures.
Ì All electrical outputs must have an adequate protective circuit for inductive loads. The outputs
must be protected with a free-wheeling diode for this purpose. The switch-on current may have to be limited for capacitive loads.
Ì The tightening torque for the screws on the connection terminals must be 0.6…0.8Nm. Ì The connection cable for the read heads must only be extended using EUCHNER plug connectors,
and adequate consideration must be given to EMC. Intermediate terminals must not be used.
Ì The screen on the connection cable for the read head must be connected to the appropriate termi-
nal SH on the evaluation unit. The portion of cable from which insulation is stripped should be kept as short as possible (max. 3cm).
8.1. Notes about
Important!
Ì For use and operation as per the requirements
1)
, a power supply with the feature “for use in
class 2 circuits” must be used. Alternative solutions must comply with the following requirements: a) Electrically isolated power supply unit with a max. open-circuit voltage of 30V/DC and a limited
current of max. 8A.
b) Electrically isolated power supply unit in combination with fuse as per UL248. This fuse should be
designed for max. 3.3A and should be integrated into the 30VDC voltage section.
Ì Use cable material made of copper wire with a temperature resistance of at least 75°C.
1) Note on the scope of the UL approval: The devices are tested according to the requirements of UL508 and CSA/ C22.2 no. 14 (protection against electric shock and re).
8.2. Safety in case of faults
Ì The operating voltage U
B
is reverse polarity protected.
Ì The connections for the read heads, ERR and OUT are not short circuit-proof. Ì A short circuit between 13/14 and 23/24 can be detected only by means of external pulsing. Ì A short circuit in the cable can be excluded by laying the cable with protection.
8.3. Fusing of the power supply and the safety contacts
Ì Provide external contact fuses (6AgG fuse or 6A circuit breaker, characteristic B or C) for relay outputs. Ì The power supply must be protected with a max. 8A fuse ahead of terminal U
B
.
Page 12
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
12
(translation of the original operating instructions) 071873-15-07/15
8.4. Correct connection
Important!
Ì To ensure safety, both safety outputs (13/14 and 23/24) must be evaluated. Ì To achieve category3 according to ENISO13849-1, it is necessary to monitor the downstream
contactors.
M
Monitoring output
(no safety function!)
Relay K
A
Relay K
B
+ 24 V
+ 24 V
To the control system
+ 24 V
0 V
24 V
OUT
14
13
24
23
Application
CES-A-ABA...
WARNING
In case of an error, loss of the safety function through incorrect connection.
Ì To ensure safety, both safety outputs (13/14 and 23/24) must always be evaluated. Sin-
gle-channel use of the safety outputs leads to a reduction of the category in accordance with EN ISO 13849-1.
M
Monitoring output
(no safety function!)
Relay K
A
Relay K
B
+ 24 V
To the control system
0 V
24 V
OUT
14
13
24
23
Application
CES-A-ABA...
+ 24 V
Page 13
13
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
8.5. Connection example CES-A-ABA-01B
24 VDC
GND
-F1
CES-A-ABA-01B
083513
0V
TST
-F2
24V
OUT ERR
-V1
SH1
GND
-K1
Read­head
H11
Trans­ponder
23
H12
24
-V2
EUCHNER
13 14
-K2
L1
-K2
13
14
-K1
13
14
M
3
~
-M1
L2
23
24
23
24
L3
33
34
33
34
Important!
To achieve category 4 according to EN ISO 13849-1, it is necessary to monitor the downstream contactors (here: contacts of -K3 and -K4 in the feedback loop).
This example shows only an excerpt that is relevant for connection of the CES system. The example illustrated here does not show complete system planning. The user is responsible for safe integration in the overall system.
Page 14
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
14
(translation of the original operating instructions) 071873-15-07/15
9. Setup
9.1. LED indicators
Designation Color Signicance
STATE green State display (multifunction display using ashing modes)
OUT yellow Safety circuit closed
ERROR Red
Ì Operating fault or Ì External fault (fault in the feedback loop) or Ì Teach-in operation not valid or Ì Internal device fault or Ì TST input activated (function test active)
9.2. Teach-in operation
The actuator must be assigned to the evaluation unit using a teach-in function before the system forms a functional unit.
During the teach-in operation the safety outputs are open and the door monitoring output LOW. The system is in the safe state.
Important!
Ì The teach-in operation can differ for read heads that are not described in this document. Observe
the information in the operating instructions for the read head used.
Ì During the teach-in operation the following conditions must be met:
- There must be no state change, e.g.opening a safety door or closing a further safety door.
- The power supply must not be switched off.
Ì If these conditions are not met, the evaluation unit switches to the safe fault state (ERROR LED
illuminates) and signals this operating fault with the STATE LED by three short ashes that are re­peated every second. The teach-in operation must be repeated.
