ETC UFD User Manual

Page 1
ETC Installation Guide
120VAC model
shown
Unison Foundry™ Phase-Adaptive Dimmer

Overview

The Unison Foundry Phase-Adaptive Dimmer provides control for 120V and 277V line voltage loads that require forward-phase or reverse-phase dimming, up to 600 watts.
The Phase-Adaptive Dimmer can be wired to individual fixtures or used for zone control, and automatically provides reverse-phase or forward-phase dimming based on the connected load type.
Control connected loads from any DMX control device. Configure the Phase­Adaptive Dimmer either remotely via RDM (using a tool like ETC Net3 Concert) or locally on the controller. See
Dimmer
on
page 6
.
Configure the Phase-Adaptive

Specifications

Ambient Environment

For indoor use only. Rated for plenum use.
• 32°F to 104°F (0°C to 40°C) operating temperatures in 5–95% non­condensing humidity.
Corporate Headquarters  Middleton, Wisconsin, USA  Tel +608 831 4116 Service (Americas)  service@etcconnect.com London, UK  Tel +44 (0)20 8896 1000  Service: (UK) service@etceurope.com Rome, IT  Tel +39 (06) 32 111 683 Service: (UK) service@etceurope.com Holzkirchen, DE  Tel +49 (80 24) 47 00-0  Service: (DE) techserv-hoki@etcconnect.com Hong Kong  Tel +852 2799 1220  Service: (Asia) service@etcasia.com Web: etcconnect.com  specifications subject to change.  7179M2100  Rev B  Released 2017-12
© 2017 Electronic Theatre Controls, Inc. 
ETC intends this document to be provided in its entirety.
Product information and
Page 2
ETC Installation Guide
Phase-Adaptive Dimmer

Electrical Specification

Two models are available:
• 120VAC, +/- 10% at 47–63Hz, maximum load 600W
• 277VAC, +/- 10% at 47–63Hz, maximum load 600W
Supported load types
• Tungsten
• 2-wire Fluorescent
•LED
• Electronic low voltage transformer
• Magnetic low voltage transformers (120V only, 300W maximum load). Transformers should be correctly loaded to their rated current.
CAUTION:
ETC does not support the use of the Phase-Adaptive Dimmer with magnetic loads at 277V.
Connecting underloaded magnetic transformers at 120V to the Phase-Adaptive Dimmer may result in damage to the Phase-Adaptive Dimmer. This damage is not covered under warranty.

Compliance

• UL and cUL listed
• Conforms to UL 916 (Energy Management Equipment) and UL 2043 (Plenum rated)
Phase-Adaptive Dimmer Page 2 of 16 ETC
Page 3
ETC Installation Guide
Phase-Adaptive Dimmer

Prepare for Installation

The Phase-Adaptive Dimmer is designed for mounting directly to an electrical junction box or panel (provided by others) at the electrical lighting load, upstream of the load in the circuit.
Note:
If your installation requires Class 2 wiring to be installed in separate conduit, a voltage barrier installation box is available from ETC. Order ETC part number 7187A1000.

DMX Control Wiring

The Phase-Adaptive Dimmer connects to a DMX512-A source (provided by others) for control.
DMX wiring runs can be daisy chains of up to 32 devices with no Y’s or loops. Each DMX daisy chain must be terminated for proper control performance (see
Terminate DMX
ETC recommends using Belden 9729 (or approved equivalent) Class 2 wire. Belden 1583A or equivalent Cat5, Cat5e, or Cat 6 UTP wire is also acceptable when properly shielded or installed in grounded metal conduit and connected using the Cat5 IDC termination kit (ETC part number 4100A1013). This termination kit is not provided with the Phase-Adaptive Dimmer.
A voltage barrier installation box (part number 7187A1000) is available for installations where DMX control wiring is installed in grounded metal conduit. Contact ETC to purchase termination kits or voltage barrier installation boxes if required.
The total combined length of a DMX wire run (using Belden 9729 or equivalent) may not exceed 1,000 ft (300 m).
Note:
on
page 5
).
All control wiring should be installed and terminated by a qualified installer and should follow standard wiring installation practices.
Leave approximately 10 in (255 mm) of wiring available for connection and to allow slack for future service
.
needs
Note:
Phase-Adaptive Dimmer Page 3 of 16 ETC
For more information on DMX control wiring requirements, see these and other Support Articles at etcconnect.com:
• etcconnect.com/Support/Articles/DMX-512-Info.aspx
• etcconnect.com/Support/Articles/DMX-Over-Cat5.aspx
Page 4
ETC Installation Guide
Phase-Adaptive Dimmer

