ETC EchoConnect Cat5 Termination Tray User Manual

ETC® Installation Guide
(16) Cat5 inputs
EchoConnect - white/black twisted wire connects between the 6 position connector on the tray and the 2 position connector on the power supply.
ESD ground wire with Faston connects between tray and ESD ground bar on the power supply
Unison® EchoConnect Cat5 Termination Tray

Overview

This EchoConnect Cat5 termination tray is intended for installation on the rear panel of the Echo Rack Mount Station Power Supply (E-SPM-RM).
6.25” (15.8cm) included
Use this termination tray to facilitate termination of up to 16 runs of Category 5 (or equivalent) cable on the EchoConnect communication bus.
The following supplies are included for installation convenience:
• 6.25” (15cm) of 2 conductor black/white wire
• 11” (28cm) ESD ground with Faston connector
• 4 x mounting screws
• Six position screw terminal connector J3263-F (x1)

Mount Tray to Rear Panel

The termination tray installs to the rear panel of the Echo Rack Mount Station Power Supply. Secure the termination tray to the rear panel using the four mounting screws provided.

Terminate Wires

This termination tray, as well as the rear panel of the Rack Mount Station Power Supply are provided with wire forms to secure wires with cable ties. Cable ties are not provided but highly recommended to use in maintaining the wire bundles.
Terminations include:
• EchoConnect between this termination tray and the Echo Rack Mount Station Power Supply.
• Up to 16 runs of Category 5 (or equivalent) cable between this termination tray and Echo control stations.
• ESD ground wires terminate to the ground bar on the rear panel of the station power supply. This connection is required for all stations that are not installed entirely in grounded metal conduit.
11” (28cm) included
EchoConnect Cat5 Termination Tray Installation Guide Page 1 of 2 Electronic Theatre Controls, Inc.
Corporate Headquarters London, UK Rome, IT  Holzkirchen, DE Hong Kong  Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong  Tel +852 2799 1220  Fax +852 2799 9325 Service: Web: 7186M2201
 Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK  Tel +44 (0)20 8896 1000  Fax +44 (0)20 8896 2000
Via Pieve Torina, 48, 00156 Rome, Italy  Tel +39 (06) 32 111 683  Fax +44 (0) 20 8752 8486
(Americas) service@etcconnect.com
www.etcconnect.com
 Rev A  Released 2014-05 
 3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA  Tel +608 831 4116  Fax +608 836 1736
 Ohmstrasse 3, 83607 Holzkirchen, Germany  Tel +49 (80 24) 47 00-0  Fax +49 (80 24) 47 00-3 00
Copyright © 2014 ETC. All Rights Reserved.  Product information and specifications subject to change.
(UK) service@etceurope.com  (DE) techserv-hoki@etcconnect.com
ETC intends this document to be provided in its entirety.
(Asia) service@etcasia.com
ETC Installation Guide
EchoConnect Cat5 Termination Tray

Connect CAT5 Inputs

Echo control stations installed for use with Category 5 control wire for the EchoConnect station bus are supplied with an EchoConnect Cat5 Station Termination Kit. This termination kit includes an additional set of instructions, insulation displacement connectors (IDC) and the Cat5 Cable Preparation for IDC Termination Kit (ETC part number 4100A1013). The last station in the control run will not require use of the second IDC connector provided in this IDC termination kit. Use the extra connector to terminate the station data run to this termination tray.
Reference the termination information that is detailed in the Cat5 Cable Preparation for IDC Termination Setup Guide (included with the station termination kit).
Step 1: Connect the prepared Cat5 cable to any of the 16 available Cat5 input receptacles on the
termination tray.
Step 2: Repeat for each EchoConnect station data run in the system.

Connect EchoConnect to the Station Power Supply

Step 1: Remove the six position screw connector from the termination tray.
Step 2: Strip 3/8” (9-10mm) from each wire on the provided white/black twisted pair.
Step 3: Insert the white wire into the data + terminal and the black wire into the data - terminal and
tighten the screws firmly onto each wire.
Step 4: Replace the connector to the board.
Step 5: Remove the two position screw connector from the rear panel of the Echo Rack Mount
Station Power Supply.
Step 6: Insert the white wire into the data + terminal and the black wire into the data - terminal and
tighten the screws firmly onto each wire.
Step 7: Replace the connector to the rear panel.

Connect ESD Ground

Step 1: Connect the ground wire (provided) with the Faston connector to the spade terminal on
the termination tray.
Step 2: Strip 3/8” (9-10mm) from the bare end of the ESD ground wire.
Step 3: Loosen a screw terminal on the ground bar located on the rear panel of the Echo Rack
Mount Station Power Supply.
Step 4: Insert the wire into the terminal then tighten the screw firmly onto the wire.
EchoConnect Cat5 Termination Tray Installation Guide Page 2 of 2 Electronic Theatre Controls, Inc.