Ì Repeated teach-in of the same actuator on the same evaluation unit is not possible. Ì The number of teach-in operations on one evaluation unit is limited to a maximum of 8 Ì The evaluation unit can only be operated with the last actuator taught Ì Actuators cannot be interchanged without a renewed teach-in operation. Ì An actuator that has not been subjected to teach-in will not be detected by the related read head. Ì Even if only one new actuator needs to be taught, a complete new teach-in operation must be car-
ried out as described in the section Setup.
Ì When the evaluation unit is switched on (operating voltage is applied), the STATE LED signals the
number of possible remaining teach-in operations (see system status table)
Ì After the eighth teach-in operation or if an "old" actuator is placed against the read head, the sys-
tem automatically switches to the teach-in mode. In both cases, a teach-in operation with a dura­tion of 60 seconds is started; however, the last actuator code remains active (see system status table) in the memory – a new code is not taught.
Page 15
15
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
9.2.1. Carrying out teach-in for rst actuator (default setting on delivery)
To trigger the rst teach-in operation, the user must perform the following actions in the stipulated order:
1. Start teach-in operation
- Switch on operating voltage (STATE LED ashes at approx. 4Hz)
- Close door to be monitored (the actuator must be in the operating distance of the read head)
- Teach-in operation starts (STATE LED ashes at approx. 1Hz)
- Wait for acknowledgment of the teach-in operation (STATE LED goes out after approx. 60 seconds)
2. End teach-in operation
- Interrupt operating voltage for at least 10 seconds (code for the actuator taught-in is activated)
3. Check safety guard for effectiveness
9.2.2. Carrying out teach-in for a new actuator
A maximum of 8 teach-in operations can be undertaken. The number of teach-in operations already undertaken is signaled after step 6 via the ashing sequence on the STATE LED (see 10. System status table on page 17, section State indication).
Faulty actuators can be replaced. Then a complete teach-in operation must be performed as per this section.
To trigger a further teach-in operation, the user must perform the following actions in the stipulated order:
1. Start teach-in operation
- Switch on operating voltage
- Close door to be monitored (the new actuator must be in the operating distance of the read head)
- Teach-in operation starts (STATE LED ashes at approx. 1Hz)
- Wait for acknowledgment of the teach-in operation (STATE LED goes out after approx. 60 seconds)
2. End teach-in operation
- Interrupt operating voltage for at least 10 seconds (code for the new actuator taught-in is activated)
The newly taught-in actuator is saved and the old actuator deactivated.
3. Check safety guard for effectiveness
Page 16
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
16
(translation of the original operating instructions) 071873-15-07/15
9.3. Functional check
After installation and any fault, the safety function must be fully checked. Proceed as follows:
WARNING
Danger of fatal injury as a result of faults in installation and functional check.
Ì Before carrying out the functional check, make sure that there are no persons in the danger area. Ì Observe the valid accident prevention regulations.
1. Switch on operating voltage.
- The safety switch carries out a self-test. The green STATE LED ashes up to three times. The STATE LED then illuminates continuously. The OUT and ERROR LEDs do not light up.
2. Close all safety guards.
- The machine must not start automatically.
- The green STATE LED and the yellow OUT LED light up continuously.
3. Enable operation in the control system.
4. Open the safety guard.
- The machine must switch off and it must not be possible to start it as long as the safety guard is open.
- The green STATE LED illuminates continuously; the OUT and ERROR LEDs do not illuminate.
Repeat steps 2…4 separately for each safety guard.
9.3.1. Self-test with test input TST
On electromechanical safety switches or magnetic switches, the function test can be performed by cyclically opening the safety guard.
From category 2 according to ENISO13849-1 and in accordance with EN 60204-1 : 1997 (chapter 9.4.2.4), a function test must be performed on the entire safety system on start-up or after dened intervals.
Testing of the internal function of the unit is not necessary because the device monitors itself in real time. Welding of an output contact (relay output) is detected by the device at the latest the next time the safety guard is opened. A short circuit in the output cable is not detected by the device.
In addition, the entire safety circuit can be tested without opening the safety guard. For this purpose, opening of the safety guard can be simulated by applying 24 V DC to the test input TST.
The safety outputs are switched off, enabling testing of the complete safety circuit. The diagnostic output ERR on the eval­uation unit is also set HIGH as a monitoring function.
When test input TST is reset, the evaluation unit resets the diagnostic output ERR to LOW, the red LED switches off and normal operation is continued.
Important!
After the self-test, the test input TST must be connected to 0 V again or must be disconnected.
Page 17
17
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
10. System status table
Operating mode
Actuator/
guard position
Safety outputs A and B
PLC
LED indicator
output
State
In-
put
Output
TST
OUT (status signal)
ERR
STATE (green)
OUT (yellow)
ERROR (red)
Normal operation
closed on N 1 0 Normal operation, door closed
open off N 0 0 Normal operation, door open
Setup
open off N 0 0 4 Hz Initial setup after delivery, ready for rst teach-in operation
closed off N 0 0
1 Hz
(60 s)
Teach-in operation
closed off N 0 0
Positive acknowledgment of completion of teach-in operation To activate the actuator code from the teach-in operation in the evaluation unit, the operating voltage must then be switched off at the evaluation unit for min. 3 seconds.
State indication
X off X 0 0
3 x +
Indication after 1st to 5th teach-in operation
X off X 0 0
2 x +
Indication of the remaining teach-in operations after the 6th teach­in operation
X off X 0 0
1 x +
Indication of the remaining teach-in operations after the 7th teach­in operation
X off X 0 0 Device cannot perform any further teach-in operation
Fault display X off N 0 1
Device-internal component failure or excessively high external interference (EMC)
Operating fault
closed off N 0 1 1 x Incorrect 9th teach-in operation
closed off N 0 1 2 x Incorrect teach-in operation for an old actuator
closed off N 0 1 3 x
Negative acknowledgement for teach-in operation. Actuator was held in front of the read head for less than 60 s
Test operation
open off 1 0 1
closed off 1 0 1
External device test to "OPEN" and function of ERR output with door closed
Key to symbols
N 0 Volt or not connected
1 24 Volt
0 0 Volt
LED not illuminated
LED illuminated
1 Hz (60 s)
LED ashes for 60 seconds at 1 Hz
3 x +
LED ashes three times and then illuminates continuously
3 x
LED ashes three times, and this is then repeated
X Any state
Important!
If you do not nd the displayed device status in the System status table, this indicates an internal device fault. In this case, you should contact the manufacturer.
Page 18
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
18
(translation of the original operating instructions) 071873-15-07/15
11. Technical Data
11.1. Evaluation unit CES-A-ABA-...
Ì Housing for rail mounting, IP20 Ì Relay output Ì 1 read head can be connected
Dimension drawing
CES
STATE
OUT
ERROR
114
22,5
99
13 14 23 24
GNDERROUTTST
24V 0V
H11 H12
SH1
Suitable for standard 35 mm mounting rail
Switching characteristics
Ì 2 safety outputs with
one NO contact each (relay outputs)
Ì 1 door monitoring output (
semiconductor output, not a safety output)
Approvals
Safety guard
closed
(actuator detected)
open
(actuator not in the operating
distance)
Read head Actuator Read head
13
14
23
24
24 VOUT
13
14
23
24
24
VO
UT
Page 19
19
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
Technical data CES-A-ABA-01B
Parameter
Value
Unit
min. typ. max.
Housing material PA6.6 plastic Dimensions 114x99x22.5 mm Weight 0.2 kg Ambient temperature at UB=DC 24 V -20 - +55 °C Atmospheric humidity, not condensing - - 80 % Degree of protection IP20 Degree of contamination 2 Mounting Mounting rail 35mm according to DIN EN 60715 Number of read heads 1 read head per evaluation unit Connection (plug-in screw terminals/coded) 0.14 - 2.5 mm² Operating voltage UB (regulated, residual ripple < 5 %) 21 24 27 V DC
For the approval according to the following applies
Operation only with UL class 2 power supply or equivalent measures
Current consumption IB (with relay energized)
1)
- 150 - mA External fuse (operating voltage UB) 0.25 - 8 A Safety contacts 2 (relays with internally monitored contacts) Switching current (relay outputs)
mA
- at switching voltage AC/DC 21…60 V
1 - 300
- at switching voltage AC/DC 10…30 V
10 - 6000
Switching load according to
Max. AC 30 V, class 2/max. DC 60 V, class 2
External fuse (safety circuit) according to EN60269-1 6 A gG or 6 A circuit breaker (characteristic B or C) Utilization category according to EN60947-5-1 AC-12 60 V 0.3 A/DC-12 60 V 0.3 A
AC-12 30 V 4 A/DC-12 30 V 6 A AC-14 30 V 2 A/DC-13 24 V 3 A
Rated insulation voltage U
i
63 V
Rated impulse withstand voltage U
imp
1.5 kV Rated conditional short-circuit current 100 A Resilience to vibration In acc. with EN60947-5-2 Mechanical operating cycles (relays) 10x10
6
Switching delay from state change
2)
- - 180 ms Discrepancy time (of the switching points of both relays) - - 120 ms Ready delay
3)
- - 3 s Dwell time
4)
0.5 - - s
Switching frequency max.
5)
- - 1 Hz Repeat accuracy R acc. to ENIEC60947-5-3 10 % Monitoring outputs (diagnostics ERR, door monitoring output
OUT, semiconductor output, p-switching)
6)
- Output voltage 0.8xU
B
- U
B
V DC
- Max. load - - 20 mA Test input TST
- Input voltage LOW 0 - 2
V DC
HIGH 15 - U
B
- Input current HIGH 5 8 10 mA EMC protection requirements In acc. with EN60947-5-3
Reliability values acc. to ENISO13849-1 as a function of the switching current at 24 V DC 0.1 A 1 A 3 A
Category 3 Performance Level (PL) e PFH
d
4.3x10
-8
Mission time 20 years Number of switching cycles/year 760 000 153 000 34 600 Diagnostic coverage DC 90 % MTTF
d
100 years
1) Without taking into account the load currents on the monitoring outputs.
2) Corresponds to the risk time according to EN60947-5-3. This is the maximum switch-off delay for the safety outputs following removal of the actuator.
3) After the operating voltage is switched on, the relay outputs are switched off and the door monitoring output is set to LOW potential during the ready delay.
4) The dwell time of an actuator inside and outside the operating distance must be at least 0.5s to ensure reliable detection of internal faults in the evaluation unit (self-monitoring).
5) If the current load is >100mA, a switching frequency of 0.1 Hz should not be exceeded as this will affect the mechanical life of the relay contacts.
6) Not short circuit-proof.
Page 20
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
20
(translation of the original operating instructions) 071873-15-07/15
11.2. Read head CES-A-LNA-…
Ì Cube-shaped design 42x25mm Ì Hard-wired cable
Dimension drawing
CES-A-L XXXXXX
25
8
4,5
42
32
±0,1
12
4,6
"l"
2 safety screws M4X14 included Active face Active face
Typical operating distance
With evaluation unit CES-A-ABA-01 and actuator CES-A-BBA
-8
-4-6-2
2
648
0
2
4
6
8
Centre offset m [mm]
Distance s [mm]
OFF
ON
Actuator
Read head
s
m
Hysteresis
Switch-on distance
ON
OFF
Hysteresis
Distance sS
ao
Output stage
Switch-off distance
OFF
With evaluation unit CES-A-ABA-01B and actuator CES-A-BBA
Side lobe
N
-10-15 -5 0 Centre offset m [mm]
Distance s [mm]
OFF
ON
Switch-on distance
ON
OFF
Hysteresis
Distance sS
ao
Output state
Switch-off distance
OFF
Hysteresis
-20 5 201510
5
10
15
20
Side lobe
N
Actuator
Read head
s
m
NOTICE
For a side approach direction for the actuator and read head, a minimum distance of s=3mm must be maintained so that the operating distance of the side lobes is not entered.
Approvals
Page 21
21
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
Terminal assignment
Read head with connection cable
H11
H12SH1
BN
WH
Screen
Read head
Evaluation unit CES-A-ABA-…
Technical data
Parameter Value Unit
min. typ. max.
Housing material Fortron, reinforced thermoplastic, fully encapsulated Dimensions 42 x 25 x 12 mm Weight (incl. 10 m cable) 0.3 kg Ambient temperature -25 - +70 °C Degree of protection IP67/IP69K Installation position Any Method of operation Inductive Power supply Via evaluation unit
In combination with actuator CES-A-BBA on evaluation unit CES-A-ABA-01
Assured switch-off distance Sar - - 23
mm
Operating distance for center offset m = 0
1)
- Switch-on distance - 6 -
- Assured switch-on distance S
ao
5 - -
- Switching hysteresis 0.5 1.5 -
In combination with actuator CES-A-BBA on evaluation unit CES-A-ABA-01B
Assured switch-off distance S
ar
- - 32
mm
Operating distance for center offset m = 0
2)
- Switch-on distance - 15 -
- Assured switch-on distance S
ao
10 - -
- Switching hysteresis 0.5 2 ­Minimum distance s for side approach direction - 3 -
In combination with actuator CES-A-BDA on evaluation unit CES-A-ABA-01
Assured switch-off distance Sar - - 24
mm
Operating distance for center offset m = 0
3)
- Switch-on distance - 7 -
- Assured switch-on distance S
ao
6 - -
- Switching hysteresis 0.5 1.5 ­Minimum distance s for side approach direction - 1 -
Installation in steel, surface/ush
Assured switch-off distance Sar - - 24
mm
Operating distance for center offset m = 0
- Switch-on distance - 4.4 / 3.6 -
- Assured switch-on distance S
ao
3.6 / 3 - -
- Switching hysteresis 0.4 / 0.3 1.2 / 1.0 ­Minimum distance s for side approach direction - 1 -
Installation in stainless steel, surface/ush
Assured switch-off distance Sar - - 24
mm
Operating distance for center offset m = 0
- Switch-on distance - 4 / 3.3 -
- Assured switch-on distance S
ao
3.3 / 2.7 - -
- Switching hysteresis 0.4 / 0.3 1.1 / 0.9 ­Minimum distance s for side approach direction - 1 -
In combination with actuator CES-A-BDA on evaluation unit CES-A-ABA-01B
Assured switch-off distance S
ar
- - 33
mm
Operating distance for center offset m = 0
3)
- Switch-on distance - 16 -
- Assured switch-on distance S
ao
11 - -
- Switching hysteresis 0.5 2 ­Minimum distance s for side approach direction - 4 ­Connection cable Hard-wired encapsulated connection cable, with crimped ferrules
PVC, 4.6 mm
PUR, 4.8 mm, suitable for drag chain
Cable length - - 25 m
1) These values apply to ush installation of the read head and the actuator in aluminum.
2) These values apply to surface installation of the read head and the actuator.
3) These values apply to non-metallic surrounding material. Other materials on request.
Page 22
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
22
(translation of the original operating instructions) 071873-15-07/15
11.3. Read head CES-A-LNA-SC
Ì Cube-shaped design 42x25mm Ì M8 plug connector (snap-action and screw terminals)
Dimension drawing
5,5
10
6,8
8
4,5
4,6
12
25
min.38
32
±0,1
4232,6
A0
CES-A-L 077715
3
4
1
A0
CES-A-L 077715
20 1,
26,5
2 safety screws M4X14 included
Cable outlet with angled connector
Active face
Active face
Typical operating distance
With evaluation unit CES-A-ABA-… and actuator CES-A-BBA
-8
-4-6-2
2
648
0
2
4
6
8
Centre offset m [mm]
Distance s [mm]
OFF
ON
Actuator
Read head
s
m
Hysteresis
Switch-on distance
ON
OFF
Hysteresis
Distance sS
ao
Output stage
Switch-off distance
OFF
Approvals
Page 23
23
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
With evaluation unit CES-A-ABA-01B and actuator CES-A-BBA
Side lobe
N
-10-15 -5 0 Centre offset m [mm]
Distance s [mm]
OFF
ON
Switch-on distance
ON
OFF
Hysteresis
Distance sS
ao
Output state
Switch-off distance
OFF
Hysteresis
-20 5 201510
5
10
15
20
Side lobe
N
Actuator
Read head
s
m
NOTICE
For a side approach direction for the actuator and read head, a minimum distance of s=3mm must be maintained so that the operating distance of the side lobes is not entered.
Terminal assignment
Read head with plug connector
H11H12 SH1
1
3
4
BN
WH
Screen
View on the plug connector of the
read head
Evaluation unit
CES-A-ABA-…
Page 24
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
24
(translation of the original operating instructions) 071873-15-07/15
Technical data
Parameter Value Unit
min. typ. max.
Housing material Fortron, reinforced thermoplastic, fully encapsulated Dimensions 42 x 25 x 12 mm Weight (incl. 10 m cable) 0.3 kg Ambient temperature -25 - +70 °C Degree of protection IP67/IP69K Installation position Any Method of operation Inductive Power supply Via evaluation unit
In combination with actuator CES-A-BBA on evaluation unit CES-A-ABA-01
Assured switch-off distance Sar - - 23
mm
Operating distance for center offset m = 0
1)
- Switch-on distance - 6 -
- Assured switch-on distance S
ao
5 - -
- Switching hysteresis 0.5 1.5 -
In combination with actuator CES-A-BBA on evaluation unit CES-A-ABA-01B
Assured switch-off distance S
ar
- - 32
mm
Operating distance for center offset m = 0
2)
- Switch-on distance - 15 -
- Assured switch-on distance S
ao
10 - -
- Switching hysteresis 0.5 2 ­Minimum distance s for side approach direction - 3 -
In combination with actuator CES-A-BDA on evaluation unit CES-A-ABA-01
Assured switch-off distance Sar - - 24
mm
Operating distance for center offset m = 0
3)
- Switch-on distance - 7 -
- Assured switch-on distance S
ao
6 - -
- Switching hysteresis 0.5 1.5 ­Minimum distance s for side approach direction - 1 -
Installation in steel, surface/ush
Assured switch-off distance Sar - - 24
mm
Operating distance for center offset m = 0
- Switch-on distance - 4.4 / 3.6 -
- Assured switch-on distance S
ao
3.6 / 3 - -
- Switching hysteresis 0.4 / 0.3 1.2 / 1.0 ­Minimum distance s for side approach direction - 1 -
Installation in stainless steel, surface/ush
Assured switch-off distance Sar - - 24
mm
Operating distance for center offset m = 0
- Switch-on distance - 4 / 3.3 -
- Assured switch-on distance S
ao
3.3 / 2.7 - -
- Switching hysteresis 0.4 / 0.3 1.1 / 0.9 ­Minimum distance s for side approach direction - 1 -
In combination with actuator CES-A-BDA on evaluation unit CES-A-ABA-01B
Assured switch-off distance S
ar
- - 33
mm
Operating distance for center offset m = 0
3)
- Switch-on distance - 16 -
- Assured switch-on distance S
ao
11 - -
- Switching hysteresis 0.5 2 ­Minimum distance s for side approach direction - 4 ­Connection M8 plug connector (snap-action and screw terminals), 3-pin Connection cable - - 25 m
1) These values apply to ush installation of the read head and the actuator in aluminum.
2) These values apply to surface installation of the read head and the actuator.
3) These values apply to non-metallic surrounding material. Other materials on request.
Page 25
25
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
11.4. Read head CES-A-LCA-…
Ì Cube-shaped design 42x25mm Ì PE-HD plastic housing material, suitable for use in aggressive media (e.g.acids, alkalis)
Dimension drawing
32
42
48
25
31
l
12
14
4,6
8
4,5
± 0,1
Active face
Active face
2 safety screws M4X14 included
Flat seal
NOTICE
The at seal provided must be used during assembly.
Typical operating distance
With evaluation unit CES-A-ABA-01 and actuator CES-A-BCA
-8
-4-6-2
2
648
0
2
4
6
8
Centre offset m [mm]
Distance s [mm]
OFF
ON
Actuator
Read head
s
m
Hysteresis
Switch-on distance
ON
OFF
Hysteresis
Distance sS
ao
Output stage
Switch-off distance
OFF
With evaluation unit CES-A-ABA-01B and actuator CES-A-BCA
Side lobe
N
-10-15 -5 0 Centre offset m [mm]
Distance s [mm]
OFF
ON
Switch-on distance
ON
OFF
Hysteresis
Distance sS
ao
Output state
Switch-off distance
OFF
Hysteresis
-20 5 201510
5
10
15
20
Side
lobe
N
Actuator
Read head
s
m
NOTICE
For a side approach direction for the actuator and read head, a minimum distance of s=3mm must be maintained so that the operating distance of the side lobes is not entered.
Approvals
Page 26
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
26
(translation of the original operating instructions) 071873-15-07/15
Terminal assignment
Read head with connection cable
H11
H12SH1
BN
WH
Screen
View
on plug connector
of the read head
Evaluation unit CES-A-ABA-…
Read head
Technical data
Parameter Value Unit
min. typ. max.
Housing material PE-HD plastic without reinforcement, fully encapsulated Flat seal material Fluororubber 75 FPM 4100 Dimensions 42 x 25 x 12 mm Weight (incl. 10 m cable) 0.3 kg Ambient temperature -25 - +50 °C Degree of protection IP67/IP69K Installation position Any Method of operation Inductive Power supply Via evaluation unit
In combination with actuator CES-A-BBA on evaluation unit CES-A-ABA-01
Assured switch-off distance Sar - - 23
mm
Operating distance for center offset m = 0
1)
- Switch-on distance - 6 -
- Assured switch-on distance S
ao
5 - -
- Switching hysteresis
0.5 1.5 -
In combination with actuator CES-A-BBA on evaluation unit CES-A-ABA-01B
Assured switch-off distance S
ar
- - 32
mm
Operating distance for center offset m = 0
2)
- Switch-on distance - 15 -
- Assured switch-on distance S
ao
10 - -
- Switching hysteresis 0.5 2 ­Minimum distance s for side approach direction - 3 -
In combination with actuator CES-A-BDA on evaluation unit CES-A-ABA-01
Assured switch-off distance Sar - - 24
mm
Operating distance for center offset m = 0
3)
- Switch-on distance - 7 -
- Assured switch-on distance S
ao
6 - -
- Switching hysteresis 0.5 1.5 ­Minimum distance s for side approach direction - 1 -
Installation in steel, surface/ush
Assured switch-off distance Sar - - 24
mm
Operating distance for center offset m = 0
- Switch-on distance - 4.4 / 3.6 -
- Assured switch-on distance S
ao
3.6 / 3 - -
- Switching hysteresis 0.4 / 0.3 1.2 / 1.0 ­Minimum distance s for side approach direction - 1 -
Installation in stainless steel, surface/ush
Assured switch-off distance Sar - - 24
mm
Operating distance for center offset m = 0
- Switch-on distance - 4 / 3.3 -
- Assured switch-on distance S
ao
3.3 / 2.7 - -
- Switching hysteresis 0.4 / 0.3 1.1 / 0.9 ­Minimum distance s for side approach direction - 1 -
In combination with actuator CES-A-BDA on evaluation unit CES-A-ABA-01B
Assured switch-off distance S
ar
- - 33
mm
Operating distance for center offset m = 0
3)
- Switch-on distance - 16 -
- Assured switch-on distance S
ao
11 - -
- Switching hysteresis 0.5 2 ­Minimum distance s for side approach direction - 4 ­Connection cable Hard-wired encapsulated connection cable, with crimped ferrules
PVC, 4.6 mm
Cable length - - 25 m
1) These values apply to ush installation of the read head and the actuator in aluminum
2) These values apply to surface installation of the read head and the actuator.
3) These values apply to non-metallic surrounding material. Other materials on request.
Page 27
27
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
Read head CES-A-LQA-SC
Ì Cube-shaped design 50x50mm Ì M8 plug connector (snap-action and screw terminals)
Dimension drawing
40
±0,15
50
0,25
0
M8
40
±0,15
50
0,25
0
20
7
6
20,2
Ø 4,5
-
x1
-
Active face
Typical operating distance
10
-30
20
30
Z
Y
10
20
30
-30
30
20
10
X
With actuator CES-A-BBA or CES-A-BCA
10
20
30
Y
10
20
30
20
10
X
30
Z
With actuator CES-A-BQA on evaluation unit CES-A-ABA-01B
Terminal assignment
Read head with connection cable
H11 H12 SH1
BN
WH
1
4
3
Screen
Read head
Evaluation unit
CES-A-ABA-…
Approvals
Page 28
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
28
(translation of the original operating instructions) 071873-15-07/15
Technical data
Parameter Value Unit
min. typ. max.
Housing material Fortron, reinforced thermoplastic, fully encapsulated Dimensions 50x50x20.2 mm Weight 0.08 kg Ambient temperature -25 - +70 °C Degree of protection IP67 Installation position Any Method of operation Inductive Power supply Via evaluation unit
In combination with actuator CES-A-BBA or CES-A-BCA
Assured switch-off distance S
ar
- - 47
mm
Operating distance for center offset m=0
1)
- Switch-on distance - 15 -
- Assured switch-on distance S
ao
10 - -
- Switching hysteresis 2 3 -
In combination with actuator CES-A-BQA on evaluation unit CES-A-ABA-01B
Assured switch-off distance Sar - - 60
mm
Operating distance with vertical approach direction Center offset m=0
1)
- Switch-on distance - 23 -
- Assured switch-on distance S
ao
16 - -
- Switching hysteresis 2 3 ­Operating distance with side approach direction Distance in x direction=10mm
- Switch-on distance - 28 -
- Assured switch-on distance S
ao
24 - -
- Switching hysteresis 1 1.3 ­Connection cable
- - 25 m
1) These values apply to surface installation of the read head and the actuator.
Page 29
29
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
11.5. Read head CES-A-LMN-SC
Ì Cylindrical design M12 Ì M8 plug connector (snap-action and screw terminals)
Dimension drawing
17
5
32
19,7
s
m
35
4
8
30
M12x 1
M8x1
37
1)
1)
Reading distance
Centre offset
connected
Active face
1) Clear zone (area of the active face without metal housing)
NOTICE
The read head is allowed to be installed as a maximum up to the clear zone (area of the active face without metal housing).
Typical operating distance
With evaluation unit CES-A-ABA-01 and actuator CES-A-BMB
-4
-2-3-1
1
324
0
1
2
3
4
Centre offset m [mm]
Distance s [mm]
OFF
ON
Actuator
Read head
s
m
Hysteresis
Switch-on distance
ON
OFF
Hysteresis
Distance sS
ao
Output state
Switch-off distance
OFF
Approvals
Page 30
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
30
(translation of the original operating instructions) 071873-15-07/15
With evaluation unit CES-A-ABA-01B and actuator CES-A-BMB
-4-6 -2 0 Centre offset m [mm]
Distance s [mm]
OFF
ON
Switch-on distance
ON
OFF
Hysteresis
Distance sS
ao
Output state
Switch-off distance
OFF
-8 2 864
2
4
6
8
Actuator
Read
head
s
m
not permissible area not permissible area
Hysteresis
NOTICE
A minimum distance of s=1.2mm must be maintained.
Terminal assignment
Read head with plug connector
H11H12 SH1
1
3
4
BN
WH
Screen
View on the plug connector of the
read head
Evaluation unit
CES-A-ABA-…
Technical data
Parameter Value Unit
min. typ. max.
Housing material Nickel-plated CuZn housing sleeve
Plastic PBT GF20 cap Dimensions M12 x 1, length 38 mm Weight (incl. 10 m cable) 0.2 kg Ambient temperature -25 - +70 °C Ambient pressure (only of active face in installed condition) - - 10 bar Degree of protection IP67 Installation position Any Method of operation Inductive Power supply Via evaluation unit
In combination with actuator CES-A-BMB on evaluation unit CES-A-ABA-01
Assured switch-off distance Sar - - 8.5
mm
Operating distance for center offset m = 0
1)
- Switch-on distance - 2.5 -
- Assured switch-on distance S
ao
1.6 - -
- Switching hysteresis 0.2 0.3 -
In combination with actuator CES-A-BMB on evaluation unit CES-A-ABA-01B
Assured switch-off distance S
ar
- - 10
mm
Operating distance for center offset m = 0
1)
- Assured switch-off distance S
ar
- - 10
- Switch-on distance - 5 -
- Assured switch-on distance S
ao
3.5 - -
- Switching hysteresis 0.1 0.3 ­Connection M8 plug connector (snap-action and screw terminals), 3-pin Connection cable - - 15 m
1) These values apply to surface installation of the read head in steel.
Page 31
31
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
11.6. Actuator CES-A-BBA/CES-A-BCA
Ì Cube-shaped design 42x25mm Ì CES-A-BCA suitable for use in aggressive media (e.g.acids, alkalis) Ì In combination with read head CES-A-LNA…/CES-A-LCA…
Dimension drawing for CES-A-BBA
CES-A-B 071840
25
ø8
ø4,5
42
32
±0,1
12
4,6
Active face
Active face
2 safety screws M4X14 included
Dimension drawing for CES-A-BCA
42
32
± 0,10
25
31
48
4,5
8
212
4,6
Active face
Active face
2 safety screws M4X14 included
Flat seal
NOTICE
CES-A-BCA: The at seal provided must be used during assembly.
Technical data
Parameter
Value
Unit
min. typ. max.
Housing material
- CES-A-BBA Fortron, reinforced thermoplastic, fully encapsulated
- CES-A-BCA PE-HD plastic without reinforcement, fully encapsulated Flat seal material (CES-A-BCA only) Fluororubber 75 FPM 4100 Dimensions 42x25x12 mm Weight 0.02 kg Ambient temperature
°C
- CES-A-BBA -25 - +70
- CES-A-BCA -25 - +50 Degree of protection IP67/IP69K Installation position Active face opposite read head Power supply Inductive via read head
Page 32
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
32
(translation of the original operating instructions) 071873-15-07/15
11.7. Actuator CES-A-BQA
Ì Cube-shaped design 50x50mm
Dimension drawing for CES-A-BQA
40
±0,15
50
0,25
0
40
±0,15
50
0,25
0
6
20,2
Ø 4,5
-
-
Active face
Technical data
Parameter
Value
Unit
min. typ. max. Housing material Fortron, reinforced thermoplastic, fully encapsulated Dimensions 50x50x20.2 mm Weight 0.07 kg Ambient temperature -25
- +70
°C
Degree of protection IP67
Installation position Active face opposite read head Power supply Inductive via read head
Page 33
33
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
11.8. Actuator CES-A-BDA
Ì Round design 20mm Ì In combination with read head CES-A-LNA…/CES-A-LCA…
Dimension drawing
20
2,2
Active face Active face
Technical data
Parameter
Value
Unit
min. typ. max. Housing material PC plastic Dimensions 20x2.2 mm Weight
0.0008 kg
Ambient temperature -25 - +70 °C Degree of protection IP67 Installation position Active face opposite read head Power supply Inductive via read head
Page 34
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
34
(translation of the original operating instructions) 071873-15-07/15
11.9. Actuator CES-A-BMB
Ì Cylindrical design M12x75 Ì In combination with read head CES-A-LMN-SC (operating distance on request for read head CES-A-LNA…/LCA…)
Dimension drawing
11
0,80
6
M12x0,75
Active face
NOTICE
Ì The actuator can be screwed into the M12x0.75 thread provided with the aid of an insertion tool
(order no. 037 662).
Ì Flush installation of the actuator in steel is permissible.
Technical data
Parameter
Value
Unit
min. typ. max. Housing material Stainless steel Dimensions M12x0.75, depth 6 mm Weight
0.002 kg
Ambient temperature -25 - +70 °C Degree of protection IP67 Installation position Active face opposite read head Power supply Inductive via read head
Page 35
35
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
12. Ordering information and accessories
Tip!
Suitable accessories, e.g. cables or assembly material, can be found at www.euchner.de. To order, enter the order number of your item in the search box and open the item view. Accessories that can be combined with the item are listed under “accessories”.
13. Inspection and service
WARNING
Loss of the safety function because of damage to the system. In case of damage, the related safety component must be replaced. The replacement of individual
parts in a safety component is not permitted.
Regular inspection of the following is necessary to ensure trouble-free long-term operation:
Ì Check the switching function (see section 9.3. Functional check on page 16) Ì Check the secure fastening of the devices and the connections Ì Check for soiling Ì Check for sealing of the plug connector on the safety switch Ì Check for loose cable connections on the plug connector Ì Check the switch-off distance
No servicing is required; repairs to the device are only allowed to be made by the manufacturer.
NOTICE
The year of manufacture can be seen in the lower right corner of the rating plate.
14. Service
If service support is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
D-70771 Leinfelden-Echterdingen
Service telephone:
+49 711 7597-500
E-mail:
support@euchner.de
Internet:
www.euchner.de
Page 36
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
36
(translation of the original operating instructions) 071873-15-07/15
15. Declaration of conformity
Page 37
37
071873-15-07/15 (translation of the original operating instructions)
Operating Instructions
EN
Page 38
Operating Instructions Non-Contact Safety System CES-A-ABA-01/CES-A-ABA-01B
38
(translation of the original operating instructions) 071873-15-07/15
Page 39
39
071873-15-07/15 (translation of the original operating instructions)