Installation

Installation should follow all local codes and standard electrical practices. Ensure that the junction box is clean and free of obstructions and that all wiring is installed correctly.
WARNING:
WARNING:
1: Locate the circuit breaker panel and turn off the power to the lighting
circuit.
2: To gain access to the line voltage wiring, remove the cover plate and
other hardware from the junction box at the load.
3: Mount the Phase-Adaptive Dimmer to the exterior of the junction box
or panel using the 1/2” threaded nipple. Use the provided 1/2” conduit locknut to secure the Phase-Adaptive Dimmer to the junction box or panel.
Note:
Risk of electric shock! This device utilizes high voltage and should only be installed by a qualified installer or electrician. Follow all local codes for installation. Before terminating the AC power wiring verify that the main breaker is in the off position and follow the proper lockout/tag out procedures per NFPA Standard 70E.
For indoor use only! Must install to an electrical junction box or wire way.
Follow all local code requirements for terminating wire.
• Notice that the harness wires on the controller are pre-stripped for your installation convenience.
• Use appropriately sized wire nuts (not provided) to secure each termination.
Phase-Adaptive Dimmer Page 4 of 16 ETC
Page 5
ETC Installation Guide
Wire jumper
Phase-Adaptive Dimmer

Connect DMX

1: Pull wiring to the junction box. 2: Terminate the DMX cable by following the steps in the termination kit
supplied with the unit.

Terminate DMX

Terminate the last device in the DMX data run for proper control performance. To terminate the DMX data run at the Phase-Adaptive Dimmer, connect the last two pins on the termination connector with a wire jumper (not included) as shown below.
Note:
Because resistance is built into the Phase-Adaptive Dimmer, no additional resistor is required to terminate the last device in the DMX data run.
Phase-Adaptive Dimmer Page 5 of 16 ETC
Page 6
ETC Installation Guide
DMX-512A
Black
Line In
White
Neutral
Dimmer
Load
Red Output
Green/Yellow Ground
Phase-Adaptive Dimmer

Connect Power Input and Dimmer Output

The power input and dimmer output wiring exits the Phase­Adaptive Dimmer through the knockout mount on the enclosure.
1: Connect the power
input wiring. The dimmer is supplied with wiring specific to the input voltage, either 120VAC or 277VAC.
a: Connect the green/yellow striped wire (12 AWG) from the
controller to the ground wire from the breaker panel and the ground wire from the lighting load.
b: Connect the white wire (14 AWG) to the incoming neutral wire
from the breaker panel and the neutral wire of the lighting load.
c: Connect the power input wire (12 AWG) to the line input feed
wire (hot) from the breaker panel. Power input wire is black for 120VAC or brown for 277VAC.
2: Connect the red dimmed output wire (12 AWG) to the dimmed line of
the lighting load.
3: Reinstall the junction box cover plate.

Configure the Phase-Adaptive Dimmer

You can use RDM to set the appropriate dimming mode, dimming curve, DMX address, and data loss behavior for the Phase-Adaptive Dimmer. You can set other parameters using RDM, too. See

Dimming Mode

The Phase-Adaptive Dimmer has two dimming modes:
• Auto: Automatically provides reverse-phase or forward-phase dimming based on the connected load type. This is the default setting.
• Forward-Phase: Provides forward-phase dimming only.
Phase-Adaptive Dimmer Page 6 of 16 ETC
RDM Parameters
on
page 14
.
Page 7
ETC Installation Guide
Control Input (%)
Dimmer Output (%)
0 20 40 60 80 100
0
20
40
60
80
100
Control Input (%)
Dimmer Output (%)
Phase-Adaptive Dimmer

Dimming Curve

The Phase-Adaptive Dimmer has two dimming curves:
• Linear: The linear curve matches the control input percentage to Root Mean Squared (RMS) voltage output. Each percent increase in control level increases dimmer voltage output by the same amount.
100
80
60
40
20
0
0 20 40 60 80 100
• Modified Square Law (Mod-Square): A standard square law curve may overcompensate for infrared loss, resulting in “steppy” response to incremental control changes at low levels. The ETC modified square law curve applies a second multiple to the standard square law curve for more uniform response to control levels changes across the entire range of dimmer output.

DMX Address

You can assign DMX addresses to an entire daisy chain of Unison Foundry devices using Net3 Concert or another RDM controller. If you cannot assign the DMX addresses using RDM, you can manually set the DMX start address on the device. The default factory-set DMX address is 1, and the range of
Phase-Adaptive Dimmer Page 7 of 16 ETC
available addresses is 1–512.
Page 8
ETC Installation Guide
SIGNAL LED
POWER LED
MODE button
SET button
201
10s 1s100s
Phase-Adaptive Dimmer

Manually Set the DMX Address

If you cannot assign the DMX addresses using RDM, use the MODE and SET buttons to set the value of each digit in the three-digit DMX address in sequence.
Task What to do What you will see
1: Put the controller into DMX addressing mode.
2: Set the 100s digit of the DMX address.
Phase-Adaptive Dimmer Page 8 of 16 ETC
Press and hold the MODE button.
Press the SET button to set the 100s digit. For example, press the button once for 1, twice for 2, and so forth up to five times for 5. Press and hold the SET button for 0.
If the 100s digit in the new DMX address is the same as in the current DMX address, you can keep the digit by skipping to step 3.
•The POWER LED indicator blinks 3 times to indicate that you can set the 100s digit of the DMX address.
•The SIGNAL LED indicator blinks the 100s digit in the current DMX address. For example, if the current DMX address is 201, the SIGNAL LED indicator blinks 2 times. (If the 100s digit is a 0, the indicator remains lit and does not blink.)
•The POWER LED indicator continues to blink 3 times to indicate that you are setting the 100s digit of the DMX address.
•The SIGNAL LED indicator blinks the value that you set for the 100s digit in the DMX address.
Page 9
ETC Installation Guide
201
10s 1s100s
Phase-Adaptive Dimmer
Task What to do What you will see
3: Set the 10s digit of the DMX address.
Press the MODE button to advance to the 10s digit.
Press the SET button to set the 10s digit. For example, press the button once for 1, twice for 2, and so forth up to nine times for 9. Press and hold the SET button for 0.
If the 10s digit in the new DMX address is the same as in the current DMX address, you can keep the digit by skipping to step 4.
•The POWER LED indicator blinks 2 times to indicate that you are setting the 10s digit of the DMX address.
•The SIGNAL LED indicator blinks the 10s digit in the current DMX address. For example, if the current DMX address is 201, the SIGNAL LED indicator remains lit and does not blink.
• If the SIGNAL LED indicator rapidly blinks red, this means that you set the 100s digit to an invalid value (for example, 6). When this occurs, the Phase-Adaptive Dimmer exits DMX addressing mode without saving.
•The POWER LED indicator continues to blink 2 times to indicate that you are setting the 10s digit of the DMX address.
•The SIGNAL LED indicator blinks the value that you set for the 10s digit in the DMX address.
Phase-Adaptive Dimmer Page 9 of 16 ETC
Page 10
ETC Installation Guide
10s
201
1s100s
Phase-Adaptive Dimmer
Task What to do What you will see
4: Set the 1s digit of the DMX address.
5: Save the new DMX address.
Press the MODE button to advance to the 1s digit.
Press the SET button to set the 1s digit.
If the 1s digit in the new DMX address is the same as in the current DMX address, you can keep the digit by skipping to step 5.
Press the MODE button. • The POWER LED indicator and SIGNAL
•The POWER LED indicator blinks once to indicate that you are setting the 1s digit of the DMX address.
•The SIGNAL LED indicator blinks the 1s digit in the current DMX address. For example, if the current DMX address is 201, the SIGNAL LED indicator blinks once.
• If the SIGNAL LED indicator rapidly blinks red, this means that you set the 10s digit to an invalid value. When this occurs, the Phase-Adaptive Dimmer exits DMX addressing mode without saving.
•The POWER LED indicator continues to blink once to indicate that you are setting the 1s digit of the DMX address.
•The SIGNAL LED indicator blinks the value that you set for the 1s digit in the DMX address.
LED indicator return to their normal functions (see
Interface
• If the SIGNAL LED indicator rapidly blinks red, this means that you set the 1s digit to an invalid value. When this occurs, the Phase-Adaptive Dimmer exits DMX addressing mode without saving.
LED Indicators and User
on
page 12
).
Note:
The Phase-Adaptive Dimmer will exit DMX addressing mode after 1 minute of inactivity. When this occurs, the controller retains the DMX address that was saved before you entered DMX addressing mode.
Phase-Adaptive Dimmer Page 10 of 16 ETC
Page 11
ETC Installation Guide
Phase-Adaptive Dimmer

Data Loss Behavior

Use RDM to set the behavior of the Phase-Adaptive Dimmer when DMX is lost. The Phase-Adaptive Dimmer has three options for data loss behavior:
• Hold last look
• Wait and fade
• Go to full
Note:
The “Go to full” data loss behavior does not meet the requirements of UL924 for emergency lighting control.

Power Up and Test

1: Restore power to the circuit. The Phase-Adaptive Dimmer will power
up and turn on all connected loads to full output.
2: Verify that DMX input is present. The green signal LED on the unit
should be lit steadily. If it is blinking, check the DMX wiring.
3: Configure the controller. If additional configuration is required, use an
RDM controller such as ETC Net3 Concert software to configure the appropriate properties. For more detailed information, see the Net3 Concert integrated help system.
4: Test the controller response. Use the DMX control system to alter the
control level, and make sure the Phase-Adaptive Dimmer responds.

Power-Up Behavior

In the event of a power loss to the Phase-Adaptive Dimmer, the controller will return to its last output level when power is restored.
Phase-Adaptive Dimmer Page 11 of 16 ETC
Page 12
ETC Installation Guide
SIGNAL LED
POWER LED
MODE button
SET button
Phase-Adaptive Dimmer

LED Indicators and User Interface

LED Indicator Color State Description
Solid DMX present, system OK.
DMX absent. Verify that the DMX wiring is
Green
SIGNAL
Red
POWER Blue
Slow blinking
Rapid blinking
Solid
Blinking
Solid Power is OK
Blinking
correct, and verify that the DMX source is functioning correctly.
DMX errors. Verify that the DMX wiring is correct, and verify that the DMX source is functioning correctly.
Shutdown due to overcurrent or short circuit. Dimmer shuts down at an overcurrent of 16 A or when short circuit occurs. To resume normal operation, set dimmer to 0% and then return it to the intended level.
Shutdown due to overtemperature. Dimmer shuts down when temperature reaches 90°C (194°F), and must cool to 75°C (167°F) before resuming normal operation.
The incoming power is outside of the operable range of voltage or frequency for the dimmer. See and verify that incoming power is correct.
Specifications
on
page 1
Phase-Adaptive Dimmer Page 12 of 16 ETC
Page 13
ETC Installation Guide
Phase-Adaptive Dimmer

Update the Software

You can update the software for the Phase-Adaptive Dimmer using ETC UpdaterAtor software and an ETC Gadget II or Gateway. Both LED indicators on the Phase-Adaptive Dimmer blink during software updates.

Restore Defaults

Return the Phase-Adaptive Dimmer to factory defaults by pressing and holding both the MODE and SET buttons simultaneously for 5 seconds. Both LEDs will blink rapidly to indicate that the factory defaults have been restored. For factory default values, see
RDM Parameters
on
page 14
.
Phase-Adaptive Dimmer Page 13 of 16 ETC
Page 14
ETC Installation Guide
Phase-Adaptive Dimmer

RDM Parameters

You can set the following RDM parameters on the Phase-Adaptive Dimmer using Net3 Concert or another RDM controller.
Parameter ID and Number Description Default Value
Device Label
DMX Start Address
DMX Fail Mode (Data Loss)
Curve and Mode
Minimum Level
Maximum Level
Output Response Time
E120_DEVICE_LABEL 0x0082
E120_DMX_START_ADDRESS 0x00F0
E137_1_DMX_FAIL_MODE 0x0141
E137_1_CURVE 0x0343
E137_1_MINIMUM_LEVEL 0x0341
E137_1_MAXIMUM_LEVEL 0x0342
E137_1_OUTPUT_RESPONSE_TIME 0x0345
User-configurable name for the device
DMX address, range = 1–512
Configures the behavior when DMX is lost:
• Hold last look
• Wait and fade
• Go to full
Configures the dimming mode and dimming curve:
• Auto, Mod-Square
• Auto, Linear
• Forward-Phase, Mod­Square
• Forward-Phase, Linear
Minimum level that the dimmer goes to (when above 0%) range = 0–127
Maximum level that the dimmer goes to (at full), range = 128–255
Configures the response time:
• Instant
• 100 ms
• 600 ms
• 800 ms
• 1000 ms
ETC DMX Single Dimmer
1
Go to full
Auto, Linear
0
255
800 ms
Phase-Adaptive Dimmer Page 14 of 16 ETC
Page 15
ETC Installation Guide
Phase-Adaptive Dimmer
Phase-Adaptive Dimmer Page 15 of 16 ETC
Page 16
ETC Installation Guide
Phase-Adaptive Dimmer
Phase-Adaptive Dimmer Page 16 of 16 ETC
Loading...