Part 1. Digital Control Stations
1.01 DIGITAL BUTTON AND FADER STATIONS
A. Button and Fader Stations
1. General
a. The control station shall be the Echo Inspire Station Series as
manufactured by ETC, Inc., or equal. It shall be a remote station on an
EchoConnect network that can recall presets, provide direct zone control,
recall presets and provide room combine actions for a control system.
b. The station shall consist of a dual function (control/ record) push-button
with an integral bi-color backlight for each corresponding button and fader.
c. The system shall support up to sixteen independent stations
2. Mechanical
a. Control stations shall operate using one, two, four, six or eight buttons. A
four button with fader station shall also be available.
b. All button stations shall be available with cream, black or white decorator
style faceplates.
1) Manufacturer's standard colors shall conform to the RAL CLASSIC
c. Stations shall have bi-color backlights for each button and fader
1) Indicators shall utilize a blue backlight for active status
2) Indicators shall utilize amber for inactive to assist in locating stations
3) Stations shall support an off backlight state of inactive status when
d. All faceplates shall be designed for flush or surface mounting and have no
visible means of attachment
e. Station faceplates shall be constructed of ABS plastic and designed based
on a standard decorator style faceplate. Station faceplates shall be
indelibly marked for each button or fader function.
f. Control station electronics shall mount directly behind the faceplate. The
entire assembly shall mount into a single gang back box. Back boxes for
flush mounted stations shall be industry standard back boxes. The
manufacturer shall supply back boxes for surface mounted stations.
3. Electrical
Standard.
in dark environments. Stations that do not provide a lit inactive or
deactivated state shall not be allowed
required.
![](/html/4f/4fc4/4fc4acc8965b35ece4c076a2a5a76d599e0f90fca65623b6ca3a412231106cff/bg2.png)
a. Control station wiring shall be EchoConnect control wiring utilizing low-
voltage, Class II unshielded twisted pair, type Belden 8471 or equivalent,
and one #14 ESD drain wire (when not installed in grounded metal
conduit).
b. The station shall operate on class 2 voltage provided by the control system
via the EchoConnect network.
c. Station wiring must be topology free. It may be point-to-point, bus, loop,
home run or any combination of these.
d. Wiring termination connectors shall be provided with all stations.
e. Control stations shall be UL/ cUL listed and CE marked and meet WEE
Compliance
4. Station Addressing
a. Station addressing shall be via two 16 position rotary dials and will be set
by installers or factory personnel. Station addressing shall require only a
space assignment and a device ID assignment.
b. Multiple stations may have overlapping control of presets and